Sunteți pe pagina 1din 9

IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO.

4, NOVEMBER 2012 1897

Autonomous DC Voltage Control of a DC


Microgrid With Multiple Slack Terminals
Dong Chen and Lie Xu, Senior Member, IEEE

AbstractAutonomous DC voltage control for a DC microgrid into two types: centrally controlled [14] and autonomously con-
with multiple power and slack terminals is studied in this paper. trolled [15][17]. For a centrally controlled architecture, the
Slack terminals respond to the generation variation and load step operational orders of the consisting converters are given by a
within a DC microgrid to maintain the DC voltage. The slack
terminals considered here are grid connected VSC and energy central controller with real-time feedback from controlled ter-
storage systems. A voltage droop based power sharing and coordi- minals. A drawback of such a solution is that communication
nation strategy among the slack terminals is proposed for power delay or failure might undermine its reliability. In addition, any
smoothing during grid-connected condition and normal operation expansion of the microgrid will result in increased complexity
during islanding condition. A prototype microgrid with two power of the central controller, which might not be economical for
and two slack terminals is established to demonstrate the excellent
operation performance of the proposed control system during an expandable system with a large number of terminals. The
various operating conditions such as power variation, islanding, autonomously controlled solution, however, is based on local
and grid reconnection. voltage detection and can effectively eliminate circulating cur-
Index TermsAutonomous control, DC microgrid, energy rent [18]. As the DC voltage can be treated as an indicator
storage, power sharing. of power balancing within a DC grid, the method of voltage
droop has been widely accepted in power sharing schemes for
its reliability and simplicity in implementation. Most of the re-
I. INTRODUCTION search conducted on droop control focuses mainly on its perfor-

D UE to increasing concerns on environmental protection mance in time domain for constant power sharing; however, fre-
and sustainable development, renewable energy has at- quency-based transient power sharing has rarely been studied.
tracted extensive interest. As renewable energy sources are usu- One extensive application of power sharing is the external
ally dispersed, distributed generation becomes an attractive so- exchange power smoothing. As real power fluctuation is un-
lution. By connecting distributed generation with local loads desirable for AC power grid, it is desirable to smooth the ex-
and energy storage, a microgrid is formed [1]. Microgrids can be change power before passing it to the AC grid. Energy storage
generalized into two types, i.e., AC and DC. A variety of studies systems (ESS) based power smoothing techniques have been
have been reported on AC microgrids regarding power sharing widely studied for renewable generation [14], [19], [20]. Such
between parallel-connected sources [2][4], islanding operation smoothing scheme usually relies on real-time detection of gen-
[5], [6], protection [7], [8], etc. erated power, which is feasible for a simple load-free DC gen-
A DC system can be designed for developing rural area or eration system, e.g., single wind turbine. However, for a more
small scale commercial facilities [9] such as a data center [10] complex DC network with various generation sources and loads,
or a residential building [11]. One advantage of DC microgrids the power fluctuation may come from any generation source or
over its AC counterparts is that there is no need for frequency, load terminal. In this case, the necessity for a fast and reliable
phase, or reactive power control. In order to ensure the sta- communication path for real-time power detection remains a po-
bility of a DC system, the power flow within the DC micro- tential problem. In this paper, a simple strategy of frequency
grid must be balanced at all times to ensure the DC voltage based autonomous smoothing scheme is proposed for grid side
can be maintained. As renewable generations, such as wind power exchange.
and photovoltaic power, are obliged to follow the meteorolog- As a grid connected voltage source converter (G-VSC) is
ical conditions [12], [13], and local loads usually operate on used to control the active power exchange between DC and
their own merits, the other controllable sources, e.g., energy AC sides, the microgrid can still actively harness the power ex-
storage, network connected converters etc., must accommodate change within its rating when an AC fault caused voltage dip oc-
their variable demands to balance the power. To achieve this, curs [21], [22]. For the most severe conditions, a DC microgrid
a power sharing scheme between controllable sources must system can be disconnected (islanded) from an AC grid with
be performed. The power sharing solutions can be generalized the support of ESS [11], [18] and reconnected when the fault is
cleared. Communication between AC and DC side converters
is usually essential for sending fault/clear signals. However, in
Manuscript received June 27, 2011; revised September 30, 2011 and January
17, 2012; accepted February 24, 2012. Date of publication April 03, 2012; date the AC fault-ride-through strategy proposed in this paper, it is
of current version October 17, 2012. Paper no. TPWRS-00598-2011. not required.
The authors are with the School of Electronics, Electrical Engineering and
To incorporate the system control of power sharing and
Computer Science, Queens University of Belfast, Belfast BT9 5AH, U.K.
(e-mail: dchen02@qub.ac.uk; l.xu@ee.qub.ac.uk). fault-ride-through, a cooperation strategy is needed. In this
Digital Object Identifier 10.1109/TPWRS.2012.2189441 paper, a comprehensive control strategy for DC voltage control

0885-8950/$31.00 2012 IEEE


1898 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO. 4, NOVEMBER 2012

Fig. 2. DC power flow.

2) DC loads. The loads consume power on their own merits.


The action of switching in/out loads tends to lead to a step
Fig. 1. DC microgrid system configuration. in the total power deficit (surplus). Again, the DC loads act
as a power terminal under normal conditions.
of a four-terminal DC microgrid is proposed. Embedded with 3) G-VSC. During normal operation, the G-VSC ensures a
a novel droop based power sharing scheme, system operation constant DC voltage by controlling the external exchange
including exchange power smoothing, AC fault ride-through, power with AC grid. Thus the G-VSC operates as a slack
and recovery can be performed autonomously. This paper is terminal. However, during abnormal conditions, e.g., AC
organized as follows. Section II defines the DC microgrid voltage dip during grid AC fault, the maximum power
under investigation and the principle of DC voltage control. transmitted by the G-VSC can be significantly reduced. In
The details of the control strategies under different operation the most severe cases, the exchange power drops to zero
modes are described in Section III and a frequency response during near zero AC voltage or in a complete island oper-
study based on the proposed power sharing scheme is also ation. Under such conditions, the G-VSC effectively oper-
carried out in this section. Experimental results are presented in ates as a power terminal.
Section IV to validate the proposed system control and finally, 4) ESS. The ESS of a DC microgrid can be based on bat-
Section V draws the conclusions. teries, fuel cells, flywheels, super capacitors, etc. The
power and energy density varies according to the usage
II. SYSTEM CONFIGURATION AND OPERATION MODES time scale, which is not discussed here. In this paper, the
ESS is represented by a bi-directional DC/DC converter
A. System Definition controlled battery energy storage system as is shown in
A typical DC microgrid system has four kinds of terminals: Fig. 1. When the energy capacity and power rating is
generation, load, ESS, and G-VSC. In this paper, these termi- sufficient, the ESS is a slack terminal, which can operate
nals can be further categorized into two types: power terminal together with the G-VSC to contribute to DC voltage
and slack terminal. Power terminals usually operate on their control (power balancing) by sharing the instant power
own merits and do not actively contribute to system control. surplus (deficit). When the G-VSC reaches its power limit,
Typical power terminals are variable generations such as wind i.e., becomes a power terminal, the ESS becomes the only
and photovoltaic systems which normally operate at maximum slack terminal in the system and is required to regulate the
power point tracking (MPPT) according to weather conditions, DC voltage on its own.
and variable load. On the other hand, slack terminals are con- The charging/discharging power of the ESS can be treated
trolled to accommodate the power variation coming from the separately from the DC voltage controller as a passive load (or
power terminals and maintain a stable system operation with source during discharging). Thus the ESS is a combination of
limited DC voltage variation. Examples of this are determin- power and slack terminals. The charging and discharging of the
istic generation such as diesel Gensets, ESS, and G-VSC during ESS controlled by its energy management system is not consid-
grid-connected operation. For satisfactory operation, a DC mi- ered in this paper.
crogrid should have at least one slack terminal.
The schematic diagram of the DC microgrid under investi- B. DC Voltage and Power Flow
gation is shown in Fig. 1. It is assumed that the four termi- Fig. 2 shows the equivalent circuit of the DC bus, where
nals are closely located and thus the DC side impedance is ne- refers to the power flowing out from the DC bus through the
glected. However, if DC resistances are considered, there will G-VSC whereas and refer to the power flowing into the
be small voltage differences among various DC terminals which DC bus from the PMSG and the ESS, respectively. is the
may need to be considered when setting the voltage controller. total power consumed by the DC loads and is the common
The proposed DC microgrid consists of the following devices: DC voltage.
1) Generation. The generation within a DC grid can come The charging power of the DC capacitor and the DC voltage
from wind, photovoltaic units, diesel generator, etc. In are given as
Fig. 1, they are represented by a wind turbine based on
(1)
permanent magnet synchronous generator (PMSG). The
output power of a wind turbine varies due to the variation (2)
of wind condition. Thus, the generator operates as a power
terminal. where refers to the DC capacitance value.
CHEN AND XU: AUTONOMOUS DC VOLTAGE CONTROL OF A DC MICROGRID WITH MULTIPLE SLACK TERMINALS 1899

As illustrated in (2), a constant DC voltage indicates a bal-


anced power flow among the microgrid terminals. Unbalanced
power flow can cause abnormal DC voltage and disrupt normal
operation. Therefore, to ensure normal operation, the DC
voltage must be maintained at all times by ensuring the power
flow is balanced.
For the proposed system, under normal operation, there are
two slack terminals, i.e., G-VSC and ESS. Thus by coordinating
the two slack terminals, it is possible not only to ensure the
DC voltage is controlled but also provide enhanced operation,
e.g., reducing the fluctuation of the power exchange between Fig. 3. Converter control for Mode 1. (a) G-VSC. (b) ESS.
the G-VSC and AC grid. It is known that load power varia-
tion, especially in distribution networks, can cause extra power
loss [23], [24]. Similarly, large power variation from distributed Under this mode, the voltage is solely regulated by the ESS
generation will also give rise to higher losses than transmit- and the G-VSC acts as a constant power source depending on
ting the same amount of energy at a constant power. In addi- current limitation and the AC voltage. Island operation can also
tion, power variation will also lead to voltage variations at local be regarded as a special case, i.e., .
AC buses. Thus, it may be desirable to reduce the variation of
active power exchange between the DC microgrid and the AC III. SYSTEM CONTROL
grid. For a DC grid, the fluctuation of generated power and a As previously described, the two slack terminals are con-
load step (switching on/off) will both inevitably affect the power trolled and coordinated to respond to the demands of the power
balance. To accommodate this power difference variation, the terminals, to ensure stable system operation and desirable per-
second slack terminal, i.e., the ESS, can be regulated to absorb formance of the DC grid. In this section the control designs for
most of the power fluctuation within the DC microgrid. Hence the two respective operation modes previously described are
the rest of the power surplus (deficit), which is to be delivered outlined.
via the G-VSC, is smoothed.
A. Control Strategies Under Mode 1
C. Operation Modes In this mode, both the ESS and G-VSC respond to the fluctu-
To achieve a satisfactory operation of the proposed DC mi- ating wind power and variable loads to maintain the DC voltage.
crogrid under wind speed fluctuation, load step, AC fault, and is- A basic control strategy for Mode 1 operation is shown in
landing, two main operation modes are considered in this paper: Fig. 3. Under this mode, is set at the nominal DC voltage
Mode 1: Under this mode, the wind generation operates on . For the G-VSC, a PI controller with proportional and inte-
its own. The ESS is regulated to smooth the fluctuations of the gral gains of and , respectively, as shown in Fig. 3(a),
power difference between the variable generation and the DC is used to regulate the DC voltage. Meanwhile, a droop (pro-
loads, and the average power of the above is automatically bal- portional) of is applied to the ESS as shown in Fig. 3(b),
anced by the G-VSC to ensure the DC voltage is maintained at where is the output DC voltage of the energy storage device.
the reference value of . Neglecting the power losses, during The respective power of the two slack terminals can be shared
steady state, there is on a frequency base. When the ESS droop gain is much
larger than of the G-VSCs PI controller, and the time con-
(3) stant of the PI controller, i.e., , is also large, the fluc-
tuating power of higher frequency tends to go to the ESS while
where the superscript refers to the reference values. the lower frequency components transmit through the G-VSC.
In this mode, the ESS acts as an exchange power smoother Thus in this case, the exporting is smoothed, which is desir-
and in addition, a charging/discharging power offset can be di- able for the AC grid.
rectly added to the to control the battery charging state. As The power/current loops of VSC and DC/DC converters are
previously discussed, this condition is not probed further in this frequently modeled as a first-order delay with small time con-
paper. Under Mode 1, the ESS and G-VSC are coordinated to stants in some literature [11]. By using the technique of pre-
contribute to the DC voltage regulation and to ensure appro- dictive current and direct power control [25], [26], the dynamic
priate power flow between them. responses of the power/current loops are usually much faster
Mode 2: In this mode, the G-VSC is incapable of delivering than the voltage loop with a time delay of usually around one
the power required in (3). Such a scenario is most likely caused switching period. Thus, to simplify the system model, it is ac-
by an AC voltage dip during grid AC fault, which can signifi- ceptable to assume that the inner power/current loop is ideal and
cantly reduce the maximum power that the G-VSC can transmit. the real powers always follow their orders and the delay time can
In this case, the G-VSC holds at its maximum power and the be neglected.
ESS regulates the DC voltage on its own. Assuming the power By combining Fig. 3 and (2), the block diagram of the close
provided by the ESS is sufficient, there is loop DC voltage control is obtained as shown in Fig. 4. As a
large gain (droop) can make the ESS vulnerable to instability
(4) due to high-frequency DC voltage ripples and measurement
1900 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO. 4, NOVEMBER 2012

For a typical G-VSC PI controller, the proportional and inte-


gration gains can be set as

(12)

where is the damping coefficient and is its natural fre-


Fig. 4. Diagram of the DC voltage control loop in Mode 1. quency. The time constant of the PI controller can be defined
as

noise, it is necessary to add a low-pass filter, say . (13)


However, the inclusion of such a filter can result in poor system
damping. Thus, a lead-lag filter is used in
real implementation as is illustrated in Fig. 4. Defining and substituting (13) into
The close loop transfer function of the DC voltage loop can (11) yields
be expressed by (5), shown at the bottom of the page.
Using the generation and load terminal as system input, the (14)
transfer function of the power at the slack terminals can be ob-
tained from Fig. 4 as shown by (6)(8) at the bottom of the page. where .
It can be seen that (5) and (6) are identical whereas transfer Equation (14) shows that to have a lower crossing frequency,
functions (7) and (8) exhibit band-pass and low-pass character- both and need to be large.
istics, respectively. When their pass-bands are not totally over- By setting s,
lapped, there must be a crossing point on the magnitude-fre- and s, the designed crossing point is set at
quency response plot, where the low-pass magnitude starts to rad/s according to (14). The corresponding Bode Plots of (5),
fall and the band-pass starts to rise. Since (7) and (8) have the (7), and (8) can be obtained, which are shown in Fig. 5. As
same denominator, the frequency of such crossing point can be illustrated in Fig. 5(a), the total bandwidth of the DC voltage
calculated by considering loop is about 500 rad/s which is sufficiently high for a typical
DC voltage control system. Within this band, the power flow
of higher frequency is mostly delivered by the ESS whereas the
(9) lower frequency part flows via the G-VSC as shown in Fig. 5(b).
Substituting into (9) yields The frequency crossing point corresponds well to the designed
value.
Under steady-state, the average DC voltage is controlled to
(10) its reference voltage of at the G-VSC terminal and
voltage error is zero. Thus the average power of the ESS is also
Among the four possible roots for (10), the crossing point zero due to the droop characteristic. However, the existence of
frequency shall be the smallest positive one. Considering the DC resistances in the DC network in reality and possible mea-
lead-lag filter time constant and the desirable fre- surement error result in the voltage at the ESS terminal being
quency no more than a few rad/s (or even lower), according to slightly different to that at the G-VSC terminal. Consequently,
(10), the crossing point frequency can be approximated by considerable ESS current (power) offset may occur due to the
large ESS gain . This offset may disrupt normal charging/
(11) discharging operation. To deal with this issue, a first-order high-
pass filter with low cut-off frequency (say, time constant of 0.5 s)

(5)

(6)

(7)

(8)
CHEN AND XU: AUTONOMOUS DC VOLTAGE CONTROL OF A DC MICROGRID WITH MULTIPLE SLACK TERMINALS 1901

Fig. 5. Bode plots of the close loop voltage and power transfer functions. Fig. 6. Bode plots of the close loop voltage and power transfer functions
(a) . (b) and . (with additional ESS high-pass filter). (a) . (b) and
.

is added to the ESS control output to filter out such voltage dif-
ference. The corresponding Bode plot is shown in Fig. 6. Com-
pared to Fig. 5, it can be seen that the voltage loop response and
power frequency pass-bands are not affected. However, higher
power attenuation for the ESS at very low frequency is obtained
due to the addition of the high-pass filter which would effec-
tively eliminate any impact due to the DC voltage offset. For Fig. 7. ESS control in Mode 2.
instance, at 0.1 rad/s, an attenuation of dB is obtained in
Fig. 6(b) compared to dB shown in Fig. 5(b).
As the basic idea of voltage control based power sharing a certain output power , the larger is, the smaller DC
scheme is shown above, the performance of G-VSC power voltage variation will be.
smoothing can be further improved by adding additional
low-pass filter to the G-VSC controller to stiff the falling edge C. Mode Switching
and lower the cutoff frequency in the magnitude-frequency Under normal operation (i.e., Mode 1), both the G-VSC and
response of the G-VSC. As the system shown in Fig. 4 performs ESS regulate the DC voltage with a small variation. However,
satisfactory, no further discussion will be provided here for this when the G-VSC reaches its maximum power, the DC voltage
option. can derivate from its nominal value. Thus, the DC voltage
derivation can be used to determine the switching of the oper-
B. Control Strategies Under Mode 2 ation mode as schematically illustrated in Fig. 8. There is no
In this mode, the G-VSC delivers constant power (zero power need to have extra communication between the various parts.
during island operation) according to the current limit and thus, When the detected DC voltage error is higher (lower)
only the ESS is controlled to maintain the DC voltage. than a certain level, e.g., , the ESS switches
The control scheme of the ESS is identical to the previous to Mode 2 operation. If relatively high DC resistance exists
case shown in Fig. 3(b) and the close loop DC voltage control between the terminals of the G-VSC and ESS, the value of
system is shown in Fig. 7. The previously mentioned high-pass might need to be set slightly bigger than it would be to
filter needs to be bypassed as the ESS has to supply net power ensure normal DC voltage variation under Mode 1 would not
during stead-state depending on the DC microgrid condition. cause mode switch. Once the voltage error falls back, e.g.,
The droop determines the DC voltage variation during , the ESS switches back to Mode 1. As seen in
power variation and can be set different to in Mode 1. For Fig. 8, a double hysteresis scheme with a band of
1902 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO. 4, NOVEMBER 2012

Fig. 8. (a) Mode switch. (b) ESS voltage droop for Mode 2.

Fig. 9. Layout of the prototype system.

is applied to avoid undesirable repetitive mode switching. In


order to distinguish the ESS system operation mode by voltage
detection, a lower (higher for overvoltage case) value is given
to the DC voltage reference during Mode 2 operation as shown Fig. 10. Operation without ESS power smoothing (0.1 s/div). (a) (108
in Fig. 8(b). This indicates that under Mode 2, the DC voltage W/DIV). (b) (54 W/DIV). (c) (5 V/DIV). (d) (360 W/DIV).
will be slightly different from the nominal DC voltage.
290 W, 180 W, and 100 W, respectively. Switching frequency
IV. EXPERIMENTAL TESTS
of 2.5 KHz is used for all the converters.
To test the previously cited control strategy, a prototype DC
microgrid rated at 100 V is developed and its layout is shown A. Mode 1 Power Sharing Test
in Fig. 9. As seen from Fig. 9, two TIs TMS320F2812 DSPs During this test, in order to simulate the random wind condi-
are used for controlling the system. The G-VSC is rated at 1 tion, a random power order of 0.5 s is given to the W-converter.
kW and is controlled by DSP 1. A three-phase PMSG rated at Due to the controllers limited memory, the random order is re-
500 W driven by a DC machine is used to simulate the vari- peated every 0.5-s period. The parameters for the DC voltage
able wind generation. The output from the PMSG is rectified controllers are identical to those used for the Bode diagrams in
and connected to the common DC link via a boost DC/DC con- Section III.
verter whose output power is controlled according to pre-spec- Fig. 10 shows the system operation without using ESSs
ified curves to simulate variable power generation under dif- power smoothing function and the DC voltage is solely con-
ferent wind conditions. A battery rated at 36 V and 20 Ah is trolled by the G-VSC with the battery power staying at 0. As
connected with a bi-directional DC/DC converter to act as the shown, the power oscillation produced by the wind generation
ESS. The two DC/DC converters are controlled by DSP 2. How- is transmitted to the grid as evident in Fig. 10(a) and (b).
ever, the control algorithms implemented in DSP 2 for the two The DC voltage also contains certain ripples due to the power
DC/DC converters are completely independent with no infor- oscillation.
mation exchange between them. The total DC capacitance is Based on the same condition, Fig. 11 shows the test results
3000 F which is split into (2000 F) and (1000 F) when the power sharing scheme is applied to the system and the
as shown in Fig. 9. Four resistive DC loads are rated at 410 W, ESS absorbs the high frequency power ripples. It can be seen
CHEN AND XU: AUTONOMOUS DC VOLTAGE CONTROL OF A DC MICROGRID WITH MULTIPLE SLACK TERMINALS 1903

Fig. 12. Operation during load switch in (0.5 s/div). (a) (270 W/DIV). (b)
(5 V/DIV). (c) (360 W/DIV).

shows. The rest of the power deficit is provided by the G-VSC


and the DC voltage quickly goes back to its nominal value. Due
to the high-pass filter in the ESS controller, its average power
gradually drops back to 0. Similar operation can be observed
during load switch off tests shown in Fig. 13. As can seen, the
Fig. 11. Operation with ESS power smoothing (0.1 s/div). (a) (108 combination of the G-VSC and ESS provide satisfactory con-
W/DIV). (b) (54 W/DIV). (c) (5 V/DIV). (d) (360 W/DIV). trol and operation during power and load variation.

C. Islanding (Mode 2) Test


from Fig. 11(b) that is significantly smoothed as the power
fluctuation of higher frequency is mostly absorbed by the bat- The test results during islanding are shown in Fig. 14. During
tery ESS system shown in Fig. 11(d). The DC voltage as shown the test, an extra 0.2 resistor is inserted in series to the pos-
in Fig. 11(c) also becomes much smoother due to higher band itive DC line at point A shown in Fig. 9 to simulate DC
width of the voltage loop. From Fig. 11(d), it can also be seen cable resistance. This effectively separates the DC microgrid
that the average ESS power is around zero, i.e., no DC offset into two groups each having a common DC bus, i.e., one being
due to the use of the high-pass filter. Without such filter, test re- the G-VSC and load, and the other being the ESS and genera-
sults show significant ESS power offset which can quickly push tion. The system starts from Mode 1 operation with light gen-
the ESS into its power limit and disrupt its normal operation. eration and a large load, i.e., average generation of 320 W and
total load of 700 W. To balance the power, the G-VSC imports
B. Mode 1 Load Step Test around 430 W from the AC grid. The DC voltage is controlled
The tests carried out during load steps are shown in Figs. 12 by the G-VSC at 100.1 V at its terminal as shown in Fig. 14(b).
and 13. The oscillating power generated from the wind gener- As the generator and ESS group exports power and a DC cur-
ator stays the same as previous tests. At the time around 2.5 s, rent of 3.3 A flows through the 0.2 resistor which results a
a load of 410 W is switched in as shown in Fig. 12 causing an slightly higher DC voltage at the ESS/generation terminal of
immediate DC voltage dip of 4.5 V. To maintain the voltage, around 100.8 V. When an AC fault occurs at , the DC grid is
both slack terminals, the G-VSC and ESS system, start to output effectively islanded and the power exchange drops to 0. As
more power upon the detection of the DC voltage dip. A power can be seen from Fig. 14(b) and (c), the DC voltages at both ter-
limit of 180 W was added to the ESS at Mode 1 operation and minals drop significantly. Upon detection of voltage lower than
thus the ESS initially shares 180 W of load demand as Fig. 12(c) 0.95 V (i.e., ) at the ESS terminal, the ESS switches
1904 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO. 4, NOVEMBER 2012

Fig. 13. Operation during load switch off (0.5 s/div). (a) (270 W/DIV). (b)
(5 V/DIV). (c) (360 W/DIV).

to Mode 2 operation to maintain the DC voltage at 95 V with


a droop of 90 W/V. Due to the nature of droop controller, the
actual voltage is around 91 V as Fig. 14(c) shows. Since the gen-
eration contains around 220 W oscillations, so is the power pro-
vided by the ESS. This results in oscillation of around 2.4 V Fig. 14. Islanding Operation (1 s/DIV). (a) (270 W/DIV). (b) on
(220/90) during islanding as seen from Fig. 14(c). The total DC G-VSC side (5 V/DIV). (c) on ESS side (5 V/DIV). (d) (360 W/DIV).
current flowing from the ESS/generation to the DC load (i.e.,
via the 0.2 resistor) is around 5.6 A which results in a lower
DC voltage appearing at the G-VSC (load terminal) of around and coordinated control between grid connected converter and
90 V, as shown in Fig. 14(b). energy storage system during normal and islanding operation
After about 1.75 s, the AC system is reconnected at . The is outlined. The impact of control parameters on power spec-
G-VSC starts to import power to drive back to 100 V. The trum flown through the AC grid and energy storage system is
investigated. Test results on a prototype DC microgrid system
ESS reduces its output power accordingly and when the DC
validate the satisfactory performance of the proposed strategy
voltage reaches 95 V (0.95 V ), its power becomes zero. The
during both power smoothing, load switching, and island oper-
ESS switches back to Mode 1 operation after the DC voltage
ation. The proposed strategy can also be applied to DC system
reaches 98 V according to the setting based on
with different configurations.
Fig. 8. As can be seen from Fig. 14, system operation during is-
landing is very smooth and the DC microgrid is well controlled.
ACKNOWLEDGMENT
The DC resistance is also shown to have minimum impact on
system control and operation during both normal and islanding Mr. D. Chen would like to thank the Chinese Scholarship
conditions. Under Mode 1 operation, the G-VSC power is again Council (CSC) for sponsoring his Ph.D. study in Queens Uni-
smoothed as previously studied. versity of Belfast, Belfast, U.K.

REFERENCES
V. CONCLUSION
[1] N. Hatziargyriou, H. Asano, R. Iravani, and C. Marnay, Microgrids,
This paper proposes a voltage control strategy for a DC mi- IEEE Power Energy Mag., vol. 5, no. 4, pp. 7894, Jul.Aug. 2007.
[2] C. L. Chen, Y. Wang, J. S. Lai, Y. S. Lee, and D. Martin, Design
crogrid with variable generation and multiple slack terminals. of parallel inverters for smooth mode transfer microgrid applications,
A power sharing scheme based on frequency band is proposed, IEEE Trans. Power Electron., vol. 25, no. 1, pp. 615, Jan. 2010.
CHEN AND XU: AUTONOMOUS DC VOLTAGE CONTROL OF A DC MICROGRID WITH MULTIPLE SLACK TERMINALS 1905

[3] F. Katiraei and M. R. Iravani, Power management strategies for a mi- [20] S. Teleke, M. E. Baran, A. Q. Huang, S. Bhattacharya, and L. An-
crogrid with multiple distributed generation units, IEEE Trans. Power derson, Control strategies for battery energy storage for wind farm dis-
Syst., vol. 21, no. 4, pp. 18211831, Nov. 2006. patching, IEEE Trans. Energy Convers., vol. 24, no. 3, pp. 725732,
[4] A. Seon-Ju, P. Jin-Woo, C. Il-Yop, M. Seung-Il, K. Sang-Hee, and N. Sep. 2009.
Soon-Ryul, Power-sharing method of multiple distributed generators [21] L. Xu, L. Yao, and C. Sasse, Grid integration of large DFIG-based
considering control modes and configurations of a microgrid, IEEE wind farms using VSC transmission, IEEE Trans. Power Syst., vol.
Trans. Power Del., vol. 25, no. 3, pp. 20072016, Jul. 2010. 22, no. 3, pp. 976984, Aug. 2007.
[5] I. J. Balaguer, Q. Lei, S. Yang, U. Supatti, and F. Z. Peng, Control [22] L. Xu, B. R. Andersen, and P. Cartwright, VSC transmission operating
for grid-connected and intentional islanding operations of distributed under unbalanced AC conditionsAnalysis and control design, IEEE
power generation, IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. Trans. Power Del., vol. 20, no. 1, pp. 427434, Jan. 2005.
147157, Jan. 2011. [23] O. M. Mikic, Variance-based energy loss computation in low voltage
[6] J. A. P. Lopes, C. L. Moreira, and A. G. Madureira, Defining con- distribution networks, IEEE Trans. Power Syst., vol. 22, no. 1, pp.
trol strategies for MicroGrids islanded operation, IEEE Trans. Power 179187, Feb. 2007.
Syst., vol. 21, no. 2, pp. 916924, May 2006. [24] E. Sortomme, M. M. Hindi, S. D. J. MacPherson, and S. S. Venkata,
[7] E. Sortomme, S. S. Venkata, and J. Mitra, Microgrid protection using Coordinated charging of plug-in hybrid electric vehicles to minimize
communication-assisted digital relays, IEEE Trans. Power Del., vol. distribution system losses, IEEE Trans. Smart Grid, vol. 2, no. 1, pp.
25, no. 4, pp. 27892796, Oct. 2010. 198205, Mar. 2011.
[8] H. J. Laaksonen, Protection principles for future microgrids, IEEE [25] D. Zhi, L. Xu, and B. Williams, Improved direct power control of grid
Trans. Power Electron., vol. 25, no. 12, pp. 29102918, Dec. 2010. connected DC/AC converters, IEEE Trans. Power Electron., vol. 24,
[9] A. Sannino, G. Postiglione, and M. H. J. Bollen, Feasibility of a DC no. 5, pp. 12801292, May 2009.
network for commercial facilities, IEEE Trans. Ind. Appl., vol. 39, no. [26] J. Q. Chen, A. Prodic, R. W. Erickson, and D. Maksimovic, Predictive
5, pp. 14991507, Sep.Oct. 2003. digital current programmed control, IEEE Trans. Power Electron.,
[10] D. Salomonsson, L. Soder, and A. Sannino, An adaptive control vol. 18, no. 1, pp. 411419, Jan. 2003.
system for a DC microgrid for data centers, IEEE Trans. Ind. Appl.,
vol. 44, no. 6, pp. 19101917, Nov.Dec. 2008.
[11] H. Kakigano, Y. Miura, and T. Ise, Low-voltage bipolar-type DC mi-
crogrid for super high quality distribution, IEEE Trans. Power Elec-
tron., vol. 25, no. 12, pp. 30663075, Dec. 2010. Dong Chen received the B.Eng. degree from South-
[12] R. Kadri, J. P. Gaubert, and G. Champenois, An improved maximum east University, Nanjing, China, in 2006 and the
power point tracking for photovoltaic grid-connected inverter based on M.Sc. degree from Zhejiang University, Hangzhou,
voltage-oriented control, IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. China, in 2008. He is currently pursuing the Ph.D.
6675, Jan. 2011.
degree in the School of Electronics, Electrical Engi-
[13] E. Koutroulis and K. Kalaitzakis, Design of a maximum power
neering and Computer Science, Queens University
tracking system for wind-energy-conversion applications, IEEE
Trans. Ind. Electron., vol. 53, no. 2, pp. 486494, Apr. 2006. of Belfast, Belfast, U.K.
[14] T. Zhou and B. Francois, Energy management and power control of a His research interest includes power electronics
hybrid active wind generator for distributed power generation and grid applications in power grid, DC network, and motion
integration, IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. 95104, control.
Jan. 2011.
[15] W. Tang and R. H. Lasseter, An LVDC industrial power distribution
system without central control unit, in Proc. IEEE 2000 Power Elec-
tronics Specialists Conf. (PESC 00), 2000, vol. 2, pp. 979984.
[16] P. Karlsson and J. Svensson, DC bus voltage control for a distributed
power system, IEEE Trans. Power Electron., vol. 18, no. 6, pp. Lie Xu (M03SM06) received the B.Sc. degree
14051412, Nov. 2003. from Zhejiang University, Hangzhou, China, in
[17] D. Salomonsson, L. Soder, and A. Sannino, An adaptive control 1993, and the Ph.D. degree from the University of
system for a DC microgrid for data centers, IEEE Trans. Ind. Appl., Sheffield, Sheffield, U.K., in 1999.
vol. 44, no. 6, pp. 19101917, Nov.Dec. 2008. Currently, he is with the School of Electronics,
[18] Y. Ito, Y. Zhongqing, and H. Akagi, DC microgrid based distribution Electrical Engineering and Computer Science,
power generation system, in Proc. IPEMC, Xian, China, Aug. 2004, Queens University of Belfast, Belfast, U.K. He
pp. 17401745. was previously with the University of Strathclyde,
[19] M. Datta, T. Senjyu, A. Yona, T. Funabashi, and C.-H. Kim, A fre- Glasgow, U.K., and ALSTOM T&D, Stafford, U.K.
quency-control approach by photovoltaic generator in a PV-diesel hy- His current research interests include power elec-
brid power system, IEEE Trans. Energy Convers., vol. 26, no. 2, pp. tronics, wind energy generation and grid integration,
559571, Jun. 2011. and application of power electronics to power systems.

S-ar putea să vă placă și