Design of Micropile GEOPROFOUND ENGINEERING SDN BHD

Pile Geotechnical Design using SPT Values


Site:
Round Pile f = 1000 mm Skin Area per 3.142 Base Area, Ab = 0.785 m2
Factor of Safety (FoS) = 2.000
Unit End Bear at
Skin Skin Cumulative depth, End Bear at Pile Ultimate Pile Allowable Pile Capacity (kN)
Depth Avg SPT Capacity, Qult = Capacity, Qall =
Fric, fs Fric, Fs Skin Fric, Fs qb=min(400N/3 depth, Qb
Interval (m) Value, N
= 2N (kN) (kN) , 10000) (kN) Fs+Qb (kN) Qult/FoS (kN) 0 500 100015002000250030003500400045005000
(kN/m2) (kN/m2) 0
1 11 22 69.1 69.1 1466.7 1151.9 1221.0 610.5
2 11 22 69.1 138.2 1466.7 1151.9 1290.1 645.1
3 2 4 12.6 150.8 266.7 209.4 360.2 180.1
4 2 4 12.6 163.4 266.7 209.4 372.8 186.4
5 2 4 12.6 175.9 266.7 209.4 385.4 192.7 5
6 13 26 81.7 257.6 1733.3 1361.4 1619.0 809.5
7 26 52 163.4 421.0 3466.7 2722.7 3143.7 1571.8
8 21 42 131.9 552.9 2800.0 2199.1 2752.0 1376.0
9 21 42 131.9 684.9 2800.0 2199.1 2884.0 1442.0

Depth (m)
10 1 2 6.3 691.2 133.3 104.7 795.9 397.9 10
11 12 24 75.4 766.5 1600.0 1256.6 2023.2 1011.6
12 5 10 31.4 798.0 666.7 523.6 1321.6 660.8
13.5 6 12 56.5 854.5 800.0 628.3 1482.8 741.4
15 6 12 56.5 911.1 800.0 628.3 1539.4 769.7
16.5 1 2 9.4 920.5 133.3 104.7 1025.2 512.6 15
18 3 6 28.3 948.8 400.0 314.2 1262.9 631.5
19.5 1 2 9.4 958.2 133.3 104.7 1062.9 531.5
21 2 4 17.0 975.2 240.0 188.5 1163.6 581.8
23 2 4 22.6 997.8 240.0 188.5 1186.3 593.1
24 2 2464.8 7743.2 8741.0 10000.0 7854.0 16595.0 8297.5
20

Specified Working Load = 8000 kN Depth required = 13 m


25

10/06/2017
Design of Micropile GEOPROFOUND ENGINEERING SDN BHD (707134-T)

Micropile Structural Capacity Calculation

Pile Diameter, f = 1000 mm


Grade, fcu 35 cement grout (w/c ratio = 0.45)
Use API Pipe, f 88.9 mm 6.45 mm thk
fy = 500 N/mm (min)
2

Area of Steel & Concrete


As (provided) = 2prt
As = 1670.707 mm2
Ac = p*d2/4
Ac = 785500 mm2

Ultimate Axial Load,


fu = 0.4fcu*Ac + 0.75fy*As
fu = 11623515 N
fu = 11623.51506 kN

Taking Factor of Safety (FoS) = 2


fall = fu/FoS
fall = 5811.8 kN
Based on the structural capacity above, the micropile is able to take the given working load
of 5811.8 kN

Micropile Details

Micropile, Dia 1000 mm

API Pipe inside


f 88.9
6.45 mm thk

Clear spacing/Cover = 455.6 mm

Cement grout, G 35 N
W/C Ratio 0.45 min

10/06/2017
Design of Micropile GEOPROFOUND ENGINEERING SDN BHD (707134-T)

10/06/2017
Design of Micropile GEOPROFOUND ENGINEERING SDN BHD (707134-T)

Micropile Structural Capacity Calculation

Pile Diameter, f = 1000 mm


Grade, fcu 35 cement grout (w/c ratio = 0.45)
Use Rebar, f 32 mm 25 Nos
fy = 460 N/mm (min)
2

Area of Steel & Concrete


As (provided) = Sprbars2
As = 20106.19 mm2
Ac = p*d2/4
Ac = 785500 mm2

Ultimate Axial Load,


fu = 0.4fcu*Ac + 0.75fy*As
fu = 17933637 N
fu = 17933.63658 kN

Taking Factor of Safety (FoS) = 2


fall = fu/FoS
fall = 8966.8 kN
Based on the structural capacity above, the micropile is able to take the given working load
of 8966.8 kN

Micropile Details

Micropile, Dia 1000 mm

R6 Spiral Link

Rebar 4Y12

Cement grout, G 35 N
W/C Ratio 0.45 min

10/06/2017
Design of Micropile GEOPROFOUND ENGINEERING SDN BHD (707134-T)

10/06/2017