Documente Academic
Documente Profesional
Documente Cultură
Current
An electrical current is the flow of electricity around an electrical circuit. The flow of electricity
follows similar principles to the flow of water in pipes, as we shall see, with the exception that an
electrical system must make a complete circuit. The circuit will contain a power source of some
kind; in mains wiring the power source is the national electrical distribution system which is
mostly outside our control. Of course, the distribution company don't run wires directly from the
power station to our houses: there is all manner of other stuff between them and us, but that
isn't all that important. For most cases you can proceed as if a small power station was
connected directly to your house.
In domestic electrical work, current is generally measured in amps. Currents you will
encounter in practice range from about 0.5 amps (through a lightbulb) to about 40 amps (an
electric shower). Technically 'amps' is short for 'Ampres', but the full name is now rarely used.
The mathematical symbol for current, as it is written in calculations, is not 'C' (for current) or 'A'
(for amps) but in fact 'I'. This is just because the symbols 'C' and 'A' are reserved for other things.
You will occasionally come across currents measured in milliamps ('mA' for short). A milliamp is a
thousandth of an amp. For example, most earth-leakage breakers used in domestic wiring trip at
30 mA, which is about one thirtieth of an amp.
To get an electrical current to flow, we need a power source, and some sort of conductor. A
conductor is defined as anything that can carry a flow of electricity. In electrical practice,
conductors tend to be copper wire or copper bars, usually hidden away inside plastic sleeves.
The sleeves are insulators, that is, materials that prevent the flow of electricity. It is the insulator
that keeps the electrical current where it belongs - inside the cable.
In the UK (and everywhere else, as far as I know), electricity is distributed around the country
in the form of alternating current. This means that the flow of electrical current changes
direction, usually 50 or 60 times per second. There are two reasons for this, both historical. First,
electrical transformers (which we need to change voltage, see below) only work with alternating
currents. Second, we generate electricity by spinning wires around inside magnets (this is a bit of
a simplification, of course), and this naturally produces an alternating current. At the points
where the current is about to change direction, there will (for a short time) be no current flowing
at all. 'Alternating current' is usually abbreviated to 'AC'.
The fact that current is alternating has little practical impact on domestic wiring. If you grab a
live conductor you'll get a shock which is just as unpleasant even though, in principle, part of the
time no current will be flowing. One area where the alternating nature of the electrical supply is
apparent, however, is in the use of fluorescent lights. Incandescent (filament) bulbs generate
their light because the filament becomes white-hot. It cannot heat up and cool down as fast as
the alternation of the electrical current, so the light is fairly constant. Fluorescent lights, on the
other hand, produce a detectable flicker at the speed of the supply alternation. The light from a
fluorescent tube will 'pulse' about 100 times per second (50 times with the supply current in one
direction and 50 in the other). We can't normally see this flicker, but it does tend to make
rotating machines look as though they're standing still, or going backwards. This is why we are
warned not to use drilling equipment, for example, in strong fluorescent light.
Voltage
Voltage is a measure of the strength of an electrical supply. A voltage may exist even when no
current is flowing. In older textbooks you will find terms like 'electrical potential' or 'electro-
motive force', which gives a better feel for what voltage means. Strictly, a voltage is only defined
Figure 1: The variation of the voltage waveform over time. One complete cycle of this variation
lasts one fiftieth of a second (in the UK)
Why is the maximum voltage 325 volts and not 230 volts as we normally say? It turns out that
this waveform (which varies between high and low voltages) carries the same amount of energy
as a constant voltage about 70% the size. So when we talk about a 230V AC supply, we mean a
supply that would carry the same energy as a constant voltage of 230 V. This actually means an
AC voltage that reaches 325 volts at certain points, and is zero at others. Electrical engineers
refer to the '230 volt' figure as the 'root mean square' voltage, for reasons that you'll find in an
engineering textbook. This is abbreviated to 'rms', so you'll sometimes seen the domestic mains
voltage written as '230 Vrms'. Unless indicated otherwise, you can expect voltages and currents
described in electrical manuals and manufacturers' catalogues as 'rms' figures, and then ignore
this fact completely. The reason you can ignore it is that in domestic work so long as all
measurements of voltage, current, and power are rms measurements, all the calculations still
give correct answers.
230 volts is quite enough to give you a nasty shock, and sometimes these shocks can be fatal.
In some parts of the world lower voltages are used, for increased safety. For reasons that will be
explained later, it is more efficient (i.e., less wasteful of energy) to distribute electricity at a
higher voltage, but increased efficiency is gained at the expense of safety.
Electrical circuits
The main difference between an electrical system, and the water system shown in figure 2 is that
electrical current must flow in a circuit. Electricity can't form a puddle in the same way that
water can; it has to be confined to conductors. So in some senses a better analogy might be a
central heating system, where water flows around a set of pipes and radiators, driven by a pump.
In any event, if a circuit is not complete, no current can flow. This is good, because it means we
can uses switches to turn things on and off. Traditionally a switch is a mechanical contact:
pressing it or moving the lever moves a piece of copper in such a way as to open or close a
circuit. It is now possible to get electronic switching devices that have no moving parts.
A practical electrical circuit consists of at least the following things: a power source, some
conductors, and an electrical appliance (see figure 3).
There is a place for both these schemes, but in nearly all domestic wiring we will want to wire
things up in parallel. Why? The problem with the series arrangement is that all the appliances in
the system get the same current. This must be the case, because there is only one set of wires to
carry the current around. Now suppose one appliance is a lightbulb and the other is an electric
shower. The lightbulb wants about half an amp, while the electric shower wants about 40 amps.
There's no way to arrange them so they both get the current they want. What would happen in
practice? Well, the resistance of the lightbulb is huge compared to that of the electric shower so,
in practice, the current in the circuit will the same as that for a lightbulb: about half an amp. That
isn't going to warm your water very well.
In a parallel system, all appliances get the same voltage across them. In the UK this means the
230 volt mains supply. Each appliance will have a particular resistance, and therefore get a
Ring wiring
We've seen how you can connect electrical appliances in parallel, but what happens if you
connect cables in parallel? In other words, rather than running one pair of wires to each
appliance, why not run two? How would this help? Well, if there are two sets of conductors
running to each appliance, this is exactly the same as having one set of conductors but with
twice as much copper area. And a conductor with twice the area can carry twice the current (for
reasons I'll explain later). So if we double the number of cables connecting each appliance, we
double the amount of current they can carry. Another way of looking at this is to say that if we
double the number of cables, they only need to have half the area, and thin cable is cheaper
than thick cable.
This principle is exploited in the wiring of 'ring' circuits in domestic installations. Rings are
almost always used in wiring power outlets, and sometime in lighting as well. In a ring, every
socket outlet has not just one live, neutral, and earth connection back to the supply, but two;
this is because the ring goes all around the area served and then back to the supply.
This also explains why it is so dangerous to allow a ring to become broken. In this situation
there will only be one set of conductors serving each power outlet. Some outlets will be on one
side of the break, and some will be on the other. So all will get a supply, and it isn't obvious that
anything is wrong. However, a double-gang 13-amp socket can draw a current of 26 amps if two
heavy-duty appliances are plugged in, and this may well be too high for a single run of 2.5 mm 2
cable, but well within the capabilities of two such cables. There is a very real risk of the cable
overheating. In normal circumstances it is impossible to plug in enough appliances to damage
the cabling. Why? Because the fuse or MCB has been chosen to suit the current rating of the
cable (see below). In a ring system, we will choose the fuse or MCB to suit the capacity of the
ring, not a single cable. The fuse will normally be rated to trip at about 30A, which is well within
the capacity of the ring, but close to, or above, the capacity of the single cable. So the fuse won't
protect us from plugging in two 13-amp appliances: 26 amps isn't enough to trip the fuse, and
the cable will overheat instead.
Power
Power is the rate at which an electrical appliance can consume electrical energy, or the rate at
which a generator can produce it. In the UK we are charged for our electricity in terms of energy:
the more energy we use, the more we pay. A high-power appliance uses energy more rapidly
than a low-power one, and therefore costs more to run.
Power is measured in watts, or in kilowatts. A kilowatt is a thousand watts, and is a more
useful figure when dealing with electric fires and heaters. The abbreviations are 'W' (for watts)
and 'kW' (for kilowatts). Note the positions of the capital letters here. It is technically incorrect to
abbreviate kilowatts to 'KW' (although plenty of people do, including electricity supply
companies).
The mathematical symbol for power is 'P'.
If we know the voltage and current in an electrical appliance we can work out its power. It
turns out that power (in watts) is equal to the voltage (in volts) multiplied by the current (in
amps). In symbols this is:
P=VI
Power is given by the square of the current times the resistance, so in this case is 13 x 13 x 2,
which is 338 watts. That's about the same as three lightbulbs. So the electrical cable will get
about as hot as three lightbulbs. Apart from being a complete waste of energy (which you're
paying for), this may be enough heat to melt the cable, which would be a Bad Thing (especially if
it's underground). This explains why we need fat cables for high-power appliances and can get
away with thin cables for low-power ones. Fat cables have lower resistances, and therefore less
energy is wasted as heat, and they don't get hot enough to melt. Is it all right to use fat cables
for low-power appliances? Well, it doesn't compromise safety, but it's not very cost-effective.
Thick cables are much more expensive than thin ones. Another problem is that thick cables are
much harder to work with than thin ones.
Electrical Symbols
Symbol Component name Meaning
SPST Relay
Relay open / close connection by an electromagnet
SPDT Relay
Ground Symbols
Used for zero potential reference and electrical shock
Earth Ground
protection.
Resistor Symbols
Potentiometer (IEEE)
Adjustable resistor - has 3 terminals.
Potentiometer (IEC)
Variable Resistor /
Rheostat(IEEE)
Adjustable resistor - has 2 terminals.
Variable Resistor / Rheostat
(IEC)
Capacitor
Capacitor is used to store electric charge. It acts as short
circuit with AC and open circuit with DC.
Capacitor
Tunnel Diode
Light Emitting Diode (LED) LED emits light when current flows through
Transistor Symbols
NPN Bipolar Transistor Allows current flow when high potential at base (middle)
PNP Bipolar Transistor Allows current flow when low potential at base (middle)
Misc. Symbols
Fuse
The fuse disconnects when current above threshold.
Used to protect circuit from high currents.
Fuse
Bus
Bus
Analog-to-digital converter
Converts analog signal to digital numbers
(ADC)
Digital-to-Analog converter
Converts digital numbers to analog signal
(DAC)
Antenna Symbols
Antenna / aerial Transmits & receives radio waves
Multiplexer / Mux2 to 1
Connects the output to selected input line.
Multiplexer / Mux 4 to 1
Coded
Conventional
Conventional panels have been around ever since electronics became small enough to
make them viable. Conventional panels are used less frequently in large buildings than
in the past, but are not uncommon on smaller projects such as small schools, stores,
restaurants, and apartments.
A conventional Fire Alarm Control Panel employs one or more circuits, connected to
sensors (initiating devices) wired in parallel. These sensors are devised to dramatically
decrease the circuit resistance when the environmental influence on any sensor exceeds
a predetermined threshold. In a conventional fire alarm system, the information density
is limited to the number of such circuits used.
To facilitate location and control of fire within a building, the structure is subdivided into
definite areas or zones. Floors of a multistory building are one type of zone boundary.
An Initiating Device Circuit connected to multiple devices within the same "zone" of
protection, effectively provides 2 bits of information about the zone corollary to the state
of the circuit; normal, or off normal and alarm or quiescent. The state of each Initiating
Device Circuit within a zone displays at the Fire Alarm Control Panel using visible
indications called Annunciators.
These Annunciators may employ a graphical representation of the Zone boundaries on a
floor plan (Zone map) using textual descriptions, illuminated icons, illuminated sections,
or illuminated points on the map corresponding to Initiating Circuits connected to the Fire
Alarm Control Panel.
For this reason, slang often inaccurately refers to initiating circuits of a Fire Alarm
Control Panel as Zones.
Larger systems and increasing demand for finer diagnostic detail beyond broad area
location and control functions expanded the control by Zone strategy of conventional
systems by providing multiple initiating circuits within a common Zone, each exclusively
connected to a particular type of initiating device, or group of devices. This arrangement
A wiring diagram for a simple fire alarm system consisting of two input loops (one closed,
one open)
Multiplex systems
Releasing panels
Releasing panels are capable of using solenoids to disperse fire-fighting chemical
agents such as halon or water from piping located throughout a building. A releasing
panel usually will have a manual abort switch to abort an accidental release which could
damage property or equipment. Releasing capability can be part of both addressable or
conventional panels.
Addressable
A Simplex 4100U InfoALARM addressable fire alarm control panel: note the voice-
evacuation microphone built into it.
System functions
A police officer resets the fire alarm control panel for Potomac Hall at James Madison
University
There are many functions on a fire alarm panel. Some of these are:
Class change
This button, or input terminals connected to an external timeswitch, will sound the
notification appliances briefly in a different cadence. It is used to signify class change /
lesson breaks in schools, and allows the fire alarm system to be used instead of a
separate class bell system. This ensures pupils are familiar with the sound of the alarm
and means the notification appliance circuits are tested several times a day.
Flame Detectors
Like their name suggests, these detectors are used to detect flames. When working
properly, they detect fire nearly at the point of ignition. They are very useful for buildings
involving with hazardous processes, as well as gas and oil refineries and manufacturing
industries.
There are three subcategories of flame detectors: optical, UV, and IR.
The modern power system deals with huge power network and huge numbers of
associated electrical equipments. During short circuit fault or any other types of electrical
fault these equipment as well as the power network suffer a high stress of fault current in
them which may damage the equipment and networks permanently. For saving these
equipment and the power networks the fault current should be cleared from the system
So for timely disconnecting and reconnecting different parts of power system network for
protection and control, there must be some special type of switching devices which can
be operated safely under huge current carrying condition. During interruption of huge
current, there would be large arcing in between switching contacts, so care should be
taken to quench these arcs in circuit breaker in safe manner. The circuit breaker is the
special device which does all the required switching operations during current carrying
condition. This was the basic introduction to circuit breaker.
The circuit breaker mainly consists of fixed contacts and moving contacts. In normal
"ON" condition of circuit breaker, these two contacts are physically connected to each
other due to applied mechanical pressure on the moving contacts. There is an
arrangement stored potential energy in the operating mechanism of circuit breaker
which is released if switching signal is given to the breaker. The potential energy can be
stored in the circuit breaker by different ways like by deforming metal spring, by
compressed air, or by hydraulic pressure. But whatever the source of potential energy, it
must be released during operation. Release of potential energy makes sliding of the
moving contact at extremely fast manner. All circuit breaker have operating coils (tripping
coils and close coil), whenever these coils are energized by switching pulse, and the
plunger inside them displaced. This operating coil plunger is typically attached to the
operating mechanism of circuit breaker, as a result the mechanically stored potential
energy in the breaker mechanism is released in forms of kinetic energy, which makes
the moving contact to move as these moving contacts mechanically attached through a
gear lever arrangement with the operating mechanism. After a cycle of operation of
circuit breaker the total stored energy is released and hence the potential energy again
stored in the operating mechanism of circuit breaker by means of spring charging motor
or air compressor or by any other means. Till now we have discussed about mechanical
working principle of circuit breaker. But there are electrical characteristics of a circuit
breaker which also should be considered in this discussion of operation of circuit
breaker.
Let's have a discussion on electrical principle of circuit breaker. The circuit breaker
has to carry large rated or fault power. Due to this large power there is always
dangerously high arcing between moving contacts and fixed contact during operation of
circuit breaker. Again as we discussed earlier the arc in circuit breaker can be quenching
safely if the dielectric strength between the current carrying contacts of circuit breaker
increases rapidly during every current zero crossing of the alternating current. The
dielectric strength of the media in between contacts can be increased in numbers of
ways, like by compressing the ionized arcing media since compressing accelerates the
deionization process of the media, by cooling the arcing media since cooling increase
the resistance of arcing path or by replacing the ionized arcing media by fresh gasses.
Hence a numbers of arc quenching processes should be involved in operation of circuit
breaker.
According different criteria there are different types of circuit breaker. According to
their arc quenching media the circuit breaker can be divided as- According to their arc
quenching media the circuit breaker can be divided as-
1. Oil circuit breaker
2. Air circuit breaker.
3. SF6 circuit breaker.
4. Vacuum circuit breaker.
According to the operating mechanism of circuit breaker they can be divided as-
1. Spring operated circuit breaker.
2. Pneumatic circuit breaker.
3. Hydrolic circuit breaker.
According to the voltage level of installation types of circuit breaker are referred as-
1. High voltage circuit breaker.
2. Medium voltage circuit breaker.
3. Low voltage circuit breaker.
In other words, to connect the metallic parts of electric machinery and devices to the
earth plate or earth electrode (which is buried in the moisture earth) through a thick
conductor wire (which has very low resistance) for safety purpose is known as Earthing
or grounding.
To earth or earthing rather, means to connect the part of electrical apparatus such as
metallic covering of metals, earth terminal of socket cables, stay wires that do not carry
current to the earth. Earthing can be said as the connection of the neutral point of a
power supply system to the earth so as to avoid or minimize danger during discharge of
electrical energy.
Earthing and Grounding is the same terms used for earthing. Grounding is the
commonly word used for earthing in the North American standards like IEEE, NEC,
ANSI and UL etc while, Earthing is used in European, Common wealth countries and
Britain standards like IS and IEC etc.
The word Bonding used for jointing two wires (as well as conductors, pipes or
appliances together. Bonding is known as connecting the metallic parts of different
machines which is not considered to be carrying electric current during normal operation
of the machines to bring them at the same level of electric potential.
The primary purpose of earthing is to avoid or minimize the danger of electrocution, fire
due to earth leakage of current through undesired path and to ensure that the potential
of a current carrying conductor does not rise with respect to the earth than its designed
insulation.
When the metallic part of electrical appliances (parts that can conduct or allow passage
of electric current) comes in contact with a live wire, maybe due to failure of installations
To avoid such instances, the power supply systems and parts of appliances have to be
earthed so as to transfer the charge directly to the earth.
POINTS TO BE EARTHED
Earthing is not done anyhow. According to IE rules and IEE (Institute of Electrical
Engineers) regulations,
Earth pin of 3-pin lighting plug sockets and 4-pin power plug should be efficiently
and permanently earthed.
All metal casing or metallic coverings containing or protecting any electric supply
line or apparatus such as GI pipes and conduits enclosing VIR or PVC cables,
That part of the earthing system which interconnects the overall metallic parts of
electrical installation e.g. conduit, ducts, boxes, metallic shells of the switches,
distribution boards, Switches, fuses, Regulating and controlling devices, metallic parts of
electrical machines such as, motors, generators, transformers and the metallic
framework where electrical devices and components are installed is known as earth wire
or earth continuity conductor as shown in the above fig.
The resistance of the earth continuity conductor is very low. According to IEEE rules,
resistance between consumer earth terminal and earth Continuity conductor (at the end)
should not be increased than 1. In simple words, resistance of earth wire should be
less than 1.
Size of the Earth Continuity Conductor or Earth Wire depends on the cable size used in
the wiring circuit.
The cross sectional area of the Earth Continuity Conductor should not be less than
the half of the cross sectional area of the thickest wire used in the electrical wiring
installation.
Generally, the size of the bare copper wire used as earth continuity conductor is 3SWG.
But keep in mind that, dont use less than 14SWG as earth wire. Copper strip is also can
be used as earth continuity conductor instead of bare copper wire but dont go for it until
manufacture recommend it.
The conductor wire connected between earth continuity conductor and earth electrode or
earth plate is called earthing joint or Earthing lead. The point where earth continuity
conductor and earth electrode meet is known as connecting point as shown in the
above fig.
Earthing lead is the final part of the earthing system which is connected to the earth
electrode (which is underground) through earth connecting point.
There should be minimum joints in earthing lead as well as lower in size and straight in
the direction.
Generally, copper wire can be used as earthing lead but, copper strip is also used for
high installation and it can handle the high fault current because of wider area than the
copper wire.
A hard drawn bare copper wire is also used as an earthing lead. In this method, all earth
conductors connected to a common (one or more) connecting points and then, earthing
lead is used to connect earth electrode (earth plat) to the connecting point.
The size or area of earthing lead should not be less than the half of the thickest wire
used in the installation.
Note: We will post additional article about Earth Plate size with simple calculations
Stay tune.
A metallic electrode or plate which is buried in the earth (underground) and it is the last
part of the electrical earthing system. In simple words, the final underground metallic
(plate) part of the earthing system which is connected with earthing lead is called earth
plate or earth electrode.
A metallic plate, pipe or rode can be used as an earth electrode which has very low
resistance and carry the fault current safely towards ground (earth).
22 (two foot wide as well as in length) and 1/8 inch thickness.. I.e. 2 x 2 x 1/8.
(600x600x300 mm)
2 x2 x = 600x600x6 mm
It is recommended to bury the earth electrode in the moisture earth. If it is not possible,
then put water in the GI (Galvanized Iron) pipe to make possible the moisture condition.
In the earthing system, put the earth electrode in vertical position (underground) as
shown in the above fig. Also, put a 1 foot (about 30cm) layer of powdered charcoal
and lime mixture around the earth plate (dont confuse with earth electrode and earth
plate as both are the same thing).
This action makes the possible increase in the size of the earth electrode which leads a
better continuity in the earth (earthing system) and also helps to maintain the moisture
condition around earth plate.
P.S: We will post Example calculation about Earth Electrode Sizing Stay tune.
Good to know:
Dont use coke (after burning coal in the furnace to emit all the gases and other
components, the remaining 88% carbon is called coke) or stone coal instead of charcoal
(wood coal) because it causes to corrosion in the earth plate.
Since, the water level is different in the different areas; therefore, the depth for earth
electrode installation is also different in various areas. But, the depth for earth electrode
installation should not be less than 10ft (3 meter) and should below 1 foot (304.8mm)
from the constant water level.
Motors, Generator, Transformers etc should be connected from to earth electrode two
different places.
In small installation, use metallic rod (diameter = 25mm (1inch) and length = 2m (6ft)
instead of earth plate for earthing system. The metallic pipe should be 2 meter below
from the surface of ground. To maintain the moister condition, put 25mm (1inch) coal
and lime mixture around the earth plate.
For effectiveness and convenience, you may use the copper rods 12.5mm (0.5 inch) to
25mm (1 inch) diameter and 4m (12ft) length. We will discuss the installation method of
rod earthing latter.
Earthing can be done in many ways. The various methods employed in earthing (in
house wiring or factory and other connected electrical equipment and machines) are
discussed as follows:
In plate earthing system, a plate made up of either copper with dimensions 60cm x 60cm
x 3.18mm (i.e. 2ft x 2ft x 1/8 in) or galvanized iron (GI) of dimensions 60cm x 60cm x
6.35 mm (2ft x 2ft x in) is buried vertical in the earth (earth pit) which should not be
less than 3m (10ft) from the ground level.
For proper earthing system, follow the above mentioned steps in the (Earth Plate
introduction) to maintain the moisture condition around the earth electrode or earth plate.
A galvanized steel and a perforated pipe of approved length and diameter is placed
vertically in a wet soil in this kind of system of earthing. It is the most common system of
earthing.
The size of pipe to use depends on the magnitude of current and the type of soil. The
dimension of the pipe is usually 40mm (1.5in) in diameter and 2.75m (9ft) in length for
ordinary soil or greater for dry and rocky soil. The moisture of the soil will determine the
length of the pipe to be buried but usually it should be 4.75m (15.5ft).
it is the same method as pipe earthing. A copper rod of 12.5mm (1/2 inch) diameter or
16mm (0.6in) diameter of galvanized steel or hollow section 25mm (1inch) of GI pipe of
length above 2.5m (8.2 ft) are buried upright in the earth manually or with the help of a
pneumatic hammer. The length of embedded electrodes in the soil reduces earth
resistance to a desired value.
In this method of earthing, the waterman (Galvanized GI) pipes are used for earthing
purpose. Make sure to check the resistance of GI pipes and use earthing clamps to
minimize the resistance for proper earthing connection.
If stranded conductor is used as earth wire, then clean the end of the strands of the wire
and make sure it is in the straight and parallel position which is possible then to connect
tightly to the waterman pipe.
In this method of earthing, strip electrodes of cross-section not less than 25mm x 1.6mm
(1in x 0.06in) is buried in a horizontal trenches of a minimum depth of 0.5m. If copper
with a cross-section of 25mm x 4mm (1in x 0.15in) is used and a dimension of 3.0mm 2 if
its a galvanized iron or steel.
If at all round conductors are used, their cross-section area should not be too small, say
less than 6.0mm2 if its a galvanized iron or steel. The length of the conductor buried in
the ground would give a sufficient earth resistance and this length should not be less
than 15m.
The usual method of earthing of electric equipments, devices and appliances are as
follow:
1. First of all, dig a 5x5ft (1.51.5m) pit about 20-30ft (6-9 meters) in the ground.
(Note that, depth and width depends on the nature and structure of the ground)
2. Bury an appropriate (usually 2 x 2 x 1/8 (600x600x300 mm) copper plate in that
pit in vertical position.
3. Tight earth lead through nut bolts from two different places on earth plate.
4. Use two earth leads with each earth plate (in case of two earth plates) and tight
them.
5. To protect the joints from corrosion, put grease around it.
6. Collect all the wires in a metallic pipe from the earth electrode(s). Make sure the
pipe is 1ft (30cm) above the surface of the ground.
7. To maintain the moisture condition around the earth plate, put a 1ft (30cm) layer
of powdered charcoal (powdered wood coal) and lime mixture around the earth
plate of around the earth plate.
8. Use thimble and nut bolts to connect tightly wires to the bed plates of machines.
Each machine should be earthed from two different places. The minimum
distance between two earth electrodes should be 10 ft (3m).
9. Earth continuity conductor which is connected to the body and metallic parts of
all installation should be tightly connected to earth lead.
10. At last (but not least), test the overall earthing system through earth tester. If
everything is going about the planning, then fill the pit with soil. The maximum
allowable resistance for earthing is 1. If it is more than 1 ohm, then increase the
size (not length) of earth lead and earth continuity conductors. Keep the external
ends of the pipes open and put the water time to time to maintain the moisture
condition around the earth electrode which is important for the better earthing
system.
However, if excessive current is not earthed, appliances will be damaged without the
help of fuse in place. You should note that excessive current are earthed at their
generating stations which is why earth wires carries very little or no current at all. It
therefore implies that it is not necessary to earth any of the wires (live, earth and neutral
wires) contained in a PVC. Earthing the live wire is catastrophic.
I have seen a person killed simply because a live wire got cut from overhead pole and
fell to the ground while the ground was wet. Excessive current is earthed at generating
stations and if at all the earthing is not efficient due to fault, earth fault interrupters will be
there to help. Fuse help only when the power transmitted is above the rating of our
appliances, it blocks the current from reaching our appliances by blowing off and
protecting our appliances in the process.
In our electrical appliances, if excessive currents are not earthed, we would experience
severe shock. Earthing takes place in electrical appliances only when there is a problem
and it is to save us from danger. If in an electronic installation, a metallic part of an
electrical appliance comes in direct contact with a live wire that results from maybe
failure of installation or otherwise, the metal will be charged and static charge will
accumulate on it.
If you happen to touch the metallic part at that moment you will be zapped. But if the
metallic part of the appliance is earthed, the charge will be transferred to earth instead of
accumulating on the metallic part of the appliance. Current dont flow through earth wires
in electrical appliances, it does so only when there is problem and only to direct the
unwanted current to earth in order to protect us from severe shock.
In addition, if a live wire touches accidentally (in a faulty system) to the metallic part of a
machine. Now, if a man touches that metallic part of the machine, then the current will
flow through their body to the ground, hence, he will get shocked (electrocuted) which
may lead to serious injuries even to death. Thats why earthing is so important.
Direct flash,
Step potential,
Touch potential,
Side flash,
Secondary effects, such as:
1- Side flash:
2- Step potential:
When lightning current is injected into the earth, a large voltage
gradient builds up around the earth electrode with respect to a more
distant point.
At the time of discharge being close to the earth electrode means the
voltage differential across this distance can be large enough to be lethal
depending upon circumstances such as condition of footwear, etc,
substantial current can flow through one lower leg to the other.
3- Touch potential:
The risk of electrocution due to touch potential is greater than for step
potential, as the passage of current flows close to the heart region.
1. LPS for Protection for buildings and installations against direct strike by
lightning,
2. LPS for Protection against overvoltage on incoming conductors and
conductor systems,
3. LPS for Protection against the electromagnetic pulse of the lightning.
First: LPS for Protection for buildings and installations against direct
strike by lightning
Notes onsingle
Improved different
mast Types
systemof(Blunt
Lightning
EndedProtection
Rods), Systems LPS
Early streamer Emission System.
Each systems design requires the following:
The lightning
Charge Transferprotection system must be solidly and permanently
System (CTS),
grounded. Poor or high resistance
Dissipation Array System (DAS). connections to ground are the
leading cause of lightning system failure for each one of these
systems.
Notes:
A pointed lightning rod or air terminal or a single mast will help prevent lightning
from striking in the immediate vicinity because it will help reduce the difference
in potential between earth and cloud by "bleeding off" charge and therefore
reducing the chance of a direct strike.
This lightning rod or air terminal or a single mast will provide a cone shaped zone
of protection with angle of 45 degree forming a circular base on the ground
around a building or part of a building.
Note:
TRANSFORMER
Electrical transformer is a static electrical machine which transforms electrical power from one
circuit to another circuit, without changing the frequency. Transformer can increase or decrease
the voltage with corresponding decrease or increase in current.
The basic principle behind working of a transformer is the phenomenon of mutual induction
between two windings linked by common magnetic flux. The figure at right shows the simplest
form of a transformer. Basically a transformer consists of two inductive coils; primary winding and
secondary winding. The coils are electrically separated but magnetically linked to each other.
When, primary winding is connected to a source of alternating voltage, alternating magnetic flux
is produced around the winding. The core provides magnetic path for the flux, to get linked with
the secondary winding. Most of the flux gets linked with the secondary winding which is called as
'useful flux' or main 'flux', and the flux which does not get linked with secondary winding is called
as 'leakage flux'. As the flux produced is alternating (the direction of it is continuously changing),
EMF gets induced in the secondary winding according to Faraday's law of electromagnetic
induction. This emf is called 'mutually induced emf', and the frequency of mutually induced emf is
same as that of supplied emf. If the secondary winding is closed circuit, then mutually induced
current flows through it, and hence the electrical energy is transferred from one circuit (primary) to
another circuit (secondary).
Basically a transformer consists of two inductive windings and a laminated steel core. The coils
are insulated from each other as well as from the steel core. A transformer may also consist of a
container for winding and core assembly (called as tank), suitable bushings to take our the
terminals, oil conservator to provide oil in the transformer tank for cooling purposes etc. The
figure at left illustrates the basic construction of a transformer. In all types of transformers, core is
constructed by assembling (stacking) laminated sheets of steel, with minimum air-gap between
them (to achieve continuous magnetic path). The steel used is having high silicon content and
sometimes heat treated, to provide high permeability and low hysteresis loss. Laminated sheets
of steel are used to reduce eddy current loss. The sheets are cut in the shape as E,I and L. To
avoid high reluctance at joints, laminations are stacked by alternating the sides of joint. That is, if
joints of first sheet assembly are at front face, the joints of following assemble are kept at back
face.
Types of transformers
Transformers can be classified on different basis, like types of construction, types of cooling etc.
In a practical transformer -
(a) Some leakage flux is present at both primary and secondary sides. This leakage gives rise to
leakage reactances at both sides, which are denoted as X 1 and X2 respectively.
(b) Both the primary and secondary winding possesses resistance, denoted as R 1 and R2
respectively. These resistances causes voltage drop as, I 1R1 and I2R2 and also copper loss I12R1
and I22R2.
(c) Permeability of the core can not be infinite, hence some magnetizing current is needed.
Mutual flux also causes core loss in iron parts of the transformer.
We need to consider all the above things to derive equivalent circuit of a transformer.
But, using this equivalent circuit does not simplifies the calculations. To make calculations
simpler, it is preferable to transfer current, voltage and impedance either to primary side or to the
secondary side. In that case, we would have to work with only one winding which is more
convenient.
The following figure shows the equivalent circuit of transformer with secondary parameters
referred to the primary.
No transformer is truly an 'ideal transformer' and hence each will incur some losses, most of
which get converted into heat. If this heat is not dissipated properly, the excess temperature in
transformer may cause serious problems like insulation failure. It is obvious that transformer
needs a cooling system. Transformers can be divided in two types as (i) dry type transformers
and (ii) oil immersed transformers. Different cooling methods of transformers are -
For dry type transformers
1. Air Natural (AN)
2. Air Blast
For oil immersed tranformers
1. Oil Natural Air Natural (ONAN)
2. Oil Natural Air Forced (ONAF)
3. Oil Forced Air Forced (OFAF)
4. Oil Forced Water Forced (OFWF)
Air Blast
For transformers rated more than 3 MVA, cooling by natural air method is inadequate. In this
method, air is forced on the core and windings with the help of fans or blowers. The air supply
must be filtered to prevent the accumulation of dust particles in ventilation ducts. This method can
be used for transformers upto 15 MVA.
This method is used for oil immersed transformers. In this method, the heat generated in the
core and winding is transferred to the oil. According to the principle of convection, the heated oil
flows in the upward direction and then in the radiator. The vacant place is filled up by cooled oil
from the radiator. The heat from the oil will dissipate in the atmosphere due to the natural air flow
around the transformer. In this way, the oil in transformer keeps circulating due to natural
convection and dissipating heat in atmosphere due to natural conduction. This method can be
used for transformers upto about 30 MVA.
The heat dissipation can be improved further by applying forced air on the dissipating surface.
Forced air provides faster heat dissipation than natural air flow. In this method, fans are mounted
near the radiator and may be provided with an automatic starting arrangement, which turns on
when temperature increases beyond certain value. This transformer cooling method is generally
used for large transformers upto about 60 MVA.