Troubleshooting
G3520C and G3520E Generator Set Engines
Media Number -RENR5979-11 Publication Date -01/08/2012 Date Updated -30/08/2012
i04905468
Event Codes
SMCS - 1900
Engine Monitoring
The Electronic Control Module (ECM) monitors the operating parameters of the engine. The ECM
will generate an event code if a specific engine parameter exceeds an acceptable range that is defined
by the engine monitoring system. For information on the engine monitoring system, refer to
Troubleshooting, "Engine Monitoring System".
Table 1
List of Event Codes
Code Troubleshooting Procedure
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 2 de 20
E073 (1) High Oil Filter Differential Troubleshooting, "Oil Filter Differential Pressure
Pressure Problem"
E073 (3) High Oil Filter Differential Troubleshooting, "Oil Filter Differential Pressure
Pressure Problem"
E096 (1) High Fuel Pressure Troubleshooting, "Fuel Pressure Problem"
E100 (1) Low Engine Oil Pressure
Troubleshooting, "Oil Pressure Is Low"
Warning
E125 (1) Engine Oil Pressure High Troubleshooting, "Oil Pressure Is High"
Warning
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 3 de 20
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 4 de 20
E245 (1) High Right Turbo Turbine Troubleshooting, "Turbocharger Turbine Temperature Is
Inlet Temperature High"
E245 (3) High Right Turbo Turbine Troubleshooting, "Turbocharger Turbine Temperature Is
Inlet Temperature High"
E246 (1) High Left Turbo Turbine Inlet Troubleshooting, "Turbocharger Turbine Temperature Is
Temperature High"
E246 (3) High Left Turbo Turbine Inlet Troubleshooting, "Turbocharger Turbine Temperature Is
Temperature High"
E264 (3) Emergency Stop Activated Troubleshooting, "Engine Shutdown Occurrence"
E267 (1) High Gas Fuel Pressure Troubleshooting, "Fuel Pressure Problem"
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 5 de 20
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 6 de 20
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 7 de 20
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 8 de 20
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 9 de 20
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 10 de 20
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 11 de 20
The definition for the levels of severity for an event are defined below:
Table 2
Indicators (1), (2), and (3)
Warning Category Indicator Severity
(1) Least Severe
(2) Moderate Severity
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 12 de 20
Active event codes are listed in ascending numerical order. The code with the lowest number is listed
first.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 13 de 20
Illustration 1 g01365757
(1) This area represents the normal operating range of the engine parameter.
(2) In these areas, the engine is operating in an unsafe operating range of the monitored parameter. An event code will be
generated for the monitored parameter. The sensor circuit does not have an electronic problem.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 14 de 20
(3) In these areas, the signal from the sensor is outside of the operating range of the sensor. The sensor circuit has an
electronic problem. A diagnostic code will be generated for the sensor circuit. Refer to Troubleshooting, "Diagnostic
Trouble Codes" for additional information on diagnostic codes.
Logged events are listed in chronological order. The most recent event code is listed first.
This information can be helpful for troubleshooting intermittent problems. Logged codes can also be
used to review the performance of the engine.
A new code is logged and there are already ten codes in memory. In this case, the oldest code is
cleared.
Always clear logged event codes after investigating and correcting the problem which generated the
code.
Troubleshooting
For basic troubleshooting of the engine, perform the following steps in order to diagnose a
malfunction:
Determine the conditions for the event. The conditions will include the engine rpm and
the load.
Determine if there are any systems that were installed by the dealer or by the customer
that could cause the event.
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 15 de 20
2. Verify that the complaint is not due to normal engine operation. Verify that the complaint is not
due to error of the operator.
3. Narrow the probable cause. Consider the operator information, the conditions of operation, and
the history of the engine.
Fuel supply
Oil level
Oil supply
Wiring
Connectors
Be sure to check the connectors. The connectors are important for problems that are intermittent.
Refer to Troubleshooting, "Electrical Connectors - Inspect".
If these steps do not resolve the problem, refer to Table 1 for the procedure to troubleshoot the event
code.
The parameter settings for the engine monitoring system can also be viewed on Caterpillar Electronic
Technician (ET). In order to view the parameters of the engine monitoring system, refer to
Troubleshooting, "Engine Monitoring System".
E043
"Low System (1) Least (1) 20 V This item cannot be
On 20
Voltage" E875 Severe programmed.
(1)
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 16 de 20
E042
(3) Most
18 V 10
E875 severe
(3)
E017
(1) Least 109
On 20
E361 Severe C
(1)
"High Engine E015
Moderate 80 to
Coolant (2) Severity Off 111 Customer 129 1 to 60
Temperature" E361 C
C
(2)
E016
(3) Most (1) 113
On 20
E361 severe C
(3)
"Low Engine E038 5 to
Coolant (1) Least 5 C
On 80 C
Temperature" E199 Severe
(1)
E004 1500
"Engine
(3) Most N/A to
Overspeed" 0 Factory 0
E362 severe 2250
(3) rpm
E020
85 to
(1) Least 102 Customer
102
"High Engine E197 Severe C
(1) C
Oil
20
Temperature" E019
85 to
(3) Most (1) 104
On Factory 104
E197 severe C C
(3) 1 to 60
E129
(1) Least 120 Customer
"High Oil E073 Severe kPa
(1) 80 to
Filter
10 138
Differential E130 kPa
Pressure" (3) Most 138
Factory
E073 severe kPa
(3)
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 17 de 20
E127
(1) Least 10
Customer
"Low Oil E666 Severe kPa
(1) 5 to
Filter
80 kPa
Differential E128
Pressure" (3) Most
5 kPa Factory
E666 severe
(3)
"High Gas 0 to
E223 60
Temperature" (1) C 20 60 C
E053 On
Least Customer 100 to
"Low Fuel (1) 105
Pressure" E198 Severe kPa 10 135
kPa 1 to 60
(1)
"High Engine E337 14 0 to
Oil to Engine (1) C 24 C
Coolant (1)
On 20
Differential E337 Most 20 0 to
Temperature" Factory 20 C
(3) severe C
"Low Gas
Fuel E864 5 kPa
Differential (1)
Pressure" 0 to
Customer 1 to 60
On 10 35 kPa
"High Gas
Fuel E865 35
Differential (1) kPa
Pressure" Least
E050 Severe
"High System (1) On 34 V 20 This item cannot be
Voltage" E876 programmed.
(1)
E027
32 to
(1) 65
On 85 C
"High Inlet E368 C
Air (1) Customer 1 to 60
20
Temperature" E025
Moderate 32 to
(2) 100
Severity Off 100
E368 C
(2) C
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 18 de 20
E026
(3) Most (1) 73
On
E368 severe C
(3)
E096
135 105 to
"High Fuel (1) Least
On kPa 10 135
Pressure" E267 Severe
kPa
(1)
(1)
This parameter is permanently enabled. The parameter cannot be disabled.
Note: To initiate the responses, the ITSM sends commands to the ECM via the Cat Data Link. If the
connection between the ITSM and the ECM is not correct, the ITSM cannot initiate any response.
The default settings for the parameters are programmed at the factory. To accommodate unique
applications and sites, the parameters may be reprogrammed with Cat ET. The screens of Cat ET
provide guidance for changing trip points.
Table 4 lists default examples of the values for the parameters. However, the values may have
changed. Use Cat ET to determine the programming for your engine. The items can be reprogrammed
in order to accommodate the requirements of individual sites.
Use care when you program the trip points and the delay times. Ensure that the response of the ITSM
is correct for the application. The monitoring system will accept any setting within the ranges.
If the trip point for a shutdown is lower than the trip point for a warning, the warning will not be
activated.
Table 4
Default Settings for the Integrated Temperature Sensing Module
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 19 de 20
Range of
Security
System Trip Delay in the
Event State Level Range
Parameter Response Point Seconds Delay in
Code Password
Seconds
E801
(1)
Warning 655
through
C
E820
"High Exhaust (1) 100 to
Temperature" 30 665 C 1 to 60
E801
(3)
Shutdown 665
through
E820 C
(3)
E821
(1) Warning 10 to
through 50 C 60 1 to 60
50 C
"Exhaust Port E840
Temperature (1)
High E821
Deviation" (3)
Shutdown 200 100 to
through 10 1 to 10
C 200 C
E840 On Customer
(3)
E841
(1)
Warning 10 to
through 50 C 60 1 to 60
50 C
"Exhaust Port E860
Temperature (1)
Low E841
Deviation" (3)
Shutdown 200 10 to
through 10 1 to 10
C 200 C
E860
(3)
E245
(1) Warning 710 100 to
"High Turbo E246 C 710 C
Turbine Inlet (1)
30 1 to 60
Temperature" E245
(3) Shutdown 730 100 to
E246 C 730 C
(3)
https://sis.cat.com/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/siswe... 30-Nov-13
G3520C Generator Set GZB00001-UP(SEBP5411 - 08) - Documentation Pgina 20 de 20
E243
(1) Warning 615
"High Turbo E244 C
Turbine Outlet (1) 100 to
60 1 to 60
Temperature" E243 625 C
(3) Shutdown 625
E244 C
(3)
Separate timers are used in the ITSM for each response that is associated with a parameter. If a trip
point is exceeded, the timer for that event is started.
For example, the warning for the "High Exhaust Temperature" (E801 (1)) can be set to 655 C with a
30 second delay. The timer starts counting if the exhaust port temperature of the number 1 cylinder
reaches 655 C. If the temperature is not reduced to less than 655 C within 30 seconds, the event
becomes active and the event is logged.