Documente Academic
Documente Profesional
Documente Cultură
Transformer protection
WINDING FAULTS
The development of modern power A fault on a transformer winding is controlled
systems has been reflected in the in magnitude by the following factors:
advances in transformer design. This has i. Source impedance
resulted in a wide range of transformers with ii. Neutral earthing impedance
sizes ranging from a few kVA to several iii. Transformer leakage reactance
hundred MVA being available for use in a iv. Fault voltage
wide variety of applications. The v. Winding connection
considerations for a transformer protection Several distinct cases arise and are
package vary with the application and examined below.
importance of the transformer. To reduce
the effects of thermal stress and electro Star-Connected Winding with Neutral Point
dynamic forces, it is advisable to ensure Earthed through an Impedance
that the protection package used The winding earth fault current
minimises the time for disconnection in the depends on the earthing impedance value
event of a fault occurring within the and is also proportional to the distance of
transformer. Small distribution transformers the fault from the neutral point, since the
can be protected satisfactorily, from both fault voltage will be directly proportional to
technical and economic considerations, by this distance.
the use of fuses or over current relays. This
results in time-delayed protection due to
downstream co-ordination requirements.
However, time-delayed fault clearance is
unacceptable on larger power transformers
used in distribution, transmission and
generator applications, due to system
operation /stability and cost of repair/ length
of outage considerations.
Transformer faults are generally
classified into five categories:
a. Winding and terminal faults
b. Core faults
c. Tank and transformer accessory
faults
d. Onload tap changer faults
e. Abnormal operating conditions
f. Sustained or uncleared external
faults
Fig 2
Overload
Overload causes increased 'copper
loss' and a consequent temperature rise.
Overloads can be carried for limited
periods and recommendations for oil-
Fig 4 immersed transformers are given in IEC
Core Faults 60354. The thermal time constant of
naturally cooled transformers lies between
A conducting bridge across the 2.5-5 hours. Shorter time constants apply in
laminated structures of the core can permit the case of force-cooled transformers.
sufficient eddy-current to flow to cause
serious overheating. The bolts that clamp System faults
the core together are always insulated to System short circuits produce a
avoid this trouble. If any portion of the core relatively intense rate of heating of the
insulation becomes defective, the resultant feeding transformers, the copper loss
heating may reach a magnitude sufficient increasing in proportion to the square of the
to damage the winding. per unit fault current. The typical duration of
The additional core loss, although external short circuits that a transformer can
causing severe local heating will not sustain without damage if the current is
produce a noticeable change in input limited only by the self-reactance is shown
current and could not be detected by the in Table 1.
normal electrical protection; it is
nevertheless highly desirable that the
condition should be detected before a
major fault has been created. In an oil-
immersed transformer, core heating
sufficient to cause winding insulation Table 1
damage will also cause breakdown of Maximum mechanical stress on windings
some of the oil with an accompanying occurs during the first cycle of the fault.
evolution of gas. This gas will escape to the Avoidance of damage is a matter of
conservator, and is used to operate a transformer design.
mechanical relay;
Over voltages
Over voltage conditions are of two kinds:
Tank Faults i. Transient surge voltages
Loss of oil through tank leaks will ii. Power frequency over voltage
ultimately produce a dangerous condition, Transient over voltages arise from faults,
either because of a reduction in winding switching, and lightning disturbances and
insulation or because of overheating on are liable to cause interturn faults, as
load due to the loss of cooling. Overheating described in previous Section. These over
may also occur due to prolonged voltages are usually limited by shunting the
high voltage terminals to earth either with a
MAGNETISING INRUSH
The phenomenon of magnetising
inrush is a transient condition that occurs Fig 5
primarily when a transformer is energised. It as magnetising inrush current and may
is not a fault condition, and therefore persist for several cycles.
transformer protection must remain stable A number of factors affect the magnitude
during the inrush transient. Figure 5(a) shows and duration of the magnetising current
a transformer-magnetizing characteristic. To inrush:
minimise material costs, weight and size,
transformers are generally operated near to
Overcurrent relays
Fig 6
With the advent of ring main units It can be of the high impedance
incorporating SF6 circuit breakers and type as shown in Figure 6, or of the biased
isolators, protection of distribution low impedance type. For the high-
transformers can now be provided by impedance type, the residual current of
overcurrent trips (e.g. tripping controlled by three line current transformers is balanced
time limit fuses connected across the against the output of a current transformer
secondary windings of in-built current in the neutral conductor. In the biased low-
transformers) or by relays connected to impedance version, the three phase
current transformers located on the currents and the neutral current become
transformer primary side. Overcurrent relays the bias inputs to a differential element.
are also used on larger transformers The system is operative for faults
provided with standard circuit breaker within the region between current
control. Improvement in protection is transformers, that is, for faults on the star
obtained in two ways; the excessive delays winding in question. The system will remain
of the HRC fuse for lower fault currents are stable for all faults outside this zone.
avoided and an earth-fault tripping The gain in protection performance
element is provided in addition to the comes not only from using an
overcurrent feature. The time delay instantaneous relay with a low setting, but
characteristic should be chosen to also because the whole fault current is
discriminate with circuit protection on the measured, not merely the transformed
secondary side. A high-set instantaneous component in the HV primary winding (if the
relay element is often provided, the current star winding is a secondary winding).
setting being chosen to avoid operation for Hence, although the prospective current
a secondary short circuit. This enables high- level decreases as fault positions
speed clearance of primary terminal short progressively nearer the neutral end of the
circuits. winding are considered, the square law
which controls the primary line current is not
applicable, and with a low effective setting,
RESTRICTED EARTH FAULT PROTECTION a large percentage of the winding can be
Conventional earth fault protection covered.
using over current elements fails to provide Restricted earth fault protection is
adequate protection for transformer often applied even when the neutral is
windings. This is particularly the case for a solidly earthed. Since fault current then
star-connected winding with an remains at a high value even to the last turn
impedance-earthed neutral, as of the winding (Figure 2), virtually complete
considered. The degree of protection is very cover for earth faults is obtained. This is an
much improved by the application of improvement compared with the
restricted earth fault protection (or REF performance of systems that do not
protection). This is a unit protection scheme measure the neutral conductor current.
for one winding of the transformer. Earth fault protection applied to a delta-
connected or unearthed star winding is
inherently restricted, since no zero