The suction strainer can connected direct to the pump suction nozzle, in case the pipe
dimension of the strainer and the suction nozzle are identical.
In case the pipe dimensions of the strainer and the suction nozzle are dissimilar, the
reducer can connected between suction nozzle and strainer.
Siemens AG . Power Generation (KWU) The reproduction, transmission or use of this document or its
contents is not permitted without express written authority. Offenders
will be liable for damages. All rights, including rights created by
patent grant or registration of a utility model or design, are reserved.
For a combination of elbows in the suction line with more than 2 elbows in the line
within a short distance, an approval is required by the pump department/ pump
supplier.
Siemens AG . Power Generation (KWU) The reproduction, transmission or use of this document or its
contents is not permitted without express written authority. Offenders
will be liable for damages. All rights, including rights created by
patent grant or registration of a utility model or design, are reserved.
A reducer in the suction line is only allowed at the start point of the line or at the pump
suction nozzle. A reducer within the routing of the pipe is not allowed.