ALSTOM Gas Turbines Ltd

SB/RM/95-08 SERVICE BULLETIN 22nd AUGUST 1995


SB/RH/95-03
SB/RT/95-11
MANDATORY
SB/TB/95-05
SB/TA/95-02
SB/TD/95-01

Subject: U/V DETECTORS

A TURBINES AFFECTED
All European Gas Turbines (EGT) acoustically enclosed turbines.

B REASON FOR BULLETIN


To ensure continued safety monitoring of all EGT acoustically enclosed turbines.

C CATEGORY
U/V detectors can be changed out in the field.

D DESCRIPTION
It is a known fact that when a hot turbine is shut down, whether by emergency or normal
shutdown, if for any reason the vent fan is not operating, the temperature in the turbine
acoustic enclosure rises rapidly. This temperature can exceed the maximum working
temperature rating of the fire detection system U/V detectors.

E IMPLEMENTATION
After a turbine shutdown, if the U/V detectors have suffered a hot soak with the vent fans
being inoperative, unless the detectors have already been replaced by the higher
temperature rated units, it is strongly recommended that the detectors should be changed.
The replacement units are fitted with higher rated tubes and calibrated to a maximum
working temperature rating of 125 deg. C.

F PLANNING INFORMATION
Users can purchase the higher temperature rated detectors through Customer Support
Centre, European Gas Turbines Limited, Freeman Road, North Hykeham, Lincoln, Lincs.
LN6 9AP. Alternatively contact can be made through the EGT approved area
representative/Repair facility or Service centre.

ALSTOM Gas Turbines Ltd. 1998


CONFIDENTIAL
This bulletin is the exclusive property of ALSTOM Gas Turbines Limited (ALSTOM) and is disclosed in confidence to ALSTOMs customers solely for their use in connection with the operation
and maintenance of their ALSTOM turbines. Its contents shall not be used for other purposes or copied or disclosed without written authorisation of ALSTOM. The information set out in this
bulletin is offered by ALSTOM as part of its ongoing product support services for you as one of its customers. However, the final decision for operating your plant in a safe and responsible
manner rests entirely with you. This involves many factors outside our knowledge and control, and therefore ALSTOM is unable to accept (and hereby disclaims) any liability (whether based
on breach of contract, warranty or statutory duty, negligence or otherwise) for damage or loss of any kind which may be incurred as a result of applying this information.

Day and night service is available 365 days of the year.

ALSTOM Gas Turbines Ltd ALSTOM Gas Turbines Ltd


Service Dept MW3A Registered Office:
P.O. Box 1 Lincoln LN2 5DJ England P.O. Box 1
Tel: +44 (0) 1522 584000 Thorngate House Lincoln LN2 5DJ England
Fax: +44 (0) 1522 586792 Tel: +44 (0) 1522 584000
Telex: 56231 Fax: +44 (0) 1522 584900 Telex: 56231
http://www.agt-ind.energy.alstom.com Registered in England No. 476835

S-ar putea să vă placă și