Documente Academic
Documente Profesional
Documente Cultură
Table of Contents
1 INTRODUCTION 3
1.1 This manual 3
1.2 Modules and requirements 3
4 PROTOCOL 6
4.1 Ext. protocol 6
5 MITSUBISHI 7
5.1 Introduction 7
5.2 Requirements 7
5.3 Software steps 8
5.3.1 GSD file 9
5.3.2 Insert slaves to the network 10
5.3.3 Download the configuration to the module 12
1 INTRODUCTION
Mitsubishi requirements:
Mitsubishi CPU system Q or AnS/QnAS with the matching card, Mitsubishi Melsec AnS/QnAS
(A1SJ71PB92D) Profibus module or Mitsubishi Melsec system Q (QJ71PB92D) Profibus module.
Mitsubishi Melsec system FX2N (FX2N-64DP-M) Profibus module.
Mitsubishi GX IEC Developer 6.01.
Mitsubishi GX Configurator-DP
Termination of the UNISAB is done with the Profibus connector, it is recommended to use WAGO 750-960
or SIEMENS 6ES7 972-0BB10-0XA0. The switch must be set to ON (terminated) for the first and last unit.
Below is an example of a Profibus connector connected to the UNISAB III connector X21.
Information about digital input can be found in the I/O matrix in the Engineering manual
Please note: Controlling the digital input through the Profibus is only possible when using the Ext. protocol.
4 PROTOCOL
The Ext. protocol has the possibility to send and receive a telegram. In this telegram it is possible to access
almost all the variables in a UNISAB. For more information on the telegram and its specifications, see the
document UNISAB Profibus Specification_Ext.
5 MITSUBISHI
5.1 Introduction
Mitsubishi Profibus DP Master:
Supports up to 60 slaves on the network depending on the CPU.
With electrical wiring and the use of repeaters, the network capacity can be up to 4.8 km.
It is the master on the network.
The UNISAB is a slave on the network.
5.2 Requirements
Mitsubishi CPU system Q or AnS/QnAS with the matching card, Mitsubishi Melsec AnS/QnAS
(A1SJ71PB92D) Profibus module or Mitsubishi Melsec system Q (QJ71PB92D) Profibus module.
Mitsubishi Melsec system FX2N (FX2N-64DP-M) Profibus module.
Mitsubishi GX IEC Developer 6.01.
Mitsubishi GX Configurator-DP
Select the Master module Profibus DP (QJ71PB92D) E Mode or Profibus DP (A1SJ71PB92D) E Mode
(E Mode = Send/receive (244 bytes/244 bytes))
Double-click the icon for the CPU to change specific data for your project.
The new project is not saved.
To save the project, select the menu File > Save.
Enter a name for the project, e.g. Example.
Press Add.
YORK095D.gsd
Press Open.
Press Yes.
The software will now ask if you want to install a bitmap to display on the network diagram.
YORK095D.bmp
Press Open.
Technical Support, Controls
E-mail: CG-EUR-DK-SupportControls@jci.com
Web: www.sabroe.com
Revision: 3.2 - Updated: 15-05-2008 Page 9 of 15
Extended protocol installation for Mitsubishi PLC
The software will now ask if you want to install a diagonal bitmap to display on the network diagram.
Press Cancel.
The software will now ask if you want to install a SF bitmap to display on the network diagram.
Press Cancel.
Choose the Slave family of your choice. In this example the slave family General is chosen.
Enter an FDL Address starting from 1 and forward, but remember only 60 slaves and slaves cannot have
the same address. A warning will appear if 2 addresses are alike.
Press OK
Press OK
Press Yes
Repeat the procedure with each UNISAB II or UNISAB III module that is required.
Select the connection type you are using to connect to the PLC. In this example the connection type is
RS232.
Verify Serial Port Number to Com 1 or select the serial port you are using.
Press Save in Project.
Press Yes.
If there is a positive response from the PLC module, the writing operation starts and the following status
window appears:
The Profibus module is now configured and the GSD file is installed.