U-Series

Air Circuit Breaker

LV &
MV
Circ
uit B
reak
ers
Leader of Technology
Hyundai Heavy Industries' state-of-the-art technologies
have created circuit breakers and contactors
for electrical systems that are genuine masterpieces.

CONTENTS
04 Features 11 Structure 13 Ratings 14 Protection Trip Relay (OCR) 30 Accessories 72 Circuit Diagrams
74 Dimensions 92 Ordering Codes 96 Technical Data 105 Operating Conditions 106 Ordering Sheet
U-Series
Air Circuit Breaker
HYUNDAI ACB meets your demands for high
breaking capacity, full line-up, and optimized
panel size. Various accessories and connection
methods realize user-friendly handling.
U-Series / Air Circuit Breaker

Features

| Full line-up |
U-Series ACB maximize your choice and satisfaction with compact size and dual (UAN/UAS) model.
460mm

766mm

624mm
D frame1)
399mm [150kA]
36

C frame
8m

328mm
m

[100kA] 4,000-6,300A(UAN)
B frame
A frame [100kA] 4,000-5,000A(UAN)
[85kA] 2,000-4,000A(UAN)
2,000-3,200A(UAS)
630-2,000A(UAN)
630-1,600A(UAS)

- Breaking capacity is at AC500V.


1) D frame will be available from October 2013.

| Applications |
U-Series ACB offering high breaking capacity and advanced protection trip relay is suitable to cover various applications
including buildings, data centers, industrials and so on. U-Series ACB protects these facilities from harmonic frequency by
100% capacity of N phase.

Buildings Data centers & Networks Industrials Electric power facilities


Multipurpose buildings Broadcasting stations Steel/Metal Electric power stations
Hospitals IT/Telecommunications Gas/Chemical Electric power substations
Commercial buildings Pulp/Paper Dispersed power generators
Hotels Renewable energy facilities

4
ACB

| Compliance with standards |


Standard
IEC 60947-1,2 International Electrotechnical Commission
EN 60947-2 European Standard
GB China National Standard (Guojia Biaozhun)
GOST R 50030.2-99 9 Government Standard of Russia
GOST R 50030.1-2000 Government Standard of Russia
KS C 4620 Korean Standards Association

Approval
ISO 18001, 14001, 9001
KS/KOREA Korea Quality Certificate Standard Association
CE Community European
GOST-R/RUSSIA Government Standard of Russia
CCC/CHINA China Compulsory Certification
KR/KOREA Korean Register of Shipping
GL/GERMANY Germanischer Lloyd
LR/U.K Lloyd's Register of Shipping
ABS/U.S.A American Bureau of Shipping
BV/FRANCE Bureau Veritas
NK/JAPAN Nippon Kaiji Kyokai

CB type test
DEKRA Formerly KEMA Quality Registered
KERI Korea Electrotechnology Research Institute

U-Series Air Circuit Breaker_ 5


U-Series / Air Circuit Breaker

Features

| Various accessories |

[ Body side ]

Motor Auxiliary switch OCR portable checker Test jumper


Closing coil Condenser trip device Key lock device Draw-in/out handle
Trip coil Lifting lug Wrong insertion preventer Draw-in/out and
Double trip coil Mechanical interlock kit Fixing block position lock device
Trip supervision coil Phase insulation barrier Counter Door flange
Under voltage trip coil ON/OFF button cover O CR & Alarm switch reset device Dust cover

6
ACB

[ Cradle side ]

UVT time delay controller Mechanical interlock kit Safety shutter


Remote operation module Phase insulation barrier Arc shield
Temperature detection module Mechanical operated cell (MOC) switch Control terminal protection cover
Short bcontact Dummy ACB
Position switch Wrong insertion preventer

U-Series Air Circuit Breaker_ 7


U-Series / Air Circuit Breaker

Features

| High performance protection trip relay (OCR) |


The protection trip relay (OCR) of U-Series ACB supports stable power supply with temperature alarm, fault recording, and
others in addition to main protection functions.

Type UPR-1L-GL UPR-2L-GS UPR-1D-GT UPR-2L-GM

Ordering 50Hz 33 35 36 37
code 60Hz 43 45 46 47

Externals

Main function L/S/I/G L/S/I/G L/S/I/G L/S/I/G


Self-power Self-power Self-power Self-power
Failsafe AC, DC100-250V AC, DC100-250V AC, DC100-250V
Pre-trip alarm Failsafe Failsafe Failsafe
Integrated Pre-trip alarm Pre-trip alarm Pre-trip alarm
instantaneous output Individual continuous Individual output Individual output
contact output contact contact contact
Fault event Fault event Fault event
Temperature alarm Temperature alarm Temperature alarm
Earth leakage trip
Communication
(Modbus)

8
ACB

| Multiple terminal busbar connections |


Increases the user's convenience by diversified terminal connection methods according to busbar's type.
Simply turn a horizontal connector 90 to make it a vertical connector (The opposite case is same).

Standard connection

Vertical Horizontal Front

Mixed connection (Top/Bottom)

Vertical/Horizontal Horizontal/Vertical Vertical/Front

Horizontal/Front Front/Vertical Front/Horizontal

- Changing connector is available only for UAN/UAS A frame 630-1,600A, UAN/UAS B frame 2,000-3,200A.
- Front connection type is suitable the panel requirement for limited installation space.
- Changing connection above 4,000A needs additional component, please contact us.

U-Series Air Circuit Breaker_ 9


U-Series / Air Circuit Breaker

Features

| Easy-to-install |
Fixed type
Installed in a switchboard directly.

Draw-out type
Consists of ACB and cradle.
Cradle is fixed to a switchboard.
ACB may be in the position of CONNECTED, TEST, ISOLATED,
and REMOVED.
Switchboard door may be closed in ISOLATED position. [ Draw-in/out guide rail ]

(Connected Position)

Connected position Test position

- Main and control circuit are all connected. - Main circuit is isolated, control circuit is connected.
- Normal condition of use - Control test is possible when switchboards door is closed.

Isolated position Removed position

- Main and control circuit are all isolated. - ACB is totally drawn out from the cradle.
- Switchboard door may be closed in isolated position.

10
ACB

Structure

| Externals |

[ Front ]

[ Fixed type ] [ Draw-out type ]

[ Cradle ]

[ Inside ] [ Rear ]

Control terminal Position lock device Manual charging handle


Front cover Position lock release button Name plate
Close/Open indicator Draw-in/out handle insertion hole Arc shield
Close button Position indicator Terminal busbar
Protection trip relay (OCR) Counter OCR & Alarm switch reset button
Open button Charged/Discharged indicator Draw-in/out guide rail

U-Series Air Circuit Breaker_ 11


U-Series / Air Circuit Breaker

Structure

| Internals |

Arc chamber MHT device Control terminal Current transformer


Frame Protection trip telay (OCR) Manual charging handle Terminal clip
Counter Mechanism Closing spring Cradle
Auxiliary switch Draw-in/out device Moving contact
Motor Front cover Fixed contact
Closing/Trip/UVT coil Control terminal protection cover T erminal busbar

12
ACB

Ratings

Frame A frame B frame C frame A frame B frame


Model UAN UAS
06 : 630 06 : 630 32 : 3,200 06 : 630 20 : 2,000
08 : 800 08 : 800 40 : 4,000 08 : 800 25 : 2,500
10 : 1,000 10 : 1,000 50 : 5,000 10 : 1,000 32 : 3,200
12 : 1,250 12 : 1,250 12 : 1,250
Recognition order code:
16 : 1,600 16 : 1,600 16 : 1,600
Rated current (In max at 40C) (A)
20 : 2,000 20 : 2,000
25 : 2,500
32 : 3,200
40 : 4,000
Rated operating voltage (Ue) (V) AC 690 AC 690
Rated insulation voltage (Ui) (V) AC 1,000 AC 1,000
Frequency (Hz) 50/60 50/60
Number of poles 3, 4 3, 4
Current setting range (.. x In max) 0.4-1.0 0.4-1.0
Rated current of neutral pole (..% x In) 100% 100%
Rated breaking capacity IEC 60947-2 AC 690/600/550V 65 85 85 55 70
(Icu) category B AC 500/480/460V 85 100 100 65 85
(kA sym) KS C 4620 AC 415/380/230/220V 85 100 100 65 85
Rated service breaking capacity (..% x Icu) 100% 100%
Rated making capacity IEC 60947-2 AC 690/600/550V 143 187 187 121 154
(Icm) category B AC 500/480/460V 187 220 220 143 187
(kA peak) KS C 4620 AC 415/380/230/220V 187 220 220 143 187
Rated short-time capacity 1 sec 65 85 85 55 70
(Icw) 2 sec 60 75 75 45 65
(kA, without Inst.) 3 sec 50 65 65 36 55
Rated impulse withstand voltage (Uimp) (kV) 12 12
Maximum total breaking time (ms) 40 40
Motor charging time (sec) max. 10 10
Closing operating time
Closing time (ms) max. 40 40
Without maintenance 20,000 15,000 10,000 20,000 15,000
Mechanical
With maintenance 30,000 2,000 2,000 30,000 20,000
Life cycle (times) 06-20 : 10,000
Without maintenance 5,000 25-40 : 5,000
2,000 5,000 5,000
Electrical
06-20 : 15,000
With maintenance 10,000 25-40 : 10,000
5,000 10,000 10,000
06-32 : 87
Draw-out type 63 40 : 107
145 63 87
3 pole
06-32 : 44
Fixed type 34 40 : 61
76 34 44
Weight (kg)
06-32 : 130
Draw-out type 280 40 : 61
173 74 103
4 pole
06-32 : 55
Fixed type 44 40 : 81
81 44 55
Draw-out type 328 x 460 x 368 399 x 460 x 368 624 x 460 x 368 328 x 460 x 368 399 x 460 x 368
3 pole
External dimension (mm) Fixed type 337 x 404 x 296 408 x 404 x 296 633 x 404 x 296 337 x 404 x 296 408 x 404 x 296
(WxHxD, except busbar) Draw-out type 413 x 460 x 368 514 x 460 x 368 794 x 460 x 368 413 x 460 x 368 514 x 460 x 368
4 pole
Fixed type 422 x 404 x 296 523 x 404 x 296 803 x 404 x 296 422 x 404 x 296 523 x 404 x 296

Fixed type Draw-out type


H

W D
W D

U-Series Air Circuit Breaker_ 13


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| Overview |

LCD display window


Fault indication LED


PTA: Pre-trip alarm
LTD: Long time delay
STD/INST: Short time or instantaneous tripping
GFT/ELT: Ground fault trip or earth-leakage trip
TAL: Temperature alarm

Overload indication LED


Function key

Reset: Fault reset


Hi/Low: Field test function
(Hi: STD/INST, Low: LTD)
Move
List: Secondary menu
Enter: Setting input


Phase indication Iine
Ir: Long time current setting knob
Tr: Long time tripping delay setting knob
Isd: Short time current setting knob
Tsd: Short time tripping delay setting knob
Ii: Instantaneous current setting knob
GFT/STD, MCR setting knob
Ip: Pre-trip alarm current setting knob
Tp: Pre-trip alarm delay setting knob
Ig: Ground fault current setting knob
Tg: Ground fault tripping delay setting knob
Rated current setting knob
Test jack
Earth leakage pick-up and
tripping delay setting knob

14
ACB

General feeder Generator


Application
UPR-1L-GL UPR-2L-GS UPR-1D-GT UPR-2L-GM UPR-1S-AL UPR-2S-AS

Externals

Control power - -
Power supply
Self power
Long time delay (LTD)
Short time delay (STD)
Instantaneous trip (INST)
Protection Pre trip alarm - -
Ground fault trip - -
Field test - -
Failsafe
True RMS detection
Fault indication LED - -
Indication
Overload indication LED - -
Display window - -

Integrated instantaneous - - PTA: 1a -
contact (1a)
L/S/I/G: 2a
Output contact

Individual continuous LTD: 1a
- PTA: 1a -
contact (4a) S/I: 1a
L/S/I/G: 2a PTA:1a
MCR
Temperature detection - - - -
Optional
Event/Fault recording - -
function
Earth leakage trip (ELT) - - - - -
Communication - - - - -
: Standard : Option

O
 rdering codes

Ordering codes Application


Model Frequency Complete parts Specifications Mounting position
Spare part UAN UAS
of ACB/Cradle
UPR-1L-GL 33 UANS OCR33A/33J for auto connection/manual connection type
UPR-2L-GS 35 UANS OCR35A/35J for auto connection/manual connection type
UPR-1D-GT 36 UANS OCR36A/36J for auto connection/manual connection type
50Hz
UPR-2L-GM 37 UANS OCR37A/37J for auto connection/manual connection type
UPR-1S-AL 38 UANS OCR38A/38J for auto connection/manual connection type
UPR-2S-AS 39 UANS OCR39A/39J for auto connection/manual connection type
Inside of ACB body
UPR-1L-GL 43 UANS OCR43A/43J for auto connection/manual connection type
UPR-2L-GS 45 UANS OCR45A/45J for auto connection/manual connection type
UPR-1D-GT 46 UANS OCR46A/46J for auto connection/manual connection type
60Hz
UPR-2L-GM 47 UANS OCR47A/47J for auto connection/manual connection type
UPR-1S-AL 48 UANS OCR48A/48J for auto connection/manual connection type
UPR-2S-AS 49 UANS OCR49A/49J for auto connection/manual connection type

U-Series Air Circuit Breaker_ 15


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| UPR-1L-GL |

Overload protection
- Long time delay
Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
Ground fault protection
- I2t on/off optional
Self power
1a DO (Digital output)

Characteristic

Ir: Long time current setting

Ir tr: Long time tripping delay setting


Isd: Short time current setting
tr tsd: Short time tripping delay setting
Ii: Instantaneous current setting
tg: Ground fault tripping delay setting
I2t on
Isd Ig: Ground fault current setting
Ig I2t on
tsd
tg

I2t off Ii
I2t off

Protection

In = Ict (A) 0.5 0.63 0.7 0.8 0.9 1


Current setting (Ir)
Ir = In (A) 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non
Long time Time delay (tr) tr at (1.5Ir) (sec) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy: 15% tr at (6.0Ir) (sec) 0.5 1.25 2 2.5 5 10 15 20 25 30
or below 100ms tr at (7.2Ir) (sec) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current setting (Isd) Isd = In (A) 1 1.5 2 2.5 3 4 6 8 10 Non
I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tsd) tsd
Short time I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 10Ir
Accuracy: 20% Min. trip time (msec) 20 80 160 260 360 460
(I2t off)
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ii) Ii = In (A) 2 3 4 6 8 10 12 15 Non
Instantaneous
Trip time below 50ms
Pick-up (Ig)
Accuracy: 15% (Ig0.4In) Ig = Ict (A) 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
20% (Ig0.4In)
Ground fault I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tg) tg
I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 1In
Min. trip time (msec) 20 80 160 260 360 460
Accuracy: 20% (I2t off)
Max. trip time (msec) 80 140 240 340 440 540

16
ACB

| UPR-2L-GS, UPR-2L-GM |

Overload protection Event recording


- Long time delay - Short time delay, instantaneous trip
Short circuit protection - I2t on/off optional (for STD)
- Short time delay, instantaneous trip Pre-trip alarm
- I2t on/off optional (for STD) - Prevent unnecessary over load trip
Ground fault protection according to rated current (In)
- I2t on/off optional Field test
Realization of protective - Simulation of long time, short time,
coordination by ZSI (Zone selective instantaneous delay
interlocking) 4a(3a) DO (Digital output)
Fault recording - 4a (UPR-2L-GS)
- Records max. up to 10 fault information - 3a (UPR-2L-GM)
about fault type, fault phase, fault
valve, occurrence time of fault

Characteristic

Ir: Long time current setting

Ir tr: Long time tripping delay setting


Isd: Short time current setting
IP
tr tsd: Short time tripping delay setting

Tp Ii: Instantaneous current setting


tg: Ground fault tripping delay setting
I2t on
Isd Ig: Ground fault current setting
Ig I2t on
tsd tp: Pre-trip alarm delay setting
tg
Ip: Pre-trip alarm current setting
I2t off Ii
I2t off

Protection

In = Ict (A) 0.5 0.63 0.7 0.8 0.9 1


Current setting (Ir)
Ir = In (A) 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non
Long time Time delay (tr) tr at (1.5Ir) (sec) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy: 15% tr at (6.0Ir) (sec) 0.5 1.25 2 2.5 5 10 15 20 25 30
or below 100ms tr at (7.2Ir) (sec) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current setting (Isd) Isd = In (A) 1 1.5 2 2.5 3 4 6 8 10 Non
I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tsd) tsd
Short time I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 10Ir
Accuracy: 15% Min. trip time (msec) 20 80 160 260 360 460
(I2t off)
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ii) Ii = In (A) 2 3 4 6 8 10 12 15 Non
Instantaneous
Trip time below 50ms
Pick-up (Ig) In = Ict 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
Time delay (tg) I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
tg
Ground fault at 1In I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Accuracy: 15% (Ig0.4In) Min. trip time (msec) 20 80 160 260 360 460
20% (Ig0.4In) (I2t off)
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ip)
Ip = In (A) 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
Pre trip alarm Accuracy: 15%
Time delay (tp) tp (sec) 5 10 15 20 40 60 80 120 160

U-Series Air Circuit Breaker_ 17


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| UPR-1D-GT |

Overload protection Event recording


- Long time delay - Records events of device related to
Short circuit protection setting change, operation and state
- Short time delay, instantaneous trip change (Max. up to 10)
- I2t on/off optional (for STD) Pre trip alarm
Ground fault protection - Prevent unnecessary over load trip
- I t on/off optional
2 according to rated current (In)

Realization of protective Field test


coordination by ZSI (Zone selective - Simulation of long time, short time,
interlocking) instantaneous delay

Fault recording 4a DO (Digital output)


-R
 ecords max. up to 10 fault information Communication: Modbus-RTU/RS-485
about fault type, fault phase, fault Earth leakage trip (Optional)
valve, occurrence time of fault

Characteristic

Ir: Long time current setting


Ir tr: Long time tripping delay setting
IP Isd: Short time current setting
tr
tsd: Short time tripping delay setting
Tp Ii: Instantaneous current setting
I2t on tg: Ground fault tripping delay setting
Isd
Ig I2t on Ig: Ground fault current setting
tsd
tg tp: Pre-trip alarm delay setting
Ip: Pre-trip alarm current setting
I2t off Ii
I2t off

Protection

In = Ict (A) 0.5 0.63 0.7 0.8 0.9 1


Current setting (Ir)
Ir = In (A) 0.8 0.83 0.85 0.88 0.9 0.93 0.95 0.98 1 Non
Long time Time delay (tr) tr at (1.5Ir) (sec) 10.4 26.1 41.7 52 104 208 312 417 521 626
Accuracy: 15% tr at (6.0Ir) (sec) 0.5 1.25 2 2.5 5 10 15 20 25 30
or below 100ms tr at (7.2Ir) (sec) 0.35 0.86 1.38 1.73 3.45 6.9 10.4 13.8 17.3 20.7
Current setting (Isd) Isd = In (A) 1 1.5 2 2.5 3 4 6 8 10 Non
I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tsd) tsd
Short time I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 10Ir
Min. trip time (msec) 20 80 160 260 360 460
Accuracy: 15% (I t off)
2
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ii) Ii = In (A) 2 3 4 6 8 10 12 15 Non
Instantaneous
Trip time below 50ms
Pick-up (Ig) Ig = Ict 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 1 Non
Time delay (tg) I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
tg
Ground fault at 1In I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Accuracy: 15%(Ig0.4In) Min. trip time (msec) 20 80 160 260 360 460
20%(Ig0.4In) (I t off)
2
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ip) Ip = In (A) 0.6 0.65 0.7 0.75 0.8 0.85 0.9 0.95 1 Non
Pre trip alarm Time delay (Tp)
tp (sec) 5 10 15 20 40 60 80 120 160
Accuracy: 15%
Current setting (In) In (A) 0.5 1 2 3 5 10 20 30 Non
Earth leakage 140 230 350 800 950 80 120 160
Time delay (t) Alarm time (msec)
(optional) t
Accuracy: 15% or below 40ms Trip time (msec) 60 140 230 350 800

18
ACB

| UPR-1S-AL |

Overload protection
- Long time delay
Short circuit protection
- Short time delay, instantaneous trip
- I2t on/off optional (for STD)
Ground fault protection
- I2t on/off optional (for STD)
Self power
1a DO (Digital output)

Characteristic

Ir: Long time current setting


Ir tr: Long time tripping delay setting
Isd: Short time current setting
tr tsd: Short time tripping delay setting
Ii: Instantaneous current setting

I2t on
Isd
tsd

I2t off Ii

Protection

In = Ict (A) (0.5-1.0) x1% unit, or 1A unit


Current setting (Ir)
Ir = In (A) 0.7 0.8 0.9 1 1.05 1.1 1.15 1.2 1.25 Non
Long time Time delay (tr) tr at (1.05Ir) (sec) 20 30 40 50 60 70 80 100 120
Accuracy: 15% tr at (1.2Ir) (sec) 10 15 20 25 30 35 40 50 60
or below 100ms tr at (3Ir) (sec) 0.99 1.49 1.99 2.48 2.98 3.48 3.97 4.97 5.96
Current setting (Isd) Isd = In (A) 1 1.5 2 2.5 3 3.5 4 4.5 5 Non
I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tsd) tsd
Short time I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 10Ir
Accuracy: 15% Min. trip time (msec) 20 80 160 260 360 460
(I2t off)
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ii) Ii = In (A) 2 3 4 6 8 10 12 15 Non
Instantaneous
Trip time below 50ms

U-Series Air Circuit Breaker_ 19


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| UPR-2S-AS |

Overload protection Event recording


- Long time delay - Records events of device related to
Short circuit protection setting change, operation and state
- Short time delay, instantaneous trip change (Max. up to 10)
- I2t on/off optional (for STD) Pre trip alarm
Realization of protective - Prevent unnecessary over load trip
coordination by ZSI (Zone selective according to rated current (In)
interlocking) Field test
Fault recording - Simulation of long time, short time,
-R
 ecords max. up to 10 fault information instantaneous delay
about fault type, fault phase, fault 3a DO (Digital output)
valve, occurrence time of fault

Characteristic

Ir: Long time current setting


Ir tr: Long time tripping delay setting
IP Isd: Short time current setting
tr tsd: Short time tripping delay setting
Tp Ii: Instantaneous current setting
I2t on tp: Pre-trip alarm delay setting
Isd
Ip: Pre-trip alarm current setting
tsd

I2t off Ii

Protection

In = Ict (A) (0.5-1.0) x1% unit, or 1A unit


Current setting (Ir)
Ir = In (A) 0.7 0.8 0.9 1 1.05 1.1 1.15 1.2 1.25 Non
Long time Time delay (tr) tr at (1.05Ir) (sec) 20 30 40 50 60 70 80 100 120
Accuracy: 15% tr at (1.2Ir) (sec) 10 15 20 25 30 35 40 50 60
or below 100ms tr at (3Ir) (sec) 0.99 1.49 1.99 2.48 2.98 3.48 3.97 4.97 5.96
Current setting (Isd) Isd = In (A) 1 1.5 2 2.5 3 3.5 4 4.5 5 Non
I2t off (sec) 0.05 0.1 0.2 0.3 0.4 0.5
Time delay (tsd) tsd
Short time I2t on (sec) 0.05 0.1 0.2 0.3 0.4 0.5
at 10Ir
Accuracy: 20% Min. trip time (msec) 20 80 160 260 360 460
(I2t off)
Max. trip time (msec) 80 140 240 340 440 540
Current setting (Ii) Ii = In (A) 2 3 4 6 8 10 12 15 Non
Instantaneous
Trip time below 50ms
Current setting (Ip) Ip = In (A) 0.7 0.75 0.8 0.85 0.9 0.95 1 1.05 1.1 Non
Ground fault Time delay (Tp)
tp (sec) 1 5 10 15 20 25 30 35 40
Accuracy: 15%

20
ACB

| Operation characteristics |

Long time delay (LTD)


Standard current setting
L type
- The scale is marked as magnification of [In].
- Setting range: (Non, 0.8, 0.83, 0.85, 0.88, 0.9, 0.93, 0.95, 0.98, 1.0)In (10 modes)
- No protection in case of non setting of [Ir].
- The breaker is not tripped below 105% of [Ir], and tripped at 120%.
t S type
t
- Setting range: (Non, 0.7, 0.8, 0.9, 1.0, 1.05, 1.1, 1.15, 1.2, 1.25 )In (8 modes)
Ir
- The breaker is tripped above 100% of [Ir].
tr
Time delay setting
L type Ig2t on
- Standard operating time (sec) is based Ig2on the time of 600%[Ir] with inverse time operation.
t off
- Setting range: 0.5, 1.25,Ig2, 2.5, 5, 10, 15, 20, 25, 30sec (10 modes)
t - The breaker is tripped
t at 15% of setting time.
S type Tg
Ir I I
- Standard operating time (sec) is based on the time of 120%[Ir] with inverse time operation.
tr
- Setting range: 10, 15, 20, 25, 30, 35, 40, 50, 60sec (9 modes)
- The breaker is tripped at 15% of setting
Ig2t ontime.
t t t t Ig2t off
Ig
Ir Standard current setting
Short time delay (STD)
tr L type Tg
I - The scale is marked as magnification of [In]. I
I2t on Ig2t on
- Setting range: (Non, 1, 1.5, 2, 2.5, 3, 4, 6, 8, 10)In (10 modes)
S type Ig2t off
I2t off Ig I n
Isd - The scale is marked as magnification of [In].
Tsd
t - Setting range: (Non,
t 1, 1.5,T2,g 2.5, 3, 3.5, 4, 4.5, 5)In (10 modes)
T
I I Time delay setting I I
L type
- Standard operating time (msec) is based on the time of 120%[Isd] with definite time operation.
I2t on
- Setting range: 50, 100, 200, 300, 400, 500msec (6 modes)
t I2t off t curveIapplied
- 1000% of inverse time n in case of inverse time (I2t on) setting.
Isd S type
t Tsd t
- Standard operating time (msec) is based on the time of 120%[Isd] with definite time operation.
T
- The range of set time is 50, 100, 200, 300, 400, 500msec (6 step).
I I
I2t on - 500% of inverse time curve applied in case of inverse time (I2t on) setting.

I2t off I n
Isd Tp(S type)
Tsd
Ip
Instantaneous trip (INST)
Standard current setting T
t Ii I - The scale is markedt as magnification of [In]. I
Tp
I - Setting range: (Non, 2, 3, 4, 6, 8, 10, 12, 15)In (9I modes)
- No protection in case of non setting of [Ii].

Time delay setting


Tp(S type)
- Total breaking time is below 50ms.
t t
Ip

Ii
Tp
I I
Tp(S type)
Ip

Ii
Tp
I I

U-Series Air Circuit Breaker_ 21


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| Operation characteristics |

Ground fault trip (GFT)


Standard current setting
L type
- The scale is marked as magnification of OCR rated primary current [ICT].
- Setting range: (Non, 0.1, 0.2, 0.3, 0.4, 0.5, 0.6, 0.7, 0.8, 1.0)[ICT] (10 modes)

Time delay setting


L type
t
- Standard operating time (msec) is based on the time of 120%[Ig] with definite time operation.
- Setting range: 50, 100, 200, 300, 400, 500msec (6 modes)
- Inverse time operated with 100% of [Ict] standard in case of [I2t on] setting.
- The breaker is tripped at 15% of setting time.
Ig2t on

Ig2t off
Ig
t
Tg
I

Ig2t on

tt Ig Ig2t off

Earth leakage trip (ELT)


Standard current setting
Tg L type
I - The scale is marked as magnification of OCR rated primary current [ZCT].
Ig2t on - Setting range: (Non, 0.5, 1, 2, 3, 5, 10, 20, 30[A]) (9 modes)

Ig I n Ig2t off Time delay setting


L type
t
TT
g
- Settings within its alarm range will prevent its breaker from tripping but activating its alarm.
II - Trip time: 60, 140, 230, 350, 800msec (5 modes)
- Alarm time: 140, 230, 350, 800, 950msec (5 modes)

t I n

t
T
I

I n Tp(S type)

Ip
T Standard current setting
tPre-trip alarm (PTA)
Tp I L type
I - The scale is marked as magnification of [In] with definite time operation.
- Setting range: (Non, 0.6, 0.65, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0)In (10 modes)
S type
Tp(S type) - The scale is marked as magnification of [In] with inverse time operation.
t Ip - Setting range: (Non, 0.7, 0.75, 0.8, 0.85, 0.9, 0.95, 1.0, 1.05, 1.1)In (10 modes)

Time delay setting


Tp L type
I - Standard operating time (sec) is based on the time of 100%[Ip].
- Setting range: 5, 10, 15, 20, 40, 60, 80, 120, 160, 200sec (10 modes)
Tp(S type)
S Type
Ip - Standard operating time (sec) is based on the time of 120%[Ip].
- Setting range: 1, 5, 10, 15, 20, 25, 30, 35, 40sec (9 modes)
Tp
I

22
ACB

| Circuit diagrams |

UPR-1L-GL

NCT
k

R S T 21 29 30

R S T N L/S
I/G
NCT NCT
1 2

UPR-1L-GL

Rn Sn Tn Nn Ac A C TN T P
CT3
TP
CT2
MHT
CT1
TN

1a for MCR

Rn Sn Tn 22

UPR-2L-GS
AC,DC100-250V S0 - S2
Source
NCT + -
k

R S T 21 23 29 30 19

R S T N L PT NCT NCT S2
1 2

UPR-2L-GS

ZO ZO
Rn Sn Tn Nn Ac S/I G/E ZI
1
ZI
2 1 2
A C TN TP S 0
CT3
TP
CT2
MHT
CT1
TN

1a for MCR

Rn Sn Tn 22 24 26 31 32 33 34 20

+ - + -
In Out
ZSI

U-Series Air Circuit Breaker_ 23


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| Circuit diagrams |

UPR-1D-GT
AC,DC100-250V S0 - S2
Source
ZCT NCT + -
k k

R S T 21 23 27 28 29 30 19

R S T N L P/T ELT ELT NCT NCT S2


1 2 1 2

UPR-1D-GT

Rn Sn Tn Nn Ac S/I G/E ZI ZI ZO ZO COM COM A C TN TP S 0


1 2 1 2
CT3
TP
CT2
MHT
CT1
TN

1a for
MCR
Rn Sn Tn 22 24 26 31 32 33 34 35 36 20

+ - + - + -
In Out Communication
ZSI

UPR-2L-GM
AC,DC100-250V S0 - S2
Source
NCT + -
k

R S T 21 23 29 30 19

R S T N L/S PT NCT NCT S2


I/G 1 2

UPR-2L-GM

Rn Sn Tn Nn Ac1 Ac2 L/S ZI


I/G 1
ZI
2
ZO ZO
1 2 A C TN TP S 0
CT3
TP
CT2
MHT
CT1
TN

1a for MCR

Rn Sn Tn 22 24 26 31 32 33 34 20

+ - + -
In Out
ZSI

24
ACB

UPR-1S-AL

R S T 21

R S T L/
N SI

UPR-1S-AL

Rn Sn Tn Nn Ac A C TN T P
CT3
TP
CT2
MHT
CT1
TN

1a for MCR

Rn Sn Tn 22

UPR-2S-AS
AC,DC100-250V S 0 - S2

Source

+ -

R S T 21 23 19

R S T N L PT S2

UPR-2S-AS

Rn Sn Tn Nn Ac S/I ZI ZI ZO ZO A C TN TP S 0
CT3 1 2 1 2

TP
CT2
MHT
CT1
TN

1a for MCR

Rn Sn Tn 22 24 31 32 33 34 20

+ - + -
In Out
ZSI

U-Series Air Circuit Breaker_ 25


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| Characteristic curves |

General feeder

4
3
Hour

2
1
50
40
30
20
10
8
Minute

6
5
4
3

2

1
50
40
30
Operating time

20

10
8
6
5
4
3
2

1
0.8
0.6
0.5 500ms 500ms
0.4
Second

0.3
0.2

0.1
0.08
0.06 50ms 50ms
0.0
0.05
0.04
0.03
0.02

0.01
0.008
0.006
0.005
1000

1500

2000
2500
3000
100

100
125
150

200
250
300

400
500
600
700
800
900
10

15

20

30

40
50
60
70
80
90

60
70
80
90
7
8
9

Percent for rated primary current of OCR [ICT] Percent for base current of OCR [Io]

Long time delay current setting range Instantaneous tripping current setting range Pre-trip alarm current setting range
Short time delay current setting range Ground fault trip current setting range

26
ACB

Generator

4
3
Hour

1
50
40
30
20

10
8
Minute

6
5
4
3
2

1
50
40
30
Operating time

20

10
8
6
5
4
3
2

1
0.8
0.6
0.5 500ms
0.4
Second

0.3
0.2

0.1
0.08
0.06
0.05
0.0
50ms
0.04
0.03
0.02

0.01
0.008
0.006
0.005
1000

1500

2000
2500
3000
100
125
150

200
250
300

400
500
600
700
800
900
10

15

20

30

40
50
60
70
80
90
7
8
9

Percent for base current of OCR [Io]

Long time delay current setting range Instantaneous tripping current setting range
Short time delay current setting range Pre-trip alarm current setting range

U-Series Air Circuit Breaker_ 27


U-Series / Air Circuit Breaker

Protection Trip Relay (OCR)

| Zone selective interlock function |


Zone selective interlocking drops delay time that eliminates faults for breakers.
It minimizes the shock that all kinds of electric machinery get under fault conditions.

Example

In case of that short time-delay or ground fault accident occurs at ZSI built in system, the breaker at accident site
sends ZSI signal to halt upstream breakers operation.
To eliminate a breakdown, trip relay of ACB at accident site activates trip operation without time delay.

The
 upstream breaker that received ZSI signal adhere to pre-set short time-delay or ground fault time delay for
protective coordination in the system. However upstream breaker that did not receive its signal will trip instantaneously.
For ordinary ZSI operation, it should arrange operation time accordingly so that downstream circuit breakers will
react before upstream ones under overcurrent/short time delay/ground fault situations.
ZSI connecting line needs to be maximum 3m.

ACB 1
Out
Zone 1 In

ACB 2-1 ACB 2-2


Out
Zone 2 Fault A
In

ACB 3-1 ACB 3-2 ACB 3-N


Zone 3 Out Out
Fault B
Out

In In In

ZSI connecting

28
ACB

| System diagram |

R S T N

ACB trip
ACB

Display
(LCD, LED)
MHT
Trip
Rogowski Relay operation
CT Measurement
part selection

PTA contact
MCU
processing
LTD contact

External
contact STD/INST contact

GFT contact
Power
CT Self power COMMON contact

Trip relay
ZSI output +
ZSI output -
ZSI
ZSI input +
ZSI input -

ZCT Earth RS-485 +


leakage COMM.
RS-485 -

SMPS Test
110V - 220V power terminal

| Communication function |
Modbus-RTU / RS-485
SCADA system
Operation mode: Differential
Distance: Max.1.2km
Modbus/RS-485
Cable: RS-485 shielded twist 2-pair cable
Baud rate: 9,600, 19,200, 38,400 bps
Transmission method: Half-duplex
Termination: 150

U-Series Air Circuit Breaker_ 29