DATA & FACTS


GEA Close Control
T-Range Aerial values always on the level
Description GEA Close Control
T-Range

The T-Range .......................................................................................3


Upflow and Downflow Versions
Direct Expansion and Chilled Water Units .............................................................3
Key to Type Codes .................................................................................................3
Energy Saving Options .....................................................................4
Dimensions and Weights ...................................................................5
Dimensions and Weights D/U 3 42 ...................................................................5
Dimensions and Weights D/U 48 - 83 ..................................................................6
Service Entry / Access ......................................................................5
Guide Specification ...........................................................................8
Typical Airflow Arrangements ........................................................ 11
General Details ................................................................................ 11
Cooling Performance ......................................................................15
Cooling Performance Models 3 19 ..................................................................15
Cooling Performance Models 21 42 ................................................................16
Cooling Performance Models 48 83 ................................................................17
Electrical Details .............................................................................. 18
"X" Version.............................................................................................................18
"A" Version.............................................................................................................19
"W" and "F" Versions.............................................................................................20
"C" Version ............................................................................................................21
Schematic Diagrams ....................................................................... 22
"X" Version.............................................................................................................22
"A" Version.............................................................................................................23
"W" Version............................................................................................................24
"F" Version.............................................................................................................25
"C" Version ............................................................................................................26
Ancillaries and Options ................................................................... 27

2 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control The Range
T-Range Key to Type Codes

Upflow and Downflow Versions


Direct Expansion and Chilled Water Units
The T Range comprises nineteen (19) models, in six (6) cabinet sizes, with nominal
capacities from 3 kW to 80 kW in the following versions: -
- X: Split System using Denco Condensing Units.
- A: Air Cooled DX System with inbuilt compressor(s) and using Denco DCRA
Condensers.
- W: Water Cooled DX System with inbuilt compressor(s) and Water Cooled
Condensers.
- F: Ambicool System.
- C: Chilled Water System.

Key to Type Codes


Example: U 28 A V G H

H= Humidifier fitted
G= Front Grille Return [Upflow only not on U48 - U83]
(as opposed to underfloor return)
V= Variable Refrigerant Flow (VRF)
A= X - Split System
A - Air Cooled System
W - Water Cooled System
F - Ambicool System
D - Combicool system
C - Chilled Water System
28 = Unit Size: 3, 4, 5,
8, 10, 12,
17, 19, 21, 23, 28,
32, 37, 42
48, 53
63, 73 and 83
(models available dependent on System)
U= Upflow (D = Downflow)

PR-2006-0295-GB y Subject to modifications y Status 10/2007 3


Energy Saving Options GEA Close Control
T-Range

T Range air conditioning units incorporate all of the energy/cost saving benefits for
which Denco products are renowned. These include:
Ambicool (Glycol freecooling system) - "F" Version
(not available on models 48 83)
This substantially reduces annual energy consumption, and
consequently costs, by exploiting low average ambient
temperatures to provide partial or full freecooling. It is very
unusual to experience the design summer ambient for any
length of time, and external temperatures are generally
considerably less for much of the year. This allows the
drycooler to produce glycol at lower temperatures.
When the glycol is colder than the room air, it is passed
through the economy coil before reaching the condenser,
picking up some heat directly from the room rather than via
the refrigeration system. Under conditions such as this, the
compressor run time is reduced, thereby saving energy. As
an example, some degree of freecooling is usually
available for 70% of the year in northern Europe, giving
very substantial running cost savings.

Variable Refrigerant Flow (VRF) - "V" Option


This provides various compressor options for efficient part-
load performance, with exceptional economy.

Full Cooling Load


Both compressors running to circulate the full design
refrigerant flow in order to achieve specified maximum
cooling capacity. The scroll compressor coefficient of
performance (COP) is typically 3.5.

Part Load Operation


Lead compressor only running to circulate approximately
60% of the refrigerant flow. Evaporator and condenser are
both oversized under this condition, causing increase in
suction pressure and a reduction in discharge pressure.
Resultant part-load COP increases to typically 5.0.
Secondary benefits include reduced temperature swing and
increased compressor reliability caused by reduced cycling
and an optional two-stage high-pressure trip. Lower inrush
current and inbuilt redundancy is also provided by dual
compressors and reduced humidifier run time due to the
very high sensible heat ratio achieved at the higher
evaporating temperatures. Payback period is typically less
than one year.

4 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Dimensions and Weights D/U 3 - 42
T-Range

Unit Weights - kgs


Model "X" "A" "W" "F" "C"
D/U3-5 135 165 175 N/A 140
D / U 8 - 12 210 255 270 305 215
D / U 17 - 28 345 445 460 505 355
D / U 32 - 42 420 520 535 590 430

PR-2006-0295-GB y Subject to modifications y Status 10/2007 5


Dimensions and Weights D/U 48 - 83 GEA Close Control
T-Range

Unit Weights - kgs


Model "X" "A" "W" "F" "C"
D / U 48 - 53 660 860 890 N/A 680
D / U 63 - 83 810 1010 1040 N/A 830

6 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Service Entry / Access
T-Range

The T Range of air conditioning units has been designed to be completely front
access for service/maintenance via the front hinged/removable doors. Therefore, no
allowance for access to the ends or back is necessary, although the end panels can
be removed in-situ if required.

PR-2006-0295-GB y Subject to modifications y Status 10/2007 7


Guide Specification GEA Close Control
T-Range

Cabinet
The cabinets shall be attractively designed having bevelled corners with flush fitting
curved panels. Units shall have a rigid frame, manufactured from non corroding
Aluzink, with hinged curved front panel(s) to provide access for installation and
servicing. Panels shall be lined with class "O" non eroding insulation material with
both thermal and acoustic properties. External panels shall be manufactured from
pre-coated steel, colour Grey (RAL number 7024).

Cooling Coil
The coils shall be multi row constructed from 3/8" O/D copper tubes with
mechanically bonded aluminium fins. Direct expansion coils shall have internal
grooving for optimum heat transfer. The coil face area shall be maximised to ensure
high sensible heat ratio and low airside pressure drop, thereby minimising fan power
and noise level. A stainless steel drain tray shall be included to ensure efficient
removal of the condensate, via a factory fitted trap.
- DX: Units shall have one, two or four refrigeration circuits (dependent upon
model), inclusive of liquid distributor, expansion valve, solenoid valve, sight glass
and filter drier, and these components shall be housed in the cabinet.
- C: Units shall be fitted with a modulating 3 way valve having manual override
facility with water pressure / temperature test points, and these components shall
be housed in the cabinet.

Fans
T Range models 3 to 5 shall be fitted with one fan, which shall be single inlet
backward curved centrifugal, and shall be direct driven by an integral motor. A
differential pressure switch shall be fitted to monitor airflow, failure of which shall
result in an alarm and automatic disabling of all functions. The fan motor shall be
single speed, the final airflow therefore depending on exact static pressure
requirements.
T Range models 8 to 42 shall be fitted with one, two or three fans, whilst models 48
to 83 shall be fitted with four or six fans, depending on unit size. The fans shall be
double inlet, double width with forward curved impeller, and shall be direct driven by
an integral motor. A differential pressure switch (8-42) and current monitoring relay
(48-83) shall be fitted to monitor airflow, failure of which shall result in an alarm and
automatic disabling of all functions. Fan motors shall be three speed. HIGH or
MEDIUM speed shall be factory selected, depending on airflow and static pressure
requirement, and LOW speed shall be assigned for dehumidification mode.

8 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Guide Specification
T-Range

Electric Heaters
Electric heaters shall have rigid Incoloy sheathed elements with stainless steel
finning balanced over three phases and rated to operate at black heat. Control shall
be in one or two stages, each stage being protected by a high temperature safety
cut-out.

Filtration
The filters shall have an efficiency of 30 % ASHRAE 52/76 Eurovent 4/5 arrestance
value 90 % (G4). They shall be fitted in the return air stream, held by quick release
retaining clips, and be accessible from the front of the unit. A differential pressure
switch shall be fitted which, through the alarm facility in the microprocessor
controller, shall indicate when the filters need changing.

Water Cooled Condensers


The condenser shall be a compact brazed plate heat exchanger having a multiplicity
of parallel stainless steel pressed plates. The construction shall give high turbulent
flows resulting in a compact heat exchanger form with low pressure drops.

Humidifier
The humidifier shall be of the electrode boiler type, located in the bottom of the unit.
Features shall include proportional steam output and microprocessor control with
alarms and diagnostic facilities. The control system shall allow the use of a wide
range of mains water conditions and optimise drain down frequency for maximum
operational economy.

Compressor and Safety Controls


Robust fully hermetic scroll compressor(s) shall be located either in the base of the
unit on "A", "W" and "F" systems or the outdoor condensing unit on "X" systems. The
compressor(s) shall be resiliently mounted on a robust frame, which assists to
minimise noise and vibration transmission to the structure. The compressor(s) shall
be fitted with back seating isolating valves together with crankcase heater ("X"
systems only) and oil level sight glass on larger models. Protection shall be provided
by an internal self-setting overload device and pressure relief valve.
An external adjustable high pressure cut off switch, with manual reset facility shall be
provided for high pressure protection, in addition to the internal devices. To protect
primarily against loss of refrigerant charge, an adjustable low pressure switch shall
also be provided, which includes an automatic reset facility.
A low pressure Alarm delay function is fitted to facilitate low ambient start condition
as standard.

Dehumidification
This shall be achieved by switching on a single stage of cooling and automatic
selection of low fan speed (models 8 to 42).

PR-2006-0295-GB y Subject to modifications y Status 10/2007 9


Guide Specification GEA Close Control
T-Range

Electrical Panel
The electrical switchgear shall be contained in a cubicle located in the top of the unit,
and shall include:
- Controller baseboard and modules (if applicable)
- MCB's and contactors for fans, heaters, humidifier and compressors as
appropriate
- MCB's for remote condensing units (if applicable)
- MCB's plus pressure operated on off switches for remote condensers (if
applicable)
Cabling shall be colour coded and numbered, and neatly run in trunking segregating
high and low voltages. All wiring shall comply with BS EN 60204 Part 1.

Microprocessor Controls
All units shall be fitted, as standard, with a C3-05 advanced microprocessor controls
system, designed by Denco. This shall provide maximum economy of operation, a
comprehensive intelligent alarm system and a wide range of information for
operators and service engineers. All information shall be presented in a user friendly
format with tamper proof setting up arrangements.
In addition to precise control of temperature and humidity, the system shall include
the following features:
- A liquid crystal semi - graphical display indicating unit function via icons,
displaying control conditions and historic logging of temperature and humidity
conditions.
- Coded security access for set point parameter adjustment
- Programmable stage delays, to minimise inrush currents
- A comprehensive alarm system. Alarms shall be memorised and displayed in the
order in which they occur in order to aid fault diagnosis
- Programmed set points and parameters shall be held in a non volatile memory,
therefore being safeguarded upon power failure
- Denco Net functions are a standard feature within the controller.
- Various third party communication and interface options are available which
connect direct to the C3-05 controller.

10 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Typical Airflow Arrangements
T-Range General Details

Section "A" Downflow, into raised floor. Return from room or ceiling.

Section "B" Upflow, with horizontal discharge plenum (as shown) or room/ceiling discharge, and front grille return (not
available on models 48 83).

Section "C" Upflow, with ceiling duct extension and underfloor return.

General Details

U / D - All Versions 3-5 8 - 12 17 - 28 32 - 42 48 - 53 63 - 83


Coil Face Area m2 0.200 0.414 0.864 1.382 1.728 2.764
No. of Fans - 1 1 2 3 4 6
Air Volume m3/s 0.415 1.00 2.17 3.3 4 6.1
m3/hr 1490 3600 7810 11880 14400 21960
Fan Heat Absorbed kW 0.27 1.17 2.86 4.37 5.37 8.24
Electric Reheat:
No. of Steps - 1 1 2 2 2 2
Capacity kW 3.0 6.0 12.0 12.0 12.0 12.0
Humidifier Capacity kg/hr 3.0 3.0 3.0 3.0 3.0 3.0
Power kW 2.3 2.3 2.3 2.3 2.3 2.3
Filters (Standard G4):
No. of Pieces - 1 2 2 3 4 6
Length mm 455 442 885 885 885 885
Width mm 455 505 505 540 505 540
Depth mm 50 50 50 50 50 50

PR-2006-0295-GB y Subject to modifications y Status 10/2007 11


General Details GEA Close Control
T-Range

3 4 5 8 10 12 17 19
"X" Versions
Suction Line ins 3/4 3/4 3/4 7/8 7/8 1-1/8 1-1/8 1-1/8
Liquid Line ins 3/8 3/8 3/8 1/2 1/2 1/2 5/8 5/8
Humidifier Feed mm 15 15 15 15 15 15 15 15
Drain mm 22 22 22 22 22 22 22 22
C.U. Type - CT18 CT18 CT22 CS40 CM48 CM61 CP72 CP81
No. fitted - 1 1 1 1 1 1 1 1
"A" Versions
Discharge Line ins N/A N/A 1/2 3/4 3/4 3/4 7/8 7/8
Liquid Line ins 3/8 1/2 1/2 1/2 5/8 5/8
Humidifier Feed mm 15 15 15 15 15 15
Drain mm 22 22 22 22 22 22
Compressor ZR N/A N/A 22 34 48 61 61 72
No. fitted - 1 1 1 1 1 1
A/C Condenser * DCRA 08-6 13-6 21-6 21-6 26-6 26-6
No. fitted - 1 1 1 1 1 1
"W" Versions
Cond Water In mm N/A N/A 22 28 28 28 35 35
Cond Water Out mm 22 28 28 28 35 35
Humidifier Feed mm 15 15 15 15 15 15
Drain mm 22 22 22 22 22 22
Compressor ZR N/A N/A 22 34 48 61 61 72
Compr. Type - Scroll Scroll Scroll Scroll Scroll Scroll
No. fitted - 1 1 1 1 1 1
W/C Condenser B8/20 B8/30 B8/30 B8/30 B10/30 B10/30
No. fitted - 1 1 1 1 1 1
F" Versions
Coolant In mm N/A N/A N/A 28 28 28 35 35
Coolant Out mm 28 28 28 35 35
Humidifier Feed mm 15 15 15 15 15
Drain mm 22 22 22 22 22
Compressor ZR N/A N/A N/A 34 48 61 61 72
No. fitted - 1 1 1 1 1
W/C Condenser B8/30 B8/30 B8/30 B10/30 B10/30
No. fitted - 1 1 1 1 1
"C" Versions
Chilled Water In mm N/A N/A 22 N/A N/A 28 N/A N/A
Chilled Water Out mm 22 28
Humidifier Feed mm 15 15
Drain mm 22 22
Valve Size ins N/A N/A 1/2" N/A N/A 3/4" N/A N/A
Valve kv m3/hr 2.5 6.3

Note:
Variable Refrigerant Flow option NOT available on models 3 - 19.
*
- Quiet / Residential Condensers are available as an alternative to the Standard versions stated.

12 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control General Details
T-Range

21 23 28 32 37 42
"X" Versions
Suction Line ins 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8 1-3/8
Liquid Line ins 5/8 5/8 5/8 3/4 3/4 3/4
Humidifier Feed mm 15 15 15 15 15 15
Drain mm 22 22 22 22 22 22
C.U. Type - CL90 CL11 CL12 CL12 CL16 CL19
No. fitted - 1 1 1 1 1 1
"A" Versions
Discharge Line ins 7/8 7/8 1-1/8 1-1/8 1-1/8 1-1/8
Liquid Line ins 5/8 5/8 5/8 3/4 3/4 3/4
Humidifier Feed mm 15 15 15 15 15 15
Drain mm 22 22 22 22 22 22
Compressor ZR 81 48 61 61 72 81
No. fitted - 1 2 ** 2 ** 2 ** 2 ** 2 **
A/C Condenser * DCRA 32-6 32-6 32-6 50-6 50-6 50-6
No. fitted - 1 1 1 1 1 1
"W" Versions
Cond Water In mm 35 35 35 42 42 42
Cond Water Out mm 35 35 35 42 42 42
Humidifier Feed mm 15 15 15 15 15 15
Drain mm 22 22 22 22 22 22
Compressor ZR 81 48 61 61 72 81
No. fitted 1 2 ** 2 ** 2 ** 2 ** 2 **
W/C Condenser - B10/30 B10/30 B10/30 B10/40 B10/40 B10/40
No. fitted - 1 1 1 1 1 1
"F" Versions
Coolant In mm 35 35 35 42 42 42
Coolant Out mm 35 35 35 42 42 42
Humidifier Feed mm 15 15 15 15 15 15
Drain mm 22 22 22 22 22 22
Compressor ZR 81 48 61 61 72 81
No. fitted 1 2 ** 2 ** 2 ** 2 ** 2 **
W/C Condenser - B10/30 B10/30 B10/30 B10/40 B10/40 B10/40
No. fitted - 1 1 1 1 1 1
"C" Versions
Chilled Water In mm N/A N/A 35 N/A N/A 42
Chilled Water Out mm 35 42
Humidifier Feed mm 15 15
Drain mm 22 22
Valve Size ins N/A N/A 1" N/A N/A 1"
Valve kv m3/hr 10 16

Note:
Variable Refrigerant Flow option NOT available on model 21.
* Quiet / Residential Condensers are available as an alternative to the Standard versions stated.
** - Variable Refrigerant Flow as Standard

PR-2006-0295-GB y Subject to modifications y Status 10/2007 13


General Details GEA Close Control
T-Range

48 53 63 73 83
"X" Versions
Suction Line ins 1-1/8 1-1/8 1-3/8 1-3/8 1-3/8
Liquid Line ins 5/8 5/8 3/4 3/4 3/4
Humidifier Feed mm 15 15 15 15 15
Drain mm 22 22 22 22 22
C.U. Type - CL11 CL12 CL12 CL16 CL19
No. fitted - 2 2 2 2 2
"A" Versions
Discharge Line ins 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8
Liquid Line ins 5/8 5/8 3/4 3/4 3/4
Humidifier Feed mm 15 15 15 15 15
Drain mm 22 22 22 22 22
Compressor ZR 48 61 61 72 81
No. fitted - 4 ** 4 ** 4 ** 4 ** 4 **
A/C Condenser * DCRA 32-6 32-6 32-6 50-6 50-6
No. fitted - 2 2 2 2 2
"W" Versions
Cond Water In mm 2 x 35 2 x 35 2 x 42 2 x 42 2 x 42
Cond Water Out mm 2 x 35 2 x 35 2 x 42 2 x 42 2 x 42
Humidifier Feed mm 15 15 15 15 15
Drain mm 22 22 22 22 22
Compressor ZR 48 61 61 72 81
No. fitted 4 ** 4 ** 4 ** 4 ** 4 **
W/C Condenser - B10/30 B10/30 B10/40 B10/40 B10/40
No. fitted - 2 2 2 2 2
"C" Versions
Chilled Water In mm N/A 54 N/A N/A 54
Chilled Water Out mm 54 54
Humidifier Feed mm 15 15
Drain mm 22 22
Valve Size ins N/A 1" N/A N/A 2"
Valve kv m3/hr 25 40

Note:
* Quiet / Residential Condensers are available as an alternative to the Standard versions stated.
** Variable Refrigerant Flow as Standard

14 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Cooling Performance Models 3 to 19
T-Range

All the cooling performances below are based on Standard EU4 filtration and with a minimum of 50 Pa external static
and Air On at 24 C, 45 %RH.

3 4 5 8 10 12 17 19
3
Airflow m /s 0.30 0.35 0.415 0.70 0.80 1.00 1.40 1.60
m3/hr 1080 1260 1490 2520 2880 3600 5040 5760
"X" Version 1
Total kW 4.6 4.8 5.6 9.5 11.6 13.4 17.6 19.4
Sensible kW 4.1 4.4 5.1 8.7 10.0 11.6 16.7 18.4
S.H.R. - 0.89 0.93 0.92 0.92 0.88 0.87 0.95 0.95
"A" Version 2
Total kW N/A N/A 5.6 8.7 12.1 14.1 16.1 18.3
Sensible kW 5.1 8.3 10.2 11.9 15.6 17.6
S.H.R. - 0.91 0.95 0.86 0.85 0.86 0.96
"W" Version 3
Total kW N/A N/A 5.7 8.7 11.7 13.9 15.7 18.0
Sensible kW 5.2 8.3 10.1 11.7 15.2 17.3
S.H.R. - 0.90 0.95 0.86 0.85 0.97 0.96
"F" Version 4
Total kW N/A N/A N/A 7.9 10.7 12.6 14.1 16.3
Sensible kW 7.6 9.7 11.1 14.0 16.0
S.H.R. - 0.97 0.90 0.88 0.99 0.98
"C" Version 5
Total kW N/A N/A 5.8 N/A N/A 13.9 N/A N/A
Sensible kW 5.4 12.5
S.H.R. - 0.92 0.90
CW Flow Rate l/s 0.279 0.664
Unit P.D kPa 49.7 57.8

Refrigerant R407C used as standard on DX units.

Notes:
1. "X" performances are NETT and based on:
(a) Standard matching Condensing Units (alternatives available, enquire for details).
(b) 1.0 C suction line loss.
(c) 32 C ambient temperature.

2. "A" performances are NETT and based on:


(a) Standard matching A/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) 32 C ambient temperature.

3. "W" performances are NETT and based on:


(a) Standard matching W/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) Condenser water in 30 C, temperature rise 8 C.

4. "F" performances are NETT and based on:


(a) Standard matching W/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) 25 % ethylene glycol solution coolant in 40 C, temperature rise 6 C.

5. "C" performances are GROSS and based on:


(a) Standard coil with chilled water in 7C, temperature rise 5 C

PR-2006-0295-GB y Subject to modifications y Status 10/2007 15


Cooling Performance Models 21 to 42 GEA Close Control
T-Range

All the cooling performances below are based on Standard EU4 filtration and with a minimum of 50 Pa external static
and Air On at 24 C, 45 %RH.

21 23 28 32 37 42
3
Airflow m /s 1.80 2.00 2.17 2.50 2.90 3.30
3
m /hr 6480 7200 7810 9000 10440 11880
"X" Version 1
Total kW 23.0 26.4 29.2 31.2 36.1 41.3
Sensible kW 21.0 23.2 25.0 29.5 33.4 37.0
S.H.R. - 0.92 0.89 0.87 0.95 0.93 0.91
"A" Version 2
Total kW 20.7 23.8 27.2 31.5 35.7 39.2
Sensible kW 19.7 22.1 24.1 29.7 33.2 36.2
S.H.R. - 0.95 0.93 0.89 0.94 0.93 0.92
"W" Version 3
Total kW 20.1 23.6 27.6 30.0 34.4 38.2
Sensible kW 19.3 22.0 24.3 28.6 32.5 35.7
S.H.R. - 0.96 0.93 0.88 0.95 0.95 0.94
"F" Version 4
Total kW 18.1 21.2 24.9 27.0 31.2 34.4
Sensible kW 17.7 20.4 23.0 26.3 30.1 32.9
S.H.R. - 0.98 0.96 0.92 0.97 0.96 0.96
"C" Version 5
Total kW N/A N/A 28.7 N/A N/A 45.4
Sensible kW 26.4 41.3
S.H.R. - 0.92 0.91
CW Flow Rate l/s 1.372 2.171
Unit P.D kPa 65.6 79.8

Refrigerant R407C used as standard on DX units.

Notes:
1. "X" performances are NETT and based on:
(a) Standard matching Condensing Units (alternatives available, enquire for details).
(b) 1.0 C suction line loss.
(c) 32 C ambient temperature.

2. "A" performances are NETT and based on:


(a) Standard matching A/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) 32 C ambient temperature.

3. "W" performances are NETT and based on:


(a) Standard matching W/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) Condenser water in 30 C, temperature rise 8 C.

4. "F" performances are NETT and based on:


(a) Standard matching W/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) 25 % ethylene glycol solution coolant in 40 C, temperature rise 6 C.

5. "C" performances are GROSS and based on:


(a) Standard coil with chilled water in 7 C, temperature rise 5 C.
.

16 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Cooling Performance Models 48 to 83
T-Range

All the cooling performances below are based on Standard EU4 filtration and with a minimum of 50 Pa external static
and Air On at 24 C, 45 %RH.

48 53 63 73 83
3
Airflow m /s 4.0 4.34 5.00 5.80 6.60
3
m /hr 14400 15620 18000 20880 23760
"X" Version 1
Total kW 52.8 58.5 62.5 72.3 78.7
Sensible kW 46.4 49.9 59.0 66.7 74.1
S.H.R. - 0.89 0.87 0.95 0.93 0.91
"A" Version 2
Total kW 47.7 54.6 63.3 71.5 78.7
Sensible kW 44.3 48.3 59.4 66.4 72.4
S.H.R. - 0.94 0.90 0.95 0.94 0.93
"W" Version 3
Total kW 47.1 55.3 60.2 68.9 76.7
Sensible kW 44.0 48.6 57.3 65.1 71.6
S.H.R. - 0.94 0.89 0.96 0.95 0.94
"C" Version 4
Total kW N/A 57.3 N/A N/A 90.7
Sensible kW 52.8 82.5
S.H.R. - 0.92 0.91
CW Flow Rate l/s 2.743 4.343
Unit P.D kPa 56.8 71.2

Refrigerant R407C used as standard on DX units.


Notes:
1. "X" performances are NETT and based on:
(a) Standard matching Condensing Units (alternatives available, enquire for details).
(b) 1.0 C suction line loss.
(c) 32 C ambient temperature.

2. "A" performances are NETT and based on:


(a) Standard matching A/C Condensers (alternatives available, enquire for details).
(b) 0.5C suction line loss.
(c) 32C ambient temperature.

3. "W" performances are NETT and based on:


(a) Standard matching W/C Condensers (alternatives available, enquire for details).
(b) 0.5 C suction line loss.
(c) Condenser water in 30 C, temperature rise 8 C.

4. "C" performances are GROSS and based on:


(a) Standard coil with chilled water in 7 C, temperature rise 5 C.

PR-2006-0295-GB y Subject to modifications y Status 10/2007 17


Electrical Details at 400 Volt / 3 Ph + N / 50 Hz GEA Close Control
"X" Version T-Range

Models 3 4 5 8 10 12 17 19 21 23

Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA 0.7 0.7 0.7 4.0 4.0 4.0 4.0 4.0 4.0 4.0
CLA 0.9 0.9 0.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0
Heaters FLA 13.0 13.0 13.0 8.7 8.7 8.7 17.4 17.4 17.4 17.4
Humidifier OA 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
CLA 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
Condensing Unit OA 6.7 6.7 3.8 6.4 7.4 9.2 10.1 11.9 14.9 17.0
CLA 8.2 8.2 4.2 7.3 8.4 10.5 12.0 14.1 16.8 19.4

Operating Amps FLA 16.3 16.3 16.3 19.1 20.1 21.9 31.5 33.3 36.3 38.4
Connected Load CLA 18.6 18.6 18.6 21.0 22.1 24.2 34.4 36.5 39.2 41.8
Maximum Inrush LRA 42.2 42.2 37.0 59.7 63.7 79.7 96.4 123 121 145
Operating kW kW 5.5 5.5 5.5 9.3 9.9 10.7 18.3 19.0 19.9 21.4
Connected Load kW kW 7.0 7.0 7.0 10.2 10.9 11.9 19.9 20.8 21.8 23.6

Models 28 32 37 42 48 53 63 73 83

Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA 4.0 4.0 4.0 4.0 8.0 8.0 8.0 8.0 8.0
CLA 5.0 5.0 5.0 5.0 10.0 10.0 10.0 10.0 10.0
Heaters FLA 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4
Humidifier OA 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
CLA 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
Condensing Unit OA 19.1 19.1 21.9 25.5 34.0 38.2 38.2 43.8 51.0
CLA 21.8 21.8 25.8 29.9 38.8 43.6 43.6 51.6 59.8

Operating Amps FLA 40.5 41.5 44.3 47.9 46.4 50.6 51.6 57.2 64.4
Connected Load CLA 44.2 45.2 49.2 53.3 55.0 59.8 60.8 68.8 77.0
Maximum Inrush LRA 149 149 189 220 159 165 166 210 245
Operating kW kW 22.5 23.1 25.2 27.8 22.6 23.7 24.9 28.5 33.7
Connected Load kW kW 25.0 25.8 28.4 31.5 26.2 29.0 30.5 35.7 41.9

Notes:

Controls are 24 volt.

Operating Amps (OA): worst case phase for components that can be selected to operate at any one time by the automatic
control system, each component operating at design conditions, i.e. Compressors (based on saturated suction 5 C, condensing
50 C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW).

Connected Load Amps (CLA): worst case phase for components that can be selected to operate at any one time by the
automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 C,
condensing 60 C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW).

18 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Electrical Details at 400 Volt / 3 Ph + N / 50 Hz
T-Range "A" Version

Models 5 8 10 12 17 19 21 23

Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA 0.7 4.0 4.0 4.0 4.0 4.0 4.0 4.0
CLA 0.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0
Heaters FLA 13.0 8.7 8.7 8.7 17.4 17.4 17.4 17.4
Humidifier OA 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
CLA 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
Compressors OA 3.0 4.5 6.2 8.0 8.0 8.7 10.5 12.4
CLA 3.5 5.4 7.2 9.3 9.3 10.6 12.7 14.4
Condenser Fans FLA 0.9 1.7 3.3 3.3 3.3 3.3 3.3 3.3

Operating Amps FLA 17.3 17.2 18.9 20.7 30.4 31.1 32.9 34.8
Connected Load CLA 19.6 19.3 20.9 23.0 32.7 34.0 36.1 37.8
Maximum Inrush LRA 38.0 53.7 63.7 79.7 89.4 97.4 125 80.6
Operating kW kW 5.5 9.2 10.6 11.4 18.2 18.9 19.6 20.8
Connected Load kW kW 7.0 10.1 11.7 12.7 19.6 20.5 21.4 22.9

Models 28 32 37 42 48 53 63 73 83

Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA 4.0 4.0 4.0 4.0 8.0 8.0 8.0 8.0 8.0
CLA 5.0 5.0 5.0 5.0 10.0 10.0 10.0 10.0 10.0
Heaters FLA 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4
Humidifier OA 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
CLA 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
Compressors OA 16.0 16.0 17.4 21.0 24.8 32.0 32.0 34.8 42.0
CLA 18.6 18.6 21.2 25.4 28.8 37.2 37.2 42.4 50.8
Condenser Fans FLA 3.3 6.6 6.6 6.6 3.3 3.3 6.6 6.6 6.6

Operating Amps FLA 38.4 44.0 45.4 49.0 41.1 47.7 51.0 52.7 59.9
Connected Load CLA 42.0 47.6 50.2 54.4 47.7 56.1 59.4 64.6 73.0
Maximum Inrush LRA 98.7 105 114 143 90.5 112.4 116.4 129.4 162.4
Operating kW kW 22.4 23.8 25.2 26.6 22.0 31.1 24.3 28.7 31.5
Connected Load kW kW 24.9 26.5 28.3 30.1 25.6 29.6 32.7 36.3 39.9

Notes:

Controls are 24 volt.

Operating Amps (OA): worst case phase for components that can be selected to operate at any one time by the automatic
control system, each component operating at design conditions, i.e. Compressors (based on saturated suction 5 C, condensing
50 C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW).

Connected Load Amps (CLA): worst case phase for components that can be selected to operate at any one time by the
automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 C,
condensing 60 C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW).

PR-2006-0295-GB y Subject to modifications y Status 10/2007 19


Electrical Details at 400 Volt / 3 Ph + N / 50 Hz GEA Close Control
"W" and "F" Versions T-Range

Models 5*** 8 10 12 17 19 21 23

Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA 0.7 4.0 4.0 4.0 4.0 4.0 4.0 4.0
CLA 0.9 5.0 5.0 5.0 5.0 5.0 5.0 5.0
Heaters FLA 13.0 8.7 8.7 8.7 17.4 17.4 17.4 17.4
Humidifier OA 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
CLA 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
Compressors OA 3.0 4.5 6.2 8.0 8.0 8.7 10.5 12.4
CLA 3.5 5.4 7.2 9.3 9.3 10.6 12.7 14.4

Operating Amps OA 16.3 17.2 18.9 20.7 29.4 30.1 31.9 33.8
Connected Load CLA 18.6 19.3 20.9 23.0 31.7 33.0 35.1 36.8
Maximum Inrush LRA 37.0 53.7 63.7 79.7 88.4 96.4 124 79.6
Operating kW kW 5.5 8.8 9.8 10.6 17.4 18.1 18.8 19.6
Connected Load kW kW 7.0 9.7 10.9 11.9 18.8 19.7 20.6 22.1

Models 28 32 37 42 48*** 53*** 63*** 73*** 83***

Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0 1.0
Main Fan(s) OA 4.0 4.0 4.0 4.0 8.0 8.0 8.0 8.0 8.0
CLA 5.0 5.0 5.0 5.0 10.0 10.0 10.0 10.0 10.0
Heaters FLA 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4 17.4
Humidifier OA 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3 3.3
CLA 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6 5.6
Compressors OA 16.0 16.0 17.4 21.0 24.8 32.0 32.0 34.8 42.0
CLA 18.6 18.6 21.2 25.4 28.8 37.2 37.2 42.4 50.8

Operating Amps OA 37.4 38.4 39.8 43.4 37.8 43.3 44.3 47.1 53.3
Connected Load CLA 41.0 42.0 44.6 48.8 44.4 52.8 53.8 58.0 66.4
Maximum Inrush LRA 97.7 98.7 108 137 87.8 110 111 123 156
Operating kW kW 21.6 22.2 23.6 25.0 21.2 22.8 24.0 25.4 28.3
Connected Load kW kW 24.1 24.9 26.7 28.5 23.6 28.0 29.5 33.1 36.7

Notes:

*** F System not available for model 5 and models 48 to 83.

Controls are 24 volt.

Operating Amps (OA): worst case phase for components that can be selected to operate at any one time by the automatic
control system, each component operating at design conditions, i.e. Compressors (based on saturated suction 5 C, condensing
50 C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW).

Connected Load Amps (CLA): worst case phase for components that can be selected to operate at any one time by the
automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 C,
condensing 60 C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW).

20 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Electrical Details at 400 Volt / 3 Ph + N / 50 Hz
T-Range "C" Version

Models 5 12 28 42 53 83

Controls FLA 1.0 1.0 1.0 1.0 1.0 1.0


Main Fan(s) OA 0.7 4.0 4.0 4.0 8.0 8.0
CLA 0.9 5.0 5.0 5.0 10.0 10.0
Heaters FLA 13.0 8.7 17.4 17.4 17.4 17.4
Humidifier OA 3.3 3.3 3.3 3.3 3.3 3.3
CLA 5.6 5.6 5.6 5.6 5.6 5.6

Operating Amps OA 16.3 16.0 24.7 25.7 28.7 29.7


Connected Load CLA 18.6 19.3 28.0 29.0 33.0 34.0
Maximum Inrush LRA 18.6 19.3 28.0 29.0 34.8 35.8
Operating kW kW 5.5 8.7 15.5 16.1 16.7 17.9
Connected Load kW kW 7.0 10.4 17.3 18.1 18.8 20.3

Notes:

Controls are 24 volt.

Operating Amps (OA): worst case phase for components that can be selected to operate at any one time by the automatic
control system, each component operating at design conditions, i.e. Compressors (based on saturated suction 5 C, condensing
50 C), Humidifier (100 %), Main Fans (80 % of rated kW) and Condenser Fans (100 % of rated kW).

Connected Load Amps (CLA): worst case phase for components that can be selected to operate at any one time by the
automatic control system at maximum load conditions for each component, i.e. Compressors (based on saturated suction 10 C,
condensing 60 C), Humidifier (170 % Alarm Condition), Main Fans (100 % of rated kW), Condenser Fans (100 % of rated kW).

PR-2006-0295-GB y Subject to modifications y Status 10/2007 21


Schematic Diagram: "X" Version GEA Close Control
T-Range

22 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control RI-Schema: "A"-Version
T-Range

PR-2006-0295-GB y Subject to modifications y Status 10/2007 23


Schematic Diagram: "W" Version GEA Close Control
T-Range

24 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Schematic Diagram: "F" Version
T-Range

PR-2006-0295-GB y Subject to modifications y Status 10/2007 25


Schematic Diagram: "C" Version GEA Close Control
T-Range

26 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Ancillaries and Options
T-Range

Plinth
For upflow units, a standard plinth is available that raises the Air Handling Unit
200mm (or 400mm) from the floor level to facilitate services entry. It is a plain
sheetmetal box supplied complete with gasket and fixing bolts, and finished to match
the Air Handling Unit.

Base Stand
When the Air Handling Unit is to be installed before the installation of a raised floor, a
matching Base Stand should be used to support it. This consists of a rigid frame of
6mm thick MS angle complete with adjustable feet. The upper face of the frame is
lined with 3mm semi hard gasket. When ordering, specify the nominal height
required, which normally will be the same as the overall height of the raised floor.
The feet have an adjustment of 25mm.

Ceiling Return Duct


The Ceiling Return Duct is a rigid riveted sheetmetal assembly comprising of unit
matched panels lined with 25mm thick insulation. The duct, which is suitable for
downflow units only, is bolted to the top of the Air Handling Unit on site. When
ordering, specify the height between the top of the Air Handling Unit and the under
side of the suspended ceiling. The overall height of the duct will be this dimension
plus 50mm.

Horizontal Discharge Section


The Horizontal Discharge Section consists of a double deflection grille fitted into a
rigid sheetmetal box. The complete assembly is bolted to the top of the Air Handling
Unit on site. The grille has two sets of blades, which allow for both vertical and
horizontal directional adjustment of airflow. The standard height for this section is
500 mm.

Ceiling Discharge Section


For upflow units, where the Air Handling Unit is required to discharge into the ceiling
void, a Ceiling Discharge Extension is available. This consists of a rigid riveted
sheetmetal assembly comprising of unit matched front; rear and end panels lined
with 25 mm thick insulation. The extension is bolted to the top of the Air Handling
Unit on site. When ordering specify the height between the top of the Air Handling
Unit and the underside of the suspended ceiling. The overall height of the duct will be
this dimension plus 50 mm.

High Efficiency Filters


Higher specification filtration can be provided in place of the standard filters having
an efficiency of 80% ASHRAE 52/76 (Eurovent F7). Pre filters are fitted, before the
main high efficiency filters, and are rated as G2. These filters are fitted in the return
airside of the Air Handling Unit within the main cabinet.

Filter Gauge
A dial type manometer can be installed to read the pressure drop across the filter to
give an accurate indication of filter condition.

PR-2006-0295-GB y Subject to modifications y Status 10/2007 27


Ancillaries and Options GEA Close Control
T-Range

Fresh Air Kit and Filter


Units can be supplied with a fresh air inlet connection and disposable fresh air filter
element. This will admit approximately 35 % of the recirculated air volume. One or
two may be fitted depending on requirements.

Special Colours
Special Colours must be specified when ordering the Air Handling Unit (quote British
Standard number, RAL number, or other, if known). If more than one colour is
specified then state the colour of each panel.

Double Skin Panels


To reduce the sound "break out", Double Skin Panels comprise: - 20 swg steel sheet
glued to the inner face of all outer panels then covered with standard 25mm class O
insulation.

Without Electric Heating


All equipment associated with electric heating is removed from the Air Handling Unit.

LPHW Heating (not available on models 48 83)


Units may be fitted with a Low Pressure Hot Water heating coil in place of the
standard electrical heating. Water flow through the coil is controlled by a modulating
3 way valve. Duties of these coils are nominally the same as standard electric
heating, based on flow and return hot water temperatures of 82 C and 71 C
respectively.

Water Detection
Water Sensors, connected directly to the water detection module of the Air Handling
Unit microprocessor control system, are located in: -
- Condensate drain pan detecting undue water level.
- Underfloor water tape, supplied loose with 5 metres of cable.
When water is detected, the Air Handling Unit's alarm system is activated and
disables humidifier function.

Sump Pump
Where, due to location, it is not possible to gravity drain units, a sump pump can be
fitted to collect any condensate and pump it to the nearest convenient drain point
(maximum available pump head 5.7 metres). For units fitted with humidifiers, a larger
capacity sump pump is available to accommodate the additional discharge of hot
water during humidifier drain down cycles (maximum available pump head 7 metres).
Please note that when using a sump pump a minimum of a 200 mm high plinth is
required.

28 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Ancillaries and Options
T-Range

VRF System
To provide energy saving and thereby limit emission of greenhouse gases that
contribute to global warming, models 23 and above are supplied with the variable
refrigerant flow (VRF) compressor configuration. By applying these models to smaller
loads, even greater energy savings will be realised, due to the very high part load
efficiency.

Electronically Controlled Fans


For applications where high airflow is not required and noise is a major
consideration, then fans with variable speed motors can be fitted. The motors are 3
phase variable frequency but only a single phase feed is provided. The airflow
provided by the fan(s) is determined by a 0 10 Vdc signal that is generated from
the cooling demand via the controls. The lower the cooling demand the lower the
airflow and vice versa. For this option, a reduced heating capacity will be necessary.

Condenser Fan Pressure Switch


A Condenser Fan Pressure Switch can be fitted to the Unit to replace the standard
fan speed controller on "A" versions.

Screwed Water Connections


BSP screwed fittings supplied instead of the standard copper solder connections on
W and C versions.

Hot Gas By Pass


"A" versions can be fitted with hot gas by pass compressor capacity control. This
consists of a hot gas control valve in the by pass line between the discharge line of
the compressor and the evaporator coil suction header, with the sensing line fitted in
the suction line.

Refrigerants
Alternative refrigerants R134a and R410A are available as standard options on
request.

Hand/Auto Switches
A hard wired switch assembly, fitted in the electrical control panel can be used as
manual override or as automatic control function, and is intended as an aid to
commissioning engineers.

Run Status
Run Status is achieved by volt free terminals, located in the electrical box, for remote
monitoring of the unit run (fans) operation.

PR-2006-0295-GB y Subject to modifications y Status 10/2007 29


Ancillaries and Options GEA Close Control
T-Range

Controller Remote Display


The C3-05 Controller Display can be supplied remote from the Air Handling Unit,
complete with interconnecting cable up to 1 kilometre.

Monitoring Display
The Monitoring Display can be connected to a network of C3-05 Controllers to
enable complete Air Handling Unit monitoring.

Electronic Expansion Valve (EEV)


On DX units the EEV option can be fitted to replace the standard TEV. This consists
of a valve, electronic driven module, pressure transducer and temperature sensor
per refrigerant circuit.

Discharge Pressure Transducer


On DX units a pressure transducer can be fitted to monitor the discharge pressure. It
is recommended that the EEV option it fitted with the Discharge Pressure
Transducer.

Remote Temperature and Humidity Sensor


The temperature and humidity sensors Unit, fitted with the required length of cable
(up to a maximum of 25 metres), can be supplied remote from the Air Handling.

Winter Start Kit (ELATE)


Generally recommended for temperatures between 25 C and 40 C, and
comprises horizontal type liquid receiver with trace heater and pressure relief valve
situated in a special section below the air cooled Condensing Unit / Condenser.
However a base section will be required and will increase the overall height of the
horizontal blow Condensing Units / Condensers by 400 mm.

Trend Interface Card


The Trend interface is a small pcb which can be plugged into the C3-05 controller to
provide it with Trend network capability.
The interface needs to be configured in order that the required controller variables
are linked to appropriate Trend parameters; these then become accessible via the
Trend network using standard Trend (text) communications. The interface provides
CNC functionality.
- Flexible number of configuration modules
- Peer to peer communications (IC Comms)
- Suitable for field installation
- Display and directory modules

30 PR-2006-0295-GB y Subject to modifications y Status 10/2007


GEA Close Control Ancillaries and Options
T-Range

RS232 Serial Card


The RS232 Serial Card is used to interface the C3-05 controller directly to a standard
HAYES modem. The following hardware signals can be managed:
- Output, request to send (RTS) in parallel to data terminal ready (DTR).
- Input, carrier detected (CD).
The maximum baud rate is 19200.

RS485 Serial Card


The RS485 Serial Card is used to interface the C3-05 controller to an RS485
network.
The card guarantees the optical isolation of the controller from the RS485 serial
network. The maximum baud rate is 19200 (adjustable in software).

Lonworks Serial Card

The LonWorks Serial Card is used to interface the C3-05 controller to a Lonworks
network.
The type of interface on the LonWorks network side is:
- PCO20000F0 interface to FTT-10A 78 Kbs (TP/FT-10).
The baud rate of the C3-05 controller must be set to 4800.

PCOWEB Interface
The pCOWeb Interface allows connection to TCP/IP and SNMP protocols on the
Ethernet standard and BACnet both on the Ethernet and EIA485 standards.

Due to our policy of continuous development and improvement, the specifications and data herein are subject to change
without notice. We must therefore reserve the right to supply equipment that may differ from that described and illustrated
herein.
All information, including illustrations, contained in this brochure, is believed to be accurate and reliable. Users, however,
should independently evaluate the suitability of each product for their own application. GEA makes no warranties as to the
accuracy or completeness of the information, and disclaims any liability regarding its use.

PR-2006-0295-GB y Subject to modifications y Status 10/2007 31


Our Market in Europe

A GEA DK GEA Klimateknik ApS IS Rafn Jensson RO GEA Klimatechnik s.r.l.


Klimatechnik GmbH DK-2610 Rdovre IS-110 Reykjavik RO-300222 Timisoara

PR-2006-0295-GB Subject to modifications Status 10/2007 Copyright GEA Air Treatment


A-4673 Gaspoltshofen Tel. +45 / 38 / 887070 Tel. +354 / 56 / 780-30 Tel. +40 / 356 / 423703
Tel. +43 / 7735 / 8000-0
E GEA Air Treatment L GEA Happel Luxembourg RUS GEA Kondicioner
B GEA Happel Belgium N.V. Marketing Services L-4940 Bascharage Moskva
B-1130 Brussels Int. GmbH - oficina Espaa Tel. +352 / 26 / 502970 RU-105094 Moskva
Tel. +32 / 2 / 2406161 E-28036 Madrid Tel. +7 / 495 / 9566674
Tel. +34 / 91 / 3837701 LT GEA Klimatechnik UAB
BG EVISS Ltd. LT-01141 Vilnius S GEA EXOS
BG-7000 Rousse EST GEA Klimatechnik UAB Tel. +370 / 5 / 2106060 Ventilation AB
Tel. +359 / 82 / 81000 LT-01141 Vilnius S -74528 Enkping
Tel. +370 / 5 / 2106060 LV GEA Klimatechnik UAB Tel. +46 / 171 / 85530
BIH GEA Klimatehnika LT-01141 Vilnius SK GEA Klimatizcia s.r.o.
RS-11070 Novi Beograd F GEA Happel France sarl Tel. +370 / 5 / 2106060
F-59436 Roncq Cedex SK-83104 Bratislava
Tel. +381 / 11 / 3193955 Tel. +421 / 7 / 44457917
Tel. +33 / 3 / 20689020 MWE GEA Klimatehnika
BY GEA Klimatechnik UAB RS-11070 Novi Beograd
LT-01141 Vilnius FIN OY TEKNOCALOR AB Tel. +381 / 11 / 3193955 SLO GEA Klimatizacijska
Tel. +370 / 5 / 2106060 FIN-01300 Vantaa Tehnika d.o.o.
Tel. + 358 / 9 / 82546020 GEA Klimaprodukter AS SI-1000 Ljubljana
N
CH GEA Klimatec N-0484 Oslo Tel. +386 / 1 / 2573850
Schweiz AG GB Denco Ltd. Tel. +47 / 220 / 27990
CH-3065 Bolligen-Station UK-HR4 8DS Hereford SRB GEA Klimatehnika
Tel. +41 / 31 / 9171919 Tel. +44 / 1432 / 277 277 NL GEA Happel RS-11070 Novi Beograd
Nederland B.V. Tel. +381 / 11 / 3193955
CZ GEA LVZ, a.s. H GEA Klimatechnika Kft NL-2909 LL
CZ-46312 Liberec H-1037 Budapest Capelle a/d Ijssel TR ISISAN
Tel. +420 / 48 / 5225-111 Tel. +36 / 1 / 4393200 Tel. +31 / 10 / 2350606 TR-80700 Balmumcu
GEA Klimatizace spol. s r.o. Istanbul
CZ-46312 Liberec HR GEA Klima-rashladna P Nnio, Lda. Tel. +90 / 212 / 2757171
Tel. +420 / 48 / 5225-303 tehnika d.o.o. P-1269-090 Lisboa
HR-10000 Zagreb Tel. +351 / 21 / 3826160 UA GEA Ukraina t.o.v.
D GEA Happel Tel. +385 / 1 / 6064900 UA-01135 Kyiv
Klimatechnik GmbH PL GEA Tel. +38 / 044 / 4619356
D-44625 Herne Klimatyzacja Sp. z o.o.
Tel. +49 / 2325 / 468-00 PL-54610 Wroclaw
Tel. +48 / 71 / 3737952