MTL4511

MTL4511 MTL5511 Hazardous area Safe area


SWITCH/ PROXIMITY To earth-leakage
detector *
DETECTOR INTERFACE
1-channel, with line fault detection 6
5
12
11
4 10
680W
The MTLx511 enables a safe-area load to be controlled by a switch or
3 9
proximity detector located in a hazardous-area. When selected, open +
22kW 2 8 Output
or short circuit conditions in the field wiring are detected by the line- 1 7
fault-detect (LFD) facility and also indicated on the top of the module.
Phase reversal for the channel is selected by a switch on the side of the Switch-type sensors
require resistors 13 14
module and output is provided by changeover relay contacts. if LFD is selected 20 to 35V dc
Vs+
Vs
SPECIFICATION
See also common specification
MTL5511
Number of channels Hazardous area Safe area
One
Location of switches To earth-leakage
Zone 0, IIC, T6 hazardous area detector *
Div. 1, Group A hazardous location
Location of proximity detector 6 7
Zone 0, IIC, T46 hazardous area if suitably certified 5 8
4 9
Div. 1, Group A hazardous location
680W
Hazardous-area inputs 3 10
+
Inputs conforming to BS EN6094756:2001 standards for 2 11 Output
22kW
proximity detectors (NAMUR) 1 12

Voltage applied to sensor 13 Vs


Switch-type sensors
7 to 9V dc from 1k 10% require resistors 14 Vs+
Input/output characteristics if LFD is selected 20 to 35V dc
Normal phase
Outputs closed if input > 2.1mA (< 2k in input circuit)
Outputs open if input < 1.2mA (> 10k in input circuit)
Hysteresis: 200A (650) nominal
Line fault detection (LFD) (when selected) * Signal plug HAZ1-3 is required for access to this function
User-selectable via switches on the side of the unit. A line fault is
LED indicators
indicated by an LED. The channel output relay is de-energised if
Green: power indication
an input line fault is detected.
Yellow: channel status, on when output energised
Open-circuit alarm on if Iin < 50A
Red: LFD indication, on when line fault detected
Open-circuit alarm off if Iin > 250A
Maximum current consumption
Short-circuit alarm on if Rin < 100
25mA at 24V
Short-circuit alarm off if Rin > 360
Note: Resistors must be fitted when using the LFD facility with a contact input Power dissipation within unit
500 to 1k in series with switch 0.6W at 24V
20k to 25k in parallel with switch Safety description (each channel)
Safe-area output Uo =10.5V Io =14mA Po =37mW Um = 253V rms or dc
Single pole relay with changeover contacts SIL capable
Note: reactive loads must be adequately suppressed
These models have been assessed for use in IEC 61508 functional
Relay characteristics safety applications. See data on MTL web site.
MTL4511 MTL5511
Response time: 10ms maximum 10ms maximum
Contact rating: 10W, 0.5A, 250V ac, 2A, cos >0.7,
35V dc 40V dc, 2A, resistive load

The given data is only intended as a product description and should not be regarded as a legal warranty of proper-