TYPE 100X/101X

ELECTRO MECHANICAL CONVERTERS CURRENT TO


PRESSURE (I/P) AND VOLTAGE TO PRESSURE (E/P)

FEATURES
Reliable, rugged, open loop control
ATEX certified units available
Proportional I/P and E/P converters
Minimum Vibration Effects
IP65 environmental protection Functional Symbol
Mounting Bracket and Connector Included

GENERAL DESCRIPTION
The 100X series is an open-loop, highly accurate proportional control valve. A rugged and reliable unit which has
been proven in application installations globally. The uncomplicated design of the 100X/101X enhances the
reliability and reduces maintenance requirements, offering a cost effective accurate solution.

TECHNICAL DATA

Pneumatic
Output Signal See product selector
Air Supply Oil free, dry air, filtered to 5 microns; at least 0.5bar above maximum required output pressure range; maximum
80psi for a standard 100X (upto 150psi for 101X)
Flow Capacity Up to 300Nl/min (10scfm)
Air Consumption 1.4 l/min (0.06scfm) typical
Response Time <2bar/30psig: less than 0.5 seconds (dependent on input for 10-90% step change in outlet pressures) into a
10cc load

Hysteresis Maximum 0.35% of span for 100X

Independent Linearity Maximum 0.5% of span for 100X

Temperature Effect Average 0.1% span/C for span and zero over operating range

Supply Sensitivity Better than 0.075% span output change per % supply pressure change

Connections 1/4 NPT standard (1/4 BSP available on request)

Physical
Operating Temperature -40C to +85C
I.P. Rating IP65 in normal operation
Electromagnetic This is a passive electromagnetic compatibility instrument and is unaffected by interfering high frequency signals

Material of Construction Zinc diecasting passivated and epoxy paint, nitrile diaphragms, Be2Cu flapper nozzle & supply valve

Mass 825g
Mounting Position Integral surface mounting bracket provided for preferred vertical mounting. Alternative mounting available with
re-calibration. 50mm pipe mounting kit available

Vibration Effect <5% of span : 4mmp-p 5-15Hz & 2g sine 15-150Hz, vertical, horizontal & inverted, in accordance with
ISA-S75.13-1996

Electrical
Electrical Signal See product selector
Failure Mode Signal falls to bleed pressure when electrical supply fails
Connections 30mm square connector DIN 43650 provided, mountable in four directions

Watson Smith Instrumentation


Installation Diagram Characteristic Graphs
Forward Flow Characteristics
(Supply Pressure 7bar)
5

Outlet Pressure (bar)


3

0
0 100 200 300 400 500 600
Flow (Nl/min)

Relief Flow Characteristics


(Supply Pressure 7bar)
8

Outlet Pressure (bar)


6

0
-700 -600 -500 -400 -300 -200 -100 0
Flow (Nl/min)

Span/Zero Adjustments
20% of
Max . output
range
Pneumatic connections: NPT female
Electrical connections: 30mm square connector DIN 43650 (provided) Outlet
Pressure

Min.

Min. Max.
Input Signal

PRODUCT SELECTOR
Standard models are 2 wire; 3 wire units require 12-24V supply

INPUT SIGNAL Options to special order:


OUTPUT PRESSURE 4-20mA 1-10V
Alternative input signal ranges
0.2-1bar 402100R 442100R Alternative pressure ranges
0.2-2bar 40049XR Conduit entry with flying leads
0.2-4bar 40064XR Junction box
0.14-8bar (3 wire) 572400R 562400R Intrinsically safe certification
50mm pipe mounting bracket
3-15psig 400100R 440100R 1/8 NPT pneumatic connections
3-30psig 40017XR Captured exhaust
3-60psig 40005XR Reverse acting
3-120psig (3 wire) 570400R 560400R Split range

CERTIFICATION
An intrinsically safe 100X model certified to ATEX (EN50 020) EEx ia IIC T4 is available. (Installations with these models must
comply with the information given in BS EN 60079.

All instruments are tested, soaked at 60C, cycled for 1000 full scale electrical and 100 pneumatic operations and retested on the
Watson Smith Automatic Testing System for linearity, hysteresis, total error, drift, supply sensitivity, response time, start up pressure,
air consumption and resistance. An individual test certificate is provided at no extra charge.

Norgren Ltd.,
Cross Chancellor Street,
Leeds, LS6 2RT. England.
Telephone: +44 (0) 113 245 7587 ds100XN-09/05
Fax: +44 (0) 113 246 5735
Email: enquiries@norgren.com

Our policy is one of continuous research and development. We therefore reserve the right to amend without notice the specifications given in this document.
Customers are responsible for ensuring that the product is used only for the purpose for which it is intended. In case of doubt Norgren will be pleased to advise.

Watson Smith Instrumentation


TYPE 120
MODULAR (I/P) PILOT BOOSTER
FEATURES
Low Cost OEM I/P
Valve Positioner Pilot
Compact and Rugged
Specific Application Customising Functional Symbol
Wide Supply Range Available

GENERAL DESCRIPTION
The 120 Pilot Booster I/P converter uses proven moving coil and flapper/nozzle technology, with a built in flow
regulator to minimize supply pressure effects. Available in a variety of packages including Explosion Proof
enclosures for incorporation into OEM products.

TECHNICAL DATA

Pneumatic
Output Pressure 0.2-1bar (3-15psig) ;
Air Supply Oil free, dry air, filtered to <5 microns; 1.4-10 bar (20-150 psig
Flow Capacity <1.5nl/min
Air Consumption <1.5 nl/min typical
Response Time </=650msecs from 10 to 90% or </=350ms from 90 to 10% of output pressure into a 4.5cc load)
Linearity +/-0.5% of span
Hysteresis +/-0.3% of span
Temperature Effect Typically less than 0.2% span/degC between -40C to +85C
Supply Sensitivity Less than+/- 0.15% of span for supply pressure change
Connections customised to suit customer requirements

Physical
Operating Temperature -40C to +85C
Weatherproofing IP20
Vibration Output pressure changes less than 2% for 2g sine 20-100Hz,
Electromagnetic Compliant with EC requirements EN Compatibility 50081-2:1994(Emissions) and EN50082-2:1995(Immunity)
Material of Construction Zinc diecasting with nitrile diaphragms, customer specific enclosures available
Mounting Position Any, to be specified by customer

Electrical

Electrical Signal 4-20mA (two wire);


Loop Resistance 230Ohm
Failure Mode Signal falls to below 15mbar (0.2psig) in < 2sec, when input signal fails
Insulation Resistance >100MOhm at 850Vdc, electrical terminals to case
Connections Clamping screw connector terminals or flying leads to customer requirements.

Watson Smith Instrumentation


Installation Diagram Characteristic Graphs

Chart displays 313ms; 10-90%


of output pressure

Chart displays 124ms; 90-10%


of output pressure

Hazardous Area Certification

The Type 120 can be supplied certified for use in intrinsically safe and flameproof applications, to CENELEC, FM and
CSA requirements. For certification and customised units please contact the factory.

Ordering Information
Options to special order:
Standard 1/8 ported base
Alternative pressure ranges
Optional Enclosures
Orientation and Application Specific Calibration set-up

All instruments are tested on the Watson Smith Automatic Testing System and an individual test certificate is provided at no extra
charge. Each unit is tested for linearity, hysteresis, total error, settling error, over pressure, air consumption, response time,
calibration, insulation, start-up current, supply sensitivity and voltage load.

Norgren Ltd.,
Cross Chancellor Street,
Leeds, LS6 2RT. England.
Telephone: +44 (0) 113 245 7587
Fax: +44 (0)113 246 5735
Email: enquiries@norgren.com ds120N 09/05

Our policy is one of continuous research and development. We therefore reserve the right to amend without notice the specifications given in this document.
Customers are responsible for ensuring that the product is used only for the purpose for which it is intended. In case of doubt Norgren will be pleased to advise.

Watson Smith Instrumentation


TYPE 140 FAILSAFE
ELECTRONIC CONVERTER CURRENT TO
PRESSURE (I/P)

FEATURES
Advanced electronic control
ATEX certified Functional Symbol
Explosion proof and Intrinsically safe
Complete Electronics Modularity For Ease of Maintenance
Jack Socket for On-site Monitoring
Fail-Safe (unit pressure falls to zero on signal failure)
Field replaceable filter

GENERAL DESCRIPTION
The 140 proportional I/P converter uses advanced closed loop solid-state electronic control to achieve accurate,
high resolution pressure control. It is available in intrinsically safe and Type n versions and its vibration immunity
and IP66 weatherproof rating make it ideal for field application.

TECHNICAL DATA
Pneumatic
Supply Pressure 1.2-10bar (18-150psig); minimum 3psi above max output pressure
Output Signal 0.2-1bar (3-15psig)
Air Supply Oil free, dry air, min filtered to 50 microns; Internal in-built air filter
Flow Capacity > 300Nl/min (12scfm)
Air Consumption < 2.5 Nl/min (0.025scfm) at 50% signal
Instrument Accuracy mean <0.1%
Independent Linearity mean <0.05% of span
Hysteresis, Resolution mean <0.05% of span & Deadband
Temperature Effect Typically less than 0.035% span/ C between -40C to +85C
Supply Sensitivity Less than 0.1% of span over full supply pressure range.
Connections 1/4 NPT female standard (plus integral 1/8 NPT gauge ports, 1/8NPT (exhaust baffle)
Calibration Independent control of 0% and 100% set points. Adjustable by potentiometers up to 20% of output range. Unit
is factory calibrated to within 1% of span.
Fail-Safe Signal falls to below 15mbar (0.2psig) in < 2sec, when input signal fails.
Tight Shut-off Control Potentiometer sets input signal failure at 3.5mA.

Physical
Operating Temperature -40C to +85C
Weatherproofing IP66, Type 4X
Vibration Output pressure changes less than 3% for vibration amplitude 4mm 5-15Hz, 2g 15-150Hz
Electromagnetic Compliant with EC requirements EN Compatibility 50081-2:1994(Emissions) and EN50082-:1995(Immunity)
Material of Construction Aluminium and zinc diecasting with nitrile diaphragms, black epoxy powder coating standard
Mass 2.07Kg
Maintenance Modular Electronics and in-built filter offered as field replaceable parts
Mounting Position Integral bracket allows for surface or 50mm pipe mounting in any orientation. Designed for mounting with
57-73mm pitch U bolts.

ELECTRICAL
Electrical Signal 4-20mA (two wire) Terminal voltage <6.5V
Min Operating Current >3.5mA
Overload Protection 100mA max overload current
Insulation Resistance >100MOhm at 850Vdc, electrical terminals to case
Connections 1/2 NPT or M20x1.5 via adapter; internal terminal block with capacity up to 2.5mm2 cable

Watson Smith Instrumentation


Installation Diagram Characteristic Graphs
Model 140 Flow Capacity at 12m A, 1.3, 2 and 4 bar Supply
Pressure

700

Output Pressure (m bar)


600 4 bar
500 1.3 bar
2 bar
400
300
200
100
0
0 50 100 150 200 250 300
Flow Capacity (l/m in)

Ordering Information
ORDER CODE
OUTPUT
CERTIFICATION Standard Multi Certified Units Only IS/Type N/Exd
PRESSURE

CENELEC 0.2-1bar EX140 01BJ4LE2


(M20x1.5)
3-15psig EX140 01PK4LE2
Standard Models:
Triple 0.2-1bar EX140 01BJ4EE1 Conduit entry 1/2 NPT
Certification/Triple
Agency 3-15psig EX140 01PK4EE1

Certification
CERTIFICATION EXPLOSION PROOF/ INTRINSICALLY SAFE TYPE N/ OTHERS
AGENCY FLAME PROOF NON-INCENDIVE

SIRA
EEx d IIC T4 EEx ia IIC T4
(CENELEC Ta=-40C to +85C EEx nL IIC T5
Ta=-20C to +40C
ATEX EExd IIB+H2 T5/T6 Ui=30V, Ii=110mA Ta=-40C to +85C
approved) Ta=-20C to +80C (T5) Pi=0.84W Ii=24mA
Ta=-20C to +65C (T6) Ci=6nF, Li=100H Ci=6nF, Li=100H
Umax=30V Sira 01ATEX2007X Sira 01ATEX4008X
Sira 01ATEX1006 1G(T4)/1D(95C) 3G(T5)/3D(95C)
2G(T4/T5/T6)/2D(95C)
Class I, Division 1, Class I, II, III, Division 1, Class I, Division 2, Dust Ingress Protection:
Group B, C, D; Group A, B, C, D, E, F, G; Group A, B, C, D; Class II, III, Division 1,
FACTORY T6, Ta=75C; T4, Ta=85C T6, Ta=75C; Group E, F, G;
MUTUAL T5, Ta=85C T5, Ta=85C T6, Ta = 75C;
T5, Ta = 85C
Suitable for:
Class II, III, Division 2,
Group F, G;
T6, Ta=75C;
T5, Ta=85C

CSA Class I, Group B, C, D; Class I, Group A, B, C, D; Class I, Division 2,


Class II, Group E, F, G; Class II, Group E, F, G; Group A, B, C, D;
Class III; Class III; Ex nL IIC; T5;
Ex d IIC; T4 Ex ia IIC; T4 Class II, Division 2,
Ex d IIB+H2; T5/T6 Group E, F, G;
Class III

Norgren Ltd.,
Cross Chancellor Street,
Leeds, LS6 2RT. England.
Telephone: +44 113 245 7587 ds140N-09/05
Fax: +44 113 246 5735
Email: enquiries@norgren.com
All instruments are tested on the Watson Smith Automatic Testing System and an individual test certificate is provided at no extra
charge. Each unit is tested for linearity, hysteresis, total error, settling error, over pressure, air consumption, response time,
calibration, insulation, start-up current, supply sensitivity and voltage load.
Our policy is one of continuous research and development. We therefore reserve the right to amend without notice the specifications given in this document.
Customers are responsible for ensuring that the product is used only for the purpose for which it is intended. In case of doubt Norgren will be pleased to advise.

Watson Smith Instrumentation


TYPE 421 FAILSAFE
COMPACT ELECTRONIC CONVERTER
CURRENT TO PRESSURE (I/P)
MANIFOLD OR RAIL MOUNT

FEATURES
Advanced electronic control
High density rail
Failsafe operation (output pressure falls to Functional Symbol
minimum on power failure)
Vibration immune

GENERAL DESCRIPTION
The 421 proportional I/P converter uses advanced electronic control to achieve outstanding
performance. It is highly reliable with long life, is free from the effects of vibration and its high
density mounting capability makes it ideal for control room applications.

TECHNICAL DATA

Pneumatic
Output Signal 0.2-1bar (3-15psig); minimum outlet pressure less than 15mbar (0.2psig)
Air Supply Oil free, dry air, filtered to 5 microns; 1.5-3.5bar (20-50psig) or at least 0.7bar above maximum output pressure
Flow Capacity Up to 150Nl/min (5scfm)
Air Consumption 0.2 l/min typical low pressure (0.007scfm)
Response Time 5 seconds (10 to 90% or 90 to 10% of output pressure into a 5 litre load)
Total Error 0.5% of span (typical, independent error includes the combined effect of non-linearity, hysteresis, deadzone and
repeatability
Temperature Effect Typically less than 1% span for span and zero between 0C and 50C
Supply Sensitivity Maximum of 2% of outlet pressure at extremes of supply range
Connections 1/8 NPT female

Physical
Operating Temperature -10C to +60C
I.P. Rating IP40
Vibration The unit possesses a high degree of immunity

Electromagnetic Compliant and CE marked in accordance Compatibility with the EC E.M.C. directive.
Tested to standards: BS EN50082-2: 1995, BS EN50081-2: 1994

Material of Construction Anodised natural aluminium


Mass 600g
Mounting Position The instrument can be mounted in
any orientation. A rail clip is provided with each instrument forTS32 EN50035)/TS35 (EN50022) rail.

Proof Pressure 10bar (150psig); pressure should be regulated to converter requirements. WARNING: maximum pressure should
not be exceeded for safety reasons

Electrical
Electrical Signal 4-20mA (two wire); load presents 10 volts (0.5V) constant voltage drop to the current source
Failure Mode Signal falls to below 15mbar (0.2psig) when input signal fails
Connections Two part quick release terminal block with capacity up to 2.5mm2 cable

Note: it is recommended that an appropriate filter-regulator be fitted to supply all converters

Watson Smith Instrumentation


Installation Diagram Characteristic Graphs

Span/Zero Adjustments
20% of
Max . output
range

Outlet
Pressure

Min.

Min. Max.
Input Signal

a) BRACKET
MOUNTED

TOP FACE
FRONT FACE
135

Ordering Information

Standard Models: 4-20mA input, forward action, terminal connector

421 OUTPUT PRESSURE ORDER CODE Options to special order:


Alternative pressure ranges
0.2-1bar AB2100 Surface mounting bracket
3-15psig AB0100

Certification

All instruments are tested on the Watson Smith Automatic Testing System and an individual test certificate is provided at no extra charge.
Each unit is tested for linearity, hysteresis, total error, settling error, over pressure, air consumption, response time, calibration, insulation,
start-up current, drop out current, supply sensitivity and voltage load.

Norgren Ltd.,
Cross Chancellor Street,
Leeds, LS6 2RT. England.
Telephone: +44 (0) 113 245 7587
Fax: +44 (0)113 246 5735 ds421N 09/05
Email: enquiries@norgren.com

Our policy is one of continuous research and development. We therefore reserve the right to amend without notice the specifications given in this document.
Customers are responsible for ensuring that the product is used only for the purpose for which it is intended. In case of doubt Norgren will be pleased to advise.

Watson Smith Instrumentation


TYPE 422 FAILFREEZE
ELECTRONIC CONVERTER
CURRENT TO PRESSURE (I/P)

FEATURES
Advanced electronic control
Failfreeze operation (output
pressure retained on power failure)
Functional Symbol
Vibration immune
IP65 environment protection
ATEX approved

GENERAL DESCRIPTION
The 422 proportional I/P converter uses advanced electronic control to achieve outstanding performance.
It offers failfreeze operation in addition to conventional I/P characteristics and its rugged construction,
vibration immunity and weatherproofing make it ideal for field application.

TECHNICAL DATA

Pneumatic
Output Signal 0.2-1bar (3-15psig) low pressure unit; 0.2-8bar (3-120psig) high pressure unit; minimum outlet pressure less
than 140mbar (2psig)
Air Supply Oil free, dry air, filtered to 5 microns; at least 0.7bar above maximum output pressure

Flow Capacity Up to 300Nl/min (10scfm)

Air Consumption 0.2 l/min typical (0.007scfm) low pressure; 0.4 l/min typical (0.013scfm) high pressure

Response Time 6 seconds (low pressure unit)/ 12 seconds (high pressure unit) (from 10 to 90% of output pressure into a 2 litre
load)

Total Error Max. error 0.5% of span (low pressure), 0.5% (high pressure) (typical, independent error includes combined
effect of non-linearity, hysteresis at 0.1%, deadzone and repeatability)

Temperature Effect Typically better than 1% span between -10C and 60C

Supply Sensitivity Negligible effect


Connections 1/4 NPT female standard (plus two integral 1/4 NPT gauge ports); others available on request

Physical
Operating Temperature -20C to +70C
I.P. Rating IP65
Vibration The unit possesses a high degree of immunity
Electromagnetic Compliant and CE marked in Compatibility accordance with the EC E.M.C. directive.
Tested to standards: BS EN50082-2: 1995, BS EN50081-2: 1994

Material of Construction Zinc diecasting passivated and epoxy painted, Verton glass/nylon cover; Nitrile diaphragms

Mass 800g
Mounting Position Operation in any attitude is possible without recalibration; integral surface mounting bracket provided for
vertical mounting

Electrical
Electrical Signal 4-20mA (two wire); load presents 6 volts (0.5V) constant voltage drop to the current source

Failure Mode Signal held at previous value when input signal falls below 2mA 0.5mA; drift rate 0.02% in 30 seconds
(mid-range)
Connections 30mm square connector DIN 43650 provided, mountable in four directions

Watson Smith Instrumentation


Installation Diagram Characteristic Graphs

Model 422 Flow Capacity at 12m A, 1.3, 2 and 4 bar Supply


Pressure

600

Output Pressure (mbar)


500 4 bar
1.3 bar
400 2 bar

300
200

100
0
0 50 100 150 200 250 300
Flow Capacity (l/m in)

Span/Zero Adjustments
20% of
Max . output
range

Outlet
Pressure

Min.

Min. Max.
Input Signal

Pneumatic connections: NPT female


Electrical connections: 30mm square
connector DIN 43650 (provided)

Ordering Information
Standard Models: 4-20mA input, forward action, DIN connector

Options to special order:


OUTPUT PRESSURE ORDER CODE Alternative pressure ranges
0.2-1bar AC2100 Conduit entry with flying leads
0.2-8bar AC2400 50mm pipe mounting bracket
1/8 NPT pneumatic connections
3-15psig AC0100
Intrinsically safe certification
3-120psig AC0400 Type nL certification

Certification
Hazardous area approvals:
The 422 is available for:
Intrinsically safe applications to EN50020:2002 with II 1G EEx ia IIC T4 (Ta= -40C to +80C)
Certificate Number: Sira 03ATEX2007X

Type nL applications to EN50021:1999 with II 3G EEx nL IIC T6 (Ta = -40C to +70C)


Certificate Number: Sira 03ATEX4103X

All instruments are tested on the Watson Smith Automatic Testing System and an individual test certificate is provided at no extra charge.
Each unit is tested for linearity, hysteresis, total error, settling error, over pressure, air consumption, response time, calibration, insulation,
start-up current, drop out current, supply sensitivity and voltage load.

Norgren Ltd.,
Cross Chancellor Street,
Leeds, LS6 2RT. England.
Telephone: +44 (0) 113 245 7587
Fax: +44 (0) 113 246 5735
Email: enquiries@norgren.com ds422N 09/05

Our policy is one of continuous research and development. We therefore reserve the right to amend without notice the specifications given in this document.
Customers are responsible for ensuring that the product is used only for the purpose for which it is intended. In case of doubt Norgren will be pleased to advise.

Watson Smith Instrumentation


TYPE 423 FAIL SAFE
ELECTRONIC I/P CONVERTER

FEATURES
Advanced electronic control
Fail-safe operation (output pressure falls to
minimum on power failure) Functional Symbol
Vibration immune
Weatherproof

GENERAL DESCRIPTION

The 423 proportional I/P converter uses advanced electronic control to achieve outstanding
performance. It has a rugged construction, vibration immunity and weatherproofing making it ideal for
field applications.

TECHNICAL DATA
Pneumatic
Output Signal 0.2-1bar (3-15psig); minimum outlet pressure less than 140mbar (2psig)

Air Supply Oil free, dry air, filtered to 3 microns;1.5-3.5bar(20-50psig) or at least 0.7bar above maximum output pressure

Flow Capacity Up to 300Nl/min (10scfm)


Air Consumption 0.6l/min typical (0.02scfm)
Response Time 5 seconds (from 10 to 90% of output pressure into a 0.5 litre load)

Total Error Max. error 0.5% of span (typical, independent error includes combined effect of non-linearity, hysteresis,
deadzone and repeatability)

Temperature Effect Typically better than 1% span between -10C and 60C

Connections 1/4 NPT female standard (plus two integral 1/4 NPT gauge ports); others available on request

Physical
Operating Temperature -20C to +70C
I.P. Rating IP65
Vibration The unit possesses a high degree of immunity
Electromagnetic Compliant and CE marked in accordance with the EC E.M.C directive.
Compatibility Tested to standards: BS EN50082-2: 1995 BS EN50081-2: 1994

Material of Construction Zinc diecasting passivated and epoxy painted, Verton glass/nylon cover; Nitrile diaphragms

Mass 800g

Mounting Position Operation in any attitude is possible without recalibration; integral surface mounting bracket provided for
vertical mounting

Electrical
Electrical Signal 4-20mA (two wire)
Failure Mode Signal falls below 15mbar(0.2psig) when input signal fails

Connections 30mm square connector DIN43650 provided, mountable in four directions.


Others available on request

Watson Smith Instrumentation


Installation Diagram Characteristics Graphs

Model 423 Flow Capacity at 12m A, 1.3, 2 and 4 bar Supply


Pressure

600

Output Pressure (mbar)


500 4 bar
1.3 bar
400 2 bar

300
200

100
0
0 50 100 150 200 250 300
Flow Capacity (l/m in)

Span/Zero Adjustments
20% of
Max . output
range

Outlet
Pressure

Min.

Min. Max.
Input Signal

Ordering Information
Standard Models: 4-20mA input, forward action, DIN connector

Options to special order:


Output Pressure Certification Part number Other pressure ranges
3-15psig None AD0100 Conduit entry
0.2-1bar None AD2100 Flying leads
50mm pipe mounting bracket
1/8 NPT pneumatic connections
Captured bleed

Certification
All instruments are tested on the Watson Smith Automatic Testing System and an individual test certificate is provided at no extra
charge. Each unit is tested for linearity, hysteresis, total error, settling error, air consumption, response time, calibration, insulation,
start-up current, supply sensitivity and voltage load.

Norgren Ltd.,
Cross Chancellor Street,
Leeds, LS6 2RT. England.
Telephone: +44 (0) 113 245 7587
Fax: +44 (0) 113 246 5735 ds423N 09/05
Email: enquiries@norgren.com

Our policy is one of continuous research and development. We therefore reserve the right to amend without notice the specifications given in this document.
Customers are responsible for ensuring that the product is used only for the purpose for which it is intended. In case of doubt Norgren will be pleased to advise.

Watson Smith Instrumentation


TYPE 425 FAILSAFE
ELECTRONIC CONVERTER
CURRENT TO PRESSURE (I/P)
FEATURES
Advanced electronic control
Explosion proof Functional Symbol
Failsafe operation (output pressure falls to
minimum on power failure)
Vibration immune
Weatherproof

GENERAL DESCRIPTION
The 425 proportional I/P converter uses advanced closed loop electronic control to achieve accurate,
high resolution pressure control. It is available in explosion proof and intrinsically safe versions and
its vibration immunity and weatherproofing make it ideal for field application.

TECHNICAL DATA

Pneumatic
Output Signal 0.2-1bar (3-15psig) ; minimum outlet pressure less than 15mbar (0.2psig)
Air Supply Oil free, dry air, filtered to 5 microns; 1.3-4bar (18-60psig)
Flow Capacity Up to 300Nl/min (10scfm)
Air Consumption 0.6 l/min (0.02scfm) typical
Response Time 5 seconds (from 0 to 90% or 100 to 10% of output pressure into a 0.5 litre load)
Total Error 0.25% of span (typical, independent error includes the combined effect of non-linearity, hysteresis, deadzone
and repeatability)
Temperature Effect Typically less than 1% span between -10C to +60C
Supply Sensitivity Less than 1% span for 10% supply pressure change
Connections 1/4 NPT female standard (plus two integral 1/4 NPT gauge ports)

Physical
Operating Temperature -40C to +85C
Weatherproofing IP66, NEMA 4X (when mounted upright)
Vibration Output pressure changes less than 1% for vibration amplitude 5mm 10-30Hz, 10g 30-500Hz

Electromagnetic Compliant and CE marked in accordance with the EC E.M.C directive.


Compatibility Tested to standards: BS EN50082-2: 1995, BS EN50081-2: 1994

Material of Construction Aluminium and zinc diecasting with nitrile diaphragms, black epoxy powder coating standard

Mass 930g
Mounting Position Integral bracket allows for surface or 50mm pipe mounting in any orientation.
Note: The unit must be mounted upright to achieve the weatherproof ratings

Electrical
Electrical Signal 4-20mA (two wire); load presents 6 volts (0.5V) constant voltage drop to the current source
Failure Mode Signal falls to below 15mbar (0.2psig) when input signal fails
Tight Shut-off A potentiometer setting causes the output to fall to zero at between 3.2 and 4.5mA
Connections 1/2 NPT or M20 female; internal terminal block with capacity up to 2.5mm2 cable

Watson Smith Instrumentation


Installation Diagrams Characteristic Graphs
73 CRS
2.874REF Model 425 Flow Capacity at 12m A, 1.3, 2 and 4 bar Supply
Pressure
OPTIONAL PIPE 600
MOUNTING

Output Pressure (mbar)


500 4 bar
1.3 bar
400 2 bar
M20 or NPT 300

200
(103)
100
4.055REF
0
0 50 100 150 200 250 300
Flow Capacity (l/m in)

(118)
4.646REF Span/Zero Adjustments
20% of
Max . output
range
(61)
2.402REF Outlet
(94) Pressure
3.701REF (107)
4.213REF
IN OUT Min.
10 (0.394) SLOTS FOR
U-BOLT MOUNTING NPT NPT
Min. Max.
Input Signal

Ordering Information

ORDER CODE Standard Models:


CERTIFICATION OUTPUT Standard Intrinsically Explosion/ Conduit entry 1/2 NPT
PRESSURE Safe Flame Proof
NONE 0.2-1bar - - Options to special order:
3-15psig AF0101 - - Alternative pressure ranges
FACTORY MUTUAL 0.2-1bar - AF2121 AF2111 Alternative conduit entry
(1/2 NPT) Dual and Triple certification
3-15psig - - AF0111

Certification

CERTIFICATION EXPLOSION PROOF/ INTRINSICALLY SAFE NON-INCENDIVE


AGENCY FLAME PROOF

FACTORY Class I, Division I, Groups B, Class I, Division I, Groups A, Class I, Division 2, Groups A, B, C and D;
MUTUAL C and D; T6 ambient 75C, T5 B, C and D; T4 ambient 40C, Class II, Division 2, Groups F and G;
ambient 85C T3B ambient 70C, T3A Class III, Division 2; T4 ambient 40C,
ambient 85C T3B ambient 70C, T3A ambient 85C

CSA Class I, Groups B, C and D; Class I, Groups A, B, C and D; Class I, Division 2, Groups A, B, C and D;
Class II, Groups E, F and G; Class II, Groups E, F and G; Class II, Division 2, Groups E, F and G;
Class III; T6 @ 75C, T5 @ Class III; T4 @ 40C, T3B @ Class III; T6 @ 75C, T5 @ 85C
85C 70C, T3A @ 85C N.B: Only Available as dual IS/NI Certified

Norgren Ltd.,
Cross Chancellor Street,
Leeds, LS6 2RT. England.
Telephone: +44 (0) 113 245 7587
Fax: +44 (0) 113 246 5735 ds425N 09/05
Email: enquiries@norgren.com
Our policy is one of continuous research and development. We therefore reserve the right to amend without notice the specifications given in this document.
Customers are responsible for ensuring that the product is used only for the purpose for which it is intended. In case of doubt Norgren will be pleased to advise.

Watson Smith Instrumentation


TYPE 440
MULTIFUNCTIONAL ELECTRO-PNEUMATIC CONVERTER

FEATURES
High precision
4-20mA feedback as standard P
U
Signal failure indicator
Failure mode selector
Functional Symbol

GENERAL DESCRIPTION
Type 440 electro-pneumatic converters combine high precision pneumatic performance with input signal
versatility for use with computer and microprocessor based control systems. The type 440 converter
accepts a 4-20mA standard control signal or voltage equivalents. Standard additional features includes
4-20mA feedback, signal failure indication and selection of failure mode. These converters are intended
for applications in which conventional two wire I/P converters are inadequate.

TECHNICAL DATA
Physical
Casing Diecast zinc alloy, black stove enamel finish
Mounting Upright, integral mounting bracket (although other mounting orientations are acceptable without recalibration)
Pneumatic connections 1/4 NPT
Electrical connections Via cable glands to Klippon terminal block
Controls Trimpots - Span, zero (control and feedback), response rate Switches - Signal freeze or instrument drives
down scale, input signal selection Relay - Power/signal (isolated contact pair in relay, NC if signal and power
supply present - contact rating - 50VA)
Weight 2.5Kg
IP. Rating IP65
Temperature Stability -5C to +45C 0.03%/C FS change
(span/zero) -10C to +60C 0.05%/C FS change
Electromagnetic Compliant with the requirements of the EMC directive, assessed against. BS EN50082-2: 1995,
Compatibility BS EN50081-2: 1994. 4% FS susceptibility observed under all test conditions when screened cable is used
connected both at source and instrument ends. CE marked.
Note: Instrument performance is guaranteed within the band 5 to 95% of range. Performance variations may exist outside this range.
Electrical
Supply Voltage 24V 10%d.c. 50mA
Input Signal 4-20mA, 1-5V, 2-10V (selected by switch and connection)
Input Common Mode 0 to +5V max (control I/p -ve to Voltage Limit(see note 2)supply -ve)
Input impedance 4-20mA 250; 1-5V, 2-10V 10k
Feedback Signal 4-20mA (o/p voltage 12V max)
Note 1: Voltage feedback obtainable via load resistor. 1 to 5V - 250 , 2 to 10V - 500
Note 2: The electronic circuit is designed to eliminate the common-mode voltage error which can occur due to resistance of long
cables (max. resistance 250)

Accuracy
Output Signal 3bar (0.2psig); minimum outlet pressur. Maximum; less than 7bar (100psig)
Air Supply Upto 100psig (7bar);with optional filter regulator-150psig (10bar). Dry, non corrosive air filtered to 5microns
Flow Capacity Up to 280Nl/min
Air Consumption Low pressure - 0.2l/min typical High pressure - 0.4l/min typical
Response Time 5 seconds (from 10 to 90% of output pressure)
Linearity 0.5% FS
Total Error 0.5% of span typical, independent error (includes combined effect of hysteresis, deadzone and repeatability)
Stability (6 months) 0.25%(span/zero)
Failfreeze stability <-2% setpoint/hour

Watson Smith Instrumentation


Installation Diagram
Connections
1 4-20mA feedback +ve
2 4-20mA feedback common
3 2-10V control input +ve
4 4-20mA/1-5V control input +ve
5 4-20mA/1-5V control input -ve
6 Power supply -ve (common)
7 Power supply +ve
8 Power fail relay contact (isolated)
9 Power fail relay contact (isolated)
Note: Terminals 2 & 6 are connected internally:
limited isolation available between 5 & 6

Ordering Information

Pressure range Part number Options to special order:


3-15psig 870100R
Other pressure ranges are available to special order.
0.2-1bar 872100R If required a filter-regulator can be supplied separately, please ask for details.
0-100psig 871600R
0-7bar 873600R

Certification
All instruments are fully tested and an individual test certificate is provided at no extra charge. Each unit is tested for linearity,
hysteresis, total error, over pressure, calibration, insulation, drift and failfreeze.

Norgren Ltd.,
Cross Chancellor Street,
Leeds, LS6 2RT. England.
Telephone:+44 (0) 113 245 7587 ds440N 09/05
Fax: +44 (0) 113 246 5735
Email: enquiries@norgren.com

Our policy is one of continuous research and development. We therefore reserve the right to amend without notice the specifications given in this document.
Customers are responsible for ensuring that the product is used only for the purpose for which it is intended. In case of doubt Norgren will be pleased to advise.

Watson Smith Instrumentation


TYPE 68 P/I TRANSMITTER
P
U
FEATURES
Functional Symbol
DIN rail or surface mounting
Weatherproof and Uses non-critical power supplies
A wide range of pressure inputs available

GENERAL DESCRIPTION
These instruments convert pneumatic pressure into electrical signals for
use with data loggers, computers and microprocessors.
The Type 68 is a two wire pressure/current device Use only non-critical
power supplies and can be supplied weatherproof to IP65.

TECHNICAL DATA
Pneumatic
Air Supply Dry, non corrosive air or gas. The units are not suitable for continuous liquid exposure
Air Consumption Nil
Pressure Ranges See ordering information
Over pressure At least 100% with negligible calibration error, except for 10bar(150psig) models which are 13.5bar (200psig)
maximum
Connections 1/8 NPT female

Physical
Operating Temperature -10C to +60C
I.P. Rating IP54 (IP65 option available)
Electromagnetic Compliant and CE marked in Compatibility accordance with the EC E.M.C. directive. Tested to standards:
BS EN50082-2: 1995 and BS EN50081-2: 1994

Material of Construction
Casing: Extruded aluminium, zinc diecast end plates; Nitrile diaphragms. Transducer: composite construction, mainly
nickel, aluminium. Kovar, silicon rubber/gel. PCB: epoxy glass fibre
Mass 200g
Mounting (1) DIN rail. clips fit TS32 and TS35 rail
(2) Direct pipe mounting
Electrical connection Standard - Klippon terminal block to accept cables upto 2.5mm2
Weatherproof - 16mm square connector to DIN43650 to accept cable upto 6mm dia with conductors of
0.75mm2

Electrical
Supply Voltage 9-30V continuous
Output 4-20mA
Voltage drop 9V min. (across unit)
Load resistance 750ohms Max. (24V supply)

Accuracy
Setting Error +/-0.2% FS Max.
Hysteresis, Linearity Typically +/-0.15% +/-0.3%max.
Repeatability
Power Supply Sensitivity+/-0.05% FS/V Max
Temperature (over range 0 to 50C)
Coefficients -Zero <+/-0.025% FS/C
-Span <+/-0.025% FS/C
-Stability<+/-0.025 over 6 months
Response Time <10ms for 95% step output
Range and Zero +/-10% FS(minimum adjustment)
Controls

Watson Smith Instrumentation


Installation Diagrams

Ordering Information
Note:
Range Standard Weatherproof
1. Other pressure ranges between 50mbar
3-15psig 680100 680110
and 10bar are available to order. Please
0-150psig 681500
consult factory for availability
0-100psig
0-100mbar 689610 2. All models supplied complete with DIN rail
0-200mbar clip and mounting plate.
0.2-1bar 682100 682110
0-4bar 683300 3. A range of models with the temperature
compensation -20C to + 40C are available
for natural gas applications to special order.

CERTIFICATION
All units are individually tested and a test certificate is supplied with every unit.

Norgren Ltd.,
Cross Chancellor Street,
Leeds, LS6 2RT. ENGLAND.
Telephone: +44 (0) 113 245 7587
Fax: +44 (0) 113 246 5735
Email: enquiries@norgren.com ds68N 09/05

Our policy is one of continuous research and development. We therefore reserve the right to amend without notice the specifications given in this document.
Customers are responsible for ensuring that the product is used only for the purpose for which it is intended. In case of doubt Norgren will be pleased to advise.

Watson Smith Instrumentation


TYPE 71 P/I CONVERTER
Intrinsically Safe P
U

Functional Symbol
FEATURES
Hazardous Area Approved to ATEX
Encapsulated electronics for good shock/vibration
performance
A wide range of media compatibility

GENERAL DESCRIPTION
The Type 71 P/I instruments convert pneumatic pressure into electrical signal.
It is a two wire device, uses non-critical power supply and is supplied to IP65.

TECHNICAL DATA
Pneumatic
Media Compatibility Fluids compatible with Stainless Steel 316L and Hastelloy C276
Air Consumption Nil
Pressure Ranges See ordering information
Over pressure 2 x FS
Connection G1/4 female or 1/4 NPT female

Physical
I.P. Rating IP65
Electromagnetic Compliant and CE marked in accordance with the EC E.M.C directive.
Compatibility Tested to standards: Immunity: EN 50082-1 : 1995
Emissions: EN 50081-1 : 1992
Surges: 600 V EN 61000-4-5: 1995
ESD: EN61000-4-2: 1995

Material of Casing: Hastelloy C276/316 Stainless Steel.


Construction Transducer: Micro-machined silicon assembly

Mass 210g (including socket)


Mounting Direct pipe mounting

Electrical Interface DIN 43650 plug/socket

Electrical Connection PIN 1 Supply Positive


PIN 2 Supply Negative
Earth not connected

Supply Voltage Units will withstand supply voltage polarity reversal without damage
Reversal

Electrical
Supply Voltage 9 - 28 Vdc
OutputCurrent 4 20 mA

Accuracy
Zero & Span Setting 0.5% FS (5% adjustment via integral pots.)

Hysteresis, Linearity 0.2% FS BSL


& Repeatability

Stability Better than 0.2% FS per year


Operating Temperature -20C to +80C
Temperature Effects 3.0% FS Total error band -20C to +80C

Insulation Resistance Greater than 10M Ohms at 500 Vdc


Watson Smith Instrumentation
Installation Diagrams

Ordering Information

Range I.S. TYPE 71 P/I Note:

3 15 psig, NPT 710101 Please consult factory for other ranges and
options.
3 15 psig, G1/4 710102

0.2 1 Bar, NPT 712101

0.2 1 Bar, G1/4 712102

Certification

Hazardous area approvals:


The I.S. Type 71 is compliance with the Essential Health and Safety Requirements and has been assured by compliance with:
EN 50014: 1997 + amendments 1 & 2
EN 50020: 2002
EN 50284: 1999

Includes the following marking: II 1G EEx ia IIC T4 ( -20C <= Tamb <= +80C)

Certificate Number: Baseefa 02ATEX0235X

All units are individually tested and complies with the specification
A test certificate is supplied with every unit upon request.

Norgren Ltd.,
Cross Chancellor Street,
Leeds, LS6 2RT. England.
Telephone: +44 (0) 113 245 7587
Fax: +44 (0) 113 246 5735 ATEX Type 71dsN 09/05
Email: enquiries@norgren.com

Our policy is one of continuous research and development. We therefore reserve the right to amend without notice the specifications given in this document.
Customers are responsible for ensuring that the product is used only for the purpose for which it is intended. In case of doubt Norgren will be pleased to advise.

Watson Smith Instrumentation

S-ar putea să vă placă și