Sunteți pe pagina 1din 40

Refrigerant

Report
14. Edition A-501-14
Refrigerant Report

Page Contents Revisions/supplements vs. 13th edition

3 General aspects on refrigerant developments


3 Introduction
4 Alternative refrigerants (overview)
6 Environmental aspects
6 Global Warming and TEWI factor
7 Eco-Efficiency

8 HCFC refrigerants
8 R22 as transitional refrigerant

10 Chlorine free (HFC) refrigerants


10 R134a as a substitute for R12 and R22 Lubricants for HFCs
12 Alternatives to R134a
12 R152a an alternative to R134a (?)
12 Low GWP refrigerants

13 Refrigerant blends
15 Service blends as substitutes for R502
16 Service blends as substitutes for R12 (R500)
17 Chlorine free R502 and R22 alternatives (blends)
17 R404A and R507A as substitutes for R502 and R22
18 R407A and R407B as substitutes for R502
19 R422A and R22 as substitute for R502
20 Chlorine free R22 alternatives (blends)
20 R407C as substitute for R22
21 R410A as substitute for R22
22 R417A and R422D as substitutes for R22
22 FX100 as substitute for R22

23 Halogen free refrigerants


23 NH3 (Ammonia) as substitute for R22
24 R723 (NH3/DME) as an alternative to NH3
25 R290 (Propane) as substitute for R502 and R22
27 Propylene (R1270) as an alternative to Propane
28 CO2 as an alternative refrigerant and secondary fluid

32 Special applications

34 Refrigerant properties

36 Application ranges Lubricants

This edition supersedes all previous issues.


General aspects on refrigerant developments

Introduction A large number of development tasks the environment could differ according to
have been completed; an extensive range the place of installation and drive method.
of compressors and equipment is already
A closer look on the HFC based substitu-
available for the various alternative refrig-
tes shows, however, that the possibilities
erants.
for directly comparable single substance
Besides the development projects BITZER refrigerants are limited. The situation for
actively supports legal regulations and R12 with the substitute R134a is relatively
Stratospheric ozone depletion as well as
self commitments concerning the respon- favourable, as it is for R502 with the alter-
atmospheric greenhouse effect due to
sible use of refrigerants (see also page 6). natives R404A and R507A. It is more criti-
refrigerant emissions have led to drastic
cal for alternatives to other CFC refrige-
changes in the refrigeration and air The following report deals with possibili-
rants and also for HCFCs, e.g. R22.
conditioning technology since the begin- ties for a short and medium term change
ning of the 90s. to environmentally benign refrigerants in The refrigerants R32, R15 and R134a are
medium and large commercial refrigera- regarded as direct substitutes from the
This is especially true for the area of com-
tion and A/C plants. At the same time, the line of HFCs. These however can only be
mercial refrigeration and A/C plants with
experience which already exists is also used exceptionally as a pure substance
their wide range of applications. Until a
dealt with and the resulting consequences due to their specific characteristics. Most
few years ago the main refrigerants used
for plant technology. important criteria in this concern are flam-
for these systems were ozone depleting
types, namely R12, R22 and R502; for mability, thermodynamic properties and
global warming potential. These substan-
special applications R114, R12B1, R13B1, ces are much more suitable as compo-
R13 and R503 were used.
nents of blends where the individual cha-
With the exception of R22 the use of racteristics can be matched to the
The results of serveral studies confirm
these chemicals is not allowed any more requirements according to the mixing pro-
that the vapour compression refrigeration
in industrialised countries. In the Euro- portions.
plants normally used in the commer-
pean Union, however, there is a current
cial field are far superior to all other pro- Besides HFC refrigerants, Ammonia (NH3)
early phase-out for R22 as well which
cesses down to a cold space temperature and hydrocarbons are considered as sub-
shall be realised step by step (see page 7
of around -40C. stitutes as well. The use for commercial
for explanations).
The main reason for this early ban of R22 The selection of an alternative refrigerant applications, however, is limited by strict
contrary to the international agreement is and the system design receives special safety requirements.
the ozone depletion potential although it significance, however. Besides the request Carbon dioxide (CO2) becomes more
is only small. for substances without ozone depletion important as an alternative refrigerant and
potential (ODP=0) especially the energy secondary fluid, too. Due to its specific
Due to this situation enormous conse-
demand of a system is seen as an essen- characteristics, however, there are restric-
quences result for the whole refrigeration
tial criterion due to its indirect contribu- tions to a general application.
and air conditioning trade. BITZER there-
tion to the greenhouse effect. On top of
fore committed itself to taking a leading The illustrations on the next pages show a
that there is the direct global warming
role in the research and development of structural survey of the alternative refrige-
potential (GWP) due to refrigerant emission.
environmentally benign system designs. rants and a summary of the single or
Therefore a calculation method has been blended substances which are now avai-
Although the chlorine free HFC refriger-
developed for the qualified evaluation of a lable. After that the individual subjects are
ants R134a, R404A, R507A, R407C,
system which enables an analysis of the discussed.
R410A as well as NH3 and various hydro-
total influence on the greenhouse effect.
carbons have already become estab- Due to the increasing interest in substitu-
lished, there are still further tasks to per- In this connection the so-called TEWI tes for R114, R12B1, R13B1, R13 and
form, especially with respect to the global factor (Total Equivalent Warming Impact) R503, the possible alternatives are also
warming impact. The aim is to significant- has been introduced. Meanwhile, another, considered in this report.
ly reduce direct emissions caused by more extensive assessment method has
refrigerant loss, and indirect emissions been developed under the aspect of Refrigerant data, application ranges and
through highly efficient plants. Eco-Efficiency. Hereby, both ecological lubricant specifications are shown on
(such as TEWI = Total Equivalent Warming pages 34 to 37.
Therefore a close co-operation exists with
Impact) and economical criteria are taken
scientific institutions, the refrigeration and For reasons of clarity the less or only
into account.
oil industries, component manufacturers regionally known products are not speci-
as well as a number of innovative refriger- Therefore it is possible that in future the fied in this issue, which is not intended to
ation and air conditioning companies. assessment of refrigerants with regard to imply any inferiority.
3
Alternative refrigerants overview

Alternative Refrigerants

Transitional/Service Medium and Long


Refrigerants Term Refrigerants

HCFC/HFC HFC Low GWP Halogen free


partly chlorinated chlorine free Refrigerants

Single Single Single


Substances Blends Substances Blends Blends Substances Blends
e.g. R22 predominantly e.g. R134a e.g. R404A Blend H e.g. NH3 e.g. R600a/
R123 R22-Based R125 R507A R290 R290
DP-1
R124 R32 R407-Series R1270 R290/
R142b R143a R410A R600a R170
R152a R170 R723

Fig. 1 General survey of the alternative refrigerants

Transitional / Service refrigerants 09.06

Previous Alternatives
refrigerants

ASHRAE Trade name Composition Detailed


Classification (with blends) Information

R401A MP39 DuPont R22/152a/124


R401B MP66 DuPont R22/152a/124 pages
R12 R409A FX56 Arkema/Solvay R22/124/142b 16, 34...37
(R500) R413A 4 ISCEON MO49 DuPont R134a/218/600a

R22
R402A HP80 DuPont R22/125/290
pages
R402B HP81 DuPont R22/125/290
8, 9, 15, 16,
R502 R403A DuPont R22/218/290
34...37
R408A FX10 Arkema R22/143a/125

R114 R124 3 pages


R12B1 R142b 1 3
32, 34...37

R13B1
R13 Alternatives see Fig. 3 Chlorine free HCFC Refrigerants
R503

Fig. 2 Alternatives for CFC refrigerants (transitional / service refrigerants)

4
Alternative refrigerants overview

Chlorine free (HFC) refrigerants and blends (long term alternatives) 09.06

Previous Alternatives
Refrigerants

ASHRAE Trade name Composition Detailed


Classification (with blends) Information
R12 R134a pages

(R500) R152a 1 10...12, 34...37
Blend H 6 Honeywell page 12
DP-1 6 DuPont

R404A various R143a/R125/R134a


R502/R22 R507A R143a/125 pages
R422A ISCEON MO79 DuPont R125/134a/600a 17...19, 34...37
R407C various R32/125/134a
R410A various R32/125
R22 pages
R417A ISCEON MO59 DuPont R125/134a/600
20...22, 34...37
R422D ISCEON MO29 DuPont R125/134a/600a
FX100 Atofina R125/R134a/R-E170
R114 R236fa pages
R12B1 R227ea 32, 34...37
R410A various R32/125 pages
R13B1 ISCEON 89 Rhodia R125/218/290 33, 34...37
R23
R13 pages
R508A KLEA 508A INEOS Fluor R23/116
R503 33, 34...37
R508B Suva 95 DuPont R23/116
Fig. 3 Alternatives for CFC and HCFC refrigerants (chlorine free HFC refrigerants)

Halogen free refrigerants (long term alternatives) 09.06

Bisherige Alternativen
Kltemittel

ASHRAE Trade name Formula Detailed


Classification Information

R12 R290/600a 1 C3H8/C4H10 pages


(R500) R600a 1 3 C4H10 25, 34...37

R717 1 2 NH3
pages
R502 R290 1 C3H8
1 23...27, 34...37
R1270 C3H6

R717 1 2 NH3
R723 1 2 5 NH3 + R-E170 pages
R22 R290 1 C3H8 23...27, 34...37
R1270 1 C3H6

R114 pages
R600a 1 C4H10
R12B1 32, 34...37

R13B1 no direct alternatives available

R13 1
pages
R170 C2H6
R503 33, 34...37

pages
Divers R744 3 CO2 28...31, 34...37
Fig. 4 Alternatives for CFC and HCFC refrigerants (halogen free refrigerants)

Explanation of Fig. 2 to 4 1 inflammable 3 large deviation in refrigerating capacity and 4 chlorine free service refrigerant
2 toxic pressures to the previous refrigerant 5 Azeotrope
6 still in development and test phase

5
Environmental aspects

Global Warming and As this is a high proportion of the total the influence upon the TEWI value with
balance it is also necessary to place an various refrigerant charges, leakage los-
TEWI Factor increased emphasis upon the use of high ses and energy consumptions.
efficiency compressors and associated This example is simplified based on an
equipment as well as optimized system overall leak rate as a percentage of the
As already mentioned in the introduction a components, in addition to the demand
method of calculation has been developed, refrigerant charge. As is known the practi-
for alternative refrigerants with favourable cal values vary very strongly whereby the
with which the influence upon the global (thermodynamic) energy consumption.
warming effect can be judged for the opera- potential risk with individually constructed
tion of individual refrigeration plants When various compressor designs are systems and extensively branched plants
(TEWI = Total Equivalent Warming Impact). compared, the difference of indirect CO2 is especially high.
emission (due to the energy requirement) Great effort is taken worldwide to reduce
All halocarbon refrigerants, including the can have a larger influence upon the total greenhouse gas emissions and legal
non-chlorinated HFCs belong to the cate- effect as the refrigerant losses. regulations have partly been developed
gory of the greenhouse gases. An emis-
already. Within the EU, the Regulation on
sion of these substances contributes to A usual formula is shown in Fig. 5, the
certain fluorinated greenhouse gases
the global warming effect. The influence is TEWI factor can be calculated and the
(also called F-Gases) was published in the
however much greater in comparison to various areas of influence are correspon-
meantime, which also defines tight requi-
CO2 which is the main greenhouse gas in dingly separated.
rements for refrigeration and air-condition-
the atmosphere (in addition to water
In addition to this an example in Fig. 6 ing systems. It will acquire legal status
vapour). Based on a time horizon of 100
(medium temperature with R134a) shows in July 2007 for all the EU member states.
years, the emission from 1 kg R134a is for
example roughly equivalent to 1300 kg of
CO2 (GWP100 = 1300). It is already appar- TEWI = TOTAL EQUIVALENT WARMING IMPACT
ent from these facts that the reduction of
refrigerant losses must be one of the main TEWI = ( GWP x L x n ) + ( GWP x m [ 1- recovery ] ) + ( n x Eannual x )
tasks for the future. Leakage Recovery losses Energy consumption
On the other hand, the major contributor direct global warming potential indirect global
to a refrigeration plants global warming warming potential
effect is the (indirect) CO2 emission GWP = Global warming potential [ CO2-related ]
caused by energy generation. Based on L = Leakage rate per year [ kg ]
the high percentage of fossil fuels used in n = System operating time [ Years ]
power stations the average European CO2 m = Refrigerant charge [ kg ]
release is around 0.6 kg per kWh of elec- recovery = Recycling factor
trical energy. A significant greenhouse Eannual = Energy consumption per year [ kWh ]
effect occurs over the lifetime of the plant = CO2-Emission per kWh (Energy-Mix)
as a result of this. Fig. 5 Method for the calculation of TEWI figures

Comparison
Example with 10% higher
energy consumtion
Medium temperature R134a 300
SST -10 C +10%

SCT +40 C +10%


E
m 10 kg // 25 kg 200 E N
TEWI x 103

N E E
L[10%] 1 kg // 2,5 kg E E N R
N G
CAP 13,5 kW E
R E
Y
G R
E 5 kW x 5000 h/a R Y G
RL = Impact of
G
0,6 kg CO2/kWh 100
Y
Y recovery
losses
0,75 RL RL

n 15 years RL RL LL = Impact of
LL LL leakage
GWP 1300 (CO2 = 1) LL LL losses
10kg 25kg 10kg 25kg
time horizon 100 years Refrigerant charge [m]
Fig. 6 Comparison of TEWI figures (example)

6
Environmental aspects

Eco-Efficiency on the relationship between added value whilst the results of the life cycle cost
(a product's economic value) and the analysis are shown on the y-axis. This
resulting environmental impact. representation shows clearly that a sys-
With this evaluation approach, the entire tem exhibits an increasingly better Eco-
life cycle of a system is taken into Efficiency, the higher it lies in the top right
As mentioned above, an assessment account in terms of: quadrant and conversely, it becomes
based on the specific TEWI value takes less efficient in the bottom left sector.
into account the effects of global warming ecological performance in accordance
during the operating period of a refrigera- with the concept of Life Cycle Assess- The diagonals plotted into the system of
tion, air-conditioning or heat pump instal- ment as per ISO 14040, coordinates represent lines of equal Eco-
lation. Hereby, however, the entire eco- Efficiency. This means that systems or
economic performance by means of
logical and economical aspects are not processes with different life cycle costs
a Life Cycle Cost Analysis.
considered. and environmental impacts can quite
This means that the overall environmental possibly exhibit the same Eco-Efficiency.
But apart from ecological aspects, when impact (including direct and indirect
evaluating technologies and making emissions), as well as the investment
investment decisions, economical aspects costs, operating and disposal costs, and
are highly significant. With technical sys- capital costs are taken into account.
tems, the reduction of environmental
impact frequently involves high costs, The study also confirmed that an increase
whereas low costs often have increased of Eco-Efficiency can be achieved by
ecological consequences. For most investing in optimized plant equipment
companies, the investment costs are (minimized operating costs). Hereby, the
decisive, whereas they are often neglect- choice of refrigerant and the associated
ed during discussions about minimizing system technology plays an important
ecological problems. role.
For the purpose of a more objective Eco-Efficiency can be illustrated in gra-
phic representation (see example in * The study was compiled by Solvay Management
assessment, a study* was presented in Support GmbH and Solvay Fluor GmbH, Hannover,
2005, using the example of supermarket Fig. 8). For this, the results of the Eco- together with the Information Centre on Heat
Efficiency evaluation are shown on the Pumps and Refrigeration (IZW), Hannover. The
refrigeration plants to describe a concept work was supported by an advisory group of
for evaluating Eco-Efficiency. It is based x-axis in the system of coordinates, experts from the refrigeration industry.

Concept of Eco-Efficiency
y
nc
ie
fic

Life Cycle Assessment


Ef

Life-Cycle-Cost Analysis
o-
Ec

(including investment according to ISO 14040


g
n
si
ea
Cost advantage

costs, cost of operation,


cr
in

capital costs)
y
nc
ie
fic
Ef

Eco-Efficiency
o-
Ec
ng
si

considers
ea
cr
de

economical and ecological

aspects
Environmental advantage

Fig. 7 Concept of Eco-Efficiency Fig. 8 Example of an Eco-Efficiency evaluation

7
HCFC Refrigerants

Despite of the generally favourable prop- Similar relationships in terms of thermal


R22 as transitional
erties R22 is already subject to various load are found in the comparison with
refrigerant regional restrictions* which control the HFC refrigerants R134a, R404A/R507A
use of this refrigerant in new systems and (pages 10 and 17).
Although the chlorine free substitutes for service purposes due to its ozone
Suitable compressors are required for
R134a and R404A/R507A (Fig. 1 and 3) have depletion potential although being low.
plants with R22, these have been avail-
extensively made their way as alternatives
With regard to components and system able and are proven for medium tempera-
to R12 and R502, in many international
technology a number of particularities are ture and air conditioning for a long time.
fields R22 is still used in new installations
to follow as well. Refrigerant R22 has
and for retrofitting of existing systems. Refrigeration and air conditioning
approximately 55% higher refrigerating
Reasons are relatively low investment capacity and pressure levels in compari- In vehicles such as cars, trucks, buses
costs, especially compared with R134a son to R12. The significantly higher dis- and trains are more problematic. The
systems, but also in its large application charge gas temperature is also a critical higher pressure and temperature levels
range, favourable thermodynamic proper- factor compared to R12 (see Fig. 9) and of R22 seriously limit here the range of
ties and low energy requirement. Addi- R502. application. Only some of the applications
tionally there is world wide availability of can therefore be covered.
R22 and the proven components for it,
Also critical due to the high discharge
which is not yet guaranteed everywhere
gas temperature are low temperature
with the chlorine free alternatives.
plants especially concerning thermal sta-
* Not allowed for new equipment in Germany and
The latter is also true for the zeotropic Denmark since 2000 January 1st and in Sweden bility of oil and refrigerant, with the dan-
service refrigerants (Fig. 1 and 2). More- as of 1998. ger of acid formation and copper plating.
Since January 1st, 2001 restrictions apply to the
over, they predominantly contain R22 and other member states of the EU as well. The mea- Special measures have to be adopted
therefore only make sense where pure sures concerned are defined in the new ODS therefore, such as two stage compres-
Regulation 2037/2000 of the EU commision on
R22 cannot be controlled due to high ozone depleting substances. This regulation also sion, controlled refrigerant injection, addi-
operation temperatures. Related to these governs the use of R22 for service reasons within tional cooling, monitoring of discharge
the entire EU.
mixtures special handling procedures are gas temperature, limiting the suction gas
Information about the world wide R22
required (see section Refrigerant blends phase-out regulation can be found under superheat and particularly careful
from page 13). www.arap.org/docs/regs.html as well. installation.

170 25
R22
tc +50 tc +60
160 20

R12 tc +40
150 tc +60 15
R502
Discharge gas temp. [C]

140
Pressure [bar]

tc +50
10
130 R22
tc +40

120 6
R12
110 4

100
2
90

80 1
-40 -30 -20 -10 0 10 -40 -20 0 20 40 60
Evaporation [C] Temperature [C]

Fig. 9 R12/R22 comparison of discharge gas temperatures of Fig. 10 R12/R22/R502 comparison of pressure levels
a semi-hermetic compressor

8
HCFC Refrigerants

Converting existing plants oil migration due to the reduced flow


An incomparably wide palette is availa-
velocities.
ble from BITZER for use with R22: Existing R12 plants can only subsequently
Open and semi-hermetic reciprocat- be converted to R22 under restrictions R502 plants can in many cases be con-
ing compressors from 0.37 to 74 kW without exchanging major components. verted to R22 with reasonable effort. The
nominal motor power with special Even if the compressor, heat exchanger individual components must however be
design features for low temperature and pressure vessel are suitable for oper- checked for suitability and possibly be
use ation with R22, the refrigeration capacity modified or exchanged.
VARICOOL semi-hermetic (up to and energy requirement (with identical In this connection the significantly lower
5.5 kW) compressor displacement) are significant- mass flow of R22 must also be considered.
Single stage semi-hermetic ly higher after the conversion. The tempe-

with (up to 60 kW) rature differences at the evaporator and
Two stage compressors condenser will be much greater and Supplementary BITZER information
(up to 44 kW) abnormal or critical operating conditions (see also http://www.bitzer.de)
Open and semi-hermetic screw com- could even occur.
pressors from 15 to 220 kW nominal Technical Information KT-650
The installation of a compressor with a
motor power (parallel operation to Retrofitting of R12 and R502
smaller displacement (same capacity as
620 kW) for single and two stage refrigerating systems to
with R12) could on the other hand lead to
systems. alternative refrigerants
unstable operation of the evaporator and

9
Chlorine free HFC refrigerants

Comprehensive tests have demonstrated several years. These lubricants are based
R134a as substitute for
that the performance of R134a exceeds on Polyol Ester (POE) and Polyalkylene
R12 and R22 theoretical predictions over a wide range Glycol (PAG).
of compressor operating conditions. They have similar lubrication characteri-
R134a was the first chlorine free (ODP=0) Temperature levels (discharge gas, oil) are stics to the traditional oils, but are more
HFC refrigerant that was tested compre- even lower than with R12 and, therefore, or less hygroscopic, dependent upon the
hensively. It is now used world-wide in substantially lower than R22 values. There refrigerant solubility.
many refrigeration and air-conditioning are thus many potential applications in This demands special care during manu-
units with good results. As well as being air-conditioning and medium temperature facturing (including dehydrating), trans-
used as a pure substance R134a is also refrigeration plants. Good heat transfer port, storage and charging, to avoid che-
applied as a component of a variety of characteristics in evaporators and mical reactions in the plant, such as
blends (see Refrigerant blends, page 13). condensers (unlike zeotropic blends) hydrolysis.
favour particularly an economical use.
R134a has similar thermodynamic pro- PAG based oils are especially critical with
perties to R12: refrigeration capacity, respect to water absorption. Moreover,
Lubricants for R134a and other HFCs
energy requirement, temperature proper- they have a relatively low dielectric
The question of a suitable lubricant for
ties and pressure levels are comparable, strength and for this reason are not very
R134a (and other HFCs described in the
at least in air-conditioning and medium suitable for semi-hermetic and hermetic
following) has been found to be a pro-
temperature refrigeration plants. This refri- compressors. They are therefore mainly
blem. The traditional mineral and synthe-
gerant can therefore be used as an alter- used in car A/C systems with open com-
tic oils are not miscible (soluble) with
native for most R12 applications. pressors, where specific demands are
R134a and are therefore only insufficiently
placed on lubrication and optimum solubi-
For some applications R134a is even transported around the refrigeration
lity is required because of the high oil cir-
preferred as a substitute for R22, an circuit.
culatation rate. In order to avoid copper
important reason being the limitations to Immiscible oil can settle out in the heat
plating, no copper containing materials
the use of R22 in new plants. However, exchangers and prevent heat transfer to
are used in these systems either.
the lower volumetric refrigeration capacity such an extent that the plant can no lon-
of R134a (see Fig. 11/2) requires a larger ger be operated. The rest of the refrigeration industry pre-
compressor displacement than with R22. fers ester oils, for which extensive expe-
There are also limitations in the applica- New lubricants were developed with the rience is already available. The results are
tion with low evaporating temperatures to appropriate solubility and have now generally positive when the water content
be considered. after a long test phase been in use for in the oil does not much exceed 100 ppm.

110 110

105 100 tc 50C


COP tc 50C
COP tc 40C
Relation R134a to R12 (=100%)

Relation R134a to R22 (=100%)

tc 40C
100 90

C C
40 50
tc t c
95 80

Qo
90 70
tc 40C
Qo
tc 50C
85 60

toh 20C toh 20C


80 50
-30 -20 -10 0 10 -20 -10 0 10 20
Evaporation [C] Evapration [C]

Fig. 11/1 R134a/R12 comparison of performance data of Fig. 11/2 R134a/R22 comparison of performance data of
a semi-hermetic compressor a semi-hermetic compressor

10
Chlorine free HFC refrigerants

However, for buses and commercial vehi- especially valid for flexible hoses where tolerate a proportion of chlorine up to a
cles, alternatives are being examined as the requirements call for a minimum few hundred ppm in an R134a system.
hygroscopic lubricants lead to increased residual moisture content and low perme-
The remaining moisture content has
risks due to the permeability of hoses and ability.
however an enormous influence. The
partly through inadequate servicing. An
The plants must be dehydrated with par- essential requirement therefore exists for
alternative to this are the (almost) non-
ticular care and the charging or changing very thorough evacuation (removal of
soluble alkylates where the flow and lubri-
of lubricant must also be done carefully. remaining chlorine and dehydration) and
cating characteristics are improved by
In addition relatively large driers should the installation of generously dimensioned
additives.
be provided, which have also to be driers. Doubtful experience has also been
In the meantime, factory made A/C and matched to the smaller molecule size of found, with systems where the chemical
cooling units are increasingly being R134a. stability was already insufficient with R12
charged with Polyvinyl Ether (PVE) oils. operation e.g. with bad maintenance,
Although they are even more hygroscopic Meanwhile, many years of very positive small drier capacity, high thermal loading.
than POE, on the other hand they are very experience with R134a and ester oils The increased deposition of oil decompo-
resistant to hydrolysis, thermally and che- have been accumulated. For this re- sition products containing chlorine often
mically stable, possess good lubricating frigerant, BITZER offers an unequalled occurs here. These products are released
properties and high dielectric strength. wide range of reciprocating, screw, and by the working of the highly polarized
Unlike POE they do not tend to form scroll compressors. mixture of ester oil and R134a and find
metal soap and thus the danger of capil- their way into the compressor and regulat-
lary clogging is reduced. Converting existing R12 plants ing devices. Conversion should therefore
be limited to systems which are in a good
At the beginning this subject had been
condition.
Resulting design and construction discussed very controversially, several
criteria conversion methods were recommended Restrictions for R134a in mobile air-
and applied. Today there is a general conditioning (MAC) systems
Suitable compressors are required for
agreement on technically and economical-
R134a with a special oil charge, and In future, a new EU Directive will restrict
ly matching solutions.
adapted system components. the use of R134a in MAC systems. Seve-
The normal metallic materials used in CFC Here, the characteristics of ester oils are ral alternative technologies are already
plants have also been proven with ester very favourable. Under certain conditions being developed. See the pertaining
oils; elastomers must sometimes be they can be used with CFC refrigerants, explanations on pages 12 and 31.
matched to the changing situation. This is they can be mixed with mineral oils and

25

20
Supplementary BITZER information
15 concerning the use of R134a
(see also http://www.bitzer.de)
10
Technical Information KT-620
Pressure [bar]

HFC-Refrigerant R134a
6 Technical Information KT-650
R22 Retrofitting of R12 and R502
4 refrigerating systems to alternative
refrigerants
R12
Technical Information KT-510
2
Polyolester oils for reciprocating
R134a compressors
1 Special edition 09.04
A new generation of compact
-40 -20 0 20 40 60 screw compressors optimised
Temperature [C] for R134a
Fig. 12 R134a/R12/R22 comparison of pressure levels

11
Chlorine free (HFC) refrigerants

Alternatives to R134a Low GWP refrigerants questions regarding the long-term stability
in refrigeration circuits under real condi-
tions. So far, laboratory and field trial
For mobile air-conditioning systems The forthcoming ban on the use of R134a have shown positive results.
(MAC) with open drive compressors and in mobile air-conditioning systems within
Critical temperature, pressure level,
hose connections in the refrigerant circuit, the EU has triggered a series of research
discharge gas temperature, and coeffi-
the risk of leakages is considerably higher projects. Apart from the CO2 technology
cient of performance (COP) are only
than with stationary systems. With a view (page 31), specially formulated (synthetic)
slightly different from R134a, and the
to reducing direct emissions in this appli- refrigerants with a very low GWP100
mass flow is approx. 40% (Blend H) or
cation area, an EU Directive (70/156/EC) (< 50) have been developed in the mean-
10% (DP-1) higher.
has therefore been passed. Within the time. They are already being tested in
scope of the Directive, and starting 2011, prototype plants. For usual applications, the cooling
type approvals for new vehicles will only capacity is about 5% lower. But by
be granted if they use refrigerants with a The aim of these projects was to find
means of corresponding system
global warming potential (GWP) of less alternative refrigerants with similar ther-
adaptations, practically identical pull
than 150. Consequently, this excludes modynamic properties as R134a, and the
down and temperature conditions have
R134a which has been used so far in possibility of replacing previous (establish-
been achieved.
these systems (GWP = 1300). ed) materials and lubricants. Current
investigations indicate that conventional In view of the preferred application,
Meanwhile, alternative refrigerants and systems can be adapted to the require- extensive investigations have been and
new technologies are being developed ments with comparably simple measures. are being conducted regarding material
and tested. This also involved a closer compatibility, permeability in hoses,
Early in 2006 two refrigerant blends were
examination of the use of R152a. Since and solubility with lubricants (PAG).
introduced under the names Blend H
some time, the focus has been on spe- Also toxicological tests are being made.
(Honeywell) and DP-1 (DuPont).
cially adapted CO2 plants (see page 31) The results so far are promising, but do
They are, however, not yet commercially
as well as system solutions with socalled not yet permit a concluding assessment.
available.
low GWP refrigerants. The latter will be In the meantime IENOS Fluor has also an- Use of these refrigerants in stationary
described in the following. nounced a corresponding development, air-conditioning and heat pump systems
but detailed information is not published could also be of interest. Here, however,
R152a an alternative so far. leakage rates and therefore the direct
to R134a (?) global warming impact are extremely low.
In the broadest sense, these refrigerants In addition, there are questions regarding
are blends of various fluorinated mol- chemical stability during the generally
Compared to R134a, R152a is very similar ecules. Due to their low hydrogen con- very long running times of such plants,
with regard to volumetric cooling capacity tent, they are not flammable. and the refrigerant costs.
(approx. -5%), pressure levels (approx.
-10%) and energy efficiency. Mass flow, The composition of Blend H has already
vapour density and thus also the pressure been published. It concerns a (near)
drop are even more favourable (approx. azeotropic blend of 1,1,12-tetrafluoro-
-40%). propene (CF3CF=CH2) as major compo-
nent, i.e. an HFC with a chemical double
R152a has been used for many years as a linkage, and trifluoro-methyl iodine (CF3I),
component in blends but not as a single an iodine-containing fluorocarbon.
substance refrigerant till now. Especially
advantageous is the very low global The exact composition of DP-1 has not
warming potential (GWP=140). yet been published (status September
2006). However, present information*
R152a is inflammable due to its low relates to a composition comprising a
fluorine content and classified in safety fluoroolefin combined with at least one
group A2. As a result, increased safety additional component.
requirements demand individual design
solutions and safety measures along with The low GWP100 value of this new refriger-
the corresponding risk analysis. ant generation is associated with the
rapid decomposition of the used blend
For this reason, the use of R152a in MAC components when exposed to the atmos-
systems is rather unlikely. phere. However, this also raises certain * PCT Application WO 2006/094303 A2

12
Refrigerant blends

(see also next section). The development


Refrigerant blends a large supermarket plant with 4
of zeotropes was mainly concentrated semi-hermetics type 4G-20.2 in parallel
on special applications in low temperature could already be commissioned at
and heat pump systems. Actual system the start of 91.
Refrigerant blends have been developed construction remained however the The use of these blends in the most
for existing as well as for new plants with exception. varied systems has been state-of-the-
properties making them comparable alter- art for many years generally with
natives to the previously used substances. A somewhat more common earlier prac- good experiences.
tice was the mixing of R12 to R22 in order
Although the situation is now less complex, to improve the oils return flow and to General characteristics of zeotropic
the range on offer is nevertheless still very reduce the discharge gas temperature blends
extensive. with higher pressure ratios. It was also
As opposed to azeotropic blends (e.g.
It is necessary to distinguish between two usual to add R22 to R12 systems for
R502, R507A), which behave as single
categories: improved performance, or to add hydro-
substance refrigerants with regard to
carbons in the extra low temperature
1. Transitional or service blends evaporation and condensing processes,
range for a better oil transport.
Most of these blends contain HCFC R22 the phase change with zeotropic fluids
as the main constituent. They are prima- This possibility of specific formulation occurs in a gliding form over a certain
rily intended as service refrigerants for of certain characteristics was indeed the range of temperature.
existing plants with view on the phase- main starting point for the development
This temperature glide can be more or
out of R12, R502 and other CFCs. of a new generation of blends.
less pronounced, it is mainly dependent
Corresponding products are offered by As already mentioned earlier, no directly upon the boiling points and the percent-
various manufacturers, the practical ex- comparable substitute for R502 and R22 age proportions of the individual compo-
perience covering the necessary steps is available from the chlorine free single nents. Certain supplementary definitions
of conversion procedure are mainly substance series of alternative refriger- are also being used, depending on the
available. ants. A similar situation can be stated for effective values, such as near-azeotrope
However, the same legal requirements R13B1 and R503. or semi-azeotrope for less than 1 K
apply for the use and phase-out regula- glide.
tions of these blends as for R22 If flammability is unacceptable, and toxi-
(see page 8). cological certainty is required and in addi- This means in practice already a small
tion, application range, COP, pressure and increase in temperature in the evaporation
2. Chlorine free HFC blends temperature conditions are to be compar- phase and a reduction during condensing.
These are long term substitutes for the able, the only substitutes which remain In other words, based on a certain pres-
refrigerants R502, R22, R13B1 and for the long term, in addition to R134a for sure the resulting saturation temperatures
R503. Above all, R404A, R507A, R407C R12, are blends. differ in the liquid and vapour phases
and R410A, are already being used to (Fig. 13).
a great extent. Substitutes for R502 had first priority,
as it was used in larger quantities and is To enable a comparison with single sub-
One group of these HFC blends also
already effected by the phase-out regula- stance refrigerants, the evaporating and
contains hydrocarbon additives. The lat-
tions in many countries. The following condensing temperatures have been
ter exhibit a particularly good solubility
discussion therefore, deals first with the mostly defined as mean values. As a con-
with lubricants, and under certain condi-
established alternatives for this refrigerant sequence the measured subcooling and
tions they allow the use of conventional
and the results from the extensive appli- superheating conditions (based on mean
oils. In many cases, this opens up possi-
cations in real systems. values) are unreal. The effective result
bilities for the conversion of existing
related to dew and bubble temperature
(H)CFC plants to chlorine-free refriger- Another focal point are alternatives for is less in each case.
ants (ODP = 0) without the need for an R22.
oil change. These factors are very important when
BITZER has already accumulated assessing the minimum superheat at the
Two and three component blends already extensive experience with the new gen- compressor inlet (usually 5 to 7 K) and the
have a long history in the refrigeration eration of blends. Laboratory and field quality of the refrigerant after the liquid
trade. A difference is made between the so testing was commenced at an early receiver.
called azeotropes (e.g. R502, R507A) stage so that basic information was
with thermodynamic properties similar obtained for the optimizing of the mix- With regard to a uniform and easily com-
to single substance refrigerants, and ing proportions and for testing suitable prehensible definition of the rated com-
zeotropes with gliding phase changes lubricants. Based on this data, pressor capacity, the revised standards

13
Refrigerant blends

25

20

Isotherms 15
tcm B B1
C1
C tg
e
Lin

10
le

Pressure [bar]
Dew line
Pressure

bb

R403B R502
Bu

D1 D tom
4
tg A A1 R404A

2
tg Temperature glide
tcm Mean condensing temperature
tom Mean evaporating temperature
1
-40 -20 0 20 40 60
Enthalpy Temperature [C]

Fig. 13 Evaporating and condensing behavior of zeotropic blends Fig. 14 Pressure levels of blends in comparison to R502

EN12900 and ARI540 are applied. Evapo- It is therefore recommended that soldered Since all blends contain at least one
rating and condensing temperatures refer or welded joints should be used in these flammable component, the entry of
to saturated conditions (dew points). sections. air into the system must be avoided.
A critical shift of the ignition point can
Evaporating temperature according to Extended investigations have in the occur under high pressure and evacu-
point A (Fig. 13). meantime shown that the effect of leak- ating when a high proportion of air is
Condensing temperature according to age leads to less serious changes in con- present.
point B (Fig. 13). centration than was previously thought. It
is in any case certain that the following The use of blends with a significant
Also in this case the assessment of the substances which are dealt with here can- temperature glide is not recommended
effective superheating and subcooling not develop any flammable mixtures, for plants with flooded evaporators.
temperatures will be simplified. either inside or outside the circuit. Essen- A large concentration shift is to be
It must however be considered that the tially similar operating conditions and expected in this type of evaporator,
actual refrigeration capacity of the system temperatures as before can only be and as a result also in the circulating
can be higher than the rated compressor obtained by supplementary charging with refrigerant mass flow.
capacity. This is partly due to an effec- the original refrigerant in the case of a
tively lower temperature at the evaporator small temperature glide.
inlet.
Further conditions/recommendations
A further characteristic of zeotropic refrig- concerning the practical handling of
erants is the potential concentration shift blends must also be considered:
when leakage occurs. Refrigerant loss in
the pure gas and liquid phases is mainly The plant always has to be charged
non-critical. Leaks in the phase change with liquid refrigerant. When vapour is
areas, e.g. after the expansion valve, taken from the charging cylinder shifts
within the evaporator and condenser/ in concentrations may occur.
receiver are considered more significant.

14
Service blends

Service blends with the variaions with regard to identical refrigerat- Resulting design criteria/
ion capacity as for R502 the laboratory Converting existing R502 plants
basic component R22* as
measurements showed a significantly
substitutes for R502 increased discharge gas temperature (Fig.
The compressor and the components
which are matched to R502 can remain in
15), which above all, with higher suction
the system in most cases. The limitations
gas superheat (e.g. supermarket use)
These refrigerants belong to the group of in the application range must however be
leads to limitations in the application range.
Service blends and are offered under considered: Higher discharge gas temper-
the designations R402A/R402B* (HP80/ On the other hand a higher proportion of ature as for R502 with R402B**, R403A**
HP81 DuPont), R403A/R403B* (formerly R125 or R218, which has the effect of and R408A** or higher pressure levels
ISCEON 69S/69L***) and R408A* reducing the discharge gas temperature with R402A** and R403B**.
(Forane FX10 Arkema). to the level of R502, results in somewhat Due to the good solubility characteristics
The basic component is in each case higher cooling capacity (Fig. 16). of R22 and R290 an increased danger
R22, the high discharge gas temperature exists, that after conversion of the plant,
of which is significantly reduced by the With regard to material compatibility the possible deposits of oil decomposition
addition of chlorine free substances with blends can be judged similarly to (H)CFC products containing chlorine may be dis-
low isentropic compression exponent refrigerants. The use of conventional refri- solved and find their way into the com-
(e.g. R125, R143a, R218). A characteristic geration oil (preferably semi or full synthetic) pressor and regulating devices. Systems
feature of these additives is an extraordi- is also possible due to the R22 and R290 where the chemical stability was already
narily high mass flow, which enables the proportions. insufficient with R502 operation (bad
mixture to achieve a great similarity to R502. maintenance, low drier capacity, high
Apart from the positive aspects there are
R290 (Propane) is added as the third
also some disadvantages. These substan-
component to R402A/B and R403A/B to
ces can also only be seen as alternatives * When using blends containing R22, legal regu-
improve miscibility with traditional lubri-
for a limited time. The R22 proportion has lations are to be observed, see also page 8.
cants as hydrocarbons have especially ** Classification according to ASHRAE nomenclature
(although low) an ozone depletion potential. *** Meanwhile, R403A (ISCEON 69S Rhodia) is no
good solubility characteristics.
The additional components R125, R143a longer available in the market. However, for
development-historic reasons of service blends,
For these blends two variations are offered and R218 still have a comparatively high this refrigerant will continue to be covered in
in each case. When optimizing the blend global warming potential. this report.

170
R22
165 [%]
115
160 to -35C
to -35C tc 40C
155
Comparison of performance

tc 40C 110
Discharge gas temp. [C]

toh 20C
toh 20C
150
105
145
R403A

140
100
135
R402B (HP81)

R402B (HP81)
R402A (HP80)

R402A (HP80)
R408A (FX10)

R408A (FX10)

95
R403A (69S)

R403A (69S)
R403B (69L)

R403B (69L)

130 R502
125
R403B

90
R502

R502

120

115 85
0 20 40 60
Content of R218 [%] Qo COP
Fig. 15 Effect of the mixture variation upon the discharge Fig. 16 Comparison of the performance data of a semi-hermetic
gas temperature (Example: R22/R218/R290) compressor

15
Service blends

thermal loading) are particularly at risk. the possibility to make an oil change, For further details, see the refrigerant
Before conversion generously dimen- which is for example not the case with manufacturer's Guidelines.
sioned suction gas filters and liquid line most hermetic type compressors.
driers should therefore be fitted for clean- Economical considerations also arise, Resulting design criteria/
ing and after approximately 100 hours especially with older plants where the Converting existing R12 plants
operation an oil change should be made; effort in converting to R134a is relatively Compressors and components can mostly
further checks are recommended. high. The chemical stability of such plants remain in the system. However, when
The operating conditions with R502 is also often insufficient and therefore the using R413A the suitability must be
(including discharge gas temperature and chance of success is very questionable. checked against R134a. The actual retro-
suction gas superheat) should be noted Therefore Service blends are also avail- fit measures are mainly restricted to
so that a comparison can be made with able for such plants as an alternative to changing the refrigerant (possibly oil) and
the values after conversion. Depending R134a and are offered under the designa- a careful check of the superheat setting of
upon the results regulating devices should tions R401A/R401B (MP39/MP66 the expansion valve. A significant temper-
possibly be reset and other additional DuPont), R409A (Forane FX56 Arkema, ature glide is present due to the relatively
measures should be taken as required. Solvay). large differences in the boiling points of
The main components are the HCFC the individual substances (Fig. 34, page
refrigerants R22, R124 and/or R142b. 35), which demands an exact knowledge
The basic suitability of BITZER com- Either HFC R152a or R600a (Isobutane) of the saturation conditions (can be
pressors has already been established is used as the third component. Operation found from vapour tables of refrigerant
by laboratory and field tests. However with traditional lubricants (preferably semi manufacturer) in order to assess the
as the result of a conversion is very or full synthetic) is also possible due to effective suction gas superheat.
much dependent upon the previous the major proportion of HCFC.
condition of the plant (see above expla- In addition the application range must
A further service blend is offered under also be observed.
nation), the judgement of a possible the designation R413A (ISCEON MO49
guarantee claim must be made subject Different refrigerant types are required for
DuPont). The constituents consist of the high and low evaporating temperatures or
to the examination of the compressor. chlorine free substances R134a, R218, distinct capacity differences must be con-
and R600a. In spite of the high R134a sidered (data and application ranges see
content the use of conventional lubricants pages 34 to 37). This is due to the steeper
Supplementary BITZER information is possible because of the relatively low capacity characteristic, compared to R12.
concerning the use of retrofit blends polarity of R218 and the favourable solu-
bility of R600a. Oil migration may, how- Due to the partially high proportion of R22
(see also http://www.bitzer.de)
ever, result in systems with a high oil especially with the low temperature blends,
Technical Information KT-650 circulation rate and/or a large liquid volume the discharge gas temperature with some
Retrofitting of R12 and R502 in the receiver for example if no oil sep- refrigerants is significantly higher than
refrigerating systems to arator is installed. with R12. The application limits of the
alternative refrigerants compressor should therefore be checked
If insufficient oil return to the compressor before converting.
is observed, the refrigerant manufacturer The remaining application criteria are simi-
recommends replacing part of the original lar to those for the substitute substances
oil charge with ester oil. But from the for R502 which have already been men-
compressor manufacturer's view, such a tioned.
measure requires a very careful examina-
tion of the lubrication conditions. For
Service blends as substi- example, if increased foam formation in
tutes for R12 (R500) the compressor crankcase is observed,
a complete change to ester oil will be
Although as experience already shows, necessary. Moreover, under the influence Supplementary BITZER information
R134a is also well suited for the conver- of the highly polarized blend of ester oil concerning the use of retrofit blends
sion of existing R12 plants, the general and HFC, the admixture of or conversion (see also http://www.bitzer.de)
use for such a retrofit procedure is not to ester oil leads to increased dissolving Technical Information KT-650
always possible. Not all compressors of decomposition products and dirt in the Retrofitting of R12 and R502
which have previously been installed are pipework. Therefore, generously dimen- refrigerating systems to alternative
designed for the application with R134a. sioned suction clean-up filters must be refrigerants
In addition a conversion to R134a requires provided.

16
Chlorine free R502 and R22 alternatives (blends)

which results in a similar, with even a ten- The newly developed POE oils can be
R404A and R507A as
dency to be lower, discharge gas temper- used as lubricants; the suitability of vari-
substitutes for R502 ature to R502 (Fig. 17). The efficient appli- ous alternatives is being investigated as
and R22 cation of single stage compressors with well (see pages 9 and 10).
low evaporating temperatures is therefore
The relatively high global warming poten-
These blends are substitutes which are guaranteed.
tial (GWP100 = 3260 3300) which is
absolutely chlorine free (ODP=0) and are
Due to the similar boiling points for R143a mainly determined by the R143a and
therefore long term alternatives for R502
and R125, with a relatively low proportion R125 is something of a hitch. It is how-
as well as for R22 in medium and low
of R134a, the temperature glide with the ever improved compared to R502
temperature ranges.
ternary blend R404A within the relevant (GWP100 = 5600) and which with regard
A composition which was already application range is less than one Kelvin. also to the favourable energy requirement
launched at the beginning of 92 is known The characteristics within the heat leads to a reduction of the TEWI value.
under the trade name Suva HP62 exchangers are not therefore very different Other improvements are possible in
(DuPont). Long term use has shown as with azeotropes. The results obtained this respect due to further developed
good results. so far from heat transfer measurements system control including for example the
Further blends were traded as Forane show favourable conditions. controlled lowering of the condensing tem-
FX70 (Atofina) and Genetron AZ50 perature with low ambient temperatures.
R507A is a binary substance combination
(Allied Signal/Honeywell) or Solkane 507
which even gives an azeotropic character-
(Solvay). In the mean time HP62 and FX70 Resulting design criteria
istic over a relatively wide range. The con-
have been listed in the ASHRAE nomen-
ditions therefore tend to be even better. The system technology can be based on
clature as R404A and AZ50 as R507A.
the experience with R502 over a wide
The performance found in laboratory
The basic components belong to the HFC area. On the thermodynamic side, a heat
tests (Fig. 18) gives hardly any difference
group, where R143a belongs to the flam- exchanger between the suction and liquid
between the various substances and show
mable category. Due to the combination line is recommended as this will improve
a large amount of agreement with R502.
with a relatively high proportion of R125 the refrigeration capacity and COP.
This justifies the good market penetration
the flammability is effectively counteract-
of these substitutes. The availability of the refrigerants is guar-
ed and also in the case of leakage.
Questions concerning material compatibil- anteed.
A feature of all three ingredients is the ity are manageable; experience with other
very low isentropic compression exponent HFCs justifies a positive assessment.
Discharge gas temp. of R404A relative difference to R502 [K]

[%] to -35C
105 tc 40C
+10
toh 20C
Comparison of performance

toh 20C 100

0
95

tc 55C
90
-10
tc 40C
85
R404A

R507A

R404A

R507A
R502

R502

-20 80
-40 -30 -20 -10
Evaporating [C] Qo COP
Fig. 17 R404A/R502 comparison of discharge gas temperatures of a semi- Fig. 18 Comparison of performance data of a semi-hermetic
hermetic compressor compressor

17
Chlorine free R502 and R22 alternatives (blends)

Apart from laboratory investigations pressed, at the same time the large differ-
R407A and R407B as
BITZER has been co-ordinating a wide ences in the boiling points with a high
program of field tests to obtain the nec-
substitutes for R502 proportion of R134a leads to a larger tem-
essary operating experience over a perature glide.
wide area for several years. Alternatively to the earlier described sub- The main advantage of R32 is the extraor-
BITZER offers the whole program of stitutes additional mixture versions have dinarily low global warming potential
reciprocating, scroll and screw com- been developed based on R32 which is (GWP100 = 650) so that even in combina-
pressors including the suitable oils for chlorine free (ODP=0) and flammable like tion with R125 and R134a it is significant-
these blends. R143a. ly lower than with the R143a based alter-
The refrigerant R32 is also of the HFC type natives mentioned above.
Converting existing (H)CFC plants
and primarily seen as a candidate for R22
Comprehensive measurements made with
Experience gained in investigative pro- alternatives (page 20). Due to the extent
R32 containing blends in the BITZER lab-
grams shows that qualified conversions of the blend variations however comparable
oratory do show certain capacity reduc-
are possible. However, major expenditure thermodynamic characteristics to R502
tions compared to R502 with low evapor-
may be necessary depending on the sys- can also be obtained.
ating temperatures, the COP however
tem design.
Such kind of refrigerants were at first in shows less deviation (Fig. 20). The TEWI
the market under the trade name KLEA values are relatively low, together with the
Supplementary BITZER information 60/61 (ICI) and are listed as R407A*/ R407B* advantageous global warming potential.
concerning the use of HFC blends in the ASHRAE nomenclature.
Where these favourable prospects are
(see also http://www.bitzer.de) The necessary conditions, however, for confirmed in real applications is subject
Technical Information KT-630 R502 alternatives containing R32 are not to the system criteria.
HFC Refrigerant Blends quite as favourable compared to the
Technical Information KT-650 R143a based substitutes as dealt with An important factor is the significant tem-
Retrofitting of R12 and R502 earlier. The boiling point of R32 is very perature glide which can have a negative
refrigerating systems to alternative low at -52C, in addition the isentropic influence upon the capacity/temperature
refrigerants compression exponent is similarly high as difference of the evaporator and condenser.
Technical Information KT-510 with R22. To match the characteristics of In order to closer examine this factor
Polyolester oils for R502 therefore requires relatively high investigations concerning the behaviour
reciprocating compressors proportions of R125 and R134a. The flam- of heat exchangers (including design/con-
mability of the R32 is thus effectively sup- struction) have already been carried out.
Discharge gas temp. of R407A/B relative difference to R502 [K]

[%] to -35C
105 tc 40C
tc 40C
+20 toh 20C
toh 20C
100
Comparison of performance

R407A
95
+10

90

0
80
R407B
R407A

R407B

R407A

R407B
R502

R502

75
-10
-40 -30 -20 -10
Evaporation [C] Qo COP
Fig. 19 Comparison of discharge gas temperature of a semi-hermetic Fig. 20 Comparison of performance data of a semi-hermetic compressor
compressor

18
Chlorine free R502 and R22 alternatives (blends)

With regard to the material compatibility, The material compatibility is comparable


Supplementary BITZER information
R32 blends can be assessed similarly to to the blends mentioned previously, the
concerning the use of HFC blends
the HFC substitutes described before; the same applies to the lubricants, as well.
(see also http://www.bitzer.de)
same applies to the lubricants. On account of the good solubility of
Technical Information KT-630 R600a, conventional lubricants can also
Despite the relatively high proportion of HFC Refrigerant Blends be used under favourable circumstances.
R125 and R134a in the R32 blends aimed Technical Information KT-650
at R502 characteristics, the discharge gas Retrofitting of R12 and R502 In particular, advantages result during the
temperature is somewhat higher than with refrigerating systems to alternative conversion of existing R502 and R22
the R143a based alternatives. As a result refrigerants systems as mentioned above. However,
certain limitations occur in the application Technical Information KT-510 for plants with high oil circulation rates
range. Polyolester oils for and/or large liquid charge in the receiver,
From this point of view, but also with reciprocating compressors it is possible for oil migration to occur
regard to the efficiency an intelligent con- for example if no oil separator is installed.
trol is recommended for controlled float- If insufficient oil return to the compressor
ing of the condensing pressure with low is observed, the refrigerant manufacturer
ambient temperatures. recommends replacing part of the original
2-stage compressors can be applied very R422A as substitute for oil charge with ester oil. But from the
efficiently where especially large lift con- R502 and R22 compressor manufacturer's view, such a
ditions are found. An important advantage measure requires a very careful examina-
thereby is the use of a liquid subcooler. tion of the lubrication conditions. For
example, if increased foam formation in
Amongst other aims, R422A (ISCEON
Resulting design criteria the compressor crankcase is observed,
MO79 DuPont) was developed in order
a complete change to ester oil* will be
to obtain a chlorine-free refrigerant
The experience with R502 and R22 can necessary. Moreover, under the influence
(ODP = 0) for the simple conversion of
be used for the plant technology in many of the highly polarized blend of ester oil
existing medium and low temperature refri-
respects, considering the temperature and HFC, the admixture of or conversion
geration systems using R502 and R22.
glide as well as the difference in the to ester oil leads to increased dissolving
thermodynamic properties. This is espe- For this, it was necessary to formulate a of decomposition products and dirt in the
cially the case for designing and con- refrigerant with comparable performance pipework. Therefore, generously dimen-
structing heat exchangers and expansion and energy efficiency to that of R404A, sioned suction clean-up filters must be
valves. R507A, and R22, which also permits the provided.
The refrigerants are available. Occassion- use of conventional lubricants. For further details, see the refrigerant
ally, individual selection will be required manufacturer's Guidelines.
This pertains to a zeotropic blend of the
for the necessary components. From a thermodynamic point of view
basic components R125 and R134a with a
* Meanwhile, R407A/B have only limited availability small addition of R600a. Due to its relati- a heat exchanger between suction and
in the market. Due to the historical development of
HFC blends they will, however, still be considered vely high R134a percentage, the tempera- liquid line is recommended, thereby
in this Report. ture glide (Fig. 34) lies higher than for improving the cooling capacity and
R404A, but lower than other refrigerants coefficient of performance. Besides this
BITZER offers a complete range of semi- with the same component blends such the resulting increase in operating tem-
hermetic reciprocating compressors as R417A and R422D (see page 22). peratures leads to more favourable lubri-
including suitable oil for these blends. cating conditions (lower solubility).
The adiabatic exponent, compared to
Converting existing CFC plants R404A and R507A, is smaller and therefo-
re the discharge gas and oil temperatures * Always applies for screw compressors.
A comprehensive test program has been of the compressor, too. Under extreme Furthermore, an individual check regarding
possible additional measures will be necessary.
completed in which practicability was low temperature conditions this can be
proven. Because of the abovementioned advantageous. In cases of low pressure
Bitzer compressors are suitable for
criteria, however, no general guidelines ratio and suction gas superheat this can
R422A. An individual selection is
can be established. Each case must be negative due to increased refrigerant
possible upon demand.
therefore be examined individually. solution if ester oil is used.

19
Chlorine free R22 alternatives (blends)

Chlorine free relatively low (GWP100 = 1520), which is a


R407C as substitute
good presupposition for favourable TEWI
R22 alternatives for R22 values.
As the HCFC refrigerant R22 (ODP=0.05) Blends of the HFC refrigerants R32, R125 The high temperature glide is a disadvan-
is still widely accepted only as a transi- and R134a are seen as the favourite tage for usual applications which requires
tional solution, a number of chlorine-free candidates for shortterm substitution for appropriate system design and can have
(ODP=0) alternatives have been devel- R22 their performance and efficiency a negative influence on the efficiency of
oped and tested extensively. They are are very similar (Fig. 21). At first two the heat exchangers (see explanations on
already being used on a large range of blends of the same composition have pages 13/14).
applications. been introduced under the trade names Due to the properties mentioned, R407C
Experience shows, however, that none of AC9000* (DuPont) and KLEA66* (ICI). They is preferably an R22 substitute for air-
these substitutes can replace the refriger- are listed in the ASHRAE nomenclature conditioning systems and (within certain
ant R22 in all respects. Amongst other as R407C. In the meantime there are also limitations) also for medium temperature
things there are differences in the volumet- further blend varieties (e.g. R407D**/ refrigeration. In low temperature refrigera-
ric refrigeration capacity, restrictions in R407E) with somewhat differing com- tion, because of the high proportion of
possible applications, special requirements positions, whose properties have been R134a, a significant drop in cooling
in system design or also considerably dif- optimized for particular applications. capacity and COP is to be expected.
fering pressure levels. So various alterna- Unlike the R502 substitutes with identical There is also the danger of an increased
tives come under consideration according blend components (see pages 18/19), the R134a concentration in the blend in evap-
to the particular operating conditions. R22 substitutes under consideration con- orators, with consequential reduction in
Apart from the single-component HFC tain higher proportions of R32 and R134a. performance and malfunctioning of the
refrigerant R134a, these are mainly blends A good correspondence with the proper- expansion valve (e.g. insufficient suction
(different compositions) of the compo- ties of R22 in terms of pressure levels, gas superheat).
nents R32, R125, R134a, R143a, and mass flow, vapour density and volumetric Material compatibility can be assessed as
R600(a). The following description mainly refrigeration capacity is thus achieved. In similar to that of the blends discussed pre-
concerns the development and potential addition, the global warming potential is viously; the same applies to the lubricants.
applications of these. The halogen-free
substitutes NH3, propane and propylene
as well as CO2 should also be considered, * Previous trade names are not used any more. ** Because of the high proportion (70%) of R134a
contained in R407D this refrigerant cannot be
however, specific criteria must be applied regarded as an alternative to R22, but rather as a
for their use (described from page 23). substitute to R12 for low temperature cooling.

110 25

20
105
C
t c 40 15
Qo
t c 50C
Relation R407C to R22 (=100%)

R407C
100
tc 40C 10
R22
Pressure [bar]

tc 50C
COP
95
6

90 4

85
2

toh 20C
80 1
-20 -10 0 10 20 -40 -20 0 20 40 60
Evaporation [C] Temperature [C]
Fig. 21 R407C/R22 comparison of performance data of a semi-hermetic Fig. 22 R407C/R22 comparison of pressure levels
compressor

20
Chlorine free R22 alternatives (blends)

Resulting design criteria BITZER can supply a range of semi-her- parison to R22, but with the consequence
metic reciprocating, screw and scroll of a proportional rise in system pressure.
With regard to system technology, previ-
ous experience with R22 can only be compressors including suitable oil
At high condensing temperatures, energy
utilized to a limited extent. The distinctive for R407C.
consumption/COP initially seems to be
temperature glide requires a particular less favourable than with R22. This is
design of the main system components, mainly due to the thermodynamic proper-
e.g. evaporator, condenser, expansion Converting existing R22 plants
ties. On the other hand, very high isen-
valve. In this context it must be consid- A series of plants have been converted tropic efficiencies are achievable (with
ered that heat exchangers should prefer- for test purposes. Because of the above reciprocating and scroll compressors),
ably be laid out for counterflow operation mentioned criteria, however, no general whereby the differences are lower in
and with optimized refrigerant distribution. guidelines can be defined. Each case reality.
There are also special requirements with must therefore be examined individually.
regard to the adjustment of regulating Added to this are the high heat transfer
devices and service handling. coefficients in evaporators and con-
densers determined in numerous tests,
Furthermore, the use in systems with with resulting especially favourable oper-
flooded evaporators is not recommended ating conditions. With an optimized
as this would result in a severe concentra- design, it is quite possible for the system
tion shift and layer formation in the evap- to achieve a better overall efficiency than
orator. R410A as substitute with other refrigerants.
for R22
Because of the negligible temperature
In addition to laboratory investigations
glide (< 0.2 K), the general usability can
BITZER was also co-ordinating a com-
In addition to R407C, there is a near be seen similar to a pure refrigerant.
prehensive program of field tests from
which the necessary operating experi- azeotropic blend being offered with the
The material compatibility is comparable
ence could be gained over a wide area. ASHRAE designation R410A. It is widely
to the previously discussed blends and
These tests have already demonstrated used already, mainly in air conditioning
the same applies for the lubricants. How-
clearly that reliable compressor opera- applications.
ever, the pressure levels and the higher
tion depends entirely on the quality and An essential feature indicates nearly 50% specific loads on the system components
design of the system. higher cooling capacity (Fig.23) in com- need to be taken into account.

150
Qo 35
tc 40C 30
140
tc 50C
25
R410A
130 20
Relation R410A to R22 (=100%)

15
Pressure [bar]

120 R22

10
110

6
100
COP tc 40C
4
90 3
tc 50C
toh 20C
80 2
-20 -10 0 10 20 -40 -20 0 20 40 60
Evaporation [C] Temperature [C]

Fig. 23 R410A/R22 comparison of performance data of a semi-hermetic Fig. 24 R410A/R22 comparison of pressure levels
compressor

21
Chlorine free R22 alternatives (blends)

Resulting design criteria and/or a large volume of liquid in the


R417A and R422D
receiver oil migration may result.
The fundamental criteria for HFC blends as substitutes for R22
also apply to the system technology with In such cases, additional measures are
R410A, however the extreme high pres- necessary. For further notes, see the
The same as for R422A (page 19), one of
sure levels have to be considered (43C chapter R422A as substitute for R502
the aims for both developments was to
condensing temperature already corre- and R22 (page 19).
provide chlorine-free refrigerants
sponds to 26 bar abs.).
(ODP = 0) for the simple conversion
BITZER compressors are suitable
Compressors and other system compo- of existing R22 plants.
for R417A and R422D.
nents of standard design have substan-
R417A was introduced to the market sev- An individual selection is possible
tial limitations for the application of this
eral years ago, and is also offered under upon demand.
refrigerant. However, due to the favou-
the trade name ISCEON MO59 (DuPont).
rable properties of R410A considerable
This substitute for R22 contains the blend
effort is taken for the development of
components R125/R134a/R600, and
suitable products.
therefore differs considerably from e.g. FX100 as a
When considering to cover usual R22 R407C with a correspondingly high pro- substitute for R22
application ranges, the significant differ- portion of R32.
ences in the thermodynamic properties FX100 (Arkema) presumable ASHRAE
Another blend version with the same main
(e.g. pressure levels mass and volume nomenclature R427A replaces the pre-
components, but with R600a as hydrocar-
flow, vapour density) must be evaluated. vious FX90. One reason for the changed
bon additive, was introduced early in
This also requires considerable construc- 2003 (trade name ISCEON MO29), and formulation was the classification of FX90
tional changes to compressors, heat meanwhile is listed as R422D in the in the safety group A1/A2. FX100, how-
exchangers, and controls, as well as ASHRAE nomenclature. Because of its ever, is classified in A1.
measures of tuning vibrations. low R134a content, the volumetric cooling This R22 substitute is offered for the
capacity as well as the pressure levels are conversion of existing R22 systems
In addition, safety requirements are con-
higher than with R417A. This results in (preferably air conditioning plants) for
cerned also affecting the quality and
different performance parameters and which a Zero ODP solution is requested.
dimensions of piping and flexible tube
emphasis in the application range. This refrigerant is a mixture with base
elements (for condensing temperatures
of approx. 60C / 40 bar). Like R407C, both refrigerants are zeo- components R32/R125/R143a/R134a.
tropic blends with a significant tempera- In spite of the blend composition based
Another criterion is the relatively low criti-
ture glide. In this respect the criteria on pure HFC refrigerants, the manufactu-
cal temperature of 73C. Irrespective of
described in connection with R407C are rer states that a simplified conversion pro-
the design of components on the high
also valid. cedure is possible. Accordingly, when
pressure side, the condensing temperature
is thus limited. Despite similar refrigeration capacity there converting from R22 to FX100, all it takes
are fundamental differences in thermody- is a replacement of the original oil charge
BITZER has done comprehensive namic properties and in oil transport with ester oil. Additional flushing sequen-
research with R410A and accompanied behaviour. The high proportion of R125 ces are not required, as proportions of
by a series of field tests. In the mean- causes a higher mass flow than with up to 15% of mineral oil and/or alkyl
time, BITZER offers two series of Octa- R407C, a lower discharge gas tempera- benzene have no significant effect on
gon and scroll compressors for R410A ture and a relatively high superheating oil circulation in the system.
including the suitable oil. enthalpy. These properties indicate that However, it must be taken into account
there could be differences in the optimiza- that under the influence of the highly
tion of system components and a heat polarized mixture of ester oil and HFC
exchanger between liquid and suction increased dissolving of decomposition
lines might be of advantage. products and dirt in the pipework is
Despite the predominant proportion of caused. Therefore, generously dimen-
HFC refrigerants the use of conventional sioned suction clean-up filters must be
lubricants is possible to some extent provided.
because of the good solubility properties
An individual compressor selection
of the R600(a) constituent. However, in
is possible upon demand.
systems with a high oil circulation rate

22
Halogen free refrigerants

the regulation of the refrigerant injection These measures significantly increase


NH3 (Ammonia)
more difficult with small capacities. the expenditure involved for NH3 plants,
as substitute for R22 especially in the medium and smaller
A further criteria which must be considered capacity area.
is the corrosive action on copper contain-
ing materials; pipe lines must therefore Efforts are therefore being made world-
The refrigerant NH3 has been used for more
be made in steel. Apart from this the wide to develop simpler systems which
than a century in industrial and larger refri-
development of motor windings resistant can also be used in the commercial area.
geration plants. It has no ozone depletion
to NH3 is also hindered. Another difficulty
potential and no direct global warming
arises from the electrical conductivity of A part of the research programs is dealing
potential. The efficiency is at least as good
the refrigerant with higher moisture content. with part soluble lubricants, with the aim
as with R22, in some areas even more
of improving oil circulation in the system.
favourable; the contribution to the indirect Additional characteristics include toxicity Simplified methods for automatic return of
global warming effect is therefore small. and flammability, which require special non-soluble oils are also being examined
In addition it is incomparably low in price. safety measures for the construction and as an alternative.
Summarized, is this then an ideal refrige- operation of such plants.
rant and an optimum substitute for R22 or
an alternative for HFCs!? NH3 has indeed Resulting design and construction BITZER is strongly involved in these
very positive features, which can also be criteria projects and has a large number of
mainly exploited in large refrigeration plants. compressors operating. The experien-
Based on the present state of technolo- ces up to now have revealed that
Unfortunately there are also negative gy, industrial NH3 systems demand total- systems with part soluble oils are diffi-
aspects, which restrict the wider use in ly different plant technology, compared to cult to govern. The moisture content in
the commercial area or require costly and usual commercial systems. the system has an important influence
sometimes new technical developments.
on the chemical stability of the circuit
Due to the insolubility with the lubricating
A disadvantage with NH3 is the high isen- and the wear of the compressor. Besi-
oil and the specific characteristics of the
tropic exponent (NH3=1.31 / R22= 1.18 / des, high refrigerant dilution in the oil
refrigerant, high efficiency oil separators
R12=1.14), that results in a discharge (wet operation, insufficient oil tempera-
and also flooded evaporators with gravity
temperature which is even significantly ture) leads to strong wear on the bea-
or pump circulation are usually employed.
higher than that of R22. Single stage rings and other moving parts. This is
Because of the danger to the public and
compression is therefore already subject to due to the enormous volume change
to the product to be cooled, the evapora-
certain restrictions below an evaporating when NH3 evaporates in the lubricated
tor often cannot be installed directly at
temperature of around -10C. areas.
the cold space. The heat transport must
The question of suitable lubricants is also then take place with a secondary refrige- These developments are being done on
not satisfactorily solved for smaller plants rant circuit. a widely used program. The emphasis
in some kinds of applications. The oils used is also on alternative solutions for non-
previously were not soluble with the refriger- Two stage compressors or screw com- soluble lubricants.
ant. They must be separated with compli- pressors with generously sized oil coolers,
cated technology and seriously limit the must already be used at medium pressure
use of direct expansion evaporators due ratios, due to the unfavorable thermal Besides to this various equipment manu-
to the deterioration in the heat transfer. behaviour. facturers have developed special evapo-
rators, where the refrigerant charge can
Special demands are made on the thermal Refrigerant lines, heat exchangers and fit- be significantly reduced.
stability of the lubricants due to the high tings must be made of steel; larger size
discharge gas temperatures. This is espe- pipe lines are subject to examination by a
In addition to this there are also solutions
cially valid when automatic operation is certified inspector.
for the sealing of NH3 plants. This deals
considered where the oil should remain
Corresponding safety measures and also with compact liquid chillers (charge below
for years in the circuit without losing any
special machine rooms are required 50 kg), installed in a closed container and
of its stability.
depending upon the size of the plant and partly with an integrated water reservoir
NH3 has an extraordinarily high enthalpy the refrigerant charge. to absorb NH3 in case of a leak. This type
difference and as a result a relatively of compact unit can be installed in areas
small circulating mass flow (approximately The refrigeration compressor is usually of which were previously reserved for plants
13 to 15% compared to R22). This feature open design, the drive motor is a sepa- with halogen refrigerants due to the safety
which is favourable for large plants makes rate component. requirements.

23
Halogen free refrigerants

It is still too early to give a final judgement Conversion of existing plants The result of this research project is a
concerning the extended use of compact The refrigerant NH3 is not suitable for the refrigerant blend of NH3 (60%) and dime-
NH3 systems, in place of plants with HFC thyl ether DME (40%), developed by the
conversion of existing (H)CFC plants; they
refrigerants and mainly conventional tech- Institut fuer Luft- und Kaeltetechnik,
must be constructed completely new with
nology. From the purely technical viewpo- Dresden, Germany (ILK), that has been
all components.
int and presupposing an acceptable price tested in a series of real systems. As a
level, it is anticipated that a wider range largely inorganic refrigerant it received the
Supplementary BITZER information
of products will become available. designation R723 due to it its average
concerning the application of NH3
molecular weight of 23 kg/kmol in accor-
(see also http://www.bitzer.de)
dance to the standard refrigerant nomen-
The production program from BITZER Technical Information KT-640 clature.
today includes an extensive selection Application of Ammonia (NH3)
of optimized NH3 compressors for as an alternative refrigerant DME was selected as an additional com-
various types of lubricants: ponent for its properties of good solubility
Single stage open reciprocating and high individual stability. It has a boi-
compressors (displacement 19 to R723 (NH3/DME) as an ling point of -26C, a relatively low adia-
152 m3/h with 1450 rpm) for air-con- batic exponent, is non toxic and is avail-
ditioning, medium temperature an
alternative to NH3
able in a high technical standard of purity.
Booster applications In the given concentration NH3 and DME
The previously described experiences form an azeotropic blend characterised by
with the use of NH3 in commercial refrige- a slightly rising pressure level in compari-
Open screw compressors (displace- ration plants with direct evaporation son to pure NH3. The boiling point lies at
ment 84 to 410 m3/h with parallel caused further experiments on the basis -36.5C (NH3 -33.4C), 26 bar (abs.) of
operation to 2460 m3/h with 2900 of NH3 under the addition of an oil soluble condensing pressure corresponds to
rpm) for air-conditioning, medium refrigerant component. The main goals 58.2C (NH3 59.7C).
and low temperature cooling. were an improvement of the oil transport
Options for low temperature cooling: characteristics and the heat transmission The discharge gas temperature in air-con-
single stage operation with conventional lubricants along with a ditioning and medium temperature ranges
Economiser operation reduced discharge gas temperature for decrease by about 10 to 25 K (Fig. 25)
Booster operation the extended application range with single and thereby allows for an extension of the
stage compressors. application range to higher pressure

180 25
R723
NH3 20
160
tc 40 C
t oh 1 0 K 15
Discharge gas temperature [C]

140 0,8
Pressure [bar]

10
120 R22
NH3
R22
6
100
R134a 4
80
R290

R404A 2
60

40 1
-40 -30 -20 -10 0 10 -40 -20 0 20 40 60
Evaporation [C] Temperature [C]

Fig. 25 Comparison of discharge gas temperatures Fig. 26 NH3/R22 comparison of pressure levels

24
Halogen free refrigerants

ratios. On the basis of thermodynamic Further characteristics are toxicity and There are no particular material problems.
calculations a single-digit percent rise in flammability. By means of the DME con- In contrast to NH3 copper materials are
cooling capacity results when compared tent, the ignition point in air diminishes also suitable, so that also semi-hermetic
to NH3. The coefficient of performance is from 15 to 6% but, despite of this, the and hermetic compressors are possible.
similar and is even more favourable at azeotrope still remains in the safety The mineral oils usually found in a CFC
high pressure ratios, which experiments group B2. system can be used here as a lubricant
have confirmed. Due to the lower tem- over a wide application range.
perature level during compression an Resulting layout criteria
improved volumetric and isentropic Refrigeration plants with R290 have been
The experiences made with the NH3 com- in operation world-wide for many years,
efficiency is also to be expected, at least
pact systems described above can be mainly in the industrial area it is a pro-
with reciprocating compressors in case
used in the plant technology. However, ven refrigerant.
of an increasing pressure ratio.
adjustments in the component layout are
necessary under consideration of the high- Meanwhile R290 is also used in smaller
Due to the higher molecular weight of
er mass flow. Besides a suitable selec- compact systems with low refrigerant
DME, mass flow and vapour density in-
tion of the evaporator and the expansion charges like residential A/C units and heat
crease with respect to NH3 by nearly 50%
valve a very stable superheat control must pumps. Furthermore, a rising trend can be
which is of little importance to commercial
be ensured. Due to the improved oil solu- seen in its use with commercial refrigera-
plants, especially in short circuits. In clas-
bility wet operation can have consider- tion systems and chillers.
sical industrial refrigeration plants, how-
ever, this is a substantial criterion with able negative results when compared to
Propane is offered also as a mixture with
regard to pressure drops and refrigerant NH3 systems with non-soluble oil.
Isobutane (R600a) or Ethan (R170). This
circulation. Also from this standpoint it With regards to safety regulations the should obtain a good performance match
can be clearly seen that in commercial same criteria apply to installation and with halocarbon refrigerants. Pure Isobu-
applications and especially in water chil- operation as in the case of NH3 plants. tane is mostly intended as a substitute for
lers, R723 has its preferred utilisation. R12 in small plants (preferably domestic
Suitable compressors are special NH3
The material compatibility is comparable refrigerators).
versions which possibly have to be adapt-
to that of NH3. Although non-ferrous ed to the mass flow conditions and to The disadvantage of hydrocarbons is the
metals (e.g. CuNi alloys, bronze, hard sol- the continuous oil circulation. An oil light flammability, and therefore been
ders) are potentially suitable, provided separator is usually not necessary with classified as refrigerants of Safety Group
that the water content in the system is at reciprocating compressors. A3. With the normal refrigerant charge
a minimum (<1000 ppm), a system design
found in commercial plants this means
that corresponds with typical ammonia Bitzer NH3 reciprocating compressors that the system must be designed accord-
practise is recommended nonetheless. are suitable for R723 in principle. An ing to flame-proof regulations.
As lubricant mineral oils or (preferred) individual selection of prototype com-
poly-alpha olefin can be used. As mention- pressors is possible on demand. The use of semi-hermetic compressors in
ed before the portion of DME creates so called hermetically sealed systems is
improved oil solubility and a partial misci- in this case subject to the regulations for
bility. Besides this the relatively low liquid danger zone 2 (only seldom and short
density and an increased concentration of
R290 (Propane) as sub- term risk). The demands for the safety
DME in the circulating oil, positively stitute for R502 and R22 technology include special devices
influences the oil circulation. PAG oils to protect against excess pressures and
would be fully or partly miscible with R290 (propane) can also be used as a special arrangements for the electrical
R723 for typical applications but are not substitute refrigerant. As it is an organic system. In addition measures are required
recommended for reasons of the chemical compound (hydrocarbon) it does not have to ensure hazard free ventilation to effec-
stability and high solubility in the com- an ozone depletion potential and a negli- tively prevent a flammable gas mixture
pressor crankcase (strong vapour devel- gible direct global warming effect. To take occurring in case of refrigerant leakage.
opment in the bearings). into consideration however, is a certain
The design requirements are defined by
Tests have shown that the heat transfer contribution to summer smog.
standards (e.g. EN378, Draft DIN 7003) and
coefficient at evaporation and high heat The pressure levels and the refrigeration may vary in different countries. For systems
flux is improved in systems with R723 and capacity are similar to R22/R502 and the applied within the EU an assessment
mineral oil than when using NH3 with temperature behaviour is as favourable as according to the EC Directive 76/117/EC
mineral oil. with R12 and R502. (ATEX 100a) may become necessary as well.

25
Halogen free refrigerants

With open compressors this will possibly to higher oil temperatures thus to lower appear that a conversion of existing plants
lead to a classification in zone 1. Zone 1 solubility with the result of an improved is only possible in exceptional cases.
demands, however, electrical equipment viscosity.
They are limited to systems, which can be
in special flame-proof design.
Due to the very favourable temperature modified to meet the corresponding safe-
Resulting design criteria behaviour (Fig. 25), single stage compres- ty regulations with an acceptable effort.
sors can be used down to approximately
Apart from the measures mentioned -40C evaporation temperature. R290
above, propane plants require practically could then also be considered as a direct
no special features in the medium and low substitute for R502 or an alternative for
temperature ranges compared with a some of the HFC blends.
usual (H)CFC and HFC system. When siz-
ing components consideration should
however be given to the relatively low On demand a palette of semi-hermetic
mass flow (approximately 55 to 60% com- reciprocating compressors is available
pared to R22). An advantage in connec- for R290. Due to the individual require-
tion with this is the possibility to greatly ments a specifically equipped compres-
reduce the refrigerant charge. sor is offered. Extension P with com-
pressor designation e.g. 4CC-9.2P.
On the thermodynamic side an internal Inquires and orders need a distinstive
heat exchanger between the suction and indication to R290. The handling of the
liquid line is recommended as this will order does include an individual agree-
improve the refrigeration capacity and ment between the contract partners.
COP. Open reciprocating compressors are
Due to the particularly good solubility with also available for R290, together with a
comprehensive program of flame-proof Supplementary BITZER information
mineral oils, it may be necessary to use concerning the use of R290
an oil with lower mixing characteristics or accessories which may be required.
increased viscosity for higher suction Technical Information KT-660
pressures (air-conditioning range). Conversion of existing CFC plants Application of Propane with
semi-hermetic reciprocating
In connection to this, an internal heat Due to the flame-proof protection meas- compressors
exchanger is also an advantage as it leads ures required for an R290 plant, it would

120
25

20
Relation R290 and R1270 to R22 (=100%)

Qo (R1270) R1270
110 15
Pressure [bar]

COP (R290)
10
COP (R1270) R22
100 R290

4
90
Qo (R290)
2
tc 40C
toh 20C
80 1
-40 -30 -20 -10 0 10 -40 -20 0 20 40 60
Evaporation [C] Temperature [C]

Fig. 27 R290/R1270/R22 comparison of performance data of a Fig. 28 R290/R1270/R22 comparison of pressure levels
semi-hermetic compressor

26
Halogen free refrigerants

perature levels. Tests carried out by


Propylene (R1270) as an BITZER has carried out a series of
hydrocarbon manufacturers and stability
alternative to Propane investigations with R1270. In addition
tests in real applications show that reac-
there are experiences with the operation
tivity in refrigeration systems is practically
in real plants. An indivdual selection is
non-existent. Doubts have occasionally
possible upon demand.
been mentioned in some literature regard-
For some time there has also been ing propylenes possible carcinogenic
increasing interest in using propylene effects. These assumptions have been
(propene) as a substitute for R22/R502. disproved by appropriate studies.
Due to its higher volumetric refrigeration
capacity and lower boiling temperature Resulting design criteria
(compared to R290) applications in medi-
um and low temperature systems, e.g. With regard to system technology, experi-
liquid chillers for supermarkets, are of ence gained from the use of propane can
particular interest. On the other hand, widely be applied to propylene. However,
higher pressure levels (>20%) and dis- component dimensions have to be altered
charge gas temperatures have to be taken due to higher volumetric refrigeration
into consideration, thus restricting the capacity (Fig. 27). The compressor dis-
possible application range. placement is correspondingly lower and
therefore also the suction and high pres-
Material compatibility is comparable with sure volume flows. Because of higher
propane, as is the choice of lubricants. vapour density the mass flow is almost
Propylene is also easily inflammable and the same as for R290. As liquid density is
belongs to the A3 group of refrigerants. nearly identical the same applies for the
The same safety regulations are therefore liquid volume in circulation.
to be observed as with propane (page 25).
As with R290 the use of an internal heat
Due to the chemical double linkage exchanger between suction and liquid
propylene is relatively reaction friendly, lines is of advantage. However, due to
which means that there is a danger of R1270s higher discharge gas temperature
polymerization at high pressure and tem- restrictions are partly necessary.

27
Halogen free refrigerants

Carbon Dioxide R744 (CO2) cations were marine refrigeration systems, operation for long periods. In this connec-
for example. With the introduction of the tion it must also be noted that the heat
as an alternative refriger-
Safety Refrigerants, CO2 became less transfer coefficients of CO2 are consider-
ant and secondary fluid popular and since the fifties had nearly ably higher than of other refrigerants
disappeared. with the potential of very low tempera-
ture differences in evaporators, con-
The main reasons for that are its relatively densers, and gas coolers. Moreover, the
CO2 has had a long tradition in the refrig-
unfavourable thermodynamic characteris- necessary pipe dimensions are very small,
eration technology reaching far into the tics for usual applications in refrigeration and the influence of the pressure drop is
19th century. It has no ozone depleting and air-conditioning.The discharge pres- comparably low. In addition, when used
potential, a negligible direct global warm- sure with CO2 is extremely high and the as a secondary fluid, the energy demand
ing potential (GWP = 1), is chemically critical temperature at 31C (74 bar) is for circulation pumps is extremely low.
inactive, non-flammable and not toxic in very low. Depending on the heat source
the classical sense. That is why CO2 is In the following section, a few examples
temperature at the high pressure side
not subjected to the stringent demands of sub-critical systems and the resulting
trans-critical operations with pressures
regarding containment as apply for HFCs design criteria are described. An addition-
beyond 100 bar are required. Under these
(F-Gas Regulation), and flammable or al section provides details on trans-critical
conditions, the energy efficiency is often
toxic refrigerants. However, compared to applications.
lower compared to the classic vapour
HFCs the lower practical limit in air has to compression process (with condensation),
be considered. For closed rooms this may and therefore the indirect global warming Sub-critical applications
require special safety and detection systems. effect is suitably higher.
CO2 is also low in cost and there is no From energy and pressure level points of
necessity for recovery and disposal. In Nonetheless, there is a range of applica- view, very beneficial applications can be
addition, it has a very high volumetric tions in which CO2 can be used very eco- seen for industrial and larger commercial
refrigeration capacity, which depending nomically and with favourable Eco-Effi- refrigeration plants. For this, CO2 can be
on operating conditions equates to ciency. For example, these include used as a secondary fluid in a cascade
approx. 58 times more than R22 and NH3. sub-critically operated cascade plants, system and if required, in combination
but also trans-critical systems, in which with a further booster stage for lower
Above all, the safety relevant characteris- the temperature glide on the highpres- evaporating temperatures (Fig. 30/1).
tics were an essential reason for the initial sure side can be used advantageously, or The operating conditions are always sub-
widespread use. The main focus for appli- the system conditions permit sub-critical critical which guarantees good efficiency

160 80
Critical temperature 31.06 C
140 R744 (CO22) 70
Trans-critical process

120 Sub-critical process 60


CO2

100 50
Pressure [bar]
Pressure [bar]

40
80 31.06C

30
60
R404A
20
40
R22
10
20
0
0 -60 -40 -20 0 20 40 60 80
100 200 300 400 500 600
Enthalpy [kJ/kg] Temperature [C]

Fig. 29/1 R744(CO2) Pressure-/Enthalpy-Diagram Fig. 29/2 R744(CO2)/R22/R404A comparison of pressure levels

28
Halogen free refrigerants

levels. In the most favourable application The extremely high volumetric refrigeration As an alternative to this CO2 absorbing
range (approx. -10 to -50C), pressures capacity of CO2 (latent heat through the storage systems are used where longer
are still on a level where already existing changing of phases) leads to very low shut-off periods can be bridged without
components or items in development, e.g. mass flow rates and makes it possible to a critical pressure increase.
for R410A, can be matched with accept- use small cross sectional pipe and minimal For systems in commercial applications
able effort. energy needs for the circulating pumps. a direct expansion version is possible as
For the combination with a further com- well.
Resulting design criteria
pression stage, e.g. for low temperatures, Supermarket plants with their usually
For the high temperature side of such a there are different solutions. widely branched pipe work offer an espe-
cascade system, a compact cooling unit cially good potential in this regard. The
Fig. 30/1 shows a variation with an addi-
can be used, whose evaporator serves on medium temperature system is then car-
tional receiver where one or more Booster
the secondary side as the condenser for ried out in a conventional design or with a
compressors will pull down to the neces-
CO2. Chlorine-free refrigerants (NH3, HCs secondary circuit and for low temperature
sary evaporation pressure. Likewise, the
or HFCs) are suitable. application combined with a CO2 cascade
discharge gas is fed into the cascade
With NH3 the cascade heat exchanger cooler, condenses and then carried over to system (for sub-critical operation). A
should be designed so that the dreaded the receiver (MT). The feeding of the low system example is shown in Fig. 30/2.
build-up of ammonium carbonate is pre- pressure receiver (LT) is achieved by a For a general application, however, not all
vented in the case of leakage. This tech- level control device. requirements can be met at the moment.
nology has been applied in breweries for Instead of classical pump circulation the It is worth considering that system tech-
a long time. booster stage can also be built as a so- nology changes in many respects and
called LPR system. specially adjusted components are
A secondary circuit for larger plants with The circulation pump is thus not necessary necessary to meet the demands.
CO2 could be constructed utilising, to a but the number of evaporators is then lim-
wide extent, the same principles for a low The compressors, for example, must be
ited with a view to an even distribution of
pressure pump circulating system, as is properly designed because of the high
the injected CO2.
often used with NH3 plants. The essential vapour density and pressure levels (parti-
difference exists therein, that the con- In the case of a system breakdown where cularly on the suction side). There are also
densing of the CO2 results in the cascade a high rise in pressure could occur, safety specific requirements with regard to mate-
cooler, and the receiver tank (accumula- valves can vent the CO2 to the atmos- rials. Furthermore only highly dehydrated
tor) only serves as a supply vessel. phere with the necessary precautions. CO2 must be used.

Simplified Simplified
sketch sketch
CO 2 Cascade
HFC (NH3 / HC)*

CO 2 NH3 / HC /
HFC

MT LT PC

CPR

LC

LT MT

* only with secondary system

Fig. 30/1 Casacde system with CO2 for industrial applications Fig. 30/2 Conventional refrigeration system combined with CO2 low
temperature cascade
29
Halogen free refrigerants

High demands are made on lubricants as Trans-critical applications Apart from that, there are application
well. Conventional oils are mostly not mis- areas in which a trans-critical process is
Trans-critical processes are characterized
cible and therefore require costly meas- energetically advantageous. These include
in that the heat rejection on the highpres-
ures to return the oil from the system. On heat pumps for sanitary water, or drying
sure side proceeds isobar but not iso-
the other hand, a strong viscosity reduc- processes. With the usually very high
therm. Contrary to the condensation pro-
tion with the use of a miscible and highly temperature gradients between the
cess during sub-critical operation, gas
soluble POE must be considered. discharge temperature at the gas cooler
cooling (de-superheating) occurs, with
intake and the heat sink intake tempera-
Further development work is necessary, corresponding temperature glide. There-
ture, a very low outlet gas temperature is
also with regard to the adaptation of fore, the heat exchanger is described as
achievable. This is positively influenced
technical standards and safety require- gas cooler. As long as operation remains
by the temperature glide curve and the
ments. above the critical pressure (74 bar), only
relatively high mean temperature differ-
high-density vapour will be transported.
ence between CO2 vapour and secondary
BITZER is actively involved in a number Condensation only takes place after
fluid. The low gas outlet temperature
of projects. For sub-critical applications expansion to a lower pressure level e.g.
leads to a particularly high enthalpy
a range of special compressors, inclu- by interstage expansion in an intermedi-
difference, and therefore to a high sys-
sive of suitable oil, can be offered. ate pressure receiver. Depending on the
tem COP.
temperature curve of the heat sink, a
system designed for trans-critical opera- Low-capacity sanitary water heat pumps
Supplementary BITZER information tion can also be operated sub-critically, are already manufactured and used in
concerning compressor selection whereby the efficiency is better under large quantities. Plants for medium to
and the use of CO2 these conditions. In this case, the gas higher capacities (e.g. hotels, indoor
cooler becomes the condenser. swimming pools) are still in the develop-
Brochure KP-120:
ment and introductory phase.
CO2 Compressors Octagon Another feature of trans-critical operation
Series is the necessary regulation of the high Apart from these specific applications,
Additional publications on request pressure to a defined level. This optimum there is also a range of developments for
pressure is determined as a function of the classical areas of refrigeration and air-
gas cooler outlet temperature by means conditioning. This also covers supermar-
of balancing between the highest possible ket refrigeration plants, for example.
enthalpy difference and simultaneous Meanwhile, and following extensive labo-
minimum compression work. It must be ratory tests, real installations with parallel
adapted to the relevant operating condi- compound compressors are in operation.
tions using an intelligent modulating con- The operating experience and the deter-
troller (see system example, Fig. 31). mined energy costs show promising
results. However, the investment costs are
As described above, under purely thermo- still considerably higher than for classical
dynamic aspects, the trans-critical operat- plants with HFCs and direct expansion.
ing mode appears to be unfavourable in
terms of energy efficiency. In fact, this is On the one hand, the reasons for the
true for systems with a relatively high favourable energy costs lie in the high
temperature level of the heat sink on the degree of optimized components and the
highpressure side. However, additional system control, and also in the previously
measures can be taken for improving effi- described advantages regarding heat
ciency, such as the use of expanders, transfer and pressure drop. On the other
ejectors, and economiser systems. hand, these installations are mostly used
in climate areas permitting very high run-
ning times in sub-critical operation due to
the annual ambient temperature profile.

30
Halogen free refrigerants

Insofar, but also in view of the very whereby separate high and low pressure appear to be relatively unfavourable. But
demanding technology and the high compressors are particularly advantage- it must be considered that present R134a
requirements placed on the qualification ous with parallel compounded systems. systems are less efficient than stationary
of planners and service personnel, CO2 plants of the same capacity. The reasons
The criteria mentioned above in connec-
technology cannot be regarded as a for this lie in the specific installation con-
tion with sub-critical systems apply to an
general replacement for plants using ditions and the relatively high pressure
even higher degree for lubricants.
HFC refrigerants. losses in pipework and heat exchangers.
Further development is necessary in With CO2, pressure losses have signifi-
Resulting design criteria many areas, and for most applications, cantly less influence. Moreover, system
Detailed information on this topic would trans-critical CO2 technology cannot yet efficiency is further improved by the high
go beyond the scope of this publication. be regarded as state-of-the-art. heat transfer coefficients in the heat
In any case, the system and control tech- exchangers.
BITZER is actively involved in a series
niques are substantially different from This is why optimized CO2 air-condition-
of projects. Meanwhile, compressors
conventional plants. Already when consid- ing systems are able to achieve effi-
can be supplied for certain applications.
ering pressure levels as well as volume ciencies that are comparable to those of
However, an individual examination of
and mass flow ratios specially developed R134a. Regarding the usual leakage rates
each application is necessary.
components, controls, and safety devices of such systems, a more favourable
as well as suitably dimensioned pipework balance is obtained in terms of TEWI.
must be provided. CO2 in mobile
air-conditioning systems From today's viewpoint, it is not possible
The compressor technology is particularly to make a clear prediction as to whether
demanding. The special requirements CO2 will generally prevail in these appli-
Within the scope of the long-discussed
result in a completely independent ap- cations. Certainly, this also depends on
measures for reducing direct refrigerant
proach. For example, this involves design, further investigations with Low GWP
emissions, and the pending ban on the
materials (bursting resistance), displace- refrigerants (page 12). Hereby, other
use of R134a in MAC systems*, the
ment, crank gear, working valves, lubrica- aspects such as operating safety,
development of CO2 systems has been
tion system, as well as compressor and costs, and global logistics will play
pursued intensively since several years.
motor cooling. Hereby, the high thermal an important role.
load severely limits the application for At the first glance, efficiency and there-
single-stage compression. Low tempera- fore the indirect emissions from CO2
ture cooling requires 2-stage operation, systems under typical ambient conditions * See page 12 for further information.

Simplified
sketch

HP Regulation Valve (HX)


Gas
Cooler

Liquid Receiver
(intermediate
pressure)

TX Device Compressor

Evaporator

Fig. 31 Example of a trans-critical CO2 system

31
Special applications

R124 and R142b as Chlorine free substitutes Alternatives for R114


substitutes for for special applications and R12B1
R114 and R12B1
Due to the limited markets for systems At present R227ea and R236fa are regard-
with extra high and low temperature appli- ed as the prefered substitutes, however,
Instead of the refrigerants R114 and
cations, the requirements for the develop- the availability of R236fa is partly limited.
R12B1 predominately found in the past in
ment of alternative refrigerants and sys- R227ea cannot be seen as a full replace-
high temperature heat pumps and crane
tem components for these areas has not ment. Recent research and field tests
cabin A/C installations, the HCFC R124
been so great. have shown favourable results, but with
and R142b can be used as alternatives in normal system technology the critical
new installations.
Only a few years ago a group of alterna- temperature of 102C limits the condens-
With these gases it is also possible to
tives for the CFC R114 and Halon R12B1 ing temperatures to about 85..90C.
use long proven lubricants, preferably
(high temperature), R13B1, R13 and R503
mineral oils and alkyl benzenes with high R236fa provides the more favourable con-
(extra low temperature) were offered as the
viscosity. ditions at least in this regard the critical
replacements. With closer observations it
temperature is above 120C. A disadvan-
Because of the Ozone Depleting Potential, has been found that the thermodynamic
tage, however, is the smaller volumetric
the use of these refrigerants must certain- properties of the alternatives differ
refrigeration capacity. This is similar to
ly only be regarded as an interim solution. considerably from the substances used
R114 and with that 40% below the perfor-
The flammability of R142b should also be untill now. This can cause costly changes
mance of R124 which is widely used for
considered with the resulting safety impli- especially with the conversion of existing
extra high temperature applications today.
cations (refrigerant group A2). systems.
In the meantime, an azeotropic blend of
Resulting design criteria/ R365mfc and a perfluoropolyether has
Converting existing plants also been developed. It is available under
the trade name Solkatherm SES36
In comparison to R114 the boiling tem- (Solvay). Its boiling temperature (at 1.013
peratures of the alternatives are lower bar) is 36.7 C, and the critical tempera-
(approx. -10C) which results in larger dif- ture is 177.4C. The preferred application
ferences in the pressure levels and refrig- areas will therefore be heat pumps in
eration volumetric capacities. This leads process technology, and Organic Rankine
to stronger limitations in the application Cycles (ORC).
range concerning high evaporation and
condensing temperatures.
A conversion of an existing installation [K]
will in most cases necessitate the 40
Discharge gas temperature relative difference to R13B1

exchanging of the compressor and regu-


to -70C
lating devices. Owing to the lower volume
30 tc 40C
flow (higher volumetric refrigeration
capacity), possible adjustments to the to 20K
evaporator and the suction line will be 20
required.

Over the previous years BITZER com- 10


R410A

pressors have been found to be well


suited with R124 and R142b in actual 0
Basis R13B1
ISCEON MO89

installations. Depending on perform-


ance data and compressor type modifi-
cations are necessary, however. Perfor- -10
mance data including further design
instructions are available on request. -20

-30
Fig. 32 R13B1/HFC alternatives comparison of discharge gas temperatures
of a 2-stage compressor

32
Special applications

Refrigerant R600a (Isobutane) will be an In addition to this, the steep fall of pres-
BITZER has already carried out investi-
interesting alternative where the safety sure limits the application at very low
gations and also collected experiences
regulations allow the use of hydrocarbons temperatures and may require a change
with several of the substitutes mentioned,
(Group A3). With a critical temperature of to a cascade system with for example
performance data and instructions are
135C, condensing temperatures of 100C R23 in the low temperature stage.
available on request.
and more are within reach. Lubrication and material compatibility are Due to the individual system technology
The volumetric refrigeration capacity is assessed as being similar to the other for these special installations, consul-
almost identical to R124. HFC blends. tation with BITZER is necessary.

Alternatives for R13B1 Alternatives for R13


and R503
Besides R410A, ISCEON MO89 (DuPont)
can be regarded as potential R13B1 The situation is more favourable with
substitute. With R410A a substantially these substances as R23 and R508A/
higher discharge gas temperature is to R508B can already replace R13 and R503.
be considered when compared to R13B1 Refrigerant R170 (Ethane) is also suitable
which restricts the application range even when the safety regulations allow the use
in 2-stage compression systems to a of hydrocarbons (Group A3).
greater extent.
Due to the partly steeper pressure curve
ISCEON MO89 is a mixture of R125 and of the alternative refrigerants and the
R218 with a small proportion of R290. higher discharge gas temperature of R23
Due to the properties of the two main compared with R13, differences in per-
components, density and mass flow are formance and application ranges for the
relatively high and discharge gas temper- compressors must be considered. Individ-
ature is very low. Liquid subcooling is of ual adaptation of the heat exchangers and
particular advantage. controls is also necessary.
Both of the mentioned refigerants have As lubricants for R23 and R508A/B,
relatively high pressure levels and are polyol ester oils are suitable, but these
therefore limited to 40 through 45C con- must be matched for the special require-
densing temperature. They also show less ments at extreme low temperatures.
capacity than R13B1 at evaporating
temperatures below -60C. R170 has also good solubility with con-
ventional oils, however an adaptation
to the temperature conditions will be
necessary.

33
Refrigerant Properties

09.06
6
Refrigerant Composition Substitute Appplication ODP GWP(100a) Safety Practical
type (Formula) for range group 4 limit
[R11=1.0] [CO2=1.0] [kg/m3] 5

HCFC-Refrigerants 5

R22 CHClF2 R502 (R12 1 ) 0,05 1500 A1 0.3


see
R124 CHClFCF3 1 0,02 470 A1 0.11
R114 , R12B1 page 36
R142b CCIF2CH3 0,06 1800 A1 0.066
HFCFC/HFC Service-Blends (Transitional Alternatives)
R401A R22/152a/124 0,03 970 A1 0.3
R401B R22/152a/124 R12 (R500) 0,035 1060 A1 0.34
R409A R22/142b/124 0,05 1290 A1 0.16
R413A R134a/218/600a R12 (R500) see 0 1770 A2 0.08
page 36
R402A R22/125/290 0,02 2250 A1 0.33
R402B R22/125/290 R502 0,03 1960 A1 0.32
R403B R22/218/290 0,03 3570 A1 0.41
R408A R22/143a/125 0,026 2650 A1 0.41
HFC chlorine free Refrigerants (Long Term Alternatives)
R134a CF3CH2F R12 (R22 1 ) 1300 (1300) A1 0.25
R152a CHF2CH3 mainly used 140 (120) A2 0.026
R125 CF3CHF2 as part 2800 (3400) A1 0.39
R143a CF3CH3 components 3800 (4300) A2 0.056
R32 CH2F2 for blends see 650 (550) A2 0.061
page 36 0
R227ea CF3-CHF-CF3 R12B1, R114 1
2900 (3500) A1 0.49
R236fa CF3-CH2-CF3 R114 6300 (9400) A1 0.59
R23 CHF3 R13 (R503) 11700 (12000) A1 0.68
HFC chlorine free Blends (Long Term Alternatives)
R404A R143a/125/134a 3260 A1 0.48
R507A R143a/125 3300 A1 0.48
(R407A) R32/125/134a R502, R22 1770 A1 0.33
(R407B) R32/125/134a 2280 A1 0.35
R422A R125/134a/600a 2530 A1 N/A
R407C R32/125/134a 1525 A1 0.31
R417A R125/134a/600 1950 A1 0.15
R22 see
R422D R125/134a/600a 2230 A1 N/A
FX100 R32/125/143a/134a page 36 0 1830 A1 N/A
R410A R32/125 R22 1 (R13B1 2 ) 1725 A1 0.44
R13B1 2
ISCEON MO89 R125/218/290 3090 N/A N/A
R508A R23/116 R503 11860 A1 0.56
R508B R23/116 11850 A1 0.2
Halogen free Refrigerants (Long Term Alternatives)
R717 NH3 R22 (R502) 0 B2 0.00035
R723 NH3/R-E170 R22 (502) 8 B2 N/A
R600a C4H10 R114, R12B1 3 A3 0.0086
R290 C3H8 R22 (R502) see 3 A3 0.008
R1270 C3H6 R22 (R502) page 37 3 A3 0.008
3 R13, R503 0
R170 C2H6 3 A3 0.013
R744 CO2 Diverse 1 A1 0.1

Fig. 33 Characteristics of CFC alternatives (continued on Fig. 34)

These statements are valid subject to reservations; they are based on information published by various refrigerant manufacturers.

1 Alternative refrigerant has larger deviation in 3 Also proposed as a component in R290/ 6 Time horizon 100 years according to
refrigerating capacity and pressure 600a-Blends (direct alternative to R12) IPCC II (1996) basis for Kyoto protocol
2 Alternative refrigerant has larger deviation 4 Classification according to EN378-1 and ASHRAE 34 Values in brackets according to IPCC III (2001)
below -60C evaporating temperature reference data in EC F-Gas Regulation
5 According to EN 378-1, Annex E (Annex I).
Data for blends change accordingly.
34 N/A Data not yet available
Refrigerant Properties

09.06
Refrigerant Boiling Temperature Critical Cond. temp. Refr. C.O.P Discharge Lubricant
type temperature glide temperature at 26 bar capacity gas temp. (compressor)
[C] 1 [K] 2 [C] 1 (abs) [C] 1 [%] 3 [%] [K] 3

HCFC-Refrigerants
R22 -41 0 96 63 80 (L) 4 88 4 +35 4

R124 -11 0 122 105 5 5 5


R142b -10 0 137 110
HFCFC/HFC Service-Blends (Transitional Alternatives)
R401A -33 6.4 108 80 107 (M) 100 +13
R401B -35 6.0 106 77 108 (L) 98 +18
R409A -34 8.1 107 75 109 (M) 99 +7
R413A -35 6.9 101 76 105 (M) 100 -9
R402A -49 2.0 75 53 109 (L) 100 ~0
R402B -47 2.3 83 56 99 (L) 98 +16
R403B -51 1.2 90 54 112 (L) 100 ~0
R408A -44 0.6 83 58 98 (L) 100 +10
HFC chlorine free Refrigerants (Long Term Alternatives)
R134a -26 0 101 80 97 (M) 103 -8
R152a -24 0 113 85 N/A N/A N/A
R125 -48 0 66 51 N/A N/A N/A
R143a -48 0 73 56 N/A N/A N/A
R32 -52 0 78 42 N/A N/A N/A
R227ea -16 0 102 96 5 5 5
R236fa -1 0 >120 117
5 5 5
see
R23 -82 0 26 1 page 37
HFC chlorine free Blends (Long Term Alternatives)
R404A -47 0,7 73 55 99 (L) 98 -9
R507A -47 0 71 54 102 (L) 98 -10
(R407A) -46 6.6 83 56 78 (L) 96 +11
(R407B) -48 4.4 76 53 93 (L) 98 -2
R422A -49 2.5 72 56 5 5 5

R407C -44 7.4 87 58 100 (H) 95 -8


R417A -43 5.6 90 68 97 (H) 5 -25
R422D -45 4.5 81 62 5 5 5
FX100 -43 7.1 87 64 5 5 5

R410A -51 <0.2 72 43 142 (7/40C) 95 -6


ISCEON MO89 -55 4.0 70 50 5 5 5

R508A -86 0 13 -3 5 5 5
R508B -88 0 14 -3
Halogen free Refrigerants (Long Term Alternatives)
R717 -33 0 133 60 100 (M) 105 +60
R723 -37 0 131 58 105 (M) 106 +35
R600a 3 -12 0 135 114 N/A N/A N/A
R290 -42 0 97 70 89 (M) 102 -25
R1270 -48 0 92 61 112 (M) 101 -20
R170 -89 0 32 3 5 5 5

R744 -57 6 0 31 -11 5 5 5


Fig. 33 Characteristics of CFC alternatives

Fig. 34 Characteristics of CFC alternatives

1 Rounded values 3 Reference refrigerant for these values 4 Valid for single stage compressors
is stated in Fig. 33 under the nomina-
2 Total glide from bubble to dew line tion Substitute for (column 3)
5 Data on request (operating conditions
based on 1 bar (abs.) pressure. Letter within brackets indicates opera- must be given)
Real glide dependent on operating ting conditions Triple point at 5,27 bar
conditions. 6
Approx. values in evaporator: H High temp (+7/55C)
H/M 70%; L 60% of total glide M Medium temp (-10/40C) Stated performance data are average values
L Low temp (-35/40C) based on calorimeter tests

35
Application ranges

Transitional/Service refrigerants

R401A R409A

R401B

R413A

R22
2-stage

R402B

R402A R403B R408A


2-stage

R124 R142b

40 20 0 -20 -40 -60 -80 -100


Application with limitations Evaporation C

Fig. 35 Application ranges for HCFCs and Service Blends

Chlorine free HFC refrigerants and blends

R134a

R404A R507 R407B


R404A R507A
R422A 2-stage

R407C R417A
R422D FX100

1
R410A 2 2-stage

R227ea R236fa

2
ISCEON MO89 2 2-stage

R23 R508A R508B CASCADE

40 20 0 -20 -40 -60 -80 -100


Application with 1 New compressor generation Evaporation C
limitations 2 Condensing temperature limited
3 For evaporating temperature below < -50C please
consult the refrigerant supplier

Fig. 36 Application ranges for HFC refrigerants and blends (ODP=O)

36
Application ranges Lubricants

Halogen free refrigerants

2-stage
NH 3
R723*

2-stage

R290/600a

R290 R1270
2-stage

R600a

R170 CASCADE

CO2 see page 28...32

40 20 0 -20 -40 -60 -80 -100


Application with limitations * see information on page 23/24 Evaporation C
Fig. 37 Application ranges for halogen free refrigerants

Lubricants
Traditional oils New lubricants
glycol (PAG)
olefin (PAO)
Poly-alpha-

ester (POE)
Mineral oil

Mineral oil

mineral oil
Polyvinyl-
benzene

benzene
+ alkyl-

treated
Polyol

Hydro
Alkyl-
(MO)

(PVE)

Poly-
ether
(AB)

(H)CFC +VG

Service blends +VG

HFC + blends T

Hydrocarbons VG VG VG VG VG

NH 3 R723

Good suitability Especially critical with moisture


Application with limitations VG Possible higher basic viscotsity
Not suitable T Extended test program
Further information see pages 9/10 and explanations for the particular refrigerants.
Fig. 38 Lubricants for compressors

37
38
39
Bitzer Khlmaschinenbau GmbH
Eschenbrnnlestr. 15
71065 Sindelfingen, Germany
fon + 49 (0) 70 31 932-0
fax + 49 (0) 70 31 932-146 &-147
www.bitzer.de . bitzer@bitzer.de

S-ar putea să vă placă și