#61-497 Understand and follow operating instructions carefully. Use the meter
#61-498 only as specified in this manual; otherwise, the protection provided by
the meter may be impaired.
WARNING
Digital Multimeter To avoid possible electric shock, personal injury or death, follow these
Instruction Manual guidelines:
Do not use if meter appears damaged. Visually inspect the meter to
ensure case is not cracked and back case is securely in place.
Inspect and replace leads if insulation is damaged, metal is exposed,
or probes are cracked. Pay particular attention to the insulation
surrounding the connectors.
Do not use meter if it operates abnormally as protection maybe impaired.
Do not use during electrical storms or in wet weather.
Do not use around explosive gas, dust, or vapor.
HFR RS232
MAX-MIN
Do not apply more than the rated voltage to the meter.
Do not use without the battery and the back case properly installed.
ACDC LV
AutoPeak HOLD FH AVG
AC+DC
mVAF
GFC%
kMHz
Unsafe Voltage
STORE RECALL dB LOG RATE
To alert you to the presence of a potentially hazardous voltage, when the MAX MIN AVG SETUP dBm DATA LOG
mV A
V Hz%
OFF CF
3 Rotary Switch
4 A Input
Hz C
A mA COM V
600V
5 V, , , HZ, C
Input
CAT IV
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
6 Common Input
7 mA Input
3 4
Making Basic Measurements High Frequency Reject mode
The HFR mode makes the voltage pass through a low pass filter to
Preparation and Caution Before Measurement reject the high frequency. The 3dB point of the low pass filter is 800
: Observe the rules of Warnings and Cautions Hz. When the rotary switch is in V, mV position, the HFR mode can be
used. To use HFR mode, press the HFR button.
When connecting the test leads to the DUT (Device Under Test) connect Measuring Resistance / Continuity / Diode Capacitance
the common (mA) test lead before connecting the live lead. When
removing the test leads remove the live test lead before removing the AUTO 1 2
4 Press 2 Sec.
5
AC
AUTO TEST
RS232
HFR
V ACDC LV MAX-MIN
AutoPeak HOLD FH AVG
AC+DC V 1 2 3 4
mVAF
GFC%
AUTO TEST
kMHz
DC
AUTO TEST RANGE HFR EBTER A-HOLD mV A
V
V Hz%
OFF CF
mV +
~ mV A Hz C
A mA COM V
V Hz%
V
600V
CAT IV
1000V
OFF CF
MAX
~ MAX
10A
FUSED
mA
FUSED
CAT III
+ Hz C
Press the function button to select the measuring function.
(/ / / )
~ A mA COM V
+ MAX
10A
MAX
mA
FUSED
600V
CAT IV
1000V
CAT III
Testing Continuity
FUSED
s
RS232
HFR
ACDC LV MAX-MIN
FH AVG
V V
AutoPeak HOLD
kHz AC+DC
mVAF
GFC%
kMHz
PRESS
STORE RECALL dB LOG RATE
MAX MIN AVG SETUP dBm DATA LOG
+ +
RANGE HFR EBTER A-HOLD
%
DIGIT CANCEL P-HOLD
kHz
mV A
V Hz%
Hz%
OFF CF
Hz C
~ A mA COM V
+ MAX
MAX
mA
600V
CAT IV
1000V
CAT III
+
10A FUSED
FUSED
Measuring Temperature C / F
AutoPeak HOLD FH AVG
AC+DC
mVAF
GFC%
kMHz
RS232
HFR
ACDC LV MAX-MIN
AutoPeak HOLD FH AVG
mV A AC+DC
DISCONNECT
V Hz% A mVAF C
GFC%
OFF CF kMHz
STORE RECALL dB LOG RATE
MAX MIN AVG SETUP dBm DATA LOG
RS232
HFR
ACDC LV MAX-MIN
AutoPeak HOLD FH AVG RANGE HFR EBTER A-HOLD
AC+DC
mVAF CF C
GFC%
kMHz DIGIT CANCEL P-HOLD
Hz C
+
STORE RECALL dB LOG RATE PRESS
A mA COM V MAX MIN AVG SETUP dBm DATA LOG
mV A F
600V RANGE HFR EBTER A-HOLD
MAX
CAT IV
1000V V Hz%
CAT III
MAX mA
10A FUSED
FUSED OFF CF
mV A
DISCONNECT
V Hz% A Sensor K Type
OFF CF
Hz C
A mA COM V Vent
or
Pipe
600V
CAT IV
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
+
Hz C
+ A mA COM V
600V
CAT IV
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
V V
STORE RECALL dB LOG RATE STORE RECALL dB LOG RATE
MAX MIN AVG SETUP dBm DATA LOG MAX MIN AVG SETUP dBm DATA LOG MIN MAX
AUTO AUTO
V
STORE RECALL dB LOG RATE STORE RECALL dB LOG RATE
Peak Hold AC Peak Hold AC
MAX MIN AVG SETUP dBm DATA LOG DIGIT MAX MIN AVG SETUP dBm DATA LOG
V P-Hold V
Press
Press the DIGIT button to select DIGIT
the display digit.
Buttons
ENTER
ENTER: Enter the Sub-function.
9 10
1. Store and Recall 2. MAX / MIN / AVG
PRESS ENTER
DC Cancel
ENTER
V
DC DC
V V
STORE
STORE
MIN
STORE DC
V
PRESS
MAX MIN AVG
DC ENTER
DC
V V
The MAX/MIN/AVG mode records the minimum and maximum input
RECALL
values. When the inputs go below the recorded minimum value
RECALL or above the recorded maximum value, the meter records the new
Last Next value. The MAX/MIN/AVG mode can also calculate the average of the
Data Data
Press Press maximum value and the minimum value.
CANCEL
DC
V
The store function records the input values to memory and recalls
them from memory. The maximum recorded records in memory
are 1000.
11 12
3. dB and dBm (ACV / ACmV only) 4. Relative mode
PRESS
PRESS AUTO
V
AUTO
kHz
AUTO AC AC
dB ENTER
AC AC V V
ENTER
V V
dB dB
dB
dBm
dB PRESS
dBm PRESS
mV A mV A
V Hz% V Hz%
OFF CF OFF CF
Hz C CANCEL Hz C
A mA COM V A mA COM V
AUTO
PRESS dB
600V 600V
AC
CAT IV CAT IV
1000V 1000V
MAX CAT III MAX CAT III
MAX mA MAX mA
10A FUSED 10A FUSED
FUSED FUSED
V
CANCEL
dBm AC 2V AC 3V
dBm PRESS
VAC
dB = 20 log
1
VAC mV A
dBm = 20 log
V Hz%
OFF CF
0.7746
Hz C
A mA COM V
600V
CAT IV
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
AC 3V
In the relative mode, the meter records the current input value as
reference and appears on the upper display. The after input values
will calculate the difference ( ) of the reference value and the input
value or the difference percent (%) of the reference value and the
input value.
13 14
5. SETUP Option 5.4 HAZARD
Press or to change the meter setting. PRESS
SETUP
SETUP DC DC
V ENTER V
Setup the APO time from 1 to 60 minutes or OFF. LOG RATE LOG RATE
SETUP
SETUP SETUP
SETUP
LOG LOG
PRESS RATE RATE
5.3 Back Light Auto OFF PRESS
CANCEL
SETUP
SETUP DC
V
LOG RATE
SETUP
LOG
SETUP RATE
20min
AUTOTEST
AC
V
OFF
Auto Backlight
The backlight is automatically turned on in dark environments.
AUTO
BACKLIT
CAUTION
AUTO AUTO
Use only a fuse with the amperage, interrupt, voltage and speed
rating specified.
K K Fuse rating: 440mA,1000V IR 10KA Fuse (size 35 x 10mm)
11A 1000V IR 20KA Fuse (size 38 x 10mm)
To avoid a false reading, replace the batteries as soon as the low
battery indicator appears.
BUZZER 1.5V x 4 alkaline batteries.
The meter beeps once for every valid key-press, and beeps twice for
every invalid key-press. Maintenance
Power On Options Clean the case with a damp cloth and mild detergent. Do not use
Press the button while turning the meter on from OFF position. abrasives or solvents.
Cancel button : Clear all stored data Service and Replacement Parts
Range button : Display LCD test frame No user-serviceable parts.
Function button : Default C / F reading For replacement parts or to inquire about service information, contact
HFR button : Display firmware version IDEAL INDUSTRIES, INC. at 1-877-201-9005 or visit our website @
A-HOLD button : Disable AUTO BACKLIT www.testersandmeters.com.
17 18
Specifications Compliance to EN 61557 : IEC61557-1, IEC61557-2,
IEC61557-4, IEC61557-10
General Specifications
Weight: (630g) including battery.
Maximum voltage applied 1000V ac rms or dc
Dimensions (W x H x D) 95mm x 207mm x 52mm with holster.
to any terminal:
Accessories: Battery (installed), Test leads and user
Display 4000/40000 counts for 61-497
manual. (The probe assembly provided with
10000/100000 counts for 61-498
the product is for use with this meter only)
Polarity Indication: OL
Power Requirements: 1.5V x 4 IEC LR6 or AA size.
Batteries Life: 100 hours
Pollution degree: 2
Low Batteries Indication: is displayed when the batteries voltage
EMC EN 61326-1
drops below operating voltage
Shock vibration: Sinusoidal vibration per MIL-T- 28800E
Low battery voltage: Approx. 4.5V
(5 ~ 55 Hz, 3g maximum).
AUto Power Off: Default 30 minutes
Drop Protection 4 ft. drop to hardwood on concrete floor.
Operating Ambient: Non-condensing 10C
Indoor Use.
11C ~ 30C ( 80% RH),
30C ~ 40C ( 75% RH),
40C ~ 50C ( 45% RH), Electrical Specifications
Accuracy is (% reading + number of digits) at 23C 5C
Storage Temperature: -20C to 60C, 0 to 80% R.H.
< 80%RH.
(batteries not fitted)
Temperature oefficient: 0.15 x (Spec. Accy) / C, < 18C or > 28C (1) Voltage
Measure Samples 3 times per second normal
61-497
Altitude 6561.7 ft. (2000m)
Range Frequency Accuracy
Safety Complies with EN61010-1, UL61010-1, 40.000mVDC (0.040% + 40d)
IEC61010-1, CAT IV 600V, CAT III 1000V
400.00mVDC (0.035% + 20d)
4.0000VDC
40.000VDC
(0.03% + 20d)
Equipment protected by double insulation. 400.00VDC
1000.0VDC
Instrument has been evaluated and complies with insulation
(overvoltage) catergory IV. Pollution degree 2 in accordance with 40Hz ~ 65Hz (1.00% + 50d) [1]
40.000mVAC
IEC-644. Indoor use. 400.00mVAC
66Hz ~ 1KHz (3.00% + 50d) [1]
1.01KHz ~ 3KHz (5.00% + 50d) [2]
CAT Application FIeld
4.0000VAC 40Hz ~ 45Hz (1.50% + 50d) [1]
I The circuits not connected to mains 40.000VAC
46Hz ~ 65Hz (0.70% + 50d) [1]
400.00VAC
II The circuits directly connected to
1000.0VAC 66Hz ~ 1KHz (1.50% + 50d) [1]
Low-voltage installation
1.01KHz ~ 10KHz (3.00% + 50d) [2]
III The building installation
4.0000VAC
10.01KHz ~ 50KHz (5.00% + 50d) [3]
IV The source of the Low-voltage installation 40.000VAC
50.01KHz ~ 100KHz (10.0% + 50d) [3]
19 20
61-498 (2) Current
Range Frequency Accuracy 61-497
100.000mVDC (0.025% + 40d) Range Frequency Accuracy
1000.00mVDC (0.020% + 20d) 40.000mADC
(0.2% + 40d)
10.0000VDC 400.00mADC
100.000VDC (0.015% + 20d) 4.0000ADC
1000.00mVDC (0.2% + 80d)
10.000ADC
40Hz ~ 65Hz (0.70% + 50d) [1] 40.000mAAC 40Hz ~ 65Hz (0.8% + 80d) [1]
100.000mVAC 400.00mAAC
66Hz ~ 1KHz (1.50% + 50d) [1]
1000.00mVAC 4.0000ADC 66Hz ~ 1KHz (3.0% + 80d) [1]
1.01KHz ~ 3KHz (3.00% + 50d) [2] 10.000AAC
40Hz ~ 45Hz (1.00% + 50d) [1] 61-498
10.0000VAC
100.000VAC 46Hz ~ 65Hz (0.40% + 50d) [1] Range Frequency Accuracy
1000.00VAC
66Hz ~ 1KHz (1.00% + 50d) [1] 10.0000mADC
(0.1% + 40d)
1.01KHz ~ 10KHz (2.00% + 50d) [1] 100.000mADC
10.0000VAC 10.01KHz ~ 20KHz (3.00% + 50d) [2] 10.0000ADC (0.1% + 80d)
100.000VAC 20.01KHz ~ 50KHz (5.00% + 50d) [3] 10.0000mAAC 40Hz ~ 65Hz (0.7% + 80d) [1]
100.000mAAC
50.01KHz ~ 100KHz (10.0% + 50d) [3] 10.0000AAC 66Hz ~ 1KHz (2.0% + 80d)[1]
[1]
Below 5% of range, add 70 counts. Below 45Hz, < 50 dgt rolling. [1]
Below 5% of range, add 70 counts. Below 45Hz, < 50dgt rolling.
[2]
Below 5% of range, add 150 counts.
[3]
Below 5% of range, add 350 counts. Equipped with High Energy Fuse.
Input Protection: 1000VDC or 1000VAC rms Input Protection: 40mA, 1000V IR 10KA fuse for mA input.
11A, 1000V IR 20KA fuse for A input.
Bandwidth: 40Hz ~ 100KHz
Bandwidth: 40Hz ~ 1KHz
Minimum Resolution: 1V in the 100mV range and the 40mV range.
1V in the 40mV range for 61-497,
Input Impedance: 10M, <100pF Minimum Resolution:
0.1A in the 10mA range for 61-498.
CMRR / NMRR: VAC : CMRR > 60dB at DC, 50Hz / 60Hz Maximum Measuring 3 minutes at A input, 10 minutes at mA input.
(Common Mode VDC : CMRR > 100dB at DC, 50Hz / 60Hz Time: Rest time is 20 minutes minimum.
Rejection Ratio) NMRR > 50dB at DC, 50Hz / 60Hz
(Normal Mode AC Conversion Type: Converstion type and additional specifications are same as
Rejection Radio voltage.
AC Conversion Type: AC conversions are ac-coupled, true rms responding,
Calibrated to the sine wave input. (3) Peak Hold
For non-sine wave add the following Crest Factor conditions:
For Crest Factor of 1.4 to 2.0, add 1.0% to accuracy. Specified accuracy (3.0% + 100d) up to 50000 count (full range)
For Crest Factor of 2.0 to 2.5, add 2.5% to accuracy. range.
For Crest Factor of 2.5 to 3.0, add 4.0% to accuracy.
AC + DC Accuracy: Add 1.0% to accuracy.
HFR Accuracy: Add 1.0% to accuracy at 40Hz ~ 400Hz
The cut-off frequency
of of the High Fre- 800Hz (-3dB)
quency Reject:
dB/dBm: 60dBm
For best measurements, use the REL function to
Note:
compensate for offsets.
21 22
(4) Resistance (6) Diode Test
61-497 61-497
Range Resolution Accuracy Range Resolution Accuracy
400.00 0.01 2.000V 1mV (1.5% + 2d)
4.0000K 0.1 (0.2% + 30d) 61-498
40.000K 1 Range Resolution Accuracy
400.00K 10 (0.3% + 30d) 0.400V ~ 0.800V 1mV (1.5% + 2d)
4.0000M 100 (1.0% + 30d) [1] Input Protection: 1000VDC or 1000VAC rms
40.00M 10K (1.5% + 30d) [1] Maximum Open Circuit Voltage: Approximate 2.5V
61-498 Maximum Test Current: Approximate 0.5mA
25
Lea primeramente: Informacin de seguridad
#61-497 Asegrese de entender y seguir cuidadosamente las instrucciones de operacin.
#61-498 Use el instrumento slo como se especifica en este manual. De lo contrario, la
proteccin que proporciona el mismo puede reducirse.
ADVERTENCIA
MULTMETRO DIGITAL Para evitar posibles riesgos de electrocucin, lesiones o la muerte, siga estas
Manual de Instrucciones pautas:
No use el instrumento si el mismo parece estar daado. Inspeccinelo
visualmente para asegurarse de que la cubierta no est fisurada y que la parte
trasera de la misma est firmemente colocada en su sitio.
Inspeccione y reemplace los cables si el aislamiento est daado, hay piezas
metlicas expuestas o las sondas estn fisuradas. Preste particular atencin al
aislamiento de alrededor de los conectores.
No use el instrumento si funciona en forma anormal, porque puede verse
reducida la proteccin.
No use el instrumento durante tormentas elctricas o con tiempo hmedo.
HFR RS232
ACDC LV MAX-MIN
No use el instrumento cerca de gases explosivos, polvo o vapor.
AutoPeak HOLD FH AVG
AC+DC No aplique al instrumento voltajes superiores al nominal.
mVAF No use el instrumento sin la batera ni si la parte posterior de la cubierta no
GFC%
kMHz est instalada correctamente.
STORE RECALL dB LOG RATE
Reemplace las bateras tan pronto aparezca en el indicador de las mismas ,
MAX MIN AVG SETUP dBm DATA LOG a fin de evitar lecturas falsas.
Retire los cables de prueba del circuito antes de desmontar la tapa de las
RANGE HFR EBTER A-HOLD
bateras.
No intente reparar esta unidad puesto que no tiene piezas reparables por el
DIGIT CANCEL P-HOLD
usuario.
PRECAUCIN
Para protegerse, piense La seguridad primero!:
mV A
Los voltajes superiores a 30 VCA o 60 VCC representan un riesgo de
V Hz%
electrocucin, por lo que debe trabajar con precaucin.
OFF CF Use equipos de proteccin personal apropiados, tales como gafas de
seguridad, mscaras faciales, guantes, calzado y/o alfombras aislantes.
Antes de cada uso.
- Realice una prueba de continuidad poniendo en contacto los cables de
prueba para verificar el funcionamiento de la batera y los cables.
- Use el mtodo de seguridad de 3 puntos. (1) Verifique el funcionamiento
del instrumento midiendo un voltaje conocido. (2) Aplique el instrumento
Hz C al circuito en prueba. (3) Vuelva al voltaje conectado conocido para
A mA COM V asegurarse de que el funcionamiento es correcto.
600V
CAT IV
Use las terminales, las funciones y el rango para sus mediciones.
MAX
MAX
mA
1000V
CAT III No se conecte a tierra cuando tome medidas elctricas.
Conecte el cable negro comn a tierra o al neutro antes de aplicar el cable rojo
10A FUSED
FUSED
voltaje (OL) en V, mV. El smbolo se despliega y el indicador de RANGE HFR EBTER A-HOLD 2 Botones
Alto Voltaje se activa.
DIGIT CANCEL P-HOLD
mV A
V Hz%
OFF CF
3 Interruptor
Rotatorio
4 Entrada A
Hz C
A mA COM V
600V
5 V, , , HZ, C
Entrada
CAT IV
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
6 Entrada Comn
7 Entrada mA
29 30
Tomando Mediciones Bsicas Modo de Rechazo de Alta Frecuencia
El modo de Rechazo de Alta Frecuencia (HFR) hace que el voltaje pase
Preparacin y Cautela Antes de la Medicin a travs de un filtro de paso bajo para rechazar la frecuencia alta. El
Observe las reglas de Advertencias y Cautela punto -3dB del filtro de paso bajo es de 800Hz. Se puede usar el modo
HFR cuando el interruptor rotativo est en la posicin V, mV. Para usar
Cuando conecte los cables de prueba al ABP (Aparato Bajo Prueba) el modo HFR, presione el botn HFR.
conecte el cable comn (mA) antes de conectar el cable con corriente. Midiendo Resistencia/ Continuidad / Capacitancia de Diodo
Cuando remueva los cables quite el cable con corriente antes de quitar
AUTO 1 2
el cable comn.
Las figuras en las prximas pginas muestran cmo hacer mediciones AUTO
bsicas.
Midiendo Voltaje CA/CD 3 AUTO TEST 5
AUTO TEST
4 Press 2 Sec.
AC 5
AUTO TEST
RS232
HFR
V ACDC LV MAX-MIN
FH AVG
AutoPeak HOLD
AC+DC
V 1 2 3 4
mVAF
GFC%
AUTO TEST
kMHz
DC
AUTO TEST RANGE HFR EBTER A-HOLD mV A
V Hz%
V
OFF CF
+
Hz C
mV ~ mV A A mA COM V
V Hz%
600V
CAT IV
1000V
MAX CAT III
MAX mA
V
10A FUSED
FUSED
~ OFF CF
+
Presione el botn de funcin para seleccionar la funcin de
+ Hz C medicin. (/ / / )
~ A mA COM V
+ MAX
10A
MAX
mA
FUSED
600V
CAT IV
1000V
CAT III
Probando Continuidad
FUSED
s
RS232
HFR
ACDC LV MAX-MIN
AutoPeak HOLD FH AVG
kHz AC+DC
V V mVAF
GFC%
kMHz
PRESS
STORE RECALL dB LOG RATE
MAX MIN AVG SETUP dBm DATA LOG
+ +
%
DIGIT CANCEL P-HOLD
kHz
mV A
V Hz%
Hz%
OFF CF
Hz C
~ A mA COM V
+ MAX
10A
MAX
mA
FUSED
600V
CAT IV
1000V
CAT III
FUSED
+
Midiendo Corriente CA/CD
Presione el botn de funcin para seleccionar la funcin de medicin
(Periodo/Ciclo de Trabajo).
RS232
HFR
ACDC LV MAX-MIN
Midiendo Temperatura (C / F)
AutoPeak HOLD FH AVG
AC+DC
mVAF
GFC%
kMHz
RS232
HFR
ACDC LV MAX-MIN
AutoPeak HOLD FH AVG
mV A AC+DC
DISCONNECT
V Hz% A mVAF C
GFC%
OFF CF kMHz
STORE RECALL dB LOG RATE
MAX MIN AVG SETUP dBm DATA LOG
RS232
HFR
ACDC LV MAX-MIN
AutoPeak HOLD FH AVG RANGE HFR EBTER A-HOLD
AC+DC
mVAF CF C
GFC%
kMHz DIGIT CANCEL P-HOLD
Hz C
+
STORE RECALL dB LOG RATE PRESS
A mA COM V MAX MIN AVG SETUP dBm DATA LOG
mV A F
600V RANGE HFR EBTER A-HOLD
MAX
CAT IV
1000V V Hz%
CAT III
MAX mA
10A FUSED
FUSED OFF CF
mV A
DISCONNECT
V Hz% A Sensor K Type
OFF CF
Hz C
A mA COM V Vent
or
Pipe
600V
CAT IV
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
+
Hz C
+ A mA COM V
600V
CAT IV
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
Presione el botn de funcin para seleccionar la funcin de medicin Presione el botn de funcin para seleccionar la funcin de medicin
(AC/DC/AC+DC). (C / F)
33 34
DIGITO: DETENCIN de Pico (Solo VAC / AAC)
Presione
Press
AUTO
AUTO Press AUTO kHz
AC
kHz kHz
AUTO
kHz AC AUTO
kHz AC V
AC V AC V Presione
Press
V V
STORE RECALL dB LOG RATE STORE RECALL dB LOG RATE
MAX MIN AVG SETUP dBm DATA LOG MAX MIN AVG SETUP dBm DATA LOG MIN MAX
AUTO AUTO
STORE RECALL dB LOG RATE STORE RECALL dB LOG RATE V
MAX MIN AVG SETUP dBm DATA LOG MAX MIN AVG SETUP dBm DATA LOG Peak Hold AC Peak Hold AC
DIGIT V P-Hold V
DIGIT Presione
Press
Presione el botn DIGIT para seleccionar el dgito de la pantalla.
AUTO DETENCIN:
Press
Presione
Press kHz
AUTO AUTO AC
kHz V V
AUTO
kHz AC AUTO
AUTO HOLD V AC
AC V A-Hold AC V Presione Presione
AUTO HOLD Press Press
V A-Hold V >2525seg.
sec >2525sec
seg.
Botones
ENTRAR
35 36
1. Almacenar y Recordar 2. MAX / MIN / AVG
Presione ENTER
PRESS
DC Cancel
ENTER V
DC DC
V V
STORE
STORE
MIN
STORE DC
V
Presione
PRESS
MAX MIN AVG
DC ENTER
DC
V V
El modo MAX/MIN/AVG graba el valor mnimo y mximo de la
RECALL
entrada. Cuando las entradas bajan por debajo del valor mnimo
RECALL grabado o por encima del valor mximo grabado, el instrumento
Last Next graba el nuevo valor. El modo MAX/MIN/AVG tambin puede calcular
Data Data
Press Press el promedio del valor mximo y el valor mnimo.
CANCEL
DC
V
37 38
3. dB y dBm (Solo en VAC / ACmV) 4. Modo relativo
Presione PRESS
PRESS AUTO
V
AUTO
kHz
AUTO AC AC
dB ENTER
AC AC V V
ENTER
V V
dB dB
dB
dBm
dB Presione
PRESS
dBm Presione
PRESS
mV A mV A
V Hz% V Hz%
OFF CF OFF CF
Hz C CANCEL Hz C
A mA COM V A mA COM V
AUTO
Presione
PRESS dB
600V 600V
AC
CAT IV CAT IV
1000V 1000V
MAX CAT III MAX CAT III
MAX mA MAX mA
10A FUSED 10A FUSED
FUSED FUSED
V
CANCEL
AC 2V AC 3V
dBm
Presione
PRESS
dBm
VAC
dB = 20 log
1
VAC mV A
dBm = 20 log
V Hz%
OFF CF
0.7746
Hz C
A mA COM V
600V
CAT IV
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
AC 3V
39 40
5. Opcin de CONFIGURACIN (SETUP) 5.4 PELIGRO Presione
PRESS
Presionar o cambiando la configuracin del Instrumento
Presione ENTER para guardar la configuracin en la memoria.
Presionar o seleccionar el artculo del Instrumento a configurar.
Presione CANCELAR (CANCEL) para salir de esta funcin. Presione
SETUP PRESS SETUP
SETUP SETUP
5.1 Alarma
Presione Configure la alarma al modo de deteccin de voltaje peligroso
PRESS
( 60VCD o 30VCA) en ENCENDIDO (ON) o APAGADO (OFF).
5.5 REINICIAR
PRESS
SETUP
Presione
PRESS SETUP
SETUP SETUP
5.2 Apagado automtico Restaurar todos los valores a la configuracin por defecto.
SETUP
SETUP PRESS SETUP
5.6 TASA DE REGISTRO
SETUP SETUP Presione
PRESS
DC DC
SETUP
SETUP
V ENTER V
Configure el tiempo de Apagado automtico (APO) desde 1 hasta 60 Presione LOG LOG
PRESS
minutos o APAGADO (OFF).
SETUP
RATE RATE
SETUP SETUP
SETUP Presione
PRESS
CANCEL
5.3 Luz de Fondo Automtico APAGADO (OFF DC
V
SETUP
SETUP
LOG RATE
LOG
RATE
SETUP
SETUP
Configure la tasa de registro desde 0.5 hasta 600 segundos.
41 42
Apagado Automatico Reemplazo de Batera y Fusible
Haga referencia a la siguiente imagen para reemplazar el fusible y
bateras:
20min
AUTOTEST
AC
V
OFF
PRECAUCIN
AUTO AUTO
Use solo un fusible con la clasificacin de amperaje, interrupcin,
voltaje y rapidez especificada.
K K Clasificacin de fusible: 440mA, fusible de 1000V IR 10KA
(tamao 35 x 10mm) 11A,
fusible de 1000V IR 20KA
(tamao 38 x 10mm)
Reemplace las bateras tan pronto aparezca el indicador de bateras
ZUMBADOR con poca carga , a fin de evitar lecturas falsas.
El instrumento pita una vez por cada pulso de botn valido, y pita dos 4 bateras alcalinas de 1.5V
veces por cada pulso de botn no valido..
Opciones de Encendido Mantenimiento
Presione el botn mientras enciende el instrumento desde la posicin Limpie la cubierta con un pao hmedo y un detergente suave. No use
de APAGADO. abrasivos ni solventes.
Botn de Cancelado : Borrar todos los datos almacenados Servicio y piezas de repuesto
Botn de rango : Mostrar marco de prueba de LCD No hay piezas reparables por el usuario.
Botn de funcin : Lectura C / F por defecto Para obtener informacin sobre piezas de repuesto o para averiguar
Botn de HFR : Mostrar la versin de firmware acerca del servicio, comunquese con IDEAL INDUSTRIES, INC. al
Botn A-HOLD : Deshabilitar LUZ DE FONDO AUTOMTICA 1-877-201-9005 o visite nuestro sitio web, www.testersandmeters.com.
43 44
Especificaciones Cumple con EN 61557 : IEC61557-1, IEC61557-2, IEC61557-4,
IEC61557-10
Especificaciones generales
Peso: (630g) incluyendo batera.
Voltaje mximo aplicado 1000V ca rms o cd
Dimensiones (A x A x P) 95mm x 207mm x 52mm con funda.
a cualquier terminal:
Accesorios: Batera (instalada), Cables y manual de
Pantalla 4000/40000 pulsos para el 61-497
usuario. (El conjunto de sonda previsto
10000/100000 pulsos para el 61-498
con este producto son para el uso
Indicacin de Polaridad: Sobrecarga nicamente con este instrumento)
Vida til de la batera: 100 horas Requerimientos de Potencia: 1.5V x 4 tamao IEC LR6 o AA.
Indicacin de bateras Aparece /SYMBOL/ si el voltaje de la batera Grado de contaminacin: 2
con poca carga cae por debajo del voltaje de operacin
EMC 61326-1
Voltaje bajo de batera: Aprox. 4.5V
Shock de vibracin: Vibracin sinusoidal segn MIL-T-
Apagado automtico: Por defecto 30 minutos 28800E (5 ~ 55 Hz, 3g mximo).
Ambiente Operacional: No condensando 10C Proteccin de Cada 4 pies a piso de madera sobre concreto.
11C ~ 30C (80% HR),
Uso en interiores.
30C ~ 40C (75% HR),
40C ~ 50C (45% HR),
Especificaciones Elctricas
Temperatura de almace- -20C a 60c, 0 a 80% H.R. Exactitud es de (% lectura + nmero de dgitos) a 23C 5C <
namiento: (Bateras no instaladas) 80%HR.
Coeficiente de tempera- 0.15 x (Exactitud de la Especificacin) / C,
tura: <18C o >28C (1) Voltaje
Medicin: Toma normal de 3 Muestras por segundo 61-497
Rango Frecuencia Exactitud
Altitud: 6561.7 pies. (2000 m)
40.000mVCD (0.040% + 40d)
Seguridad: Cumple con EN61010-1, UL61010-1,
IEC61010-1, CAT IV 600V, CAT III 1000V 400.00mVCD (0.035% + 20d)
4.0000VCD
40.000VCD
(0.03% + 20d)
400.00VCD
Equipo protegido con aislamiento doble. 1000.0VCD
Este instrumento ha sido evaluado y se comprob que cumple la cat-
40Hz ~ 65Hz (1.00% + 50d) [1]
egora de aislamiento IV (sobrevoltaje). Grado 2 de contaminacin, de 40.000mVCA
acuerdo a IEC-644. Uso en interiores. 66Hz ~ 1KHz (3.00% + 50d) [1]
400.00mVCA
1.01KHz ~ 3KHz (5.00% + 50d) [2]
CAT Campo de Aplicacin
4.0000VCA 40Hz ~ 45Hz (1.50% + 50d) [1]
I El circuito no est conectado a la red 40.000VCA
46Hz ~ 65Hz (0.70% + 50d) [1]
elctrica 400.00VCA
1000.0VCA 66Hz ~ 1KHz (1.50% + 50d) [1]
II El circuito est conectado directamente a
Instalacin de bajo voltaje 1.01KHz ~ 10KHz (3.00% + 50d) [2]
4.0000VCA
III Instalacin en edificio 10.01KHz ~ 50KHz (5.00% + 50d) [3]
40.000VCA
IV La fuente de la instalacin de Bajo voltaje 50.01KHz ~ 100KHz (10.0% + 50d) [3]
45 46
61-498 (2) Corriente
Rango Frecuencia Exactitud 61-497
100.000mVCD (0.025% + 40d) Rango Frecuencia Exactitud
1000.00mVCD (0.020% + 20d)
40.000mACD
(0.2% + 40d)
10.0000VCD 400.00mACD
100.000VCD (0.015% + 20d)
4.0000ACD
1000.00mVCD (0.2% + 80d)
10.000ACD
40Hz ~ 65Hz (0.70% + 50d) [1]
Proteccin de Entrada: 1000VCD o 1000VCA rms Equipado con Fusible de Alta Energa. Fusible de 40mA,
Proteccin de
1000V IR 10KA para entrada de mA. Fusible de 11A, 1000V
Ancho de Banda: 40Hz ~ 100KHz Entrada:
IR 20KA para entrada de A.
Resolucin Mnima: 1V en el rango de 100mV y el rango de 40mV.
Ancho de Banda: 40Hz ~ 1KHz
Impedancia de entrada: 10M, <100pF
1A en el rango de 40mA para el 61-497,
CMRR / NMRR: VCA : CMRR > 60dB a DC, 50Hz / 60Hz Resolucin Mnima:
0.1A en el rango de 10mA para el 61-498.
(Relacin de rechazo VCD : CMRR > 100dB a DC, 50Hz / 60Hz
de modo comn) NMRR > 50dB a DC, 50Hz / 60Hz Tiempo de Medicin 3 minutos en la entrada A, 10 minutos en la entrada mA.
(Relacin de rechazo Mxima: Tiempo de descanso es de 20 minutos mnimos.
de modo comn) Tipo de Conversin Tipo de conversin y especificaciones adicionales son igual
Tipo de Conversin de Las conversiones de CA estn acoplados a la CA, respuestas de CA: al voltaje
CA: rms verdaderas Calibrado a la entrada de onda sinusoidal.
Para las ondas no sinusoidales aadir los siguientes
Factores de Cresta: (3) Detencin de Pico
Para el Factor de Cresta de 1.4 a 2.0, aadir 1.0% a la Exactitud. Exactitud Especificada (3.0% + 100d) hasta 50000 pulsos (rango
Para el Factor de Cresta de 2.0 a 2.5, aadir 2.5% a la Exactitud.
Para el Factor de Cresta de 2.5 a 3.0, aadir 4.0% a la Exactitud. completo) rango.
Exactitud CA + CD: Aadir 1.0% a la Exactitud.
Exactitud HFR: Aadir 1.00% a la Exactitud a 40Hz ~ 400Hz
La frecuencia de corto
de la Alta Frecuencia 800Hz (-3dB)
Rechazo:
dB/dBm: 60dBm
Para las mejores medidas, use la funcin de REL para
Nota:
compensar por los desplazamientos
47 48
(4) Resistencia (6) Prueba de Diodo
61-497 61-497
Rango RESOLUCIN EXACTITUD RANGO RESOLUCIN EXACTITUD
400.00 0.01 2.000V 1mV (1.5% + 2d)
4.0000K 0.1 (0.2% + 30d) 61-498
40.000K 1 RANGO RESOLUCIN EXACTITUD
400.00K 10 (0.3% + 30d) 0.400V ~ 0.800V 1mV (1.5% + 2d)
4.0000M 100 (1.0% + 30d) [1] Proteccin de Entrada: 1000VDC o 1000VCA rms
40.00M 10K (1.5% + 30d) [1] Voltaje Mximo de Circuito Abierto: Aproximadamente 2.5V
61-498 Corriente Mxima de Prueba: Aproximadamente 0.1mA
51 52
Lire dabord : informations de scurit
#61-497 Lire et sassurer davoir compris toutes les instructions de fonctionnement.
#61-498 Nutiliser le multimtre que de la faon spcifie dans le prsent manuel ;
dfaut, la protection offerte par le multimtre pourra tre compromise.
AVERTISSEMENT
MULTIMTRE NUMRIQUE Se conformer aux directives suivantes pour viter tout risque dlectrocution, de
Manuel dinstructions lsions personnelles ou de mort :
Ne pas utiliser le multimtre sil parat endommag. Examiner le multimtre
pour sassurer que son botier nest pas fissur et que sa partie arrire est bien
assujettie.
Inspecter et remplacer les cordons si leur isolation est endommage, le mtal
expos ou les sondes craqueles. Porter une attention particulire lisolant
qui entoure les connecteurs.
Ne pas utiliser le multimtre sil fonctionne de manire anormale, la protection
quil offre pouvant tre compromise.
HFR RS232
ACDC LV MAX-MIN Ne pas utiliser lappareil pendant des orages ou par temps trs humide.
FH AVG
AutoPeak HOLD
AC+DC Ne pas utiliser lappareil en prsence de gaz, poussire ou vapeur explosifs.
mVAF Ne pas soumettre le multimtre une tension suprieure la tension
GFC%
kMHz nominale.
STORE RECALL dB LOG RATE Ne pas utiliser sans la pile ou si larrire du botier nest pas bien mont.
MAX MIN AVG SETUP dBm DATA LOG
Retirer les fils dessai du multimtre avant de retirer le capuchon de pile.
RANGE HFR EBTER A-HOLD Ne pas tenter de rparer cet appareil. Il ne comporte aucune pice rparable
par lutilisateur.
ATTENTION
DIGIT CANCEL P-HOLD
Pour vous protger, ayez le rflexe la scurit dabord .
Les tensions dpassant 30 V CA ou 60 V CC peuvent prsenter un risque
mV A dlectrocution, il faut donc faire preuve de prudence.
V Hz% Utiliser un quipement de protection individuelle appropri, comme lunettes
OFF CF de scurit, masque facial, gants isolants, chaussures isoles, et/ou tapis
isolants.
Avant chaque utilisation :
- Procder un essai de continuit et mettant les fils dessai en contact lun
avec lautre afin de contrler le fonctionnement de la pile et des fils dessai.
- Utiliser la mthode de scurit en 3 points. (1) Vrifier le fonctionnement
du multimtre en mesurant une tension connue. (2) Appliquer le multimtre
Hz C au circuit en cours de contrle. (3) Retourner la tension active connue
A mA COM V pour vrifier le bon fonctionnement.
600V
CAT IV
Utiliser les bonnes bornes fonction et plages pour vos mesures
MAX
10A
MAX
mA
FUSED
1000V
CAT III Ne jamais se mettre la terre quand on procde des mesures lectriques.
FUSED
Connecter le fil commun noir la terre avant dappliquer le fil dessai rouge
sur la tension. Commencer par dconnecter le fil dessai rouge de la tension.
Travailler toujours avec un quipier.
Quand on se sert des sondes, tenir les doigts aussi loin que possible des
pointes de sonde.
53 54
Symboles tels quils apparaissent sur lappareil et le manuel. Description de lappareil
Illustration du panneau avant
Risque dlectrocution 1. Affichage LCD: 4000/40000 units pour le 61-497.
10000/100000 units pour le 61-498.
Voir le manuel dinstructions 2. Boutons-poussoirs.
Mesure de c.c. 3. Interrupteur rotatif pour allumer/teindre et slectionner la fonction.
4. Borne dentre pour A.
Matriel protg par une isolation double ou renforce 5. Borne dentre pour les fonctions V,, @, Hz, C.
6. Borne dentre commune (rfrence de terre).
Batterie
7. Borne dentre pour mA.
Fusible
Terre
Mesure de C.A.
Conforme aux directives de lU.E. HFR RS232
ACDC LV MAX-MIN
AutoPeak HOLD FH AVG
1 Affichage
Ne pas mettre au rebut ou jeter ce produit AC+DC
mVAF
GFC%
kMHz
Tension dangereuse
STORE RECALL dB LOG RATE
Afin de signaler la prsence dune tension potentiellement dangereuse MAX MIN AVG SETUP dBm DATA LOG
mV A
V Hz%
OFF CF
3 Interrupteur rotatif
4 Entre A
Hz C
A mA COM V
600V
5 Entre V, , ,
HZ, C
CAT IV
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
6 Entre commune
7 Entre mA
55 56
Prise de mesures lmentaires Mode de rejet de haute frquence
Le mode RHF achemine la tension travers un filtre passe-bas pour
Prparation et mise en garde avant la mesure rejeter la haute frquence. Le point de 3dB du filtre passe-bas est
: Se conformer aux rgles Avertissements et Mises en garde de 800 Hz. Quand le commutateur rotatif est sur la position V, mV
position, on peut utiliser le mode RHF. Pour utiliser le mode RHF
Quand on connecte les conducteurs dessai au dispositif test, Appuyer sur le bouton HFR.
connecter le conducteur commun (mA) avant de connecter le conducteur Mesure de la rsistance / continuit / capacit de diode
charg. Quand on retire les conducteurs dessai, retirer le conducteur
dessai charg avant de retirer le conducteur dessai commun. AUTO 1 2
mesures lmentaires.
Mesure de la tension c.a./c.c. 3 AUTO TEST 5
AUTO TEST
4 Press 2 Sec.
AC
AUTO TEST
5
RS232
HFR
V ACDC LV MAX-MIN
FH AVG
AutoPeak HOLD
AC+DC
V 1 2 3 4
mVAF
GFC%
AUTO TEST
kMHz
DC
AUTO TEST RANGE HFR EBTER A-HOLD mV A
V Hz%
V
OFF CF
+
Hz C
mV ~ mV A A mA COM V
V Hz%
600V
CAT IV
1000V
MAX CAT III
MAX mA
V
10A FUSED
FUSED
~ OFF CF
+
Appuyer sur le bouton de fonction pour slectionner la
+ Hz C fonction de mesure (/ / / )
~ A mA COM V
+ MAX
10A
MAX
mA
FUSED
600V
CAT IV
1000V
CAT III
Essai de continuit
FUSED
57 58
Test de diode Mesure de la frquence
s
RS232
HFR
MAX-MIN
V V
ACDC LV
AutoPeak HOLD FH AVG
kHz AC+DC
mVAF
GFC%
kMHz
PRESS
STORE RECALL dB LOG RATE
MAX MIN AVG SETUP dBm DATA LOG
+ + %
RANGE HFR EBTER A-HOLD
mV A
V Hz%
Hz%
OFF CF
Hz C
~ A mA COM V
+
+
600V
CAT IV
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
mVAF
GFC%
Measuring Temperature C / F
kMHz
mV A
DISCONNECT
V Hz% A
RS232
HFR
ACDC LV MAX-MIN
OFF CF
AutoPeak HOLD FH AVG
AC+DC
mVAF C
GFC%
kMHz
+ CF
GFC% C
A mA COM V kMHz
F
mV A
DISCONNECT
V Hz% A
OFF CF
Sensor K Type
Hz C
A mA COM V Vent
or
Pipe
600V
CAT IV
1000V
MAX CAT III
MAX mA
Hz C
10A FUSED
FUSED
+ A mA COM V
600V
CAT IV
+
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
AUTO-HOLD : Press
Appuyer
Press kHz
AUTO
AC
AUTO
V
AUTO HOLD kHz
AUTO
kHz AC AUTO V
V AC
AC V A-Hold
AUTO HOLD
AUTO HOLD
AC V Appuyer
Press Appuyer
Press
V A-Hold V 25
>25sec.
sec >25
25 sec.
sec
Boutons
ENTER
ENTER : Saisir la sous-fonction.
CANCEL
CANCEL : Quitter la fonction.
61 62
1. Enregistrer et rappeler 2. MAX / MIN / AVG
Appuyer
PRESS ENTER
DC Cancel
ENTER V
DC DC
V V
STORE
STORE MIN
DC
STORE
V
Appuyer
PRESS MAX MIN AVG
DC ENTER
DC
V V
Le mode MAX/MIN/AVG enregistre les valeurs dentre minimale et
RECALL
maximale. Quand les entres chutent en de de la valeur minimale
RECALL enregistre ou dpasse la valeur maximale enregistre, lappareil
Last Next enregistre la nouvelle valeur. Le mode MAX/MIN/AVG peut galement
Data Data
Press Press calculer la moyenne de la valeur maximale et de la valeur minimale.
CANCEL
DC
V
63 64
3. dB et dBm (c.a. V / c.a. mV uniquement) 4. Mode relatif
Appuyer
PRESS
Appuyer
PRESS AUTO
V
AUTO
kHz
AUTO AC AC
dB ENTER
AC AC V V
ENTER
V V
dB dB
dB
dBm
dB Appuyer
PRESS
dBm Appuyer
PRESS
mV A mV A
V Hz% V Hz%
OFF CF OFF CF
Hz C CANCEL Hz C
A mA COM V A mA COM V
AUTO
Appuyer
PRESS dB
600V 600V
AC
CAT IV CAT IV
1000V 1000V
MAX CAT III MAX CAT III
MAX mA MAX mA
10A FUSED 10A FUSED
FUSED FUSED
V
CANCEL
AC 2V AC 3V
dBm
Appuyer
PRESS
dBm
dBm = 20 log
V Hz%
OFF CF
0.7746
Hz C
A mA COM V
600V
CAT IV
1000V
MAX CAT III
MAX mA
10A FUSED
FUSED
AC 3V
65 66
5. Option de CONFIGURATION (SETUP) 5.4 DANGER
Appuyer
PRESS
Appuyer sur ou pour changer la configuration de lappareil.
Appuyer sur ENTER pour enregistrer la co nFiguration.
Appuyer sur ou pour slectionner larticle de configuration de
lappareil. SETUP
Appuyer
PRESS SETUP
SETUP SETUP
Appuyer sur CANCEL pour quitter cette fonction.
5.1 Avertisseur sonore Rgler lavertisseur sur marche ou arrt du mode de dtection de
Appuyer
tension dangereuse ( 60 Vc.c. ou 30 V c.a.)
PRESS
Appuyer
PRESS
SETUP SETUP
SETUP SETUP
sur ONPRESS
SETUP
Mettre lavertisseur sonoreSETUP
SETUP (marche) ou OFF (arrt).
PRESS SETUP
SETUP
SETUP
5.2 Arrt automatique Remettre toutes les valeurs de configuration sur les valeurs implicites..
DC DC
SETUP
SETUP
V ENTER V
Rgler le temps darrt automatique de 1 60 minutes ou sur OFF Appuyer LOG LOG
PRESS
(arrt).SETUP
RATE RATE
SETUP Appuyer
PRESS
SETUP
SETUP
5.3 Arrt automatique de rtroclairage CANCEL
DC
V
SETUP
SETUP
LOG RATE
LOG
RATE
SETUP
SETUP
Rgler la frquence de consignation entre 0,5 et 600 secondes.
Setup the back light Auto OFF time from 1 to 60 minutes. 5.7 DATALOG (Consignation de donnes)
Le mode de consignation de donnes enregistre les valeurs dentre
successives en mmoire et les rappelle par la suite. Le nombre de
mmoires enregistres est de 20000.
67 68
Arrt automatique Battery and Fuse Replacement
Refer to the following figure to replace the fuse and batteries :
20min
AUTOTEST
AC
V
OFF
Rtroclairage automatique
Le retroclairage sallume automatiquement dans les milieux sombres.
AUTO
BACKLIT
CAUTION
AUTO AUTO
Utiliser uniquement un fusible de la bonne classification en ce qui
concerne lintensit, linterruption, la tension et la vitesse spcifis.
K K Classification de fusible : fusible de 440 mA, 1000 V IR 10 KA
(taille : 35 x 10 mm) fusible de 11 A,
1000 V IR 20 KA (taille 38 x 10 mm)
AVERTISSEUR SONORE Afin dviter les fausses lectures, remplacer les piles ds que le
Lappareil met un bip pour chaque actionnement valide dune touche et tmoin de pile dcharge saffiche.
deux bips pour chaque actionnement non valide. Piles alcalines de 1,5 V x 4
Options dallumage Entretien
Appuyer sur le bouton tout en mettant lappareil en service partir de Nettoyer avec un chiffon humide et un dtergent doux. Ne pas utiliser
la position OFF (arrt). des abrasifs ou des solvants.
Bouton Cancel : Effacer toutes les donnes enregistres Entretien et pice dtaches
Bouton Range : Affiche le cadre dessai LCD Aucune pice entretenir.
Bouton Function : Lecture implicite en C / F En ce qui concerne les pices de rechange ou les renseignements
Bouton HFR : Affiche la version de micro logiciel concernant lentretien, se mettre en rapport avec IDEAL INDUSTRIES,
Bouton A-HOLD : Invalider AUTO BACKLIT (rtroclairage INC. au 1-877-201-9005 ou visiter notre site web :
automatique) www.testersandmeters.com.
69 70
Caractristiques ConFormit avec EN 61557 : IEC61557-1, IEC61557-2,
IEC61557-4, IEC61557-10
Carractristiques gnrales
Poids : (630 g) Pile comprise.
Tension maximales 1000 V c.c. rms ou c.c.
appliqus toute borne: Dimensions (l x L x P) 95 mm x 207 mm x 52 mm avec tui.
Affichage 4000/40000 units pour le 61-497 Accessoires : Exigences Pile (monte), conducteurs dessai et
10000/100000 units pour le 61-498 dalimentation : manuel de lutilisateur. (Lensemble de sonde
fourni avec ce produit ne doit tre utilis
Indication de polarit : OL quavec cet appareil uniquement)
Dure de service des piles : 100 heures Degr de pollution : 1,5V x 4 IEC taille LR6 ou AA.
Tmoin de dcharge de est affich quand la tension des piles EMC 2
piles : chute en de de la tension de service
Vibration dimpact : EN 61326-1
Tension de pile insuffisante : Environ 4,5 V
Protection contre la chute Vibration sinusodale selon MIL-T- 28800E
Arrt automatique : Valeur implicite de 30 minutes (5 ~ 55 Hz, 3 g maximum).
Milieu de fonctionnement : Sans condensation 10C
Utilisation lintrieur. 1,2 m sur bois franc sur sol en bton.
11C ~ 30C (80 % HR),
30C ~ 40C (75 % HR), Indoor Use.
40C ~ 50C (45 % HR),
Caractristiques lectriques
Temprature de rangement : -20C to 60C, 0 80 % H.R.
(piles non montes) La precision est de ( % lecture + nombre de chiffres) 23C 5C <
80 % H.R.
Coefficient de temprature: 0,15 x (Pcis. Spc.) / C, <18C ou > 28C
Mesure Altitude 3 relevs par seconde normal (1) Voltage
Scurit 6561.7 ft. (2000 m) 61-497
1000,00 K 10 (0,3 % + 30 d)
40,00 nF 10 pF (1,2 % + 20 d)
10,0000 M 100 (1,0 % + 30 d) [1]
400,0 nF 100 pF
40,00 M 10 K (1,5 % + 30 d) [1] 0,7 sec.
4,000 F 1 nF
[1]
< 100dgt rolling (0,9 % + 2 d)
40,00 F 10 nF
Protection dentre : 1000 Vc.c. ou 1000 Vc.a. rms 400,0 F 100 nF
Tension maximale de circuit ouvert: Environ 2,5 V
4,000 mF 1 F (1,2 % + 20 d) 3,75 sec.
Couant de test maximal de circuit ouvert: Environ 0,5 mA
40,00 mF 10 F (1,2 % + 40 d) [1]
7,5 sec.
Remarque : Pour les meilleures mesures, utiliser la fonction REL pour compenser les
dcalages. 61-498
(5) Contrle de continuit Plage Rsolution Prcision Temps de mesure
4,000 nF 1 pF (1,2 % + 40 d) [1]
61-497
40,00 nF 10 pF (1,2 % + 20 d)
Plage Rsolution Prcision
400,0 nF 100 pF
400,0 0,1 (0,2 % + 3 d) 0,7 sec.
4,000 F 1 nF
61-498 (0,8 % + 2 d)
40,00 F 10 nF
Plage Rsolution Prcision
400,0 F 100 nF
1000,0 0,1 (0,05 % + 3 d)
4,000 mF 1 F (1,2 % + 20 d) 3,75 sec.
Protection dentre : 1000 Vc.c. ou 1000 Vc.a. rms
40,00 mF 10 F (1,2 % + 40 d) [1]
7,5 sec.
Tension maximale de circuit ouvert: Environ 2,5 V
Couant de test maximal de circuit ouvert: Environ 0,5 mA
[1]
< 50dgt rolling.
Seuil de continuit : Environ 50 Protection dentre : 1000 Vc.c. ou 1000 Vc.a. rms
Tmoin de contuit : Avertisseur sonore tonalit de 2 KHz Remarque : Pour les meilleures mesures, utiliser la fonction REL pour compenser les
dcalages.
75 76
(8) Compteur de frquence vacuation des dchets de matriel lectrique et lectronique
Afin de prserver, protger et amliorer la qualit de lenvironnement,
61-497 / 61-498 protger la sant humaine et utiliser les ressources naturelles prudem-
Plage Rsolution Prcision Sensibilit ment et rationnellement, lutilisateur doit retourner les produits non
40,000 Hz 0,001 Hz (0,002 % + 50 d)
rparables aux installations pertinentes conformment aux disposi-
tions lgales. La poubelle barre indique que le produit doit tre trait
400,00 Hz 0,01 Hz sparment et non comme des dchets municipaux.
1VP-P
4,0000 KHz 0,1 Hz
vacuation des piles et accumulateurs usags!
40,000 KHz 1 Hz (0,002 % + 10 d) Lutilisateur est lgalement oblig de rapporter les piles et accu-
400,00 KHz 10 Hz mulateurs usags. Lvacuation des piles uses dans les ordures
5VP-P mnagres est interdite! Les piles et accumulateurs contenant des
4,0000 MHz 100 Hz
substances dangereuses sont marqus par la poubelle barre dune
Protrection dente: 1000 Vc.c. ou 1000 Vc.a. rms croix. Le symbole indique quil est interdit dvacuer le produit dans
Frquence min: 5 Hz les ordures mnagres. Les symboles chimiques pour les substances dangere-
uses respectives sont Cd = Cadmium, Hg = mercure, Pb = plomb.
(9) Service usine Vous pouvez rendre les piles et accumulateurs uss gratuitement tout point
de collecte des autorits locales, dans nos magasins, ou dans les lieux o les
61-497 / 61-498 piles et accumulateurs sont vendus. Vous vous conformerez ainsi aux obliga-
Plage Rsolution Prcision Sensibilit tions lgales et contribuerez la protection de lenvironnement.
20,0 % ~ 80,0 % 0,1 % (0,1 % + 10 d) 5 VP-P Dclaration de garantie:
Ce testeur est garanti lacheteur primitif contre tout vice de matire ou de
Protrection dente: 1000 Vc.c. ou 1000 Vc.a. rms faon pendant deux ans compter de la date dachat. Durant cette priode de
Type donde: Square Wave (5 Hz ~ 10 KHz) garantie IDEAL INDUSTRIES, INC., son choix, remplacera ou rparera lunit
dfectueuse, suite la vrification du dfaut ou du dysfonctionnement. Cette
(10) Temprature garantie ne sapplique pas aux fusibles, aux piles ou aux dommages rsultant
dune utilisation abusive, de la ngligence, dun accident, dune rparation non
61-497 / 61-498 autorise, dune modification ou dune utilisation draisonnable de linstrument.
Plage Rsolution Prcision Toutes les garanties implicites rsultant de la vente dun produit IDEAL, incluant
-200,0 C ~ 10,0 C (1,0 % + 2 C) sans y tre limites les garanties implicites de valeur marchande et dadaptation
0,1 C une fin particulire, sont limites aux conditions ci-dessus. Le fabricant ne
10,1 C ~ 1200,0 C (1,0 % + 1 C)
sera pas tenu pour responsable de la perte dusage de linstrument, ni dautres
-328,0 F ~ 50,0 F (1,0 % + 4 F) dommages accessoires ou indirects, dpenses ou prjudice financier, ou de
0,1 F
50,1 F ~ 2192,0 F (1,0 % + 2 F) toute(s) rclamation(s) pour de tels dommages, dpenses ou prjudices.
Protrection dente: 1000 Vc.c. ou 1000 Vc.a. rms Les lois des provinces varient, donc les limitations et exclusions prcdentes
peuvent ne pas sappliquer dans votre cas. Cette garantie vous donne des
droits lgaux spcifiques, et vous pouvez aussi avoir dautres droits qui varient
dune province lautre.
La garantie ne concerne pas les piles ou les conducteurs dessai.
IDEAL INDUSTRIES, INC.
Sycamore, IL 60178, U.S.A. / Etats-Unis
877- 201-9005 / Technical Hotline / Lnea de soporte tcnico directa /
Ligne dassistance technique
www.testersandmeters.com
77 ND 7459-2 Made in Taiwan / Fabricado en Taiwn / Fabriqu Tawan