Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
No Data Check Messages.
C:\Users\user\Documents\condensor3.htri
Run Log Page 2
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Beginning Design Run
Running Shortcut Design Grid
**** DESIGN LOGIC MONITOR ****************************************************
*Shell Const.*** Velocity Drop Heat Transfer Tube Length= 16.0(ft)
Cross Cent Tube ------- ------- -------------- Over
Diam Pas Spce Pass Shl Tub Shl Tub Shell Tube Uo Area Mtd Delta Dsgn
---- --- ---- --- --- --- --- --- ----- ---- ---- ----- --- ---- ----- ----
Designing Smallest Shell to Pressure Drop. No. in Series= 1 Parallel= 1
17 4 47.5 4 31. 21. 1.5 74. 219 4044 124 415 93 .9364 .9993 -77.
17 4 47.5 4 31. 21. 1.5 74. 219 4044 124 415 93 .9364 .9993 -77.
Designing Smallest Shell to Pressure Drop. No. in Series= 1 Parallel= 2
17 4 47.5 4 15. 11. .46 20. 186 2328 110 829 93 .9364 .9993 -60.
17 4 47.5 4 15. 11. .46 20. 186 2328 110 829 93 .9364 .9993 -60.
Designing Smallest Shell to Pressure Drop. No. in Series= 1 Parallel= 3
17 5 38.0 4 13. 7.1 .41 9.4 197 1693 111 1244 93 .9364 .9994 -39.
17 23 7.2 4 49. 7.1 -.9 9.4 313 1714 141 1244 93 .9364 .9937 -23.
Designing Smallest Shell to Pressure Drop. No. in Series= 2 Parallel= 3
17 5 38.0 4 13. 7.1 .82 19. 198 1693 112 2487 98 .9848 .9997 29.3
17 5 38.0 4 13. 7.1 .82 19. 198 1693 112 2487 98 .9848 .9997 29.3
Designing Smallest Shell to Pressure Drop. No. in Series= 1 Parallel= 4
17 5 38.0 4 9.4 5.3 .26 5.8 195 1349 109 1658 93 .9364 .9994 -20.
17 24 6.9 4 38. 5.3 -.6 5.8 297 1363 135 1658 93 .9364 .9932 -1.8
Designing Smallest Shell to Pressure Drop. No. in Series= 2 Parallel= 4
17 5 38.0 4 9.4 5.3 .53 11. 196 1349 109 3316 98 .9848 .9997 68.4
17 5 38.0 4 9.4 5.3 .53 11. 196 1349 109 3316 98 .9848 .9997 68.4
Designing Smallest Shell to Pressure Drop. No. in Series= 1 Parallel= 5
17 5 38.0 4 7.5 4.2 .21 3.8 191 1132 106 2073 93 .9364 .9993 -3.1
17 5 38.0 4 7.5 4.2 .21 3.8 191 1132 106 2073 93 .9364 .9993 -3.1
Maximizing Heat Transfer to Meet Duty. No. in Series= 1 Parallel= 5
17 24 7.0 4 31. 4.2 -.2 3.8 284 1141 129 2073 93 .9364 .9931 17.9
17 24 7.0 4 31. 4.2 -.2 3.8 284 1141 129 2073 93 .9364 .9931 17.9
Running Rigorous Rating for Best Case
Running rigorous rating with larger and smaller values of shell inside diameter.
Running rigorous rating with larger and smaller values of shell inside diameter.
Running rigorous rating with larger and smaller values of central baffle spacing.
Running rigorous rating with larger and smaller values of central baffle spacing.
Running best case
Run Completed. Solution Reached in 00:08.
C:\Users\user\Documents\condensor3.htri
Runtime Messages Page 3
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Unit ID 100 - WARNING MESSAGES (CALCULATIONS CONTINUE)
The estimated tube count for this shell is 66. A large variation from the expected tube count may
indicate that program has used different clearances (such as bundle-to-shell clearance and
heights-under-nozzles) than those expected. Although the specified number of tubes has been
used to calculate the available heat transfer area, discrepancies in exchanger clearances can result
in inaccurate pressure drop and heat transfer calculations.
The physical properties of the cold fluid have been extrapolated beyond the valid temperature range.
Check calculated values.
The physical properties of the hot fluid have been extrapolated beyond the valid temperature range.
Check calculated values.
C:\Users\user\Documents\condensor3.htri
Final Results Page 4
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Process Data Hot Shellside Cold Tubeside
Fluid name mix Water
Fluid condition Cond. Vapor Sens. Liquid
Total flow rate (1000-lb/hr) 65.0000 523.426
Weight fraction vapor, In/Out (--) 1.000 0.000 0.000 0.000
Temperature, In/Out (Deg F) 240.00 165.00 90.00 130.00
Temperature, Average/Skin (Deg F) 202.50 159.98 110.00 122.76
Wall temperature, Min/Max (Deg F) 102.46 157.28 101.78 155.23
Pressure, In/Average (psia) 18.000 17.128 40.000 38.046
Pressure drop, Total/Allowed (psi) 1.744 2.000 3.908 10.000
Velocity, Mid/Max allow (ft/sec) 17.24 4.24
Mole fraction inert (--) 0.0000
Average film coef. (Btu/ft2-hr-F) 240.57 1117.75
Heat transfer safety factor (--) 1.000 1.000
Fouling resistance (ft2-hr-F/Btu) 0.00200 0.00100
Overall Performance Data
Overall coef., Reqd/Clean/Actual (Btu/ft2-hr-F) 107.05 / 189.43 / 119.22
Heat duty, Calculated/Specified (MM Btu/hr) 21.1155 /
Effective overall temperature difference (Deg F) 95.2
EMTD = (MTD) * (DELTA) * (F/G/H) (Deg F) 97.81 * 0.9731 * 1.0000
Tube Information
Tube type Plain Tubecount per shell 100
Overall length (ft) 16.000 Pct tubes removed (both) 24
Effective length (ft) 15.833 Outside diameter (inch) 1.0000
Total tubesheet (inch) 2.0000 Wall thickness (inch) 0.0490
Area ratio (out/in) 1.1086 Pitch (inch) 1.2500 Ratio 1.2500
Tube metal Carbon steel Tube pattern (deg) 45
C:\Users\user\Documents\condensor3.htri
Final Results Page 5
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Shellside Performance
Nom vel, X-flow/window 23.15 / 27.75
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Externally Enhanced Tube Geometry Internally Enhanced Tube Geometry
Type Plain Type None
Fin density (fin/inch) Thickness (inch)
Fin height (inch) Pitch (L/D)
Fin thickness (inch)
Root diameter (inch)
Area/length (ft2/ft)
C:\Users\user\Documents\condensor3.htri
Shellside Incremental Monitor Page 7
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Shellside Flow Region 1 13.0000 1000-lb/hr
Point number (--) 1 2 3 4 5
Shell pass (--) 1 1 1 1 1
Length from tube inlet (inch) 190.000 177.630 161.750 154.731 147.712
Mass fraction vapor (--) 1.0000 0.9502 0.8341 0.7682 0.7047
Bulk temperature (F) 240.00 218.59 217.01 216.08 215.18
Skin temperature (F) 163.18 185.93 183.83 181.95
MTD (F) 110.4 105.5 104.6 103.7
Delta MTD correction (--) 1.000 0.999 0.999 0.999
Pressure (psia) 18.000 17.919 17.743 17.501 17.293
Pressure drop (psi) 0.071 0.092 0.259 0.224 0.192
Friction loss (psi) 0.103 0.337 0.295 0.256
Static head loss (psi) 0.000 0.000 0.000 0.000
Momentum loss (psi) -0.011 -0.078 -0.070 -0.063
Crossflow velocity (ft/sec)
Longitudinal velocity (ft/sec)
Shear stress at tube wall
Crossflow (psi) 0.000 0.000 0.000 0.000
Longitudinal flow (psi) 0.000 0.000 0.000
Area (ft2) 53.974 15.314 15.314 15.314
Cumulative area (ft2) 53.974 69.288 84.602 99.916
Duty (MM Btu/hr) 0.5767 0.2373 0.2306 0.2246
Cumulative duty (MM Btu/hr) 0.5767 0.8140 1.0446 1.2692
Heat flux (Btu/hr ft2) 10685.0 15494.1 15057.8 14667.1
Calculated heat flux (Btu/hr ft2) 12284.9 17620.6 17122.5 16675.6
Critical heat flux (Btu/hr ft2)
Overall U (Btu/ft2-hr-F) 114.13 167.10 163.80 160.91
Shellside h (Btu/ft2-hr-F) 249.64 568.11 531.88 502.74
Sensible liquid h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Sensible vapor h (Btu/ft2-hr-F) 36.98 57.96 54.99 52.04
Condensate film h (Btu/ft2-hr-F) 742.67 876.53 794.47 730.40
Vapor phase h (Btu/ft2-hr-F) 546.16 1615.49 1610.05 1613.70
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Local Reynolds (--) 53600 11444 9303 7339 6170
Vapor Reynolds (--) 53600 43972 94991 87391 80086
Liquid Reynolds (--) 0 50 430 599 761
Vapor Prandtl (--) 0.71 0.70 0.70 0.70 0.70
Liquid Prandtl (--) 9.91 9.94 9.99 10.01 10.04
Flow regime param. (--) 0.1687 0.1480 0.1820 0.2140
Condensate regime (--) Shear Shear Shear Shear
Boiling regime (--)
Boiling mechanism (--)
C:\Users\user\Documents\condensor3.htri
Shellside Incremental Monitor Page 8
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Shellside Flow Region 1
Point number (--) 6 7 8 9 10
Shell pass (--) 1 1 1 1 1
Length from tube inlet (inch) 140.692 133.673 126.654 119.634 112.615
Mass fraction vapor (--) 0.6434 0.5845 0.5288 0.4769 0.4282
Bulk temperature (F) 214.31 213.45 212.64 211.88 211.17
Skin temperature (F) 180.19 177.87 173.94 170.28 167.20
MTD (F) 102.9 102.0 101.2 100.5 99.8
Delta MTD correction (--) 0.999 0.999 0.999 0.998 0.998
Pressure (psia) 17.115 16.964 16.836 16.727 16.635
Pressure drop (psi) 0.163 0.139 0.118 0.100 0.083
Friction loss (psi) 0.220 0.189 0.162 0.137 0.116
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) -0.057 -0.051 -0.044 -0.038 -0.032
Crossflow velocity (ft/sec)
Longitudinal velocity (ft/sec)
Shear stress at tube wall
Crossflow (psi) 0.000 0.000 0.000 0.000 0.000
Longitudinal flow (psi) 0.000 0.000 0.000 0.000 0.000
Area (ft2) 15.314 15.314 15.314 15.314 15.314
Cumulative area (ft2) 115.229 130.543 145.857 161.171 176.484
Duty (MM Btu/hr) 0.2190 0.2116 0.1991 0.1875 0.1777
Cumulative duty (MM Btu/hr) 1.4882 1.6998 1.8990 2.0864 2.2642
Heat flux (Btu/hr ft2) 14301.3 13819.2 13003.5 12243.7 11605.1
Calculated heat flux (Btu/hr ft2) 16256.5 15707.6 14776.5 13905.7 13183.2
Critical heat flux (Btu/hr ft2)
Overall U (Btu/ft2-hr-F) 158.22 154.17 146.19 138.66 132.33
Shellside h (Btu/ft2-hr-F) 477.45 442.92 383.02 335.42 300.63
Sensible liquid h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Sensible vapor h (Btu/ft2-hr-F) 49.11 46.20 43.36 40.63 37.99
Condensate film h (Btu/ft2-hr-F) 676.20 606.22 495.62 415.94 361.54
Vapor phase h (Btu/ft2-hr-F) 1625.31 1648.77 1690.17 1736.21 1786.35
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 5383 4816 4393 4070 3813
Vapor Reynolds (--) 73010 66246 59867 53927 48391
Liquid Reynolds (--) 916 1066 1207 1337 1460
Vapor Prandtl (--) 0.71 0.71 0.71 0.71 0.71
Liquid Prandtl (--) 10.06 10.08 10.10 10.11 10.13
Flow regime param. (--) 0.2456 0.2777 0.3103 0.3436 0.3784
Condensate regime (--) Shear Transition Transition Transition Transition
Boiling regime (--)
Boiling mechanism (--)
C:\Users\user\Documents\condensor3.htri
Shellside Incremental Monitor Page 9
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Shellside Flow Region 1
Point number (--) 11 12 13 14 15
Shell pass (--) 1 1 1 1 1
Length from tube inlet (inch) 105.596 98.5765 91.5572 84.5378 77.5185
Mass fraction vapor (--) 0.3824 0.3390 0.2976 0.2574 0.2176
Bulk temperature (F) 210.50 209.87 209.26 208.68 208.11
Skin temperature (F) 164.51 162.10 160.42 160.09 159.96
MTD (F) 99.1 98.5 98.0 97.4 96.9
Delta MTD correction (--) 0.998 0.998 0.998 0.998 0.998
Pressure (psia) 16.559 16.496 16.445 16.405 16.374
Pressure drop (psi) 0.069 0.057 0.046 0.035 0.026
Friction loss (psi) 0.097 0.081 0.066 0.054 0.042
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) -0.028 -0.024 -0.021 -0.018 -0.016
Crossflow velocity (ft/sec)
Longitudinal velocity (ft/sec)
Shear stress at tube wall
Crossflow (psi) 0.000 0.000 0.000 0.000 0.000
Longitudinal flow (psi) 0.000 0.000 0.000 0.000 0.000
Area (ft2) 15.314 15.314 15.314 15.314 15.314
Cumulative area (ft2) 191.798 207.112 222.426 237.739 253.053
Duty (MM Btu/hr) 0.1692 0.1616 0.1563 0.1553 0.1549
Cumulative duty (MM Btu/hr) 2.4334 2.5949 2.7512 2.9064 3.0613
Heat flux (Btu/hr ft2) 11048.7 10549.5 10203.8 10139.3 10115.3
Calculated heat flux (Btu/hr ft2) 12547.2 11981.2 11586.3 11512.7 11483.8
Critical heat flux (Btu/hr ft2)
Overall U (Btu/ft2-hr-F) 126.81 121.82 118.52 118.45 118.85
Shellside h (Btu/ft2-hr-F) 273.67 251.49 237.82 237.57 239.18
Sensible liquid h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Sensible vapor h (Btu/ft2-hr-F) 35.40 32.84 30.30 27.70 24.99
Condensate film h (Btu/ft2-hr-F) 321.61 290.00 270.76 269.51 270.71
Vapor phase h (Btu/ft2-hr-F) 1838.94 1896.37 1956.49 2006.55 2055.89
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 3603 3427 3278 3146 3028
Vapor Reynolds (--) 43182 38241 33556 28987 24490
Liquid Reynolds (--) 1575 1684 1787 1888 1988
Vapor Prandtl (--) 0.72 0.72 0.72 0.72 0.72
Liquid Prandtl (--) 10.14 10.15 10.15 10.16 10.17
Flow regime param. (--) 0.4155 0.4558 0.5006 0.5529 0.6164
Condensate regime (--) Transition Transition Gravity Gravity Gravity
Boiling regime (--)
Boiling mechanism (--)
C:\Users\user\Documents\condensor3.htri
Shellside Incremental Monitor Page 10
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Shellside Flow Region 1
Point number (--) 16 17 18 19 20
Shell pass (--) 1 1 1 1 1
Length from tube inlet (inch) 70.4992 63.4799 56.4606 49.4413 42.4219
Mass fraction vapor (--) 0.1782 0.1394 0.1013 0.0638 0.0266
Bulk temperature (F) 207.55 207.00 206.47 205.95 205.45
Skin temperature (F) 159.58 159.05 158.50 158.07 158.20
MTD (F) 96.3 95.8 95.3 94.8 94.3
Delta MTD correction (--) 0.998 0.998 0.998 0.997 0.986
Pressure (psia) 16.351 16.336 16.326 16.321 16.318
Pressure drop (psi) 0.019 0.012 7.240e-3 3.620e-3 1.376e-3
Friction loss (psi) 0.032 0.023 0.016 9.807e-3 4.966e-3
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) -0.014 -0.011 -8.65e-3 -6.19e-3 -3.59e-3
Crossflow velocity (ft/sec)
Longitudinal velocity (ft/sec)
Shear stress at tube wall
Crossflow (psi) 0.000 0.000 0.000 0.000 0.000
Longitudinal flow (psi) 0.000 0.000 0.000 0.000 0.000
Area (ft2) 15.314 15.314 15.314 15.314 15.314
Cumulative area (ft2) 268.367 283.681 298.995 314.308 329.622
Duty (MM Btu/hr) 0.1538 0.1521 0.1505 0.1492 0.1496
Cumulative duty (MM Btu/hr) 3.2151 3.3673 3.5177 3.6669 3.8165
Heat flux (Btu/hr ft2) 10041.7 9934.54 9825.17 9740.01 9770.52
Calculated heat flux (Btu/hr ft2) 11399.6 11276.4 11151.9 11054.4 10959.0
Critical heat flux (Btu/hr ft2)
Overall U (Btu/ft2-hr-F) 118.65 118.03 117.36 116.89 117.87
Shellside h (Btu/ft2-hr-F) 238.40 235.92 233.27 231.46 235.35
Sensible liquid h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Sensible vapor h (Btu/ft2-hr-F) 22.10 19.03 15.66 11.84 6.90
Condensate film h (Btu/ft2-hr-F) 268.95 265.13 261.60 258.34 255.27
Vapor phase h (Btu/ft2-hr-F) 2101.10 2145.91 2160.20 2228.15 3098.61
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 2921 2824 2736 2656 2583
Vapor Reynolds (--) 20026 15666 11366 7166 2984
Liquid Reynolds (--) 2087 2184 2280 2374 2467
Vapor Prandtl (--) 0.72 0.72 0.73 0.73 0.73
Liquid Prandtl (--) 10.17 10.18 10.18 10.18 10.19
Flow regime param. (--) 0.6976 0.8062 0.9673 1.2474 2.0708
Condensate regime (--) Gravity Gravity Gravity Gravity Gravity
Boiling regime (--)
Boiling mechanism (--)
C:\Users\user\Documents\condensor3.htri
Shellside Incremental Monitor Page 11
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Shellside Flow Region 1
Point number (--) 21 22 23 24 25
Shell pass (--) 1 1 1 1 1
Length from tube inlet (inch) 35.4026 28.3833 21.3640 14.3446 5.4175
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 203.05 193.21 184.99 177.65 169.60
Skin temperature (F) 143.99 136.75 133.75 131.13 128.33
MTD (F) 90.9 82.1 73.9 66.6 58.5
Delta MTD correction (--) 0.920 0.897 0.880 0.865 0.837
Pressure (psia) 16.317 16.314 16.312 16.310 16.308
Pressure drop (psi) 2.175e-3 2.393e-3 2.383e-3 2.374e-3 1.295e-3
Friction loss (psi) 2.492e-3 2.393e-3 2.383e-3 2.374e-3 1.295e-3
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) -3.17e-4 0.000 0.000 0.000 0.000
Crossflow velocity (ft/sec)
Longitudinal velocity (ft/sec)
Shear stress at tube wall
Crossflow (psi) 1.251e-5 1.271e-5 1.298e-5 1.323e-5 0.000
Longitudinal flow (psi)
Area (ft2) 15.314 15.314 15.314 15.314 23.638
Cumulative area (ft2) 344.936 360.250 375.563 390.877 414.516
Duty (MM Btu/hr) 0.1041 0.0816 0.0721 0.0638 0.0850
Cumulative duty (MM Btu/hr) 3.9206 4.0022 4.0743 4.1381 4.2231
Heat flux (Btu/hr ft2) 6797.62 5326.96 4708.65 4168.77 3594.90
Calculated heat flux (Btu/hr ft2) 7107.91 5437.58 4715.13 4102.91 3423.23
Critical heat flux (Btu/hr ft2)
Overall U (Btu/ft2-hr-F) 84.76 73.86 72.50 71.27 69.90
Shellside h (Btu/ft2-hr-F) 133.81 107.54 104.71 102.16 99.39
Sensible liquid h (Btu/ft2-hr-F) 109.90 107.54 104.71 102.16 99.39
Sensible vapor h (Btu/ft2-hr-F) 2.38 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 161.51 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 3727.75 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 2462 2267 2098 1953 1480
Vapor Reynolds (--) 227 0 0 0 0
Liquid Reynolds (--) 2454 2267 2098 1953 1480
Vapor Prandtl (--) 0.73 0.73 0.73 0.73 0.73
Liquid Prandtl (--) 10.45 11.10 11.79 12.48 13.28
Flow regime param. (--) 2.8295 0.6000 0.6000 0.6000 0.6000
Condensate regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling regime (--)
Boiling mechanism (--)
C:\Users\user\Documents\condensor3.htri
Shellside Incremental Monitor Page 12
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Shellside Flow Region 1
Point number (--) 26
Shell pass (--) 1
Length from tube inlet (inch) 0.0000
Mass fraction vapor (--) 0.0000
Bulk temperature (F) 165.00
Skin temperature (F)
MTD (F)
Delta MTD correction (--)
Pressure (psia) 16.256
Pressure drop (psi) 0.016
Friction loss (psi)
Static head loss (psi)
Momentum loss (psi)
Crossflow velocity (ft/sec)
Longitudinal velocity (ft/sec)
Shear stress at tube wall
Crossflow (psi)
Longitudinal flow (psi)
Area (ft2)
Cumulative area (ft2)
Duty (MM Btu/hr)
Cumulative duty (MM Btu/hr)
Heat flux (Btu/hr ft2)
Calculated heat flux (Btu/hr ft2)
Critical heat flux (Btu/hr ft2)
Overall U (Btu/ft2-hr-F)
Shellside h (Btu/ft2-hr-F)
Sensible liquid h (Btu/ft2-hr-F)
Sensible vapor h (Btu/ft2-hr-F)
Condensate film h (Btu/ft2-hr-F)
Vapor phase h (Btu/ft2-hr-F)
Nucleate boiling h (Btu/ft2-hr-F)
Conv. boiling h (Btu/ft2-hr-F)
Film boiling h (Btu/ft2-hr-F)
Boiling thin film h (Btu/ft2-hr-F)
Natural convective h (Btu/ft2-hr-F)
Local Reynolds (--) 1919
Vapor Reynolds (--) 0
Liquid Reynolds (--) 1919
Vapor Prandtl (--) 0.73
Liquid Prandtl (--) 13.76
Flow regime param. (--)
Condensate regime (--)
Boiling regime (--)
Boiling mechanism (--)
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 13
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 1 2 3 4 5
Tube Pass (--) 1 1 1 1 1
Length from tube inlet (inch) 0.0000 5.4175 14.3446 21.3640 28.3833
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 90.00 90.13 90.36 90.56 90.79
Skin temperature (F) 95.94 97.27 97.80 99.18
MTD (F) 76.3 88.4 91.9 104.0
Pressure (psia) 40.000 39.692 39.668 39.643 39.619
Pressure drop (psi) 0.267 0.041 0.024 0.024 0.024
Enhanced pressure drop mult (--)
Friction loss (psi) 0.041 0.024 0.024 0.024
Static head loss (psi) 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.22 4.22 4.22 4.23
Average velocity (ft/sec) 4.22 4.22 4.22 4.23
Shear stress at tube wall (psi) 7.849e-4 7.837e-4 7.825e-4 7.812e-4
Area (ft2) 5.910 3.828 3.828 3.828
Cumulative area (ft2) 5.910 9.738 13.566 17.395
Duty (MM Btu/hr) 0.0273 0.0211 0.0222 0.0258
Cumulative duty (MM Btu/hr) 0.0273 0.0485 0.0706 0.0964
Heat flux (Btu/hr ft2) 4625.34 5519.20 5786.25 6731.94
Calculated heat flux (Btu/hr ft2) 5263.36 6280.49 6584.45 7660.03
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 68.97 71.03 71.65 73.67
Tubeside h (Btu/ft2-hr-F) 1005.77 1008.10 1009.55 1012.22
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1005.77 1008.10 1009.55 1012.22
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00
Local Reynolds (--) 38578 38594 38694 38784 38883
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 38522 38594 38694 38784 38883
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 5.19 5.18 5.16 5.15 5.14
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 14
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 6 7 8 9 10
Tube Pass (--) 1 1 1 1 1
Length from tube inlet (inch) 35.4026 42.4219 49.4413 56.4606 63.4799
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 91.04 91.38 91.80 92.22 92.65
Skin temperature (F) 99.86 105.75 106.08 106.52 106.94
MTD (F) 108.4 114.2 114.0 114.4 114.2
Pressure (psia) 39.595 39.571 39.547 39.523 39.499
Pressure drop (psi) 0.024 0.024 0.024 0.024 0.024
Enhanced pressure drop mult (--)
Friction loss (psi) 0.024 0.024 0.024 0.024 0.024
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.23 4.23 4.23 4.23 4.23
Average velocity (ft/sec) 4.23 4.23 4.23 4.23 4.23
Shear stress at tube wall (psi) 7.773e-4 7.736e-4 7.730e-4 7.724e-4 7.717e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 21.223 25.052 28.880 32.709 36.537
Duty (MM Btu/hr) 0.0271 0.0446 0.0444 0.0446 0.0447
Cumulative duty (MM Btu/hr) 0.1235 0.1682 0.2126 0.2571 0.3018
Heat flux (Btu/hr ft2) 7089.90 11657.6 11596.8 11639.3 11663.7
Calculated heat flux (Btu/hr ft2) 8066.27 13263.9 13194.5 13242.5 13270.4
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 74.42 116.17 115.73 115.79 116.20
Tubeside h (Btu/ft2-hr-F) 1014.04 1023.14 1024.69 1026.70 1028.85
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1014.04 1023.14 1024.69 1026.70 1028.85
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 38993 39143 39329 39517 39705
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 38993 39143 39329 39517 39705
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 5.12 5.10 5.07 5.04 5.02
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 15
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 11 12 13 14 15
Tube Pass (--) 1 1 1 1 1
Length from tube inlet (inch) 70.4992 77.5185 84.5378 91.5572 98.5765
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 93.07 93.50 93.93 94.36 94.79
Skin temperature (F) 107.51 107.93 108.32 108.69 109.70
MTD (F) 114.6 114.4 114.9 114.7 115.2
Pressure (psia) 39.475 39.451 39.427 39.403 39.379
Pressure drop (psi) 0.024 0.024 0.024 0.024 0.024
Enhanced pressure drop mult (--)
Friction loss (psi) 0.024 0.024 0.024 0.024 0.024
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.23 4.23 4.23 4.23 4.23
Average velocity (ft/sec) 4.23 4.23 4.23 4.23 4.23
Shear stress at tube wall (psi) 7.710e-4 7.704e-4 7.698e-4 7.689e-4 7.678e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 40.366 44.194 48.022 51.851 55.679
Duty (MM Btu/hr) 0.0452 0.0452 0.0452 0.0451 0.0471
Cumulative duty (MM Btu/hr) 0.3470 0.3922 0.4375 0.4826 0.5296
Heat flux (Btu/hr ft2) 11808.5 11818.7 11813.1 11784.6 12294.0
Calculated heat flux (Btu/hr ft2) 13435.2 13447.7 13441.3 13409.0 13989.8
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 117.23 117.52 117.01 116.88 121.48
Tubeside h (Btu/ft2-hr-F) 1031.35 1033.34 1035.48 1037.59 1041.00
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1031.35 1033.34 1035.48 1037.59 1041.00
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 39896 40090 40284 40478 40678
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 39896 40090 40284 40478 40678
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 4.99 4.96 4.94 4.91 4.88
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 16
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 16 17 18 19 20
Tube Pass (--) 1 1 1 1 1
Length from tube inlet (inch) 105.596 112.615 119.634 126.654 133.673
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 95.24 95.71 96.20 96.72 97.27
Skin temperature (F) 110.39 111.85 112.67 114.58 115.51
MTD (F) 115.1 115.6 115.5 116.1 115.9
Pressure (psia) 39.355 39.331 39.307 39.284 39.260
Pressure drop (psi) 0.024 0.024 0.024 0.024 0.024
Enhanced pressure drop mult (--)
Friction loss (psi) 0.024 0.024 0.024 0.024 0.024
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.23 4.23 4.23 4.23 4.23
Average velocity (ft/sec) 4.23 4.23 4.23 4.23 4.23
Shear stress at tube wall (psi) 7.664e-4 7.650e-4 7.634e-4 7.617e-4 7.602e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 59.508 63.336 67.165 70.993 74.822
Duty (MM Btu/hr) 0.0479 0.0512 0.0524 0.0571 0.0585
Cumulative duty (MM Btu/hr) 0.5776 0.6288 0.6812 0.7383 0.7968
Heat flux (Btu/hr ft2) 12518.6 13384.5 13695.8 14916.7 15278.9
Calculated heat flux (Btu/hr ft2) 14245.9 15231.7 15586.0 16975.2 17387.7
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 123.87 131.82 135.07 146.31 150.07
Tubeside h (Btu/ft2-hr-F) 1043.50 1047.16 1050.04 1054.48 1057.71
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1043.50 1047.16 1050.04 1054.48 1057.71
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 40881 41091 41311 41545 41794
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 40881 41091 41311 41545 41794
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 4.86 4.83 4.80 4.77 4.74
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 17
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 21 22 23 24 25
Tube Pass (--) 1 1 1 1 1
Length from tube inlet (inch) 140.692 147.712 154.731 161.750 177.630
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 97.84 98.43 99.02 99.63 100.44
Skin temperature (F) 116.97 117.63 118.82 119.54 111.54
MTD (F) 116.7 116.5 117.3 117.1 128.7
Pressure (psia) 39.236 39.213 39.189 39.165 39.077
Pressure drop (psi) 0.024 0.024 0.024 0.024 0.088
Enhanced pressure drop mult (--)
Friction loss (psi) 0.024 0.024 0.024 0.024 0.088
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.23 4.23 4.23 4.23 4.23
Average velocity (ft/sec) 4.23 4.23 4.23 4.23 4.23
Shear stress at tube wall (psi) 7.589e-4 7.578e-4 7.566e-4 7.629e-4 7.710e-4
Area (ft2) 3.828 3.828 3.828 3.828 13.494
Cumulative area (ft2) 78.650 82.478 86.307 90.135 103.629
Duty (MM Btu/hr) 0.0616 0.0620 0.0642 0.0647 0.1051
Cumulative duty (MM Btu/hr) 0.8585 0.9205 0.9847 1.0494 1.1545
Heat flux (Btu/hr ft2) 16094.4 16203.7 16767.8 16903.1 7790.21
Calculated heat flux (Btu/hr ft2) 18313.4 18438.2 19080.1 19234.0 9550.51
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 157.02 158.32 162.75 164.32 90.18
Tubeside h (Btu/ft2-hr-F) 1061.75 1064.39 1068.58 1071.37 1068.75
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1061.75 1064.39 1068.58 1071.37 1068.75
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 42054 42323 42599 42884 43253
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 42054 42323 42599 42884 43253
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 4.70 4.67 4.64 4.60 4.56
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 18
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 26 27 28 29 30
Tube Pass (--) 2 2 2 2 2
Length from tube inlet (inch) 177.630 161.750 154.731 147.712 140.692
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 101.86 103.09 103.69 104.26 104.82
Skin temperature (F) 118.79 122.49 122.14 122.38 122.14
MTD (F) 116.3 114.1 112.1 111.1 109.2
Pressure (psia) 38.715 38.691 38.668 38.644 38.621
Pressure drop (psi) 0.363 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.363 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.23 4.24 4.24 4.24 4.24
Average velocity (ft/sec) 4.23 4.24 4.24 4.24 4.24
Shear stress at tube wall (psi) 7.667e-4 7.540e-4 7.520e-4 7.520e-4 7.518e-4
Area (ft2) 13.494 3.828 3.828 3.828 3.828
Cumulative area (ft2) 117.122 120.951 124.779 128.608 132.436
Duty (MM Btu/hr) 0.1958 0.0640 0.0610 0.0600 0.0575
Cumulative duty (MM Btu/hr) 1.3503 1.4143 1.4753 1.5353 1.5928
Heat flux (Btu/hr ft2) 14509.7 16716.7 15935.3 15681.4 15018.3
Calculated heat flux (Btu/hr ft2) 16523.3 19023.8 18134.4 17845.3 17090.6
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 142.48 166.78 161.84 160.66 156.57
Tubeside h (Btu/ft2-hr-F) 1084.88 1088.25 1089.91 1092.18 1094.02
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1084.88 1088.25 1089.91 1092.18 1094.02
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 43906 44481 44759 45030 45294
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 43906 44481 44759 45030 45294
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 4.48 4.42 4.39 4.36 4.33
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 19
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 31 32 33 34 35
Tube Pass (--) 2 2 2 2 2
Length from tube inlet (inch) 133.673 126.654 119.634 112.615 105.596
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 105.36 105.87 106.35 106.80 107.23
Skin temperature (F) 122.39 121.29 121.29 120.51 120.56
MTD (F) 108.3 106.5 105.7 104.1 103.4
Pressure (psia) 38.597 38.574 38.551 38.527 38.504
Pressure drop (psi) 0.023 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.24 4.24 4.24 4.24 4.24
Average velocity (ft/sec) 4.24 4.24 4.24 4.24 4.24
Shear stress at tube wall (psi) 7.517e-4 7.520e-4 7.525e-4 7.528e-4 7.531e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 136.265 140.093 143.922 147.750 151.578
Duty (MM Btu/hr) 0.0566 0.0513 0.0498 0.0457 0.0445
Cumulative duty (MM Btu/hr) 1.6494 1.7007 1.7505 1.7962 1.8407
Heat flux (Btu/hr ft2) 14782.4 13394.7 12997.2 11932.9 11620.1
Calculated heat flux (Btu/hr ft2) 16824.0 15244.8 14792.2 13580.7 13224.7
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 155.48 143.24 140.04 130.50 127.95
Tubeside h (Btu/ft2-hr-F) 1095.94 1096.57 1098.29 1098.84 1100.41
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1095.94 1096.57 1098.29 1098.84 1100.41
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 45548 45786 46010 46222 46424
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 45548 45786 46010 46222 46424
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 4.30 4.28 4.25 4.23 4.21
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 20
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 36 37 38 39 40
Tube Pass (--) 2 2 2 2 2
Length from tube inlet (inch) 98.5765 91.5572 84.5378 77.5185 70.4992
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 107.63 108.02 108.40 108.78 109.15
Skin temperature (F) 119.98 120.12 120.30 120.61 120.78
MTD (F) 102.0 101.4 100.1 99.5 98.2
Pressure (psia) 38.480 38.457 38.433 38.410 38.387
Pressure drop (psi) 0.023 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.24 4.24 4.24 4.24 4.24
Average velocity (ft/sec) 4.24 4.24 4.24 4.24 4.24
Shear stress at tube wall (psi) 7.533e-4 7.534e-4 7.532e-4 7.528e-4 7.525e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 155.407 159.235 163.064 166.892 170.721
Duty (MM Btu/hr) 0.0412 0.0405 0.0399 0.0397 0.0391
Cumulative duty (MM Btu/hr) 1.8819 1.9224 1.9622 2.0019 2.0410
Heat flux (Btu/hr ft2) 10774.1 10571.0 10412.2 10365.7 10209.0
Calculated heat flux (Btu/hr ft2) 12261.4 12030.0 11848.2 11795.4 11616.3
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 120.25 118.72 118.41 118.61 118.29
Tubeside h (Btu/ft2-hr-F) 1101.10 1102.51 1104.06 1105.66 1107.39
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1101.10 1102.51 1104.06 1105.66 1107.39
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 46616 46801 46983 47163 47343
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 46616 46801 46983 47163 47343
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 4.19 4.17 4.16 4.14 4.12
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 21
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 41 42 43 44 45
Tube Pass (--) 2 2 2 2 2
Length from tube inlet (inch) 63.4799 56.4606 49.4413 42.4219 35.4026
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 109.52 109.88 110.24 110.60 110.92
Skin temperature (F) 121.04 121.14 121.40 121.78 119.78
MTD (F) 97.6 96.4 95.8 94.7 92.8
Pressure (psia) 38.363 38.340 38.316 38.293 38.270
Pressure drop (psi) 0.023 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.24 4.24 4.24 4.24 4.24
Average velocity (ft/sec) 4.24 4.24 4.24 4.24 4.24
Shear stress at tube wall (psi) 7.522e-4 7.519e-4 7.517e-4 7.513e-4 7.521e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 174.549 178.378 182.206 186.034 189.863
Duty (MM Btu/hr) 0.0388 0.0380 0.0377 0.0378 0.0297
Cumulative duty (MM Btu/hr) 2.0798 2.1177 2.1554 2.1932 2.2228
Heat flux (Btu/hr ft2) 10127.7 9913.37 9836.93 9870.94 7746.23
Calculated heat flux (Btu/hr ft2) 11523.8 11279.8 11193.0 11232.2 8802.06
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 118.06 117.01 116.80 118.67 94.45
Tubeside h (Btu/ft2-hr-F) 1108.96 1110.65 1112.04 1113.69 1112.90
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1108.96 1110.65 1112.04 1113.69 1112.90
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 47521 47697 47872 48047 48203
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 47521 47697 47872 48047 48203
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 4.10 4.09 4.07 4.05 4.04
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 22
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 46 47 48 49 50
Tube Pass (--) 2 2 2 2 3
Length from tube inlet (inch) 28.3833 21.3640 14.3446 5.4175 5.4175
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 111.15 111.33 111.49 111.66 111.87
Skin temperature (F) 116.93 116.83 115.98 115.89 116.07
MTD (F) 78.8 75.5 63.4 60.1 59.9
Pressure (psia) 38.246 38.222 38.199 38.159 37.843
Pressure drop (psi) 0.023 0.024 0.024 0.040 0.316
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.024 0.024 0.040 0.316
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.24 4.24 4.24 4.24 4.24
Average velocity (ft/sec) 4.24 4.24 4.24 4.24 4.24
Shear stress at tube wall (psi) 7.546e-4 7.561e-4 7.566e-4 7.570e-4 7.565e-4
Area (ft2) 3.828 3.828 3.828 5.910 5.910
Cumulative area (ft2) 193.691 197.520 201.348 207.258 213.167
Duty (MM Btu/hr) 0.0195 0.0185 0.0151 0.0220 0.0219
Cumulative duty (MM Btu/hr) 2.2423 2.2608 2.2759 2.2979 2.3197
Heat flux (Btu/hr ft2) 5081.38 4834.28 3946.16 3714.79 3700.67
Calculated heat flux (Btu/hr ft2) 5782.89 5501.73 4491.18 4227.82 4210.91
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 73.41 72.90 70.88 70.37 70.28
Tubeside h (Btu/ft2-hr-F) 1109.49 1110.07 1109.40 1110.29 1111.10
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1109.49 1110.07 1109.40 1110.29 1111.10
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 48318 48406 48485 48572 48674
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 48318 48406 48485 48572 48674
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 4.03 4.02 4.01 4.01 4.00
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 23
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 51 52 53 54 55
Tube Pass (--) 3 3 3 3 3
Length from tube inlet (inch) 14.3446 21.3640 28.3833 35.4026 42.4219
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 112.05 112.21 112.39 112.62 112.93
Skin temperature (F) 116.64 117.62 118.21 121.29 123.71
MTD (F) 64.7 74.7 79.5 91.2 92.4
Pressure (psia) 37.820 37.796 37.773 37.750 37.726
Pressure drop (psi) 0.024 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.024 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.24 4.24 4.24 4.24 4.24
Average velocity (ft/sec) 4.24 4.24 4.24 4.24 4.24
Shear stress at tube wall (psi) 7.556e-4 7.548e-4 7.528e-4 7.499e-4 7.484e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 216.996 220.824 224.653 228.481 232.310
Duty (MM Btu/hr) 0.0155 0.0183 0.0197 0.0292 0.0368
Cumulative duty (MM Btu/hr) 2.3352 2.3535 2.3732 2.4024 2.4392
Heat flux (Btu/hr ft2) 4046.20 4778.28 5145.95 7635.78 9605.33
Calculated heat flux (Btu/hr ft2) 4604.06 5436.96 5855.10 8674.85 10931.1
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 71.13 72.83 73.66 94.73 118.32
Tubeside h (Btu/ft2-hr-F) 1112.33 1114.26 1115.71 1121.12 1125.26
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1112.33 1114.26 1115.71 1121.12 1125.26
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 48762 48842 48932 49047 49204
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 48762 48842 48932 49047 49204
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 3.99 3.98 3.97 3.96 3.95
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 24
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 56 57 58 59 60
Tube Pass (--) 3 3 3 3 3
Length from tube inlet (inch) 49.4413 56.4606 63.4799 70.4992 77.5185
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 113.28 113.62 113.97 114.33 114.68
Skin temperature (F) 123.97 124.34 124.80 125.17 125.57
MTD (F) 92.8 92.8 93.2 93.1 93.6
Pressure (psia) 37.703 37.680 37.656 37.633 37.610
Pressure drop (psi) 0.023 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.25 4.25 4.25 4.25 4.25
Average velocity (ft/sec) 4.25 4.25 4.25 4.25 4.25
Shear stress at tube wall (psi) 7.480e-4 7.475e-4 7.470e-4 7.466e-4 7.461e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 236.138 239.966 243.795 247.623 251.452
Duty (MM Btu/hr) 0.0365 0.0367 0.0371 0.0372 0.0375
Cumulative duty (MM Btu/hr) 2.4757 2.5124 2.5495 2.5868 2.6242
Heat flux (Btu/hr ft2) 9540.55 9577.52 9697.62 9724.75 9787.02
Calculated heat flux (Btu/hr ft2) 10856.5 10898.5 11035.3 11066.0 11136.5
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 117.02 117.53 118.49 118.86 119.03
Tubeside h (Btu/ft2-hr-F) 1126.54 1128.18 1130.26 1131.89 1133.94
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1126.54 1128.18 1130.26 1131.89 1133.94
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 49378 49553 49730 49908 50089
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 49378 49553 49730 49908 50089
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 3.93 3.92 3.90 3.89 3.87
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 25
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 61 62 63 64 65
Tube Pass (--) 3 3 3 3 3
Length from tube inlet (inch) 84.5378 91.5572 98.5765 105.596 112.615
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 115.03 115.39 115.75 116.13 116.52
Skin temperature (F) 125.89 126.31 126.85 127.92 128.61
MTD (F) 93.5 94.0 94.0 94.5 94.5
Pressure (psia) 37.587 37.564 37.540 37.517 37.494
Pressure drop (psi) 0.023 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.25 4.25 4.25 4.25 4.25
Average velocity (ft/sec) 4.25 4.25 4.25 4.25 4.25
Shear stress at tube wall (psi) 7.457e-4 7.451e-4 7.443e-4 7.433e-4 7.422e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 255.280 259.109 262.937 266.766 270.594
Duty (MM Btu/hr) 0.0374 0.0377 0.0384 0.0409 0.0420
Cumulative duty (MM Btu/hr) 2.6616 2.6993 2.7377 2.7786 2.8207
Heat flux (Btu/hr ft2) 9766.91 9846.96 10027.3 10685.5 10978.9
Calculated heat flux (Btu/hr ft2) 11113.5 11203.3 11408.3 12157.0 12490.8
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 118.82 119.13 121.33 128.55 132.10
Tubeside h (Btu/ft2-hr-F) 1135.53 1137.54 1139.54 1142.73 1145.13
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1135.53 1137.54 1139.54 1142.73 1145.13
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 50270 50453 50638 50832 51036
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 50270 50453 50638 50832 51036
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 3.86 3.84 3.82 3.81 3.79
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 26
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 66 67 68 69 70
Tube Pass (--) 3 3 3 3 3
Length from tube inlet (inch) 119.634 126.654 133.673 140.692 147.712
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 116.93 117.37 117.83 118.31 118.80
Skin temperature (F) 129.88 130.68 132.27 132.87 133.81
MTD (F) 95.1 95.1 95.8 95.8 96.6
Pressure (psia) 37.471 37.448 37.425 37.402 37.379
Pressure drop (psi) 0.023 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.25 4.25 4.25 4.25 4.25
Average velocity (ft/sec) 4.25 4.25 4.25 4.25 4.25
Shear stress at tube wall (psi) 7.411e-4 7.398e-4 7.387e-4 7.378e-4 7.370e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 274.422 278.251 282.079 285.908 289.736
Duty (MM Btu/hr) 0.0451 0.0465 0.0506 0.0511 0.0529
Cumulative duty (MM Btu/hr) 2.8658 2.9123 2.9630 3.0141 3.0670
Heat flux (Btu/hr ft2) 11793.2 12157.0 13226.5 13358.8 13808.4
Calculated heat flux (Btu/hr ft2) 13417.2 13831.2 15049.1 15200.3 15711.8
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 140.99 145.35 157.01 158.61 162.64
Tubeside h (Btu/ft2-hr-F) 1148.41 1151.12 1155.02 1157.27 1160.77
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1148.41 1151.12 1155.02 1157.27 1160.77
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 51251 51479 51721 51975 52237
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 51251 51479 51721 51975 52237
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 3.77 3.75 3.74 3.71 3.69
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 27
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 71 72 73 74 75
Tube Pass (--) 3 3 3 4 4
Length from tube inlet (inch) 154.731 161.750 177.630 177.630 161.750
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 119.30 119.82 120.88 122.19 122.95
Skin temperature (F) 134.43 135.49 134.27 129.34 137.74
MTD (F) 96.6 97.4 97.3 106.9 93.9
Pressure (psia) 37.356 37.333 37.248 36.887 36.864
Pressure drop (psi) 0.023 0.023 0.085 0.362 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.023 0.085 0.362 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.25 4.25 4.25 4.25 4.25
Average velocity (ft/sec) 4.25 4.25 4.25 4.25 4.25
Shear stress at tube wall (psi) 7.361e-4 7.360e-4 7.438e-4 7.460e-4 7.369e-4
Area (ft2) 3.828 3.828 13.494 13.494 3.828
Cumulative area (ft2) 293.565 297.393 310.887 324.380 328.209
Duty (MM Btu/hr) 0.0534 0.0555 0.1686 0.1072 0.0531
Cumulative duty (MM Btu/hr) 3.1204 3.1759 3.3445 3.4517 3.5048
Heat flux (Btu/hr ft2) 13949.4 14491.1 12493.3 7946.71 13865.4
Calculated heat flux (Btu/hr ft2) 15872.4 16489.3 14207.0 8869.14 15775.7
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 164.31 169.27 145.71 78.14 168.02
Tubeside h (Btu/ft2-hr-F) 1163.13 1166.91 1174.63 1173.11 1181.91
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1163.13 1166.91 1174.63 1173.11 1181.91
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 52506 52782 53355 54071 54491
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 52506 52782 53355 54071 54491
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 3.67 3.65 3.61 3.56 3.52
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 28
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 76 77 78 79 80
Tube Pass (--) 4 4 4 4 4
Length from tube inlet (inch) 154.731 147.712 140.692 133.673 126.654
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 123.44 123.92 124.39 124.84 125.27
Skin temperature (F) 137.91 137.73 137.91 137.55 137.49
MTD (F) 92.9 91.1 90.2 88.4 87.6
Pressure (psia) 36.841 36.818 36.795 36.773 36.750
Pressure drop (psi) 0.023 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.25 4.26 4.26 4.26 4.26
Average velocity (ft/sec) 4.25 4.26 4.26 4.26 4.26
Shear stress at tube wall (psi) 7.326e-4 7.326e-4 7.325e-4 7.325e-4 7.326e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 332.037 335.865 339.694 343.522 347.351
Duty (MM Btu/hr) 0.0520 0.0497 0.0488 0.0459 0.0442
Cumulative duty (MM Btu/hr) 3.5568 3.6064 3.6552 3.7011 3.7453
Heat flux (Btu/hr ft2) 13578.7 12975.0 12733.7 11989.1 11545.6
Calculated heat flux (Btu/hr ft2) 15449.4 14762.2 14487.7 13639.0 13134.5
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 166.30 162.04 160.67 154.13 149.87
Tubeside h (Btu/ft2-hr-F) 1183.87 1185.55 1187.48 1188.80 1190.35
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1183.87 1185.55 1187.48 1188.80 1190.35
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 54768 55038 55300 55553 55795
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 54768 55038 55300 55553 55795
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 3.50 3.49 3.47 3.45 3.43
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 29
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 81 82 83 84 85
Tube Pass (--) 4 4 4 4 4
Length from tube inlet (inch) 119.634 112.615 105.596 98.5765 91.5572
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 125.66 126.04 126.39 126.73 127.05
Skin temperature (F) 136.77 136.74 136.29 136.33 136.14
MTD (F) 86.1 85.3 84.0 83.3 82.1
Pressure (psia) 36.727 36.704 36.681 36.658 36.636
Pressure drop (psi) 0.023 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.26 4.26 4.26 4.26 4.26
Average velocity (ft/sec) 4.26 4.26 4.26 4.26 4.26
Shear stress at tube wall (psi) 7.330e-4 7.333e-4 7.334e-4 7.336e-4 7.336e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 351.179 355.008 358.836 362.664 366.493
Duty (MM Btu/hr) 0.0402 0.0388 0.0359 0.0348 0.0330
Cumulative duty (MM Btu/hr) 3.7854 3.8242 3.8601 3.8949 3.9279
Heat flux (Btu/hr ft2) 10488.6 10124.0 9370.61 9102.51 8612.67
Calculated heat flux (Btu/hr ft2) 11931.7 11517.0 10660.0 10355.2 9799.23
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 138.54 134.90 126.87 124.23 119.34
Tubeside h (Btu/ft2-hr-F) 1190.85 1192.26 1192.98 1194.29 1195.27
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1190.85 1192.26 1192.98 1194.29 1195.27
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 56023 56237 56440 56633 56818
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 56023 56237 56440 56633 56818
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 3.42 3.40 3.39 3.38 3.36
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 30
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 86 87 88 89 90
Tube Pass (--) 4 4 4 4 4
Length from tube inlet (inch) 84.5378 77.5185 70.4992 63.4799 56.4606
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 127.36 127.67 127.98 128.28 128.58
Skin temperature (F) 136.39 136.61 136.84 136.94 137.15
MTD (F) 81.5 80.3 79.7 78.6 78.0
Pressure (psia) 36.613 36.590 36.567 36.544 36.521
Pressure drop (psi) 0.023 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.26 4.26 4.26 4.26 4.26
Average velocity (ft/sec) 4.26 4.26 4.26 4.26 4.26
Shear stress at tube wall (psi) 7.336e-4 7.333e-4 7.330e-4 7.328e-4 7.326e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 370.321 374.150 377.978 381.807 385.635
Duty (MM Btu/hr) 0.0328 0.0325 0.0323 0.0316 0.0313
Cumulative duty (MM Btu/hr) 3.9607 3.9932 4.0254 4.0570 4.0883
Heat flux (Btu/hr ft2) 8564.85 8489.69 8424.75 8249.10 8170.54
Calculated heat flux (Btu/hr ft2) 9744.80 9659.34 9585.85 9385.88 9296.46
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 119.57 120.23 120.23 119.39 119.11
Tubeside h (Btu/ft2-hr-F) 1196.51 1198.05 1199.54 1201.01 1202.32
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1196.51 1198.05 1199.54 1201.01 1202.32
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 56999 57179 57358 57535 57710
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 56999 57179 57358 57535 57710
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 3.35 3.34 3.33 3.32 3.31
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 31
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 91 92 93 94 95
Tube Pass (--) 4 4 4 4 4
Length from tube inlet (inch) 49.4413 42.4219 35.4026 28.3833 21.3640
Mass fraction vapor (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Bulk temperature (F) 128.87 129.16 129.39 129.55 129.69
Skin temperature (F) 137.24 137.48 134.33 134.11 133.30
MTD (F) 77.0 76.4 71.0 66.2 53.8
Pressure (psia) 36.499 36.476 36.453 36.430 36.407
Pressure drop (psi) 0.023 0.023 0.023 0.023 0.023
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.023 0.023 0.023 0.023
Static head loss (psi) 0.000 0.000 0.000 0.000 0.000
Momentum loss (psi) 0.000 0.000 0.000 0.000 0.000
Maximum velocity (ft/sec) 4.26 4.26 4.26 4.26 4.26
Average velocity (ft/sec) 4.26 4.26 4.26 4.26 4.26
Shear stress at tube wall (psi) 7.324e-4 7.322e-4 7.336e-4 7.352e-4 7.357e-4
Area (ft2) 3.828 3.828 3.828 3.828 3.828
Cumulative area (ft2) 389.463 393.292 397.120 400.949 404.777
Duty (MM Btu/hr) 0.0306 0.0304 0.0181 0.0166 0.0132
Cumulative duty (MM Btu/hr) 4.1189 4.1493 4.1674 4.1840 4.1972
Heat flux (Btu/hr ft2) 7985.75 7948.18 4718.54 4348.55 3435.79
Calculated heat flux (Btu/hr ft2) 9086.04 9043.85 5366.64 4947.04 3908.93
Critical heat flux (Btu/hr ft2) 0.00 0.00 0.00 0.00 0.00
Overall U (Btu/ft2-hr-F) 118.02 118.33 75.45 74.69 72.64
Tubeside h (Btu/ft2-hr-F) 1203.73 1204.99 1201.70 1202.03 1201.41
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1203.73 1204.99 1201.70 1202.03 1201.41
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00 0.00 0.00 0.00
Local Reynolds (--) 57882 58053 58189 58287 58371
Vapor Reynolds (--) 0 0 0 0 0
Liquid Reynolds (--) 57882 58053 58189 58287 58371
Vapor Prandtl (--) 0.00 0.00 0.00 0.00 0.00
Liquid Prandtl (--) 3.30 3.29 3.28 3.27 3.27
Flow regime param. (--) 0.0000 0.0000 0.0000 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq Sens Liq Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Tubeside Incremental Monitor Page 32
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Point number (--) 96 97 98
Tube Pass (--) 4 4 4
Length from tube inlet (inch) 14.3446 5.4175 0.0000
Mass fraction vapor (--) 0.0000 0.0000 0.0000
Bulk temperature (F) 129.81 129.93 130.00
Skin temperature (F) 133.13 132.39
MTD (F) 50.0 38.0
Pressure (psia) 36.384 36.346 36.092
Pressure drop (psi) 0.023 0.039 0.253
Enhanced pressure drop mult (--)
Friction loss (psi) 0.023 0.039
Static head loss (psi) 0.000 0.000
Momentum loss (psi) 0.000 0.000
Maximum velocity (ft/sec) 4.26 4.26
Average velocity (ft/sec) 4.26 4.26
Shear stress at tube wall (psi) 7.362e-4 7.366e-4
Area (ft2) 3.828 5.910
Cumulative area (ft2) 408.606 414.515
Duty (MM Btu/hr) 0.0121 0.0138
Cumulative duty (MM Btu/hr) 4.2093 4.2231
Heat flux (Btu/hr ft2) 3163.50 2338.81
Calculated heat flux (Btu/hr ft2) 3599.21 2660.77
Critical heat flux (Btu/hr ft2) 0.00 0.00
Overall U (Btu/ft2-hr-F) 72.02 70.00
Tubeside h (Btu/ft2-hr-F) 1201.74 1201.27
Enhanced heat transfer mult (--)
Sensible liquid h (Btu/ft2-hr-F) 1201.74 1201.27
Sensible vapor h (Btu/ft2-hr-F) 0.00 0.00
Condensate film h (Btu/ft2-hr-F) 0.00 0.00
Vapor phase h (Btu/ft2-hr-F) 0.00 0.00
Nucleate boiling h (Btu/ft2-hr-F) 0.00 0.00
Conv. boiling h (Btu/ft2-hr-F) 0.00 0.00
Film boiling h (Btu/ft2-hr-F) 0.00 0.00
Boiling thin film h (Btu/ft2-hr-F) 0.00 0.00
Natural convective h (Btu/ft2-hr-F) 0.00 0.00
Local Reynolds (--) 58442 58515 58491
Vapor Reynolds (--) 0 0 0
Liquid Reynolds (--) 58442 58515 58530
Vapor Prandtl (--) 0.00 0.00 0.00
Liquid Prandtl (--) 3.26 3.26 3.25
Flow regime param. (--) 0.0000 0.0000
Condensate regime (--)
Boiling regime (--) Sens Liq Sens Liq
Boiling mechanism (--) Sens Liq Sens Liq
C:\Users\user\Documents\condensor3.htri
Vibration Analysis Page 33
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Shellside condition Cond. Vapor (Level 2.3)
Axial stress loading (1000-psi) 0.000 Added mass factor 1.517
Beta 3.745
Position In The Bundle Inlet Center Outlet
Length for natural frequency (ft) 2.062 0.585 0.903
Length/TEMA maximum span (--) 0.334 0.095 0.146
Number of spans (--) 24 24 24
Tube natural frequency (Hz) 273.0 + 1698.6 1033.3
Shell acoustic frequency (Hz) 245.0 +
Flow Velocities Inlet Center Outlet
Window parallel velocity (ft/sec) 89.79 25.55 0.28
Bundle crossflow velocity (ft/sec) 11.01 11.34 7.922e-2
Bundle/shell velocity (ft/sec) 15.94 16.43 0.11
Fluidelastic Instability Check Inlet Center Outlet
Log decrement HTRI 0.026 0.052 0.038
Critical velocity (ft/sec) 376.91 3508.98 162.84
Baffle tip cross velocity ratio (--) 0.0528 0.0058 8.796e-4
Average crossflow velocity ratio (--) 0.0448 0.0050 7.468e-4
Acoustic Vibration Check Inlet Center Outlet
Vortex shedding ratio (--) 0.497
Chen number (--) 5442
Turbulent buffeting ratio (--) 0.453
Tube Vibration Check Inlet Center Outlet
Vortex shedding ratio (--) 0.281 0.290 0.002
Parallel flow amplitude (inch) 0.0001 0.0000 0.0000
Crossflow amplitude (inch) 0.0000 0.0000 0.0000
Tube gap (inch) 0.2500 0.2500 0.2500
Crossflow RHO-V-SQ (lb/ft-sec2) 42.55 158.78 0.70
Bundle Entrance/Exit
(analysis at first tube row) Entrance Exit
Fluidelastic instability ratio (--) 0.079 0.002
Vortex shedding ratio (--) 0.762 0.009
Crossflow amplitude (inch) 0.00035 0.00000
Crossflow velocity (ft/sec) 29.83 0.36
Tubesheet to inlet/outlet support (inch) None None
Shell Entrance/Exit Parameters Entrance Exit
Impingement plate No
Flow area (ft2) 0.417 0.085
Velocity (ft/sec) 58.14 0.90
RHO-V-SQ (lb/ft-sec2) 503.72 37.98
Shell type AES Baffle type NTIW-Seg.
Tube type Plain Baffle layout Parallel
Pitch ratio 1.2500 Tube diameter, (inch) 1.0000
Layout angle 45 Tube material Carbon steel
Supports/baffle space
Program Messages
+ Frequency ratios are based upon lowest natural or acoustic frequency
* Items with asterisk exceed a conservative lower limit for vibration-free design. Review your case
using the procedure described in Online Help; You may find that a vibration problem is unlikely.
C:\Users\user\Documents\condensor3.htri
HEAT EXCHANGER RATING DATA SHEET Page 34
US Units
C:\Users\user\Documents\condensor3.htri
HEAT EXCHANGER SPECIFICATION SHEET Page 35
US Units
Job No.
Customer Reference No.
Address Proposal No.
Plant Location Date 6/18/2017 Rev
Service of Unit Item No.
Size 17.2500 x 192.000 inch Type AES Horz. Connected In 5 Parallel 1 Series
Surf/Unit (Gross/Eff) 2094.39 / 2072.58 ft2 Shell/Unit 5 Surf/Shell (Gross/Eff) 418.88 / 414.52 ft2
PERFORMANCE OF ONE UNIT
Fluid Allocation Shell Side Tube Side
Fluid Name mix Water
Fluid Quantity, Total lb/hr 65000.0 523426
Vapor (In/Out) 65000.0
Liquid 65000.0 523426 523426
Steam
Water
Noncondensables
Temperature (In/Out) F 240.00 165.00 90.00 130.00
Specific Gravity 0.7578 0.9944 0.9859
Viscosity cP 0.0102 0.6551 0.7609 0.5008
Molecular Weight, Vapor
Molecular Weight, Noncondensables
Specific Heat Btu/lb-F 0.4386 0.7021 1.0083 1.0096
Thermal Conductivity Btu/hr-ft-F 0.0153 0.0809 0.3579 0.3760
Latent Heat Btu/lb 260.859 300.119
Inlet Pressure psia 18.000 40.000
Velocity ft/sec 17.24 4.24
Pressure Drop, Allow/Calc psi 2.000 1.744 10.000 3.908
Fouling Resistance (min) ft2-hr-F/Btu 0.00200 0.00100
Heat Exchanged Btu/hr 21115482 MTD (Corrected) 95.2 F
Transfer Rate, Service 107.05 Btu/ft2-hr-F Clean 189.43 Btu/ft2-hr-F Actual 119.22 Btu/ft2-hr-F
CONSTRUCTION OF ONE SHELL Sketch (Bundle/Nozzle Orientation)
Shell Side Tube Side
Design/Test Pressure psig 150.000 / 150.000 /
Design Temperature F 240.00 240.00
17.25
inch
C:\Users\user\Documents\condensor3.htri
Properties Profile Monitor Page 36
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Physical Properties Profile: Hot Shellside (mix)
Reference pressure, (psia) (P1= 18.000)
(P) 1 2 3 4 5 6 7 8 9 10
Temperature, (F) 1 220.00 219.26 218.54 217.81 217.08 216.35 215.61 214.99 214.38 213.76
Heat duty/flow rate, (Btu/lb) 1 0.0000 0.3180 14.6780 29.0380 43.3980 57.7570 72.1170 84.0836 96.0501 108.016
Weight fraction vapor 1 1.0000 1.0000 0.9462 0.8927 0.8396 0.7869 0.7347 0.6914 0.6485 0.6058
Vapor Properties
Density, (lb/ft3) 1 0.1540 0.1542 0.1537 0.1531 0.1526 0.1520 0.1515 0.1510 0.1506 0.1501
Viscosity, (cP) 1 0.0099 0.0099 0.0099 0.0099 0.0099 0.0099 0.0100 0.0100 0.0100 0.0100
Thermal conductivity, (Btu/hr-ft-F) 1 0.0148 0.0148 0.0148 0.0147 0.0147 0.0146 0.0146 0.0146 0.0145 0.0145
Enthalpy, (Btu/lb) 1 0.0000 -0.3187 -0.6280 -0.9391 -1.2523 -1.5667 -1.8816 -2.1444 -2.4070 -2.6696
Specific heat, (Btu/lb-F) 1 0.4302 0.4299 0.4293 0.4287 0.4281 0.4275 0.4269 0.4264 0.4259 0.4254
Liquid Properties
Density, (lb/ft3) 1 45.8505 45.8505 45.8560 45.8616 45.8671 45.8726 45.8781 45.8825 45.8869 45.8912
Viscosity, (cP) 1 0.4337 0.4337 0.4348 0.4358 0.4368 0.4378 0.4387 0.4394 0.4401 0.4408
Thermal conductivity, (Btu/hr-ft-F) 1 0.0756 0.0756 0.0756 0.0757 0.0758 0.0758 0.0759 0.0760 0.0761 0.0761
Enthalpy, (Btu/lb) 1 0.0000 -0.5286 -1.0424 -1.5603 -2.0831 -2.6092 -3.1373 -3.5792 -4.0214 -4.4648
Specific heat, (Btu/lb-F) 1 0.7133 0.7133 0.7140 0.7147 0.7154 0.7162 0.7170 0.7176 0.7183 0.7190
Surface tension, (dyne/cm) 1 15.1499 15.1499 15.1652 15.1806 15.1964 15.2123 15.2284 15.2419 15.2555 15.2691
Critical temperature, (F) 1 517.56 517.56 516.74 515.91 515.07 514.23 513.38 512.66 511.95 511.23
Critical pressure, (psia) 1 706.607 706.607 708.825 711.105 713.446 715.845 718.298 720.383 722.501 724.650
Latent heat, (Btu/lb) 1 260.859 260.859 260.859 262.457 264.121 265.851 267.712 269.444 271.089 272.758
C:\Users\user\Documents\condensor3.htri
Properties Profile Monitor Page 37
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Physical Properties Profile: Hot Shellside (mix)
Reference pressure, (psia) (P1= 18.000)
(P) 11 12 13 14 15 16 17 18 19 20
Temperature, (F) 1 213.15 212.53 211.92 211.20 210.47 209.76 209.05 208.36 207.51 206.68
Heat duty/flow rate, (Btu/lb) 1 119.983 131.950 143.916 158.276 172.635 186.995 201.355 215.715 233.664 251.614
Weight fraction vapor 1 0.5634 0.5214 0.4796 0.4298 0.3805 0.3316 0.2831 0.2350 0.1754 0.1164
Vapor Properties
Density, (lb/ft3) 1 0.1496 0.1492 0.1487 0.1482 0.1476 0.1471 0.1466 0.1461 0.1454 0.1448
Viscosity, (cP) 1 0.0100 0.0100 0.0100 0.0100 0.0100 0.0100 0.0100 0.0100 0.0101 0.0101
Thermal conductivity, (Btu/hr-ft-F) 1 0.0145 0.0144 0.0144 0.0144 0.0143 0.0143 0.0142 0.0142 0.0141 0.0141
Enthalpy, (Btu/lb) 1 -2.9310 -3.1913 -3.4504 -3.7587 -4.0640 -4.3659 -4.6631 -4.9553 -5.3129 -5.6612
Specific heat, (Btu/lb-F) 1 0.4248 0.4243 0.4238 0.4232 0.4225 0.4219 0.4213 0.4207 0.4199 0.4192
Liquid Properties
Density, (lb/ft3) 1 45.8954 45.8995 45.9035 45.9081 45.9125 45.9166 45.9206 45.9243 45.9286 45.9325
Viscosity, (cP) 1 0.4414 0.4420 0.4425 0.4431 0.4437 0.4442 0.4446 0.4450 0.4455 0.4458
Thermal conductivity, (Btu/hr-ft-F) 1 0.0762 0.0763 0.0764 0.0765 0.0766 0.0767 0.0768 0.0769 0.0770 0.0772
Enthalpy, (Btu/lb) 1 -4.9072 -5.3486 -5.7889 -6.3143 -6.8359 -7.3531 -7.8638 -8.3671 -8.9852 -9.5890
Specific heat, (Btu/lb-F) 1 0.7197 0.7204 0.7211 0.7220 0.7229 0.7238 0.7248 0.7257 0.7269 0.7281
Surface tension, (dyne/cm) 1 15.2828 15.2964 15.3099 15.3261 15.3421 15.3579 15.3734 15.3886 15.4071 15.4251
Critical temperature, (F) 1 510.52 509.80 509.08 508.22 507.36 506.51 505.66 504.82 503.79 502.78
Critical pressure, (psia) 1 726.829 729.034 731.262 733.963 736.687 739.430 742.184 744.945 748.394 751.831
Latent heat, (Btu/lb) 1 274.497 276.266 278.066 280.086 282.327 284.576 286.876 289.172 291.739 294.580
C:\Users\user\Documents\condensor3.htri
Properties Profile Monitor Page 38
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Physical Properties Profile: Hot Shellside (mix)
Reference pressure, (psia) (P1= 18.000)
(P) 21 22 23 24 25 26 27 28
Temperature, (F) 1 205.87 205.09 200.08 195.06 190.04 185.03 180.02 175.00
Heat duty/flow rate, (Btu/lb) 1 269.564 287.513 291.168 294.803 298.420 302.019 305.600 309.164
Weight fraction vapor 1 0.0579 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Vapor Properties
Density, (lb/ft3) 1 0.1442 0.1436 0.1436 0.1436 0.1436 0.1436 0.1436 0.1436
Viscosity, (cP) 1 0.0101 0.0101 0.0101 0.0101 0.0101 0.0101 0.0101 0.0101
Thermal conductivity, (Btu/hr-ft-F) 1 0.0140 0.0140 0.0140 0.0140 0.0140 0.0140 0.0140 0.0140
Enthalpy, (Btu/lb) 1 -5.9991 -6.3257 -8.4207 -10.516 -12.611 -14.706 -16.801 -18.896
Specific heat, (Btu/lb-F) 1 0.4185 0.4178 0.4178 0.4178 0.4178 0.4178 0.4178 0.4178
Liquid Properties
Density, (lb/ft3) 1 45.9360 45.9391 46.1162 46.2904 46.4620 46.6309 46.7973 46.9611
Viscosity, (cP) 1 0.4461 0.4463 0.4674 0.4897 0.5134 0.5386 0.5654 0.5939
Thermal conductivity, (Btu/hr-ft-F) 1 0.0773 0.0774 0.0779 0.0783 0.0788 0.0792 0.0796 0.0801
Enthalpy, (Btu/lb) 1 -10.177 -10.747 -14.401 -18.037 -21.654 -25.253 -28.834 -32.398
Specific heat, (Btu/lb-F) 1 0.7293 0.7305 0.7268 0.7231 0.7194 0.7159 0.7124 0.7089
Surface tension, (dyne/cm) 1 15.4424 15.4591 15.7814 16.1049 16.4296 16.7555 17.0826 17.4109
Critical temperature, (F) 1 501.78 500.81 500.81 500.81 500.81 500.81 500.81 500.81
Critical pressure, (psia) 1 755.244 758.622 758.622 758.622 758.622 758.622 758.622 758.622
Latent heat, (Btu/lb) 1 297.376 300.119 300.119 300.119 300.119 300.119 300.119 300.119
C:\Users\user\Documents\condensor3.htri
Properties Profile Monitor Page 39
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Physical Properties Profile: Cold Tubeside (Water)
Reference pressure, (psia) (P1= 40.000)
(P) 1 2 3 4 5
Temperature, (F) 1 110.00 105.00 100.00 95.00 90.00
Heat duty/flow rate, (Btu/lb) 1 -790.43 -795.47 -800.51 -805.56 -810.60
Weight fraction vapor 1 0.0000 0.0000 0.0000 0.0000 0.0000
Liquid Properties
Density, (lb/ft3) 1 61.7913 61.8597 61.9256 61.9889 62.0496
Viscosity, (cP) 1 0.6140 0.6461 0.6810 0.7192 0.7609
Thermal conductivity, (Btu/hr-ft-F) 1 0.3672 0.3650 0.3627 0.3604 0.3579
Enthalpy, (Btu/lb) 1 0.0000 -5.0422 -10.085 -15.127 -20.169
Specific heat, (Btu/lb-F) 1 1.0087 1.0085 1.0084 1.0083 1.0083
Surface tension, (dyne/cm) 1 69.0497 69.5040 69.9543 70.4003 70.8421
Critical temperature, (F) 1 705.14 705.14 705.14 705.14 705.14
Critical pressure, (psia) 1 3198.81 3198.81 3198.81 3198.81 3198.81
Latent heat, (Btu/lb) 1 0.0000 0.0000 0.0000 0.0000 0.0000
C:\Users\user\Documents\condensor3.htri
Stream Properties Page 40
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Hot Shellside Fluid Inlet Outlet
Fluid name mix
Temperature (F) 240.00 165.00
Pressure (psia) 18.000 16.256
Weight fraction vapor (--) 1.0000 0.0000
Vapor Properties
Density (lb/ft3) 0.1490 0.1436
Viscosity (cP) 0.0102 0.0101
Conductivity (Btu/hr-ft-F) 0.0153 0.0140
Heat capacity (Btu/lb-F) 0.4386 0.4178
Molecular weight (--) 0 0
Liquid Properties
Density (lb/ft3) 45.8505 47.2877
Viscosity (cP) 0.4337 0.6551
Conductivity (Btu/hr-ft-F) 0.0756 0.0809
Heat capacity (Btu/lb-F) 0.7133 0.7021
Molecular weight (--) 0 0
Latent heat (Btu/lb) 260.859 300.119
Surface tension (dyne/cm) 15.1499 18.0655
Molar Composition Vapor Liquid K-Value Vapor Liquid K-Value
C:\Users\user\Documents\condensor3.htri
Stream Properties Page 41
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Cold Tubeside Fluid Inlet Outlet
Fluid name Water
Temperature (F) 90.00 130.00
Pressure (psia) 40.000 36.092
Weight fraction vapor (--) 0.0000 0.0000
Vapor Properties
Density (lb/ft3) -- --
Viscosity (cP) -- --
Conductivity (Btu/hr-ft-F) -- --
Heat capacity (Btu/lb-F) -- --
Molecular weight (--) -- --
Liquid Properties
Density (lb/ft3) 62.0496 61.5177
Viscosity (cP) 0.7609 0.5008
Conductivity (Btu/hr-ft-F) 0.3579 0.3760
Heat capacity (Btu/lb-F) 1.0083 1.0096
Molecular weight (--) 0 0
Latent heat (Btu/lb) -- --
Surface tension (dyne/cm) 70.8421 67.2321
Molar Composition Vapor Liquid K-Value Vapor Liquid K-Value
C:\Users\user\Documents\condensor3.htri
Input Reprint Page 42
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Shell Data
Service type Generic Shell and Tube
TEMA type AES
Run mode Design
Hot fluid location Shellside
Number of shells in series 1
Number of shells in parallel 1
Shell inside diameter 25.0000 inch
Flow in 1st tubepass Countercurrent
Train flow direction Countercurrent
Reboiler Data
Reboiler type No piping specified
Inlet pressure location Inlet nozzle
Tube Data
Tube type Plain
Tube outside diameter 1.0000 inch
Tube wall thickness 0.0490 inch
Tube pitch 1.2500 inch
Tube pitch ratio 1.2500
Tubepasses per shell 4
Tube pattern 45 degrees
Number of tubes per shell 100
Tube count method Rigorous
Tube length 16.000 ft
Tube material Carbon steel
Baffle Data
Baffle type NTIW Single segmental
Baffle orientation Parallel
Baffle cut percent 20 % shell ID
Central baffle spacing 25.0000 inch
Variable baffle spacing No
Window cut from baffles No
Support plates/baffle space Calculated
Clearance Data
Number of seal strip pairs Calculated
Baffle clearance type TEMA
Block A stream No
Block E stream No
Block F stream No
Number of passlane seal rods Calculated
C:\Users\user\Documents\condensor3.htri
Input Reprint Page 43
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Nozzle Data
Number of shellside inlet nozzles 1
Number of shellside outlet nozzles 1
Number of tubeside inlet nozzles 1
Number of tubeside outlet nozzles 1
Radial position on shell inlet nozzle Program decides
Longitudinal position on shell of inlet nozzle At rear head
Radial position on shell outlet nozzle Program decides
Tubeside entry type Radial
Tubeside inlet position Front head
Tubeside exit type Same as inlet
Front head location Left
Impingement Data
Impingement device present If required by TEMA
Impingement type Circular plate
C:\Users\user\Documents\condensor3.htri
Input Reprint Page 44
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Hot Fluid Physical Property Data
Pressure Set, 18.000 psia
Vapor Vapor Vapor Vapor Liquid
Mass Vapor Dynamic Thermal Heat Liquid Dynamic
Temp. Enthalpy Fraction Density Viscosity Cond. Capacity Density Viscosity
F Btu/lb lb/ft3 cP Btu/hr-ft-F Btu/lb-F lb/ft3 cP
220.00 180.764 1 0.1540 0.0099 0.0148 0.4302 -- --
219.26 180.446 1 0.1542 0.0099 0.0148 0.4299 45.8505 0.4337
218.54 166.086 0.94616 0.1537 0.0099 0.0148 0.4293 45.8560 0.4348
217.81 151.726 0.89269 0.1531 0.0099 0.0147 0.4287 45.8616 0.4358
217.08 137.366 0.83962 0.1526 0.0099 0.0147 0.4281 45.8671 0.4368
216.35 123.007 0.78694 0.1520 0.0099 0.0146 0.4275 45.8726 0.4378
215.61 108.647 0.73466 0.1515 0.0100 0.0146 0.4269 45.8781 0.4387
214.99 96.6804 0.69142 0.1510 0.0100 0.0146 0.4264 45.8825 0.4394
214.38 84.7139 0.64846 0.1506 0.0100 0.0145 0.4259 45.8869 0.4401
213.76 72.7475 0.6058 0.1501 0.0100 0.0145 0.4254 45.8912 0.4408
213.15 60.7810 0.56343 0.1496 0.0100 0.0145 0.4249 45.8954 0.4414
212.53 48.8145 0.52136 0.1492 0.0100 0.0144 0.4243 45.8995 0.4420
211.92 36.8481 0.47958 0.1487 0.0100 0.0144 0.4238 45.9035 0.4425
211.19 22.4883 0.42984 0.1482 0.0100 0.0144 0.4232 45.9081 0.4431
210.47 8.1286 0.38051 0.1476 0.0100 0.0143 0.4225 45.9125 0.4437
209.76 -6.2312 0.33160 0.1471 0.0100 0.0143 0.4219 45.9166 0.4442
209.05 -20.591 0.28309 0.1466 0.0100 0.0142 0.4213 45.9206 0.4446
208.36 -34.951 0.23499 0.1461 0.0100 0.0142 0.4207 45.9243 0.4450
207.51 -52.900 0.17540 0.1454 0.0101 0.0141 0.4199 45.9286 0.4455
206.68 -70.850 0.11639 0.1448 0.0101 0.0141 0.4192 45.9325 0.4458
205.87 -88.800 0.05793 0.1442 0.0101 0.0140 0.4185 45.9360 0.4461
205.09 -106.75 0 0.1436 0.0101 0.0140 0.4178 45.9391 0.4463
200.07 -110.40 0 -- -- -- -- 46.1162 0.4673
195.06 -114.04 0 -- -- -- -- 46.2904 0.4897
190.04 -117.66 0 -- -- -- -- 46.4620 0.5134
185.03 -121.25 0 -- -- -- -- 46.6309 0.5386
180.01 -124.84 0 -- -- -- -- 46.7973 0.5654
175.00 -128.40 0 -- -- -- -- 46.9611 0.5939
C:\Users\user\Documents\condensor3.htri
Input Reprint Page 45
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Hot Fluid Physical Property Data
Pressure Set, 18.000 psia
Liquid Liquid Liquid Liquid Liquid
Thermal Heat Surface Critical Critical Vapor Vapor Vapor
Temp. Cond. Capacity Tension Pressure Temp. Mole Frac. Mole Frac. Mole Frac.
F Btu/hr-ft-F Btu/lb-F dyne/cm psia F Comp. 1 Comp. 2 Comp. 3
213.76 0.0761 0.7190 15.2691 724.650 511.23 0.3883 0.1158 0.2242
213.15 0.0762 0.7197 15.2828 726.829 510.51 0.3965 0.1174 0.2224
212.53 0.0763 0.7204 15.2964 729.034 509.80 0.4048 0.1191 0.2204
211.92 0.0764 0.7211 15.3099 731.262 509.08 0.4132 0.1207 0.2182
211.19 0.0765 0.7220 15.3261 733.963 508.22 0.4233 0.1226 0.2153
210.47 0.0766 0.7229 15.3421 736.687 507.36 0.4335 0.1244 0.2122
209.76 0.0767 0.7238 15.3579 739.430 506.51 0.4437 0.1261 0.2088
209.05 0.0768 0.7248 15.3734 742.184 505.66 0.4539 0.1277 0.2052
208.36 0.0769 0.7257 15.3886 744.945 504.82 0.4641 0.1292 0.2015
207.51 0.0770 0.7269 15.4071 748.394 503.79 0.4768 0.1310 0.1966
206.68 0.0772 0.7281 15.4251 751.831 502.78 0.4892 0.1326 0.1915
205.87 0.0773 0.7293 15.4424 755.244 501.78 0.5015 0.1340 0.1864
205.09 0.0774 0.7305 15.4591 758.622 500.81 0.5135 0.1353 0.1812
200.07 0.0779 0.7268 15.7814 758.622 500.81 -- -- --
195.06 0.0783 0.7231 16.1049 758.622 500.81 -- -- --
190.04 0.0788 0.7194 16.4296 758.622 500.81 -- -- --
185.03 0.0792 0.7159 16.7555 758.622 500.81 -- -- --
180.01 0.0796 0.7124 17.0826 758.622 500.81 -- -- --
175.00 0.0801 0.7089 17.4109 758.622 500.81 -- -- --
C:\Users\user\Documents\condensor3.htri
Input Reprint Page 46
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Hot Fluid Physical Property Data
Pressure Set, 18.000 psia
C:\Users\user\Documents\condensor3.htri
Input Reprint Page 47
Released to the following HTRI Member Company:
fryda
user
Xist E Ver. 6.00 6/18/2017 20:20 SN: Vals100+ US Units
Design - Horizontal Multipass Flow TEMA AES Shell With NTIW-Segmental Baffles
Design Options Data
End baffle spacing equal to central Program decides
Minimize number of baffles No
Crosspass design Program control
Tubepass design sequence Even 2,4,6
C:\Users\user\Documents\condensor3.htri