U-Series
Air Circuit Breaker
HYUNDAI ACB meets your demands for high
breaking capacity, full line-up, and optimized
panel size. Various accessories and connection
methods realize user-friendly handling.
U-Series / Air Circuit Breaker
Features
| Full line-up |
U-Series ACB maximize your choice and satisfaction with compact size and dual (UAN/UAS) model.
460mm
766mm
624mm
D frame1)
399mm [150kA]
36
C frame
8m
328mm
m
[100kA] 4,000-6,300A(UAN)
B frame
A frame [100kA] 4,000-5,000A(UAN)
[85kA] 2,000-4,000A(UAN)
2,000-3,200A(UAS)
630-2,000A(UAN)
630-1,600A(UAS)
| Applications |
U-Series ACB offering high breaking capacity and advanced protection trip relay is suitable to cover various applications
including buildings, data centers, industrials and so on. U-Series ACB protects these facilities from harmonic frequency by
100% capacity of N phase.
4
ACB
Approval
ISO 18001, 14001, 9001
KS/KOREA Korea Quality Certificate Standard Association
CE Community European
GOST-R/RUSSIA Government Standard of Russia
CCC/CHINA China Compulsory Certification
KR/KOREA Korean Register of Shipping
GL/GERMANY Germanischer Lloyd
LR/U.K Lloyd's Register of Shipping
ABS/U.S.A American Bureau of Shipping
BV/FRANCE Bureau Veritas
NK/JAPAN Nippon Kaiji Kyokai
CB type test
DEKRA Formerly KEMA Quality Registered
KERI Korea Electrotechnology Research Institute
Features
| Various accessories |
[ Body side ]
6
ACB
[ Cradle side ]
Features
Ordering 50Hz 33 35 36 37
code 60Hz 43 45 46 47
Externals
8
ACB
Standard connection
- Changing connector is available only for UAN/UAS A frame 630-1,600A, UAN/UAS B frame 2,000-3,200A.
- Front connection type is suitable the panel requirement for limited installation space.
- Changing connection above 4,000A needs additional component, please contact us.
Features
| Easy-to-install |
Fixed type
Installed in a switchboard directly.
Draw-out type
Consists of ACB and cradle.
Cradle is fixed to a switchboard.
ACB may be in the position of CONNECTED, TEST, ISOLATED,
and REMOVED.
Switchboard door may be closed in ISOLATED position. [ Draw-in/out guide rail ]
(Connected Position)
- Main and control circuit are all connected. - Main circuit is isolated, control circuit is connected.
- Normal condition of use - Control test is possible when switchboards door is closed.
- Main and control circuit are all isolated. - ACB is totally drawn out from the cradle.
- Switchboard door may be closed in isolated position.
10
ACB
Structure
| Externals |
[ Front ]
[ Cradle ]
[ Inside ] [ Rear ]
Structure
| Internals |
12
ACB
Ratings
W D
W D
| Overview |
PTA: Pre-trip alarm
LTD: Long time delay
STD/INST: Short time or instantaneous tripping
GFT/ELT: Ground fault trip or earth-leakage trip
TAL: Temperature alarm
Phase indication Iine
Ir: Long time current setting knob
Tr: Long time tripping delay setting knob
Isd: Short time current setting knob
Tsd: Short time tripping delay setting knob
Ii: Instantaneous current setting knob
GFT/STD, MCR setting knob
Ip: Pre-trip alarm current setting knob
Tp: Pre-trip alarm delay setting knob
Ig: Ground fault current setting knob
Tg: Ground fault tripping delay setting knob
Rated current setting knob
Test jack
Earth leakage pick-up and
tripping delay setting knob
14
ACB
Externals
Control power - -
Power supply
Self power
Long time delay (LTD)
Short time delay (STD)
Instantaneous trip (INST)
Protection Pre trip alarm - -
Ground fault trip - -
Field test - -
Failsafe
True RMS detection
Fault indication LED - -
Indication
Overload indication LED - -
Display window - -
Integrated instantaneous - - PTA: 1a -
contact (1a)
L/S/I/G: 2a
Output contact
Individual continuous LTD: 1a
- PTA: 1a -
contact (4a) S/I: 1a
L/S/I/G: 2a PTA:1a
MCR
Temperature detection - - - -
Optional
Event/Fault recording - -
function
Earth leakage trip (ELT) - - - - -
Communication - - - - -
: Standard : Option
O
rdering codes
| UPR-1L-GL |
Overload protection
- Long time delay
Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
Ground fault protection
- I2t on/off optional
Self power
1a DO (Digital output)
Characteristic
I2t off Ii
I2t off
Protection
16
ACB
| UPR-2L-GS, UPR-2L-GM |
Characteristic
Protection
| UPR-1D-GT |
Characteristic
Protection
18
ACB
| UPR-1S-AL |
Overload protection
- Long time delay
Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
Ground fault protection
- I2t on/off optional (for STD)
Self power
1a DO (Digital output)
Characteristic
I2t on
Isd
tsd
I2t off Ii
Protection
| UPR-2S-AS |
Characteristic
I2t off Ii
Protection
20
ACB
| Operation characteristics |
I2t off I n
Isd Tp(S type)
Tsd
Ip
Instantaneous trip (INST)
Standard current setting T
t Ii I - The scale is markedt as magnification of [In]. I
Tp
I - Setting range: (Non, 2, 3, 4, 6, 8, 10, 12, 15)In (9I modes)
- No protection in case of non setting of [Ii].
Ii
Tp
I I
Tp(S type)
Ip
Ii
Tp
I I
| Operation characteristics |
Ig2t off
Ig
t
Tg
I
Ig2t on
tt Ig Ig2t off
t I n
t
T
I
I n Tp(S type)
Ip
T Standard current setting
tPre-trip alarm (PTA)
Tp I L type
I - The scale is marked as magnification of [In] with definite time operation.
- Setting range: (Non, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0)In (10 modes)
S type
Tp(S type) - The scale is marked as magnification of [In] with inverse time operation.
t Ip - Setting range: (Non, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0, 1.05, 1.1)In (10 modes)
22
ACB
| Circuit diagrams |
UPR-1L-GL
NCT
k
R S T 21 29 30
R S T N L/S
I/G
NCT NCT
1 2
UPR-1L-GL
Rn Sn Tn Nn Ac A C TN T P
CT3
TP
CT2
MHT
CT1
TN
1a for MCR
Rn Sn Tn 22
UPR-2L-GS
AC,DC100-250V S0 - S2
Source
NCT + -
k
R S T 21 23 29 30 19
R S T N L PT NCT NCT S2
1 2
UPR-2L-GS
ZO ZO
Rn Sn Tn Nn Ac S/I G/E ZI
1
ZI
2 1 2
A C TN TP S 0
CT3
TP
CT2
MHT
CT1
TN
1a for MCR
Rn Sn Tn 22 24 26 31 32 33 34 20
+ - + -
In Out
ZSI
| Circuit diagrams |
UPR-1D-GT
AC,DC100-250V S0 - S2
Source
ZCT NCT + -
k k
R S T 21 23 27 28 29 30 19
UPR-1D-GT
1a for
MCR
Rn Sn Tn 22 24 26 31 32 33 34 35 36 20
+ - + - + -
In Out Communication
ZSI
UPR-2L-GM
AC,DC100-250V S0 - S2
Source
NCT + -
k
R S T 21 23 29 30 19
UPR-2L-GM
1a for MCR
Rn Sn Tn 22 24 26 31 32 33 34 20
+ - + -
In Out
ZSI
24
ACB
UPR-1S-AL
R S T 21
R S T L/
N SI
UPR-1S-AL
Rn Sn Tn Nn Ac A C TN T P
CT3
TP
CT2
MHT
CT1
TN
1a for MCR
Rn Sn Tn 22
UPR-2S-AS
AC,DC100-250V S 0 - S2
Source
+ -
R S T 21 23 19
R S T N L PT S2
UPR-2S-AS
Rn Sn Tn Nn Ac S/I ZI ZI ZO ZO A C TN TP S 0
CT3 1 2 1 2
TP
CT2
MHT
CT1
TN
1a for MCR
Rn Sn Tn 22 24 31 32 33 34 20
+ - + -
In Out
ZSI
| Characteristic curves |
General feeder
4
3
Hour
2
1
50
40
30
20
10
8
Minute
6
5
4
3
2
1
50
40
30
Operating time
20
10
8
6
5
4
3
2
1
0.8
0.6
0.5 500ms 500ms
0.4
Second
0.3
0.2
0.1
0.08
0.06 50ms 50ms
0.0
0.05
0.04
0.03
0.02
0.01
0.008
0.006
0.005
1000
1500
2000
2500
3000
100
100
125
150
200
250
300
400
500
600
700
800
900
10
15
20
30
40
50
60
70
80
90
60
70
80
90
7
8
9
Percent for rated primary current of OCR [ICT] Percent for base current of OCR [Io]
Long time delay current setting range Instantaneous tripping current setting range Pre-trip alarm current setting range
Short time delay current setting range Ground fault trip current setting range
26
ACB
Generator
4
3
Hour
1
50
40
30
20
10
8
Minute
6
5
4
3
2
1
50
40
30
Operating time
20
10
8
6
5
4
3
2
1
0.8
0.6
0.5 500ms
0.4
Second
0.3
0.2
0.1
0.08
0.06
0.05
0.0
50ms
0.04
0.03
0.02
0.01
0.008
0.006
0.005
1000
1500
2000
2500
3000
100
125
150
200
250
300
400
500
600
700
800
900
10
15
20
30
40
50
60
70
80
90
7
8
9
Long time delay current setting range Instantaneous tripping current setting range
Short time delay current setting range Pre-trip alarm current setting range
Example
In case of that short time-delay or ground fault accident occurs at ZSI built in system, the breaker at accident site
sends ZSI signal to halt upstream breakers operation.
To eliminate a breakdown, trip relay of ACB at accident site activates trip operation without time delay.
The
upstream breaker that received ZSI signal adhere to pre-set short time-delay or ground fault time delay for
protective coordination in the system. However upstream breaker that did not receive its signal will trip instantaneously.
For ordinary ZSI operation, it should arrange operation time accordingly so that downstream circuit breakers will
react before upstream ones under overcurrent/short time delay/ground fault situations.
ZSI connecting line needs to be maximum 3m.
ACB 1
Out
Zone 1 In
In In In
ZSI connecting
28
ACB
| System diagram |
R S T N
ACB trip
ACB
Display
(LCD, LED)
MHT
Trip
Rogowski Relay operation
CT Measurement
part selection
PTA contact
MCU
processing
LTD contact
External
contact STD/INST contact
GFT contact
Power
CT Self power COMMON contact
Trip relay
ZSI output +
ZSI output -
ZSI
ZSI input +
ZSI input -
SMPS Test
110V - 220V power terminal
| Communication function |
Modbus-RTU / RS-485
SCADA system
Operation mode: Differential
Distance: Max.1.2km
Modbus/RS-485
Cable: RS-485 shielded twist 2-pair cable
Baud rate: 9,600, 19,200, 38,400 bps
Transmission method: Half-duplex
Termination: 150