Documente Academic
Documente Profesional
Documente Cultură
AbstractAutonomous DC voltage control for a DC microgrid into two types: centrally controlled [14] and autonomously con-
with multiple power and slack terminals is studied in this paper. trolled [15][17]. For a centrally controlled architecture, the
Slack terminals respond to the generation variation and load step operational orders of the consisting converters are given by a
within a DC microgrid to maintain the DC voltage. The slack
terminals considered here are grid connected VSC and energy central controller with real-time feedback from controlled ter-
storage systems. A voltage droop based power sharing and coordi- minals. A drawback of such a solution is that communication
nation strategy among the slack terminals is proposed for power delay or failure might undermine its reliability. In addition, any
smoothing during grid-connected condition and normal operation expansion of the microgrid will result in increased complexity
during islanding condition. A prototype microgrid with two power of the central controller, which might not be economical for
and two slack terminals is established to demonstrate the excellent
operation performance of the proposed control system during an expandable system with a large number of terminals. The
various operating conditions such as power variation, islanding, autonomously controlled solution, however, is based on local
and grid reconnection. voltage detection and can effectively eliminate circulating cur-
Index TermsAutonomous control, DC microgrid, energy rent [18]. As the DC voltage can be treated as an indicator
storage, power sharing. of power balancing within a DC grid, the method of voltage
droop has been widely accepted in power sharing schemes for
its reliability and simplicity in implementation. Most of the re-
I. INTRODUCTION search conducted on droop control focuses mainly on its perfor-
D UE to increasing concerns on environmental protection mance in time domain for constant power sharing; however, fre-
and sustainable development, renewable energy has at- quency-based transient power sharing has rarely been studied.
tracted extensive interest. As renewable energy sources are usu- One extensive application of power sharing is the external
ally dispersed, distributed generation becomes an attractive so- exchange power smoothing. As real power fluctuation is un-
lution. By connecting distributed generation with local loads desirable for AC power grid, it is desirable to smooth the ex-
and energy storage, a microgrid is formed [1]. Microgrids can be change power before passing it to the AC grid. Energy storage
generalized into two types, i.e., AC and DC. A variety of studies systems (ESS) based power smoothing techniques have been
have been reported on AC microgrids regarding power sharing widely studied for renewable generation [14], [19], [20]. Such
between parallel-connected sources [2][4], islanding operation smoothing scheme usually relies on real-time detection of gen-
[5], [6], protection [7], [8], etc. erated power, which is feasible for a simple load-free DC gen-
A DC system can be designed for developing rural area or eration system, e.g., single wind turbine. However, for a more
small scale commercial facilities [9] such as a data center [10] complex DC network with various generation sources and loads,
or a residential building [11]. One advantage of DC microgrids the power fluctuation may come from any generation source or
over its AC counterparts is that there is no need for frequency, load terminal. In this case, the necessity for a fast and reliable
phase, or reactive power control. In order to ensure the sta- communication path for real-time power detection remains a po-
bility of a DC system, the power flow within the DC micro- tential problem. In this paper, a simple strategy of frequency
grid must be balanced at all times to ensure the DC voltage based autonomous smoothing scheme is proposed for grid side
can be maintained. As renewable generations, such as wind power exchange.
and photovoltaic power, are obliged to follow the meteorolog- As a grid connected voltage source converter (G-VSC) is
ical conditions [12], [13], and local loads usually operate on used to control the active power exchange between DC and
their own merits, the other controllable sources, e.g., energy AC sides, the microgrid can still actively harness the power ex-
storage, network connected converters etc., must accommodate change within its rating when an AC fault caused voltage dip oc-
their variable demands to balance the power. To achieve this, curs [21], [22]. For the most severe conditions, a DC microgrid
a power sharing scheme between controllable sources must system can be disconnected (islanded) from an AC grid with
be performed. The power sharing solutions can be generalized the support of ESS [11], [18] and reconnected when the fault is
cleared. Communication between AC and DC side converters
is usually essential for sending fault/clear signals. However, in
Manuscript received June 27, 2011; revised September 30, 2011 and January
17, 2012; accepted February 24, 2012. Date of publication April 03, 2012; date the AC fault-ride-through strategy proposed in this paper, it is
of current version October 17, 2012. Paper no. TPWRS-00598-2011. not required.
The authors are with the School of Electronics, Electrical Engineering and
To incorporate the system control of power sharing and
Computer Science, Queens University of Belfast, Belfast BT9 5AH, U.K.
(e-mail: dchen02@qub.ac.uk; l.xu@ee.qub.ac.uk). fault-ride-through, a cooperation strategy is needed. In this
Digital Object Identifier 10.1109/TPWRS.2012.2189441 paper, a comprehensive control strategy for DC voltage control
(12)
(5)
(6)
(7)
(8)
CHEN AND XU: AUTONOMOUS DC VOLTAGE CONTROL OF A DC MICROGRID WITH MULTIPLE SLACK TERMINALS 1901
Fig. 5. Bode plots of the close loop voltage and power transfer functions. Fig. 6. Bode plots of the close loop voltage and power transfer functions
(a) . (b) and . (with additional ESS high-pass filter). (a) . (b) and
.
is added to the ESS control output to filter out such voltage dif-
ference. The corresponding Bode plot is shown in Fig. 6. Com-
pared to Fig. 5, it can be seen that the voltage loop response and
power frequency pass-bands are not affected. However, higher
power attenuation for the ESS at very low frequency is obtained
due to the addition of the high-pass filter which would effec-
tively eliminate any impact due to the DC voltage offset. For Fig. 7. ESS control in Mode 2.
instance, at 0.1 rad/s, an attenuation of dB is obtained in
Fig. 6(b) compared to dB shown in Fig. 5(b).
As the basic idea of voltage control based power sharing a certain output power , the larger is, the smaller DC
scheme is shown above, the performance of G-VSC power voltage variation will be.
smoothing can be further improved by adding additional
low-pass filter to the G-VSC controller to stiff the falling edge C. Mode Switching
and lower the cutoff frequency in the magnitude-frequency Under normal operation (i.e., Mode 1), both the G-VSC and
response of the G-VSC. As the system shown in Fig. 4 performs ESS regulate the DC voltage with a small variation. However,
satisfactory, no further discussion will be provided here for this when the G-VSC reaches its maximum power, the DC voltage
option. can derivate from its nominal value. Thus, the DC voltage
derivation can be used to determine the switching of the oper-
B. Control Strategies Under Mode 2 ation mode as schematically illustrated in Fig. 8. There is no
In this mode, the G-VSC delivers constant power (zero power need to have extra communication between the various parts.
during island operation) according to the current limit and thus, When the detected DC voltage error is higher (lower)
only the ESS is controlled to maintain the DC voltage. than a certain level, e.g., , the ESS switches
The control scheme of the ESS is identical to the previous to Mode 2 operation. If relatively high DC resistance exists
case shown in Fig. 3(b) and the close loop DC voltage control between the terminals of the G-VSC and ESS, the value of
system is shown in Fig. 7. The previously mentioned high-pass might need to be set slightly bigger than it would be to
filter needs to be bypassed as the ESS has to supply net power ensure normal DC voltage variation under Mode 1 would not
during stead-state depending on the DC microgrid condition. cause mode switch. Once the voltage error falls back, e.g.,
The droop determines the DC voltage variation during , the ESS switches back to Mode 1. As seen in
power variation and can be set different to in Mode 1. For Fig. 8, a double hysteresis scheme with a band of
1902 IEEE TRANSACTIONS ON POWER SYSTEMS, VOL. 27, NO. 4, NOVEMBER 2012
Fig. 8. (a) Mode switch. (b) ESS voltage droop for Mode 2.
Fig. 12. Operation during load switch in (0.5 s/div). (a) (270 W/DIV). (b)
(5 V/DIV). (c) (360 W/DIV).
Fig. 13. Operation during load switch off (0.5 s/div). (a) (270 W/DIV). (b)
(5 V/DIV). (c) (360 W/DIV).
REFERENCES
V. CONCLUSION
[1] N. Hatziargyriou, H. Asano, R. Iravani, and C. Marnay, Microgrids,
This paper proposes a voltage control strategy for a DC mi- IEEE Power Energy Mag., vol. 5, no. 4, pp. 7894, Jul.Aug. 2007.
[2] C. L. Chen, Y. Wang, J. S. Lai, Y. S. Lee, and D. Martin, Design
crogrid with variable generation and multiple slack terminals. of parallel inverters for smooth mode transfer microgrid applications,
A power sharing scheme based on frequency band is proposed, IEEE Trans. Power Electron., vol. 25, no. 1, pp. 615, Jan. 2010.
CHEN AND XU: AUTONOMOUS DC VOLTAGE CONTROL OF A DC MICROGRID WITH MULTIPLE SLACK TERMINALS 1905
[3] F. Katiraei and M. R. Iravani, Power management strategies for a mi- [20] S. Teleke, M. E. Baran, A. Q. Huang, S. Bhattacharya, and L. An-
crogrid with multiple distributed generation units, IEEE Trans. Power derson, Control strategies for battery energy storage for wind farm dis-
Syst., vol. 21, no. 4, pp. 18211831, Nov. 2006. patching, IEEE Trans. Energy Convers., vol. 24, no. 3, pp. 725732,
[4] A. Seon-Ju, P. Jin-Woo, C. Il-Yop, M. Seung-Il, K. Sang-Hee, and N. Sep. 2009.
Soon-Ryul, Power-sharing method of multiple distributed generators [21] L. Xu, L. Yao, and C. Sasse, Grid integration of large DFIG-based
considering control modes and configurations of a microgrid, IEEE wind farms using VSC transmission, IEEE Trans. Power Syst., vol.
Trans. Power Del., vol. 25, no. 3, pp. 20072016, Jul. 2010. 22, no. 3, pp. 976984, Aug. 2007.
[5] I. J. Balaguer, Q. Lei, S. Yang, U. Supatti, and F. Z. Peng, Control [22] L. Xu, B. R. Andersen, and P. Cartwright, VSC transmission operating
for grid-connected and intentional islanding operations of distributed under unbalanced AC conditionsAnalysis and control design, IEEE
power generation, IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. Trans. Power Del., vol. 20, no. 1, pp. 427434, Jan. 2005.
147157, Jan. 2011. [23] O. M. Mikic, Variance-based energy loss computation in low voltage
[6] J. A. P. Lopes, C. L. Moreira, and A. G. Madureira, Defining con- distribution networks, IEEE Trans. Power Syst., vol. 22, no. 1, pp.
trol strategies for MicroGrids islanded operation, IEEE Trans. Power 179187, Feb. 2007.
Syst., vol. 21, no. 2, pp. 916924, May 2006. [24] E. Sortomme, M. M. Hindi, S. D. J. MacPherson, and S. S. Venkata,
[7] E. Sortomme, S. S. Venkata, and J. Mitra, Microgrid protection using Coordinated charging of plug-in hybrid electric vehicles to minimize
communication-assisted digital relays, IEEE Trans. Power Del., vol. distribution system losses, IEEE Trans. Smart Grid, vol. 2, no. 1, pp.
25, no. 4, pp. 27892796, Oct. 2010. 198205, Mar. 2011.
[8] H. J. Laaksonen, Protection principles for future microgrids, IEEE [25] D. Zhi, L. Xu, and B. Williams, Improved direct power control of grid
Trans. Power Electron., vol. 25, no. 12, pp. 29102918, Dec. 2010. connected DC/AC converters, IEEE Trans. Power Electron., vol. 24,
[9] A. Sannino, G. Postiglione, and M. H. J. Bollen, Feasibility of a DC no. 5, pp. 12801292, May 2009.
network for commercial facilities, IEEE Trans. Ind. Appl., vol. 39, no. [26] J. Q. Chen, A. Prodic, R. W. Erickson, and D. Maksimovic, Predictive
5, pp. 14991507, Sep.Oct. 2003. digital current programmed control, IEEE Trans. Power Electron.,
[10] D. Salomonsson, L. Soder, and A. Sannino, An adaptive control vol. 18, no. 1, pp. 411419, Jan. 2003.
system for a DC microgrid for data centers, IEEE Trans. Ind. Appl.,
vol. 44, no. 6, pp. 19101917, Nov.Dec. 2008.
[11] H. Kakigano, Y. Miura, and T. Ise, Low-voltage bipolar-type DC mi-
crogrid for super high quality distribution, IEEE Trans. Power Elec-
tron., vol. 25, no. 12, pp. 30663075, Dec. 2010. Dong Chen received the B.Eng. degree from South-
[12] R. Kadri, J. P. Gaubert, and G. Champenois, An improved maximum east University, Nanjing, China, in 2006 and the
power point tracking for photovoltaic grid-connected inverter based on M.Sc. degree from Zhejiang University, Hangzhou,
voltage-oriented control, IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. China, in 2008. He is currently pursuing the Ph.D.
6675, Jan. 2011.
degree in the School of Electronics, Electrical Engi-
[13] E. Koutroulis and K. Kalaitzakis, Design of a maximum power
neering and Computer Science, Queens University
tracking system for wind-energy-conversion applications, IEEE
Trans. Ind. Electron., vol. 53, no. 2, pp. 486494, Apr. 2006. of Belfast, Belfast, U.K.
[14] T. Zhou and B. Francois, Energy management and power control of a His research interest includes power electronics
hybrid active wind generator for distributed power generation and grid applications in power grid, DC network, and motion
integration, IEEE Trans. Ind. Electron., vol. 58, no. 1, pp. 95104, control.
Jan. 2011.
[15] W. Tang and R. H. Lasseter, An LVDC industrial power distribution
system without central control unit, in Proc. IEEE 2000 Power Elec-
tronics Specialists Conf. (PESC 00), 2000, vol. 2, pp. 979984.
[16] P. Karlsson and J. Svensson, DC bus voltage control for a distributed
power system, IEEE Trans. Power Electron., vol. 18, no. 6, pp. Lie Xu (M03SM06) received the B.Sc. degree
14051412, Nov. 2003. from Zhejiang University, Hangzhou, China, in
[17] D. Salomonsson, L. Soder, and A. Sannino, An adaptive control 1993, and the Ph.D. degree from the University of
system for a DC microgrid for data centers, IEEE Trans. Ind. Appl., Sheffield, Sheffield, U.K., in 1999.
vol. 44, no. 6, pp. 19101917, Nov.Dec. 2008. Currently, he is with the School of Electronics,
[18] Y. Ito, Y. Zhongqing, and H. Akagi, DC microgrid based distribution Electrical Engineering and Computer Science,
power generation system, in Proc. IPEMC, Xian, China, Aug. 2004, Queens University of Belfast, Belfast, U.K. He
pp. 17401745. was previously with the University of Strathclyde,
[19] M. Datta, T. Senjyu, A. Yona, T. Funabashi, and C.-H. Kim, A fre- Glasgow, U.K., and ALSTOM T&D, Stafford, U.K.
quency-control approach by photovoltaic generator in a PV-diesel hy- His current research interests include power elec-
brid power system, IEEE Trans. Energy Convers., vol. 26, no. 2, pp. tronics, wind energy generation and grid integration,
559571, Jun. 2011. and application of power electronics to power systems.