Sunteți pe pagina 1din 2

VERIFICARE CAPACITATE PORTANTA STALP 50 110

20 5 x 20 20 60
50

5.0
N= 4160 kN
My= 45 kNm 40

2 x20

2 x20
Qx= 20 kN 30

50

40
20
Y directia slaba het = 576 cm
10

5.0
0
20 20 0 110
5.0 100 5.0 Mx= 145 kNm
110 Qy= 20 kN
X - Directia principala
DIMENSIUNILE SUNT EXPRIMATE IN CENTIMETRI
ARMARE LONGITUDINALA
Clasa de beton C30/37 Rezist compres beton Rc= 17.0 N/mm2
Zona de calcul stalp B Rezist intindere beton Rt= 2.1 N/mm2
Otel longitudinal BST500 Rezist armatura longitudinala Ra= 420 N/mm2
Otel transversal BST500 Rezist armatura transversala Ra= 420 N/mm2
Mcap gr/ Mef.gr Kg = 1.0 Factor moment Kt = 1.4 Modul elasticitate beton Eb= 32000 N/mm2
Tip stalp Interior Modul elasticitate otel Ea= 205000 N/mm2
Mxref=MxKtKg= 203.0 kNm Mxcalc=Mx ref+Ne= 286.2 kNm
Myref=MyKtKg= 63.0 kNm Mycalc=My ref+Ne= 146.2 kNm
Tipul de armare Aax=1,5-2Aay n=N/(bhRc)= 0.445 > 0.30 Stalp subdimensionat
mx=Mx/(bh2Rc)= 0.028 se alege din tabelul n,b b= 1.350
my=My/(b2hRc)= 0.031 se aleg kx si ky din kx= 0.585
mx/my= 0.890 tabelul mx/my,b ky= 0.612
=N/(bh0Rc)= 0.466 >0.4 Mareste zona plastica b= 0.550 <b Sectiune de beton OK
proc. armare sect. pmin t%= 0.60 % pmax t%= 2.50 % proc. min armare pe lat pmin l %= 0.20 %
a/h = 0.045 m x0=m /k =
x x 0.048 Aanec x=bhRc/Ra= 0.0 cm2 Aef x= 12.56 cm2
Se alege de pe curba A = 0.000 pef x %= 0.23 % Armare OK
a/b = 0.100 my0=my/ky= 0.051 Aanec y=bhRc/Ra= 0.0 cm2 Aef y= 21.98 cm2
Se alege de pe curba C = 0.000 pef y %= 0.40 % Armare OK
x=AaxRa/(bhRc)= 0.099 mx0 de pe curba C mx0= 0.184 Mcapx=mxob2hRc= 925.7 kNm
y=AayRa/(bhRc)= 0.056 my0 de pe curba A my0= 0.169 Mcapy=myoh2bRc= 1741.0 kNm
1.350 1.350
mx m
0.028
+
0.031
= 0.181 + y 1 VERIFICARE OK
m
0.171 0.198 mx0 y0
pef tot=Aatot100/(bh)= 1.03 % pef tot < padm ARMARE LONGITUDINALA OK
ARMARE TRANSVERSALA
Qnec x=2Mcapx/het= 707.1 kN 1.5Qx<Qnec x<5Qx Qcalc x= 100.0 kN
Qnec y=2Mcapy/het= 277.6 kN 1.5Qy<Qnec y<5Qy Qcalc y= 100.0 kN
Q'x=Qcalc x/bh0Rt= 0.07 R't=Rt(1+0.5n0)= 2.61 N/mm2
Q'y=Qcalc y/hb0Rt= 0.08
si 100 p Rt' l0 5.49 l 0 12.80 Q x' 2 R t' 100 si l s
= = pe = 0 K i 2.5 M1
ho pe 0 . 8 Ra = 3 .2 p R e h0 h0 h0
p h0 b0 ' p
Q ' 50 Rt Q 50 Rt
2. 5 l0 s l
0 h0 si l s

pe = 2 .5 K i > 2 .5 M 2 pe = > 0 K i 2 .5 M3
Re h0 h0 Ra h0 h0 h0
lo/ho > 2.5 si si/ho= 13.086 > 2.5 pex se va calcula in modul M 2 pex %= -0.03 %
lo/bo > 2.5 si si/bo= 16.322 > 2.5 pey se va calcula in modul M 2 pey %= -0.04 %
Zona de calcul a stalpului B zona curenta proc. minim armare transversala pe min%= 0.15 %
Diametru etrieri 8 A n ARMARE TRANSVERSALA
pe = e e
Distanta intre etrieri ae= 10.0 cm ae b 28/10 cm
Numar etrieri directia x nex= 2 pef x %= 0.40 % ARMARE TRANSVERSALA OK
Numar etrieri directia y ney= 2 pef y %= 0.18 % ARMARE TRANSVERSALA OK
CANTITATI ESTIMATIVE
Volum de beton V= 3.17 m3 Consum kg/m3= 109.53 kg/m3
Armatura 347 kg Cofraj = 18.43 m2