Documente Academic
Documente Profesional
Documente Cultură
The different selectivity techniques, also from the operational point of view
Selectivity (discrimination) is achieved by automatic protective devices when a fault is
cleared by the protection device installed immediately upstream of it, while all the other
protection devices remain unaffected.
Two areas can be defined, depending on the current ranges and circuit-breaker trip curves:
Overload zone
In which the thermal protection for thermal-magnetic trip units and protection L for
electronic trip units are normally called upon to trip.
Short-circuit zone
In which the magnetic protection for thermal-magnetic trip units or protections S, D and I
for solid-state trip units are normally called upon to trip.
I 810 x In
The protections against overload generally have a definite time characteristic, whether
they are realized by means of a thermal trip unit or by means of function L of an
electronic trip unit.
By definite time characteristic we mean a trip characteristic for which, as the current
increases, the trip time of the circuit-breaker decreases.
When there are protections with this type of characteristics, the selectivity technique
used is time-current selectivity.
Time-current selectivity realizes trip selectivity by adjusting the protections so that the
load-side protection, for any possible overcurrent value, trips more rapidly than the
supply-side circuit-breaker.
When the trip times of the two circuit-breakers are analyzed, it is necessary to
consider:
The tolerances over the thresholds and trip times;
With regard to tolerances, ABB SACE makes the trip curves of its trip units available in
the technical catalogues and in DOCWin software. In particular, in the curve module of
DOCWin, the curves of both the electronic and thermomagnetic trip units include the
tolerance values. Thus, a trip of the protection unit is represented by two curves, one
showing the highest trip times (top curve), and the other one indicating the most rapid
trip times (bottom curve).
For a correct analysis of selectivity, the worst conditions must be considered, i.e.:
if the two circuit-breakers are passed through by the same current, it is sufficient
that there is no overlapping between the curve of the supply-side circuit-breaker
and of the load-side circuit-breaker;
In particular, in the case of circuit-breakers equipped with electronic trip units, since
the trend of the curves is at I2t=const, to verify them properly, it is sufficient to
examine two current values:
1.05 x I11 of the supply-side circuit-breaker (value below which the supply-side
protection never trips)
1.20XI3 (or I2)2 of the load-side circuit-breaker (value above which the load-side
protection certainly trips with the protections against short-circuit).
1.05 x I11 of the supply-side
circuit-breaker
By assuming IA =1.05xI1, and with
reference to what has been said about
the real currents circulating inside the
circuit-breakers, the IB current on the
load side is obtained.
1. 1.05 is the value for minimum definite non-intervention defined in the Standard
(IEC60947-2). For some types of circuit-breakers this value could vary
(see the technical catalogue for further information).
2. 1.2 is the value for maximum definite intervention for protection against short-
circuit defined in the Standard (IEC60947-2). For some types of circuit-breakers,
this value might be lower
(see the technical catalogue for further information).
Current selectivity
Introduction
This type of selectivity is based on the observation that the closer the fault point to the
power supply source of the installation, the higher the short-circuit current. Therefore,
it is possible to discriminate the zone where the fault occurs, by setting the
instantaneous protections to different current values.
Total selectivity can normally be achieved in specific cases only where the fault current
is not high and where there is a component with high impedance interposed between
the two protections (transformer, very long cable or a cable with reduced cross-
section, etc.), and consequently there is a great difference between the short-circuit
current values.
Therefore, this type of coordination is used above all in final distribution (low rated
current and short-circuit current values, and high impedance of the connection cables).
The time-current trip curves of the devices are normally used for this study.
It is intrinsically fast (instantaneous), easy to realize and cost-effective.
However:
The ultimate selectivity current is usually low and therefore selectivity is often
partial;
The setting level of the protections against overcurrent rises rapidly;
It is impossible to have redundancy of protections, which guarantees that the
fault is cleared rapidly if one protection fails to operate.
This type of selectivity can also be realized between circuit-breakers of the same size
not providing time-delayed overcurrent protection (S).
Operatively speaking
Note
This type of selectivity is a development of the previous one. For this type of
coordination, in addition to the current trip threshold, a trip time is also defined: a
certain current value will make the protections trip after a defined time delay, such as
to allow any protection placed closer to the fault to trip, excluding the area of the fault.
Thus, the setting strategy is to increase gradually the current thresholds and the trip
delays by getting closer to the power supply sources (setting level directly correlated
to the hierarchical level).
The delayed trip thresholds must take into account the tolerances of the two protection
devices and the effective currents flowing through them.
The difference between the delays set for the protections in series must take into
account the times of fault detection and clearance of the device on the load side and of
the inertia time (over-shoot) of the device on the supply side (time interval during
which the protection can trip even when the phenomenon is over). As in the case of
current selectivity, the study is made by comparing the time-current trip curves of the
protection devices.
However:
The trip times and energy levels let through by the protections, especially by
those close to the sources, are high.
This type of selectivity can also be realized between circuit-breakers of the same size,
equipped with electronic trip units providing time-delayed overcurrent protection.
Operatively speaking
The protections against short-circuit of the two circuit-breakers will be set:
With the I2 trip thresholds against
time-delayed short-circuit set so as
not to create trip overlapping,
taking into consideration the
tolerances and the real currents
circulating inside the circuit-
breakers;
Note
These selectivity limits are exceeded in all the cases where energy type selectivity is
realized.
If the settings indicated for energy selectivity are respected for the combinations of
circuit-breakers with an energy selectivity value given in the coordination tables
published by ABB, the selectivity limit to be taken into consideration is the one given in
the tables, and not the one that can be obtained from the considerations in this
paragraph.
Energy selectivity
Introduction
The coordination of the energy type is a particular type of selectivity that exploits the
current-limiting characteristics of moulded-case circuit-breakers. It is recalled that a
current-limiting circuit-breaker is "a circuit-breaker with a break-time short enough to
prevent the short-circuit current reaching its otherwise attainable peak value" (IEC
60947-2).
In fact, all the ABB SACE moulded-case circuit-breakers of the Tmax series, the
miniature circuit-breakers and the air current-limiting circuit-breaker E2L and E3L have
more or less marked current-limiting characteristics. Under short-circuit conditions,
these circuit-breakers are extremely fast (trip times in the range of a few milliseconds)
and open when there is a strong asymmetrical component. Thus, it is impossible to use
the time-current trip curves of the circuit-breakers, obtained with symmetrical
sinusoidal types of wave forms, for the coordination study.
These phenomena are mainly dynamic (therefore proportional to the square of the
instantaneous current value) and are heavily dependent on the interaction between the
two devices in series. Therefore, the end user cannot determine the energy selectivity
values. The manufacturers provide tables, slide-rules and calculation programs giving
the ultimate current selectivity values of Is under short-circuit conditions for different
combinations of circuit-breakers. These values are defined by theoretically integrating
the results of tests carried out in compliance with the prescriptions in Annex A of Std.
IEC 60947-2.
Operatively speaking
The short-circuit protections of the two circuit-breakers shall observe the conditions
below.
I3=OFF