NTPC DRG NO: 9578-001-572-PVC-U-0909

Larsen & Toubro Ltd. Rev No: 2


NTPC-Khargone STPP (2X660MW) Date: 12-01-2017
TATA Bluescope Steel Ltd.

WIND LOAD CALCULATIONS:


Panel profile considered = LYSAGHT TRIMDEK 1072
Thickness of profile, BMT = 0.5 mm
Basic wind speed,(Vb) = 39.00 m/sec (As per Specification)
As pre IS 875_3 (CL:5.3.1 TABLE-1), K1 = 1.06 (As per Specification)
As per IS 875_3 (CL:5.3.2.2 TABLE-2), K2 = 1.17 CATEGORY 2 CLASS A
As per IS 875_3 (CL:5.3.3), K3 = 1.00
Therefore, Design Wind Speed, (Vz)= Vb x K1 x K2 x K3
= 48.37 m/sec
Design Wind Pressure, (Pz) = 0.6Vz2
= 1.50 kN/m2 (As per specification)
1.Sheeting panel:
1.External pressure co-efficient ,(Cpe)
For Internal Zone, (Cpe) = 0.80 IS 875_3 ( Table-5 )
2.Internal Pressure Co-efficient ,(Cpi) = +/- 0.50 IS 875_3 ( Clause 6.2.3 )
Wind load on panel per m2, p= (Cpe- Cpi) x Pz (REFERENCE:IS875-1987(PART-3) (CL:6.2.1)
THEREFORE,
Wind load for internal zone, p1 = 1.95 kN/m2

Self weight of panel, dl = 0.0480 kN/m2 (Weight Per Square meter for the
designed Trimdek 0.5BMT)
Cover width of panel, c = 1.015 m

Therefore, UDL on panel


1.Wind Load (WL)
Wind load for internal zone, WL = p1 x c = 1.98 kN/m UPWARD
2.Dead Load (DL)
Self weight of panel, DL = 0.0487 kN/m DOWNWARD
Combined load,W = (DL+WL)
Therefore, for internal zone, W = 1.93 kN/m UPWARD
Live Load, LL = 0.75 kN/m2 (As per Code)

Live Load, LL = 0.76 kN/m


Combined Gravity load,W = (DL+LL)
0.81 kN/m

Page 1
NTPC DRG NO: 9578-001-572-PVC-U-0909
Client Larsen & Toubro Ltd. Rev No: 2
Project NTPC-Khargone STPP (2X660MW) Date: 12-01-2017
Supplier TATA Bluescope Steel Ltd.

DESIGN CALCULATIONS FOR TRIMDEK 1072, 0.50 BMT, 550Mpa PANEL

Step 1 : Calculations of Gross Sectional Properties of Trimdek Panel

Assumptions made in Calculations

1. Gross Sectional Properties are calculated for one module of panel (Module width will be 203 mm)

2. Trimdek Panel is considered as simple line element neglecting smooth edges caused due to profiling

3. For calculating gross sectional properties, the Panel has been broaken into 4 Triangles
& 3 Rectangles as shown in Fig

Area of Rectangle 2892.75 mm

Area of Segment 1 125.45 mm

Area of Segment 2 125.50 mm

Area of Segment 3 1154.60 mm

Area of Segment 4 552.16 mm

Area of Segment 5 292.46 mm

Area of Segment 6 292.46 mm

Area of Segment 7 291.48 mm

Now Area of Trimdek Segment 58.64 mm

Area of Overlap Rib both side 20.78 mm

Total Gross Area of Trimdek Panel 607.18 mm

Page 2
NTPC DRG NO: 9578-001-572-PVC-U-0909
Client Larsen & Toubro Ltd. Rev No: 2
Project NTPC-Khargone STPP (2X660MW) Date: 12-01-2017
Supplier TATA Bluescope Steel Ltd.
Calculation of Location of Neutral Axis for Panel

Neutral Axis (From bottom) 8.21 mm

Neutral Axis (From Top) 20.29 mm

MOI of Rectangle about Neutral Axis 301492.29 mm

MOI of Segment 1 about Neutral Axis 5538.03 mm

MOI of Segment 2 about Neutral Axis 2573.35 mm

MOI of Segment 3 about Neutral Axis 140199.00 mm

MOI of Segment 4 about Neutral Axis 57951.40 mm

MOI of Segment 5 about Neutral Axis 47876.47 mm

MOI of Segment 6 about Neutral Axis 13110.27 mm

MOI of Segment 7 about Neutral Axis 28830.14 mm

Moment of Inertia Overlap rib portion 589.17 mm

Now MoI of Trimdek Panel Segment about Neutral Axis 5413.63 mm

Therefore MoI of Full (1015 mm Cover Width) Trimdek Panel , Ix = 54725.52 mm

Sectional Modolus Zx from Top 2696.57 mm

Sectional Modolus Zx from Bot 6669.37 mm

Step 3 : Calculations of Effective Sectional Properties at Loading Conditions

Assumption made in Calculations

1. Under Gravity Loads,wind loads Section below the Neutral Axis the section is Considered
fully effective. Top and bottom flange & Web Member will be in Compression
and has to be checked for Local Buckling.

2. Since we have taken only Half of the Top Flange for Computation, for Effectve width
will be calculated for full top flange width and it is distributed equally to both sides of flange
i.e Local Buckling width will be distributed equally to both sides of flange
Actual Top Flange width, W= 19.34 mm

2. For Moment / Strength determination are done for one Full Panel (width of 1072 mm)

3. For First Itteration, Effective Stress is taken as Allowable Stress (i.e f = 0.6 * 550 = 330 Mpa)

First Itteration

f = 330 Mpa

Page 3
NTPC DRG NO: 9578-001-572-PVC-U-0909
Client Larsen & Toubro Ltd. Rev No: 2
Project NTPC-Khargone STPP (2X660MW) Date: 12-01-2017
Supplier TATA Bluescope Steel Ltd.

As per IS:801-1975, Clause 5.2.1.1, for Stiffened Elements, limiting w/t is given by

(w/t) lim 1435 / sqrt (f) MKS Units

(w/t) lim 446 / sqrt (f) SI Units

(w/t) lim 24.55

For Top Flange of Trimdek Panel

Actual (w/t) for Flange 38.68 > 24.55 Local Buckling Occurs

Reduced Width as per IS:801-1975, Clause 5.2.1.1

(w/t) = (2120/sqrt(f)) * (1 - (465/((w/t)*sqrt(f)) MKS Units

(w/t) = (658/sqrt(f)) * (1 - (145/((w/t)*sqrt(f)) SI Units

(w/t) 28.75

Therefore,w= 28.75 * t = 14.37 mm

Locally buckled width,wb = W-w= 4.97 mm

Hence Each Side = wb / 2 = 2.48 mm

For Web of Trimdek Panel

Web will be in Compression, and neutral axis is towords bottom of Panel


hence entire web will be considered for effective width calculations
Actual width of web, W= 30.14 mm

Actual (w/t) for Web = 60.28 > 24.55 Local Buckling Occurs

Reduced Width as per IS:801-1975, Clause 5.2.1.1

(w/t) = (658/sqrt(f)) * (1 - (145/((w/t)*sqrt(f)) SI Units

(w/t) 31.43

Therefore,w= 31.43 * t = 15.71 mm


Locally buckled width = 30.14-15.71 = 14.43mm
For Bottom Flange of Panel

Actual width of bottom flange, W= 137.93 mm


Actual (w/t) for Flange 275.86
Reduced Width as per IS:801-1975, Clause 5.2.1.2
(b/t) = (658/sqrt(f)) * (1 - (145/((w/t)*sqrt(f))
b/t = 35.17
be/t = (b/t)-0.1x((w/t)-60)
Therefore, be/t = 13.59

Locally buckled width,wb = W-w= 124.34 mm

Hence Each Side = wb / 2 = 62.17 mm

Page 4
NTPC DRG NO: 9578-001-572-PVC-U-0909
Client Larsen & Toubro Ltd. Rev No: 2
Project NTPC-Khargone STPP (2X660MW) Date: 12-01-2017
Supplier TATA Bluescope Steel Ltd.
For Curved Elements of Trimdek Panel

Since the Flat width of Curved Elements are very small, it is assumed that No Local Buckling occurs in
these elements.

Calculation of Effective Section Properties

Effective Area of Segment 49.54 mm

Effective Area of Whole Trimdek Panel 495.42 mm

Calculation of Location of Neutral Axis for Panel

Neutral Axis (From bottom) 6.74 mm

Neutral Axis (From Top) 21.76 mm

MOI of Rectangle about Neutral Axis 358753.88 mm

MOI of Segment 1 about Neutral Axis 3409.04 mm

MOI of Segment 2 about Neutral Axis 1237.99 mm

MOI of Segment 3 about Neutral Axis 170878.76 mm

MOI of Segment 4 about Neutral Axis 69284.65 mm

MOI of Segment 5 about Neutral Axis 57866.98 mm

MOI of Segment 6 about Neutral Axis 14698.17 mm

MOI of Segment 7 about Neutral Axis 34387.04 mm

MOI of Segment 8 about Neutral Axis 574.3 mm Locally Buckled Segment

MOI of Segment 9 about Neutral Axis 604.19 mm Locally Buckled Segment

Now MoI of Trimdek Panel Segment about Neutral Axis 5812.81 mm

Moment of Inertia Overlap rib portion 807.82 mm

Therefore MoI of Full (1015 mm Cover Width) Trimdek Panel , Ix = 58935.89 mm

Eff Sectional Modolus (Zxe) from Top 2709.03 mm

Eff Sectional Modolus (Zxe) from Bot 8738.21 mm

Strength Check

Total UDL on panel, W = 1.93 kN/m

Live Load on panel, LL = 0.81 kN/m

Panel has to Checked for 2 Span Beam Condition. Moments, Shear & Deflection Eqns
is Attached in Appendix

Spacing of support, L = 1.5 m (Girt / Runner Spacing)

Two Span Condition Max Support Moment,WL = 0.125 W L = 0.54 kNm

Two Span Condition Max Support Moment, LL = 0.125 W L = 0.23 kNm

Moment Capacity , WL =0.6 fy Zx(t) = 0.89 kNm > 0.54 kNm


Hence OK
Moment Capacity , LL =0.6 fy Zx(t) = 0.89 kNm > 0.23 kNm
Hence OK
Stress at Top Fibres of Panel (M/Zxe) 200.43 N/mm

Page 5
NTPC DRG NO: 9578-001-572-PVC-U-0909
Client Larsen & Toubro Ltd. Rev No: 2
Project NTPC-Khargone STPP (2X660MW) Date: 12-01-2017
Supplier TATA Bluescope Steel Ltd.

Second Iteration

Now for the second Itteration, we will calculate Effective Sectional Properties for the
Stress,f = 200.43 N/mm

As per IS:801-1975, Clause 5.2.1.1, for Stiffened Elements, limiting w/t is given by

(w/t) lim 1435 / sqrt (f) MKS Units

(w/t) lim 446 / sqrt (f) SI Units

(w/t) lim 31.50

For Top Flange of Trimdek Panel

For Top Flange the Total Effective Width Calculated for First Itteration = 14.37 mm

Actual (w/t) for Flange 28.75 < 31.50 No Local Buckling Occurs

For Web of Trimdek Panel

For Web the Total Effective Width Calculated for First Itteration = 15.71 mm

Actual (w/t) for Web 31.43 < 31.50 No Local Buckling Occurs
For Curved Elements of Trimdek Panel

Since the Flat width of Curved Elements are very small, it is assumed that No Local Buckling occurs in
these elements.

Since the Actual & Limiting w/t Ratios are almost matching it can be considered that futrthur there
will not be any Local Buckling and the Actual Stress in Top Fibre of Flange

Page 6
NTPC DRG NO: 9578-001-572-PVC-U-0909
Client Larsen & Toubro Ltd. Rev No: 2
Project NTPC-Khargone STPP (2X660MW) Date: 12-01-2017
Supplier TATA Bluescope Steel Ltd.

DEFLECTION DETERMINATION

Assumption made in Calculations

1. Under Gravity Loads,wind loads Section below the Neutral Axis the section is Considered
fully effective. Top and bottom flange & Web Member will be in Compression
and has to be checked for Local Buckling.

2. Since we have taken only Half of the Top Flange for Computation, for Effectve width
will be calculated for full top flange width and it is distributed equally to both sides of flange
i.e Local Buckling width will be distributed equally to both sides of flange
Actual Top Flange width, W= 19.34 mm

2. Strength & Serviceability Calculations are done for one Full Panel (width of 1072 mm)

3. For First Itteration, Effective Stress is calculated at Allowable Stress (i.e f = 0.6 * 550 = 330 Mpa)

First Itteration

f = 330 Mpa

As per IS:801-1975, Clause 5.2.1.1, for Stiffened Elements, limiting w/t is given by

(w/t) lim 1850 / sqrt (f) MKS Units

(w/t) lim 574 / sqrt (f) SI Units

(w/t) lim 31.60

For Top Flange of Trimdek Panel

Actual (w/t) for Flange 38.68 > 31.60 Local Buckling Occurs

Reduced Width as per IS:801-1975, Clause 5.2.1.1

(w/t) = (2710/sqrt(f)) * (1 - (600/((w/t)*sqrt(f)) MKS Units

(w/t) = (842/sqrt(f)) * (1 - (186/((w/t)*sqrt(f)) SI Units

(w/t) 34.08

Therefore,w= 34.08 * t = 17.04 mm

Locally buckled width,wb = W-w= 2.30 mm

Hence Each Side = wb / 2 = 1.15 mm

Page 7
NTPC DRG NO: 9578-001-572-PVC-U-0909
Client Larsen & Toubro Ltd. Rev No: 2
Project NTPC-Khargone STPP (2X660MW) Date: 12-01-2017
Supplier TATA Bluescope Steel Ltd.

For Web of Trimdek Panel

Web will be in Compression, and neutral axis is towords bottom of Panel


hence entire web will be considered for effective width calculations

Actual width of web, W= 30.14 mm

Actual (w/t) for Web 60.28 > 31.60 Local Buckling Occurs

Reduced Width as per IS:801-1975, Clause 5.2.1.2

(w/t) 38.48

Therefore,w= 38.48 * t = 19.24 mm

For Curved Elements of Trimdek Panel

Since the Flat width of Curved Elements are very small, it is assumed that No Local Buckling occurs in
these elements.

Calculation of Effective Section Properties

Effective Area of Segment 58.07 mm

Effective Area of Whole Trimdek Panel 580.65 mm

Calculation of Location of Neutral Axis for Panel

Neutral Axis (From bottom) 5.65 mm

Neutral Axis (From Top) 22.85 mm

MOI of Rectangle about Neutral Axis 409933.76 mm

MOI of Segment 1 about Neutral Axis 2161.07 mm

MOI of Segment 2 about Neutral Axis 586.82 mm

MOI of Segment 3 about Neutral Axis 198050.02 mm

MOI of Segment 4 about Neutral Axis 79356.94 mm

MOI of Segment 5 about Neutral Axis 66199.85 mm

MOI of Segment 6 about Neutral Axis 16713.97 mm

MOI of Segment 7 about Neutral Axis 39383.97 mm

MOI of Segment 8 about Neutral Axis 293.7 mm Locally Buckled Segment

MOI of Segment 9 about Neutral Axis 1008.76 mm Locally Buckled Segment

Now MoI of Trimdek Panel Segment about Neutral Axis 6178.6 mm

Moment of Inertia Overlap rib portion 1001.4 mm

Therefore MoI of Full (1015 mm Cover Width) Trimdek Panel, Ix = 62787.7 mm

Page 8
NTPC DRG NO: 9578-001-572-PVC-U-0909
Client Larsen & Toubro Ltd. Rev No: 2
Project NTPC-Khargone STPP (2X660MW) Date: 12-01-2017
Supplier TATA Bluescope Steel Ltd.

Deflection Check

Spacing of support, L = 1.5 m

Total External Load Acting on Panel, W= 1.93 kN/m

Gravity Load Acting on Panel , (DL+LL) 0.81 kN/m

E= 205000 N/mm

I= 62788 mm

Two Span Beam Conditions Max Deflection = (W*L) / (185 * E* Iex)

= 4.10 mm

Two Span Beam Conditions Max Deflection DL+LL = (W*L) / (185 * E* Iex)

= 1.72 mm

Allowable Deflection of Panel = Span / 250

= 6.00 mm > 4.10 mm

Hence OK

= 6.00 mm > 1.72 mm

Hence OK