Sunteți pe pagina 1din 1

PROK DVS RESTRICTED EARTH FAULT RELAY

Calculation of stabilizing resistor for Restricted Earth Fault Relay

Knee Point Voltage of the CT: It will be provided by the manufacturer.


Alternatively it can be evaluated,

Voltage across CT( Vk) = If( RCT+2RL)

If- Secondary fault current


RCT- CT resistance.
RL- Resistance of leads between CT and Relay

Vk

Stabilizing resistance ---------- Ohms.


Current setting in the relay

For More details contact:

M/S.PROK DEVICES PVT LTD


# 2930, SIMHDARI, 14th Cross
off K.R.Road, Banashankri 2nd Stage
Bangalore -560 070
e mail: prokdvs@blr.vsnl.net.in
web: www.prokdvs.com
ph: +91 80 26761719 / 26760718
Fax: +91 80 26761720