A Professional GSM Alarm System designer and manufacturer!

GSM SMS Controller Alarm &GSM House Alarm System&


GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Remote Monitoring your assets in anywhere and anytime!

An Innovative GPRS RTU to reduce your management costs!

GSM GPRS Telemetry Data Logger


GSM/GPRS RTU

S240
User Manual
Ver 1.10 Date Issued: 2011-08-20
All rights reserved by King Pigeon Hi-Tech. Co., Ltd.
Website: Http://www.GSMalarmsystem.com

Page 1 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 1 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Table of contents
1. Brief introduction --------------------------------------------------------------------------------------------------------------3
2. Safety Directions ---------------------------------------------------------------------------------------------------------------3
3. Standard Packing list ---------------------------------------------------------------------------------------------------------4
4. Physical Layout -----------------------------------------------------------------------------------------------------------------4
5. Features& Specifications ----------------------------------------------------------------------------------------------------8
5.1 Features------------------------------------------------------------------------------------------------------------------------8
5.2 Specifications-----------------------------------------------------------------------------------------------------------------9
6. Settings ---------------------------------------------------------------------------------------------------------------------------10
6.1 Configuration the Basic Communication Parameters--------------------------------------------------------------10
6.1.1 Install the Driver and PC Configurator-------------------------------------------------------------------------------10
6.1.2 Configuration/Inquiry the GSM/GPRS RTU Parameters by SMS Commands----------------------------13
6.1.3 Configuration/Test/Real-Time monitoring the GSM/GPRS RTU by GPRS remotely--------------------14
6.1.3.1 Configuration GPRS Parameters by PC Configurator--------------------------------------------------------14
6.2 Configuration the GSM/GPRS RTU------------------------------------------------------------------------------------18
6.2.1 Communication Connection-------------------------------------------------------------------------------------------18
6.2.2 Basic Parameter Settings ---------------------------------------------------------------------------------------------19
6.2.3 I/O Port Parameter Settings AIN Parameters-------------------------------------------------------------------20
6.2.4 I/O Port Parameter Settings DIN(Counter) Parameters------------------------------------------------------22
6.2.5 I/O Port Parameter Settings DOUT Relay Parameters-------------------------------------------------------23
6.2.6 I/O Port Parameter Settings RS232 and RS485(Modbus RTU) Parameters----------------------------24
6.2.7 Programmable InterLock Settings Programmable InterLock Parameters--------------------------------24
6.2.8 Programmable InterLock Settings Timer InterLock Parameters--------------------------------------------25
6.2.9 Programmable InterLock Settings Telephone InterLock Parameters--------------------------------------26
6.2.10 Data Logger Monitoring Current Value--------------------------------------------------------------------------27
6.2.11 Data Logger Historical Data Records----------------------------------------------------------------------------27
6.2.12 Data Tunneling ---------------------------------------------------------------------------------------------------------28
6.2.13 Help------------------------------------------------------------------------------------------------------------------------28
7. Installation ------------------------------------------------------------------------------------------------------------------------29
8. Monitoring Center or OPC Server or SCADA ------------------------------------------------------------------------31
8.1 Directly to SCADA System-----------------------------------------------------------------------------------------------31
8.2 Monitoring by SCADA System through OPC Server--------------------------------------------------------------31
8.3 By customer customization monitoring center----------------------------------------------------------------------32
8.4 By Mobile phone through SMS-----------------------------------------------------------------------------------------33
8.5 Real-Time monitoring by PC Configurator---------------------------------------------------------------------------33
9. Warranty -------------------------------------------------------------------------------------------------------------------------33
10. Appendix -------------------------------------------------------------------------------------------------------------------------33

This handbook has been designed as a guide to the installation and operation of S2xx Series GSM GPRS RTU.
Statements contained in the handbook are general guidelines only and in no way are designed to supersede the instructions
contained with other products.
We recommend that the advice of a registered electrician be sought before any Installation work commences.
King Pigeon Hi-Tech.Co., Ltd, its employees and distributors, accept no liability for any loss or damage including
consequential damage due to reliance on any material contained in this handbook.
King Pigeon Hi-Tech.Co., Ltd, its employees and distributors, accept no liability for GSM Network upgrading or SIMCard
upgrading due to the technology specifications contained in this handbook.

Page 2 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 2 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

1. Brief introduction
The King Pigeon S Serial GSM/GPRS RTU Telemetry Data Logger equipped Siemens MC55i quad-band GSM
Module inside, is a low cost, M2M, data logger, universal GSM GPRS Engine which can transmit and receive
analog, digital and pulse counter data, PLC, Varity metering equipments to any device connected to the
GSM/GPRS network such as mobile phones, Web Sites, monitoring center, control room, SCADA, etc.

The GPRS RTU suitable for below applications:

1. Security Alarm System applications;


2. Supervision and monitoring alarm systems;
3. Automatic monitoring system;
4. Vending Machines security protection;
5. Pumping Stations, Tanks, Oil or Water levels;
6. Buildings and Real Estate;
7. Weather Stations;
8. River Monitoring and Flood Control;
9. Oil and gas pipelines;
10. Corrosion protection
11. Temperatures, water leakage applications;
12. Wellheads, boat, vehicle;
13. Energy saving, street lights control system;
14. Valve controls;
15. Transformer stations;
16. Unmanned machine rooms;
17. Control room application;
18. Automation System, M2M;
19. GSM Access Control System, GSM Gate Opener, etc.

2.Safety Directions
Safe Startup
Do not use GSM/GPRS RTU when using GSM equipment is prohibited or might bring
disturbance or danger.

Interference
All wireless equipment might interfere network signals of GSM/GPRS RTU and influence its
performance.

Avoid Use at Gas Station


Do not use GSM/GPRS RTU at a gas station. Power off GSM/GPRS RTU when it near fuels or
chemicals.
Power it off near Blasting Places
Please follow relevant restrictive regulations. Avoid using the device in blasting places.

Reasonable Use
Please install the product at suitable places as described in the product documentation. Avoid
signal shielded by covering the mainframe.

Page 3 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 3 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Use Qualified Maintenance Service


Maintenance can be carried out only by qualified maintainer.

3. Standard Packing List

GPRS RTU USB cable

12V Adaptor GSM antenna CD(User Manual and PC Configurator)

4. Physical Layout
4.1 Control Unit physical layout
LED Instruction

Power The Power status indicator, when power on the LED will turn normally on.

Page 4 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 4 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

GPRS Satus GPRS Module indicator, GPRS Connective successful will slowly flick.
Transmitting GPRS Transmitting data out is on, otherwise is off.
Receiving GPRS Receiving data is on, otherwise is off.
Alarming Alarm Indicator, on is alarming, off is normally;

Relay Relay status, when relay acting is on, otherwise is off;

RS232 RS232 Port communication indicator, normally is off;

RS485 RS485 Port communication indicator, normally is off;

Interface 1 Instruction

Upgrade Button
This Button(Nearby SIMCard) is for download the firmware, the user no need to use it. Press
Download the button then switch on the panel, after 3S loose the button. Then update the firmware
through the USB cable from computer.
Reset Button
This is the reset button(Nearby SIMCard), Press the button then switch on the panel, after 3S
loose the button. After reset, only the passwords will recovery to defaults. The Inquiry
Reset
password is: 0000, the Administrator Password is 1111. The user can use these passwords to
inquiry and control the GSM/GPRS RTU by mobile phones.

Interface 2 Instruction

Page 5 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 5 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Power Connector Definition

Internal Backup battery Switch, these two point is the backup battery switch, normally, must
BATSW short contact them to switch on the backup battery. If long time no use the unit, please
disconnect them to save the battery, otherwise, when the backup battery turn over, it will

BATSW
cannot be re-charged any more. See below:

External Power Connector, Connect to 1.5A@12V DC power through AC/DC Adaptor,


DC IN+
positive electrode.

DC IN- External Power Connector, negative electrode.

Digital Relay Output Connector Definition

DO4+ Digital Relay Output 4+, positive electrode, this output can be programmed as NC or NO;

DO4- Digital Relay Output 4-, negative electrode, this output can be programmed as NC or NO;

DO3+ Digital Relay Output 3+, positive electrode, this output is only NO type;

DO3- Digital Relay Output 3-, negative electrode, this output is only NO type;

DO2+ Digital Relay Output 2+, positive electrode, this output can be programmed as NC or NO;

DO2- Digital Relay Output 2-, negative electrode, this output can be programmed as NC or NO;

DO1+ Digital Relay Output 1+, positive electrode, this output is only NO type;

DO1- Digital Relay Output 1-, negative electrode, this output is only NO type.

COM Port Connector Definition

485A 485A

485B 485B

RST RSTRS232 CONTORL

TXD TXD(RS232)

RXT RXD(RS232)

GND GND

USB Port Connector Definition

USB USB port, for configuration the GSM GPRS RTU.

ATN Port Connector Definition

ATN GSM Antenna connector, 50Ohm, SMA female.

Interface 3 Instruction

Page 6 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 6 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Analog Input Connector Definition


DC3.3V +3.3VDC@400mA power output for external device (Fuse inside).
GND GND

AIN1+ Analog input 1, positive electrode.

AIN2+ Analog input 2, positive electrode.

AIN3+ Analog input 3, positive electrode.

AIN4+ Analog input 4, positive electrode.

GND GND

AIN5+ Analog input 5, positive electrode.

AIN6+ Analog input 6, positive electrode.

AIN7+ Analog input 7, positive electrode.

AIN8+ Analog input 8, positive electrode.

GND GND

AIN9+ Analog input 9, positive electrode.

AIN10+ Analog input 10, positive electrode.

Digital Input Connector Definition

DC12V +12VDC@750mA power output for external device (Fuse inside).

Opto-isolated digital input1, negative electrode (Active Contact, 3~24VDC, Completely


DIN1-
isolated).

DIN1+ Opto-isolated digital input 1, positive electrode.

Opto-isolated digital input 2, negative electrode (Active Contact, 3~24VDC, Completely


DIN2-
isolated).

DIN2+ Opto-isolated digital input 2, positive electrode.

GND GND

DIN3+ Opto-isolated digital input 3(Active Contact, 3~24VDC).

DIN4+ Opto-isolated digital input 4(Active Contact, 3~24VDC).

DIN5+ Opto-isolated digital input 5(Active Contact, 3~24VDC).

Page 7 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 7 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

DIN6+ Opto-isolated digital input 6(Active Contact, 3~24VDC).

Temperature Connector Definition (For Temperature Meter DS18B20)

DC3.3V +3.3VDC@400mA power output for external device (Fuse inside).

AIN11+ Temperature Meter DS18B20 Input

GND GND

DC3.3V +3.3VDC@400mA power output for external device (Fuse inside).

AIN12+ Temperature Meter DS18B20 Input

GND GND

5. Features& Specifications of GPRS RTU:

Relay output Analog/Digital inputs


RS-232 Interface

Watchdog GSM/GPRS
Engine

STM
Industrial
MCU
Power
RS-485 Interface

management Battery

Audio
management

Temperature DC Input
USB Interface
Sensor

5.1 Features

1) Quad-band Siemens MC55i GPRS Module and High-density performance line ARM 32-bit MCU inside;
2) Direct connection to the GSM GPRS Network;
3) Transparent Serial Data Tunneling using low cost SMS/GPRS network;
4) Remote Configuration by SMS Messages or GPRS;
5) Upload data via GPRS or SMS on Schedule or event occurs;
6) Supports Dynamic Domain name or Static IP address;
7) Supports SMS, GPRS UDP and TCP protocols;
8) Supports Modbus RTU protocols;

Page 8 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 8 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

9) 1USB Port, 1 RS232 Serial Port, and 1 RS485 Serial Port;


10) 6 Opto-isolated digital inputs can be programmed to NC/NO/Edge/Level type by switch, Passive Contact
Type and Active Contact (3~24VDC) type can be programmed by DIP switch, DIN1 and DIN2 are
Completely isolated. when alarm occurs can send Alarm Messages by SMS or GPRS or auto dial the
preset phone numbers;
11) 6 digital inputs can be used as Pulse Counters;
12) 4 Digital Relay Outputs can be programmed as dial to switch on/off with free communication fee,
alarm-linkage and Schedule to action, also can be send SMS to switch on/off;
13) 10 Analog Inputs. (12 bit resolution, 0-5V or 0-20mA);
14) 2 Thermometer Inputs for DS18B20, measures temperatures from -55C to +125C. Fahrenheit equivalent
is -67F to +257F, 0.5C accuracy from -10C to +85C, Thermometer resolution is programmable from 9
to 12 bits;
15) 4 Power Source Outputs for external device, like Thermometer or transducer, 3 with 3.3V/400mA, another
with 12VDC/750mA;
16) Supports 1 SMS Center Number and 1 IP address or 1 Dynamic Domain name;
17) User friendly PC Programming Interface, it can remotely program the terminals as well as to upload the
data from the terminals by SMS or GPRS, all of the Current Value or status of the terminal can be display
directly, and also will display the SMS Command details while you programming it;
18) More Protocols can be updated by user through USB Port with the updated firmware;
19) Power supply 9V to 24V(Recommend 12VDC);
20) Size: 168mm*113mm*32.3mm.

5.2 Specifications
Parameter Item Reference Scope
DC Power supply Standard adapter: DC 12V/1.5A Reference scope 9-24V DC
Power consumption Standby:12V/70mA; Working Max.: 12V/300mA
GPRS Module Siemens MC55i

Frequency bands Quad-band: EGSM 850,EGSM900, GSM 1800, GSM 1900, Compliant to
GSM Phase 2/2+
Transmit power Class 4 (2W) at EGSM 900 and EGSM 850
Class 1 (1W) at GSM 1800 and GSM 1900
GPRS connectivity GPRS multi-slot class 10

GPRS Data GPRS data downlink transfer: max. 85.6 kbps


GPRS data uplink transfer: max. 42.8 kbps
Transmission
Coding scheme: CS-1, CS-2, CS-3 and CS-4
TCP/IP stack TCP,UDP
SIM interface Supporting 3V SIM Card

External antenna Connected via 50 Ohm antenna connector or antenna pad, SMA Antenna
interface

Page 9 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 9 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Serial Interfaces 1 RS-232 Port,1 RS485 Port, 1 USB Port;

Protocols SMS, GPRS UDP,TCP, Modbus RTU, and more equipment protocols can
be added according to requirements.
6 OPT Coupler (3-24V)
NC/NO/Edge/Level type
Digital Inputs
Active Contact and Passive Contact By Switch
Can be used as Pulse Counters;
Analog Inputs 10 Analog Inputs. 12 bit resolution, 0-5V or 0-20mA;
2 Ports DS18B20.
Thermometer Inputs Measures temperatures from -55C to +125C. Fahrenheit equivalent is
-67F to +257F, 0.5C accuracy from -10C to +85C, Thermometer
resolution is programmable from 9 to 12 bits.
4, 120VAC/3A, 24VDC 3A, Can be controlled by Event, scheme, Incoming
Digital Relay Outputs call, SMS Commands, Timer, Interlock, 2 outputs can setup as NC or NO
type;
Power Source Outputs 3 Ports with 3.3VDC/400mA Power for external device;
1 Port with 12VDC/750mA Power for external device;
Memory Capacity 4MB Memory inside, can save the data for 1 month.
Internal Backup Battery 7.4V 1200mAH
Temperature range -10-+70 C
Humidity range Relative humidity 95% (condensation free)
Exterior dimension 168mm*113mm*32.3mm
Net Weight 1000 g

6. Settings
The GSM/GPRS RTU is for user-friendly design. The user can setup it by the PC Configurator through USB
cable. The GSM/GPRS RTU also can be configured parameters by SMS Commands or GPRS remotely.
Tips!
1) Please insert the SIMCard firstly, and install the GSM Antenna, please power on to check the LEDs can
work or not, then switch off it before you program it by PC Configurator.
2) The PC Configurator in the CD, please click it to run it.
3) The PC Configurator can not display all pages until it contacted to the GPRS RTU successful.

6.1 Configuration the Basic Communication Parameters


6.1.1 Install the Driver and PC Configurator

Please following the below steps one by one to install them, otherwise you cannot install them successfully.
Step1: Please Contact the unit to the PC by USB Cable, and then install the USB Driver to the computer from
the CD firstly. When successful, it can be found out at the device manager of the XP or Windows 7,
please see the below photo. And remember the COM port. Also, the driver for different OS can be
downloaded from Silicon Laboratories, Inc. http://www.silabs.com , the model is CP210x.

Page 10 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 10 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

If the Com port is not Com1~Com5, then please right click the Device, then enter the Properties to
change it, see below photos, after you changed it, and please restart the computer.

Page 11 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 11 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Step2: Please insert the SIMCard into the GSM/GPRS RTU carefully;
Step3: Please running the PC Configurator, neednt installed it, but the below documents must be is the same

folder.
Step4: Please connect the GSM/GPRS RTU to the computer through USB cable, and switch on the
GSM/GPRS RTU;
Step5: Select the correctly Com Port at the Com Port, then click Open, normally is Com3.

Then click the Connect button, if it displays success, then means the GSM/GPRS RTU communicating with

Page 12 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 12 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

the computer now. otherwise, please check the Com port and the USB Driver.

6.1.2 Configuration/Inquiry the GSM/GPRS RTU Parameters by SMS Commands


The user can configure or Inquiry the parameters by SMS Commands. The commands please see the
Operation Commands in the PC Configurator or see 10. Appendix. When you click any button the commands
will be display in the Operation command, this is the command for SMS or GPRS. When use the SMS
Commands or GPRS to configure or inquiry the settings, please plus the password correctly as Basic
Parameter settings. Please use the Inquiry Password to instead of the PPPP, and use the Administrator
Password to instead of SZJH#.
For example:
If you want to setup the Station Number as 00001, the administrator password is 1111 , and the inquiry
passowrd is 0000, then please edit SMS content as 1111#BST:00001# then send to the GSM/GPRS RTU.
Also you can send 0000#E1# from Mobile phone to inquiry the settings.

Notice:

Page 13 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 13 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

1. In some GSM operators they use different SMS protocols, if the unit cant return the SMS confirmation is
normally. It is not product problem. Also, you can try to add the country code before the number, see the
below settings:

For example:

In China, the country code is +86, or 0086.

The user cell phone number is 13570810254 and has been assigned as a SMS Alert number, the simcard number in the
panel is 13512345678.

Problem 1: Alarm but the user hasnt received the SMS Alert.

Solution: Please plus the country code while you setup the 13570810254 as SMS Alert number, means setup
+8613570810254 to instead of the 13570810254.

Problem 2: The user number can receive the SMS Alert message from alarm panel, but the alarm panel can not receive
the commands from the user number.

Solution: Please add country code to the SIMCard number in the alarm panel. Means send sms commands to
+8613512345678 to instead of 13512345678.

Solution 3: When you use cell phone dial another one, what number it will be displayed then you can set the displayed
number as dial numbers; when you use cell phone send SMS to another cell phone, what number it will be displayed then
you can set the displayed number as SMS Alert number, just use the + to replace the 00, also, you can try the 00.

6.1.3 Configuration/Test/Real-Time monitoring the GSM/GPRS RTU by GPRS remotely


Before using the GPRS function, please setup the GPRS parameters by PC Confirgurator or by SMS
commands firstly. The SMS Commands please refer to 10. Appendix. The parameters please refer to
Configuration GPRS Parameters by PC Configurator.
6.1.3.1 Configuration GPRS Parameters by PC Configurator
1) Successfully connect the communication between RTU S240 and computer, refer to 6.1 Install the Driver
and PC Configurator step5.
2) Click the Basic Parameter Settings in the PC Configurator.

Page 14 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 14 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

a) Setup the IP Send Period time as 5minutes or 10minutes.


b) Setup the other GPRS Parameters, please see below explanations:
Notice:
1. Please help to ensure the Set Success! Alerting in the Received Data after you click the Save button, otherwise,
means the setting is failure.
2. if you want to use the PC Configurator for remotely setup the GSM/GPRS RTU, or test the GPRS communication, or
remotely real-time monitoring the GSM/GPRS RTU. Must setup the GPRS Protocol as TCP.
Step 1: Access the Local Network Router, usually is 192.168.1.1, like below:

Step 2: Enter the Router, and click the Running Status, will display the below:

Find out the WAN IP Address, and then write down this IP Address. Abovementioned is
183.13.236.205
Step 3: Configures the IP Port for S240 on the Router
Click the Forwarding rules button at the left side, will display the below page:

Page 15 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 15 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

The Service IP Port is the defined by the Router; please refer to the Router Instruction. For TCP
Protocol and UDP Protocol, the Router has specificities a fixed different Service Port. Like
abovementioned 4662 for TCP, and 4673 for UDP, please fill it and remember the port number
for both of them.
The Enable/Disable option is for enable or disables TCP protocol or UDP protocol
communication function. Please enable both of them.
For IP Address, this is the Local Network IP Address of the Computer, It is the Router assigned to
the LAN PC. Like the abovementioned is 192.168.1.107. You can find out your Local IP address of
the computer by below steps:

After you setup the Service IP Port, Local Network IP Address, and TCP or UDP, then click Save
button to save the settings.

Page 16 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 16 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Step 4: Configuration the 240 GPRS Parameters


Click the Basic Parameter Settings and go to the GPRS Parameter settings in the PC Configurator.
APN: is provided by the GSM Operator, please ask your GSM Operator to get it and fill it.
DNS : is the Server Domain, the format is www.xxxx.xxx
IP Address: this IP Address is Server IP Address, from the Router you can get it from the WAN IP
address, you have got it at the Router WAN Status, abovementioned is 183.13.236.205. Please fill
your WAN IP to these blank.
IP Port: This port is the Server IP Port of the Router; you can get it in the Forwarding Rule of the
Router. E.g.: if you select the TCP Protocol, then abovementioned port is 4662. If you select UDP
protocol, then is 4673. Please check your router for these items.
Heart Pack Period: only when you setup as UDP protocol, need to fill it, you can fill it from
1~100S, recommend value is 10. If you setup as TCP Protocol, then no need to fill the Heart Pack
Period.
Reconnect Period: you can setup it from 1~100S, recommend value is 10.
TCP/UDP: to setup which protocol would you like to use it for transporting the data by GPRS.
Please select TCP.
GPRS Enable: Setup it as Open.

3) Configuration the GSM/GPRS RTU parameters remotely by GPRS.


After you setup the basically GPRS Parameters in the GSM/GPRS RTU S240, then you can remotely
setup the other parameters or monitoring real-time values of the GSM/GPRS RTU S240 on site.

Running the GSM/GPRS RTU PC Configurator in remotely Computer, select the IP Communication at the

Page 17 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 17 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Choose Communications, at the Server IP then select this computer IP address(as abovementioned is
192.168.1.107), and fill its IP Port(as abovementioned the port of the TCP Protocol is 4662 ), and then click
the Establish Connection Button.

Please wait 1-120seconds for the GPRS communication.

When the computer received the GSM/GPRS RTU data, will display the GSM/GPRS RTU S240 IP Address
and its Port at the Client IP and Port Status, choose the displayed IP and Port, the IP address and Port of
S240 will automatically display at Target IP and IP Port, then click the Connect button, in the Received
Data will display Connection Success.

Then you can configure the other parameters or monitoring the GSM/GPRS RTU by this computer.

6.2 Configuration the GSM/GPRS RTU


6.2.1 Communication Connection
After you connect the GSM/GPRS RTU to computer, then you can start to configure the parameters.
1) Query GPRS Modules Status: Click the Query GPRS Modules Status button, the GPRS Module status
will be displayed;
2) Reset: Click it to reset the parameters to the factory defaults;
3) Read Settings: Click it to read the present parameters in the GSM/GPRS RTU;
4) Save Settings: Click it to save the present settings to GSM/GPRS RTU;
5) Load Profile: Load the settings from the Saved file in the computer to the PC Configurator;
6) Save As Profile: Save the present settings as a profile and saved in the computer for future use.
Notice:
When you want to save the present parameter settings as a profile from the GSM/GPRS RTU to the
computer, please fill the profile name in the Profile Name, and click Read Settings to read the

Page 18 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 18 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

parameters to the PC Configurator firstly, after finished, it will display Read Successful in Received Data,
then click Save As Profile to save it. When saved it, the file name will plus the prefix STA before the name
you write, and saved under the Profile folder.
When you want to Load Profile from computer to the GSM/GPRS RTU, please click Load Profile button,
at the right side will pop up the profile list, select the correct one then click the Save Settings button, after
finished, it will display Set Completion! in the received Data. It means the Profile download to the
GSM/GPRS RTU successfully.

6.2.2 Basic Parameter Settings


Click the Basic Parameter Settings to configure the basic parameters.
Notice: Please help to ensure the Set Success! Alerting in the Received Data after you click the Save button,
otherwise, means the setting is failure.

1) Station Number: To setup the Station Number, Max 5digits;


2) Setup Inquiry Password: To setup the password for mobile phone inquiry, 4digits;
3) Setup Administrator Password: To setup the administrator password for mobile phone setup,4digits;
4) Setup Date Time: To setup the GSM/GPRS RTU time, format is: Month/Day/Year/Hour/Minute;
5) IP Send data Period: To setup the time intervals to transmit out complete data by GSM/GPRS RTU;
6) Save Data Period: To setup time intervals to save the data into the GSM/GPRS RTU memory
7) SMS Center Number: To setup the SMS Center Number, must be SIMCard Number. This number will
receive the alarm message and complete report data from GSM/GPRS RTU by SMS;
8) Send SMS Period: To setup the time intervals to send complete report data to SMS Center Number;
9) Tel NO.1-NO.6: To setup the Alarm numbers, when alarm arises, the GSM/GPRS RTU will dial these
numbers and send Alarm messages by SMS one by one(SMS prior to Dial);

Page 19 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 19 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

10) APN: To setup the GSM Operator Access Point Name; (This parameter please ask your GSM Operator.)
DNS: To setup the Domain Name of the Monitoring Center, the format is WWW.xxx.xxx
IP Address: To setup the IP Address of the Monitoring Center or Server;
IP Port: To setup the IP Port of the Monitoring Center;
Heart Pack Period: To setup the GPRS Heart Pack Period (Only used it in UDP mode), recommend value
is 1~100Seconds;
Reconnect Period: To setup the GPRS resend period;
TCP/UDP: To setup the GPRS Transmission mode, TCP or UDP;
GPRS Enabled: To Close or Open the GPRS Transmission;
11) Read Setting: To review the present parameter settings of the GSM/GPRS RTU.
6.2.3 I/O Port Parameter Settings AIN Parameters
Click the I/O Port Parameter Settings to configure the AIN parameters.
Notice: Please help to ensure the Set Success! Alerting in the Received Data after you click the Save button,
otherwise, means the setting is failure.

AIN1-AIN10: These the Analog inputs, the analog input can be 0-5V or 0-20mA. Therere 3 Actions for
selectable of each input.
Ignore: Dont care;
Acquire Data: Only acquire data;
Alarm and Acquire: Acquire the data from the analog input and also alarm when the value is abnormal.
Measured Hi: The measured High Value, like 100 Celsius degree;
Mesured Lo: The measured Low Value, like -100 Celsius degree;
Start: The value to start to process the linear transformation with the equal-slope, like 0V or 1V, the value must
be voltage value according to the Linear Transformation with Equal-slope Calculation Simulator.
Threshold Hi: The higher value need to alarm, like 50Celsius degree;
Threshold Lo: The low value need to alarm, like -50Celsius degree;

Page 20 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 20 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

An analog input gets data from a sensor device and measures a scalar value (volts, mill ampere or resistance)
it than returns an integer value ranging to the GSM/GPRS RTU device. In order to convert the returned integer
value to a proper engineering measurement value, the GSM/GPRS RTU use the linear transformation with the
equal-slope calculation formula inside and based on 0-5V, the value at the Start must be voltage value
according to the Linear Transformation with Equal-slope Calculation Simulator.

To make thing clearer, consider the following example:


Example 1: Suppose a sensor, which output 0V at a temperature of -100 Celsius degree and
5V at a temperature of 100 Celsius degree, is attached to the GSM/GPRS RTU. And the Threshold Low
Alarm value is -50 Celsius degree, the Threshold High Alarm value is 50 Celsius degree, when alarm, the
Relay 2 close, and send SMS to Tel No.1, You can make the following settings:

Page 21 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 21 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Example 2: Suppose a sensor, which output 4mA at a temperature of -100 Celsius degree and
20mA at a temperature of 100 Celsius degree is attached to the GSM/GPRS RTU. And the Threshold Low
Alarm value is -50 Celsius degree, the Threshold High Alarm value is 50 Celsius degree, when alarm, the
Relay 2 close, and send SMS to Tel No.1, You can make the following settings:

Notice: Please note the Start Value is 1 while use the 4-20mA sensor. See Linear Transformation with Equal-slope Calculation
Simulator. The linear transformation with the equal-slope calculation formula based on 0-5V, the value at the Start must be
voltage value according to the Linear Transformation with Equal-slope Calculation Simulator.

Relay1~Relay4: To setup when the input arising alarms, the relay action;
Tel No.1~No.6: To setup when the input arising alarms, the relay action;
AIN11~AIN12: Special for Temperature Meter DS18B20;
AC Power: This is the power voltage value after rectified voltage from the external AC Power or internal
backup battery that supply to the GSM/GPRS RTU;
Alarm Message settings: The user can select the specified analog input from the AIN Channel, and edit its
alarm SMS Alert content, then click the Save Setting to configure the alarm message for each input.

6.2.4 I/O Port Parameter Settings DIN(Counter) Parameters


Click the I/O Port Parameter Settings and open the DIN(Counter) Settings to configure the DIN parameters.
Notice: Please help to ensure the Set Success! Alerting in the Received Data after you click the Save button,
otherwise, means the setting is failure.

DIN1-DIN6: These the digital Opto-isolated inputs, the user can change the DIP switchers in the motherboard

Page 22 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 22 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

to setup each input to be Passive contact or Active contact type, default is Passive contact. If setup as Active
contact type, the voltage range is 3~24VDC. The DIN1 and DIN2 are completely isolated, both of them with
therere own signal negative electrode. The signal negative electrode of them are disconnect to the Circuit
board GND. The signal negative electrode of DIN3~DIN6 are connect to the circuit board GND, Therere 5
Actions for selectable of each input.
Ignore: Dont care;
Counter: For pulse counter;
Close Alarm: Normally open, when close will alarm;
Open Alarm: Normally close, when open will alarm;
OC-CO Alarm: When the status of the input change will alarm (Rising, falling)
Pulse (Counter) Alarm Value: When used the input as Counter, the user can setup the alarm value of the
counter in correspondence.
Alarm Message settings: The user can select the specified analog input from the AIN Channel, and edit its
alarm SMS Alert content, then click the Save Setting to configure the alarm message for each input.

6.2.5 I/O Port Parameter Settings DOUT Relay Parameters


Click the I/O Port Parameter Settings and open the DOUT Relay Settings to configure the Digital Output Relay
parameters.
Notice: Please help to ensure the Set Success! Alerting in the Received Data after you click the Save button,
otherwise, means the setting is failure.

The user can setup the digital output action according to the conditions. When the relay close time setup as
0(the Max. time is 9999Seconds), then the relay will keep the close status, will not open. The user can test the
relay by press the Save Button of When it be Controlled by Sending SMS Commands, and the relay close time
will be the same as the settings at When it Be Controlled By Sending SMS Commands, the Relay Output Time.

Page 23 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 23 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

6.2.6 I/O Port Parameter Settings RS232 and RS485(Modbus RTU) Parameters

Click the I/O Port Parameter Settings and open the RS232 and RS485 (Modbus RTU) Settings to configure the
RS232 and RS485 (Modbus RTU) parameters.
Notice: Please help to ensure the Set Success! Alerting in the Received Data after you click the Save button,
otherwise, means the setting is failure.

The RS485(Modbus RTU) can read 4 Analog data and 4 pulse counter data, the RS232 can read special
electric meters, Max. 2 analog data and 2 pulse data. We can add the other protocols and more analog and
pulse counters values according to the requirements of the projects.
The GPRS RTU supports Modbus RTU protocol by RS485.
M_Addr: this is the modbus address of the meters;
D_Addr: this is the register address of the meter.

6.2.7 Programmable InterLock Settings Programmable InterLock Parameters


Click the Programmable InterLock Settings to configure the Programmable InterLock parameters.
Notice: Please help to ensure the Set Success! Alerting in the Received Data after you click the Save button,
otherwise, means the setting is failure.

Page 24 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 24 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

InterLock: therere InterLock1~InterLock4, can be setup as 4 independent interlock. if the Condition1~4


co-occurrence, then the relay1~Relay4 will execute the actions in correspondence. If any one or more
conditions of condition1~condition4 is not used as condition, then its value must be setup as True in the drop
menu.
Pulse Alarm(Counter, Pulse Input): To setup if the counter reach the value then how to handle it.
Pulse Interval Alarm Value: To setup the value (Counter) interval to alarm; like every 5000 then alarm once;
Total Alarm Value: To setup the total value, means when the counter value reach this value.
Alarm Action: To setup when the total value reach the setup value, need to alarm or not. 0 stand for ingore, 1
stand for alarm.

6.2.8 Programmable InterLock Settings Timer InterLock Parameters


Click the Programmable InterLock Settings and open the Timer InterLock Settings to configure the Timer
InterLock parameters.
Notice: Please help to ensure the Set Success! Alerting in the Received Data after you click the Save button,
otherwise, means the setting is failure.

Page 25 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 25 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

The user can setup the dialy timers and Weekly timers of the actions of the output relays. The relay close time
is according to DOUT Relay Settings.
6.2.9 Programmable InterLock Settings Telephone InterLock Parameters
Click the Programmable InterLock Settings and open the Telephone InterLock Settings to configure the
Telephone InterLock parameters.
Notice: Please help to ensure the Set Success! Alerting in the Receive Data after you click the Save button,
otherwise, means the setting is failure.

Page 26 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 26 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

The user can setup the authorized telephone numbers to control the digital output relays. The GSM/GPRS
RTU will verify the incoming numbers, if it is the same as the preset numbers, the GSM/GPRS RTU will hang
up then the output relays will execute the actions.
6.2.10 Data Logger Monitoring Current Value
Click the Data Logger, the user can check all of the current value of different inputs.

6.2.11 Data Logger Historical Data Records


Click the Data Logger and open the Historical data records, the user can check all of the historical value of
different inputs.

Page 27 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 27 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Save data: To setup the time interval to save the history data;
Counter: To setup the how many history data to search.

6.2.12 Data Tunneling


Click the Data Tunneling, the user can read all of the original data of the RS232 and RS485 Communication.

6.2.12 Help

The user can open the user manual from this page. The user manual must be saved at the folder
firstly.

Page 28 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 28 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

7. Installation
Before installing the control unit and detectors and sirens, please help to test the system firstly, including wired
detector, power supply, gsm signal, etc.
7.1 Insert SIMcard into Control Unit

In the backside of the control unit, please install the GSM SIM card . The GSM ANT must be Vertical
installation to ensure it in good working condition.

7.2 Connecting the Wired Detectors and Electricity equipments


Please help to install them by engineer according the detectors and electricity equipment wiring
diagram.
1) Digital Output Relay Connection
The GSM/GPRS RTU equips 4 digital output relay, the DO2 and DO4 can be programmed as NC or
NO Type, please remove the cover, then you can see the DIP connectors as below, the defaults are
NO type. If you need to change them to NC, please make the Black Jumper to contact the left side
two pins. The DO1 and DO3 are only support NO type.

2) Digital Input Connection(Passive Contact and Active Contact Type)

Page 29 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 29 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

3) Pulse Inputs connection


The GPRS RTU supports the digital inputs be used as counters, if the digital inputs used as counters,
it can be passive contact type and active contact type.
4) Analog inputs
The GPRS RTU supports 10 analog inputs, all of the inputs can be 0~5V or 0~20mA or 4~20mA, no
need to change any hardware, the GPRS RTU with linear transformation of the equal-slope.
5) Temperature Inputs
The GPRS RTU supports two DS18B20, Measures temperatures from -55C to +125C. Fahrenheit
equivalent is -67F to +257F, 0.5C accuracy from -10C to +85C, Thermometer resolution is
programmable from 9 to 12 bits.
6) RS485 Port
The GPRS RTU supports Modbus RTU by RS485 port, also, more protocols can be added according
to project requirements.

Page 30 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 30 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

7) RS232 Port
The RS232 Port is reserved, more protocols can be added according to project requirements.

8. Monitoring Center or OPC Server or SCADA


The user can create the monitoring center to monitoring the devices remotely by internet, GPRS or SMS.
In the monitoring center, it requires a Dynamic Domain name or Static IP address, if use the GPRS DTU as
the Data transmitter, then the user must supply a fixed IP address SIMCard.
More about the monitoring center, SCADA, OPC Server, OPC Client, web access functions and GPRS DTU
information please read the user manuals. In this user manual, we only introduce the basic knowledge of them.

8.1 Directly to SCADA System

If the users want to log data to its present SCADA system directly, the user must develop the
GSM/GPRS Driver then install in its present SCADA according to our communication protocols, the
communication protocols please see appendix. The topological graph please see below:

8.2 Monitoring by SCADA System through OPC Server

If the users want to log data to its present SCADA system through OPC Server, the user must develop
the GSM/GPRS Driver then install in its present OPC Server according to our communication protocols,
so that the OPC Clients can access the GSM/GPRS RTU through OPC Server. The communication
protocols please see appendix. The topological graph please see below:

Page 31 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 31 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

8.3 By customer customization monitoring center


If the users want to log data to its customization monitoring center, the user must develop the
GSM/GPRS Driver then install in its monitoring center software according to our communication
protocols. The communication protocols please see appendix. The topological graph please see below:

Page 32 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 32 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

8.4 By Mobile phone through SMS.


The GSM/GPRS RTU can send the reports and events by SMS to 1 SMS Center number and 6 user
numbers.

8.5 Real-Time monitoring by PC Configurator


The user can remotely real-time monitoring the GSM/GPRS RTU by GPRS remotely. Please refer to
6.1.3 Configuration/Test/Real-Time monitoring the GSM/GPRS RTU by GPRS remotely.

9. Warranty
1) This system is warranted to be free of defects in material and workmanship for one year from the date of
purchase.
2) This warranty does not extend to any defect, malfunction or failure caused by abuse or misuse by the
Operating Instructions.

10. Appendix
Appendix1: GSM/GPRS RTU Protocol (SMS Command List and Report data format)
The Protocol is special for the customers who want to develop its own OPC Server and Driver for its
SCADA or HMI. Also it the SMS Commands to setup or inquiry the GSM/GPRS RTU.

1)Reset S240 sms command:


SZJH#RESET# (SZJH is setup password)

Page 33 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 33 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

2)Setup RTU address:


MMMM#BST:XXXXX# (XXXXX is setup station number, MMMM is setup administrator password)

3)Setup system clock:


MMMM #BTM:AABBCCDDEE# (AA is year, BB is month, CC is day, DD is hour, EE is minute, MMMM is
setup administrator password)

4)Setup inquiry password and setup administrator password:


MMMM#BPS:nnnn,mmmm#nnnn is new inquiry password, mmmm is new setup administrator password

5)Setup GPRS transmitting period (when having alarm, transmit at once):


MMMM #BIS:XX#XX is 00,01,02,03,0411
XX in turns: not send,30s,1m,2m,5m,15m,30m,1h,2h,6h,12h,24h

6)Setup inquiry history data period:


MMMM#BSA:X#X is 0,1,2,3,4
X in turns:not save,5m,15m,30m,60m

7)Setup SMS center numbers and time interval of sending SMS to this center (when having alarm, transmit at
once):
MMMM#BSM:130123456789!,X#130123456789 is SMS center number, optional digit number. X is
0,1,2,3,4,5,6,7,8
X in turns:not send,5m,15m,30m,60m,2h,6h,12h,24h

8)Setup 6 phone numbers (receiving SMS or dialing)


MMMM#APNX:130123456789!# (130123456789 is the setup phone number, optional digit. X is the serial
number of setup number,1-6

9)Setup APN (GPRS service operator)


MMMM #GAN:CMNET!#CMNET is service operator Access Point Name, please ask the GSM Operator for it,
China mobile is CMNET

10)Setup GPRS Server domain name(DNS)


MMMM#GDN:XXXXXXXXXXXXX!#XXXXXXXXXXXXX is domain name,digits unlimited

11)Setup GPRS Server IP address


MMMM #GIA:XXX.XXX.XXX.XXX!#XXX.XXX.XXX.XXX is IP address

12)Setup GPRS Server IP port


MMMM#GIP:XXXXX#XXXXX is port number,at most 5 digits

13)Setup Heart Pack Period (under UDP mode)


MMMM#GHP:XXXX#XXXX is 4 digits,unit is second

14)Setup GPRS connection failure reconnect period

Page 34 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 34 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

MMMM#GRP:XXXX#XXXX is 4 digits,unit is second

15)Setup GPRS transmitting protocol (TCP/UDP)


MMMM#GTU:X#X is 0 or 1. 0 refer to TCP,1 refer to UDP

16)Open or close GPRS function


MMMM#GCL:X#X is 0 or 1. 0 refer to close,1 refer to open

17)Inquiry GSM/GPRS RTU basic parameters


NNNN#E1# (NNNN is inquiry password)
Return:
#E1:station number; TM(system time):year/month/day/hour/minute; PS(password):inquiry password, setup
administrator password; SA(history data storage period):X; IS(GPRS transmitting period):XX; SM(SMS
center):SMS center number: the time interval of sending data to SMS center; AP1:the first alarm number;
AP2:the second alarm number; AP3:the third alarm number; AP4:the fourth alarm number; AP5:the fifth
number; AP6:the sixth alarm number; GA(GPRS service operator): CMNET; GU(GPRS center address): X (0:
use domain name resolution, 1: use IP address); GI(GPRS center IP address):XXX.XXX.XXX.XXX; GD(GPRS
center domain name): XXXXXXXXXXXXXXXXXXXX; GP(GPRS center IP port):XXXXX; GH(Heart Pack
Period):XXXX; GR(failure reconnection period):XXXX; GT(GPRS transmit mode):X(0:TCP,1:UDP); GC(GPRS
running status):X(0:close GPRS running,1:open GPRS running); GE(module running status):XXX(in turns
corresponding module status, SIM card status, GPRS status); XH(module signal value):XX;#

18)Inquiry analog collected parameters


NNNN#E2# (NNNN is inquiry password)
Return:
#E2:station number;AD00(battery voltage): process mode, alarm high threshold, alarm low threshold, linked
status of 4 relay, process mode of 6 alarm phone;AD01(AIN1):data highest range, data lowest range, original
voltage, process mode, alarm high threshold, alarm low threshold, linked status of 4 relay, process mode of 6
alarm phone; AD02(AIN2): data highest range, data lowest range, original voltage, process mode, alarm high
threshold, alarm low threshold, linked status of 4 relay, process mode of 6 alarm phone; AD03(AIN3): data
highest range, data lowest range, original voltage, process mode, alarm high threshold, alarm low threshold,
linked status of 4 relay, process mode of 6 alarm phone; AD04(AIN4): data highest range, data lowest range,
original voltage, process mode, alarm high threshold, alarm low threshold, linked status of 4 relay, process
mode of 6 alarm phone; AD05(AIN5): data highest range, data lowest range, original voltage, process mode,
alarm high threshold, alarm low threshold, linked status of 4 relay, process mode of 6 alarm phone;
AD06(AIN6): data highest range, data lowest range, original voltage, process mode, alarm high threshold,
alarm low threshold, linked status of 4 relay, process mode of 6 alarm phone; AD07(AIN7): data highest range,
data lowest range, original voltage, process mode, alarm high threshold, alarm low threshold, linked status of 4
relay, process mode of 6 alarm phone; AD08(AIN8): data highest range, data lowest range, original voltage,
process mode, alarm high threshold, alarm low threshold, linked status of 4 relay, process mode of 6 alarm
phone; AD09(AIN9): data highest range, data lowest range, original voltage, process mode, alarm high
threshold, alarm low threshold, linked status of 4 relay, process mode of 6 alarm phone; AD10(AIN10): data
highest range, data lowest range, original voltage, process mode, alarm high threshold, alarm low threshold,
linked status of 4 relay, process mode of 6 alarm phone; AD11(AIN11-T1): process mode, alarm high threshold,
alarm low threshold, linked status of 4 relay, process mode of 6 alarm phone; AD12(AIN12): process mode,

Page 35 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 35 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

alarm high threshold, alarm low threshold, linked status of 4 relay, process mode of 6 alarm phone;

19)Setup 01-10 analog input channel parameters


MMMM#ADNXX:A,B.BBB,C.CCC,D.DDD,E.EEE,F.FFF,GGGG,HHHHHH#
XX: analog channel serial number, 01-10
A: process mode, 0-no collected, 1-only collected but no alarm, 2-collected and alarm
B.BBB: highest range of actual data
C.CCC: lowest range of actual data
D.DDD: original voltage of collected point (suggest 0.000)
E.EEE: alarm high threshold
F.FFF: alarm low threshold
GGGG: separately corresponding Relay1-Relay4 4 relays, 0-no linked, 1-linked
HHHHHH: separately corresponding Tel No.1-Tel No.6 6 pre-set phone numbers. 0-no alarm aim at this
number, 1-send alarm SMS to this number when alarming, 2-dial to this number when alarming, 3- send SMS
and dial to this number when alarming.

20)Setup 11-12 analog input parameters(temperature)


MMMM#ADNXX:A,E.EEE,F.FFF,GGGG,HHHHHH#
XX: analog input serial number, 11 and 12
A: process mode, 0-no collected, 1-only collected but no alarm, 2-collected and alarm
E.EEE: alarm high threshold
F.FFF: alarm low threshold
GGGG: separately corresponding Relay1-Relay4 4 relays, 0-no linked, 1-linked
HHHHHH: separately corresponding Tel No.1-Tel No.6 6 pre-set phone numbers. 0-no alarm aim at this
number, 1-send alarm SMS to this number when alarming, 2-dial to this number when alarming, 3- send SMS
and dial to this number when alarming.

21)Setup battery voltage alarm parameters


MMMM#ADN00:A,E.EEE,F.FFF,GGGG,HHHHHH#
A: process mode, 0-no collected, 1-only collected but no alarm, 2-collected and alarm
E.EEE: alarm high threshold
F.FFF: alarm low threshold
GGGG: separately corresponding Relay1-Relay4 4 relays, 0-no linked, 1-linked
HHHHHH: separately corresponding Tel No.1-Tel No.6 6 pre-set phone numbers. 0-no alarm aim at this
number, 1-send alarm SMS to this number when alarming, 2-dial to this number when alarming, 3- send SMS
and dial to this number when alarming.

22)Inquiry analog value alarm SMS contents


NNNN#EMSXX# (NNNN is inquiry password, XX is 00-12 digit, in turns corresponding battery
voltage,AIN1-AIN12)
Return alarm SMS contents

23)Setup analog alarm SMS contents


MMMM#ADSXX:AAAAAAAAAA#(MMMM is setup administrator password, XX is 00-12 digit, in turns
corresponding battery voltage,AIN1-AIN12. AAAAAAAAAA is alarm SMS contents to need setup)

Page 36 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 36 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

24)Inquiry switch value collected parameters


NNNN#E3#NNNN is inquiry password
Return:
#E3:station number; DIN1:process mode, linked status of 4 relay, process mode of 6 alarm phone;
DIN2:process mode, linked status of 4 relay, process mode of 6 alarm phone; DIN3:process mode, linked
status of 4 relay, process mode of 6 alarm phone; DIN4:process mode, linked status of 4 relay, process mode
of 6 alarm phone; DIN5:process mode, linked status of 4 relay, process mode of 6 alarm phone; DIN6:process
mode, linked status of 4 relay, process mode of 6 alarm phone;#

25)Setup switch value collected parameters


MMMM#DINX:A,BBBB,CCCCCC#
MMMM: setup administrator password
X: switch value serial number, 1-6
A: process mode. 0-no collected, 1-pulse count, 2-closed alarm, 3-open alarm, 4-displacements alarm
BBBB: separately corresponding Relay1-Relay4 4 relays, 0-no linked, 1-linked
CCCCCC: separately corresponding Tel No.1-Tel No.6 6 pre-set phone numbers. 0-no alarm aim at this
number, 1-send alarm SMS to this number when alarming, 2-dial to this number when alarming, 3- send SMS
and dial to this number when alarming.

26)Setup pulse counter original value


MMMM#DIPX:AAAAAAAA#
When certain switch value set as pulse count, need to setup pulse original value with the same serial number
MMMM: setup administrator password
X: serial number of switch value, 1-6
AAAAAAAA: pulse original value, 8 digit

27)Inquiry switch value alarm SMS contents


NNNN#EMSXX#(NNNN is inquiry password, XX is 19-24 digit, in turns corresponding DIN1-DIN12)

28)Setup switch value alarm SMS contents


MMMM#DISXX:AAAAAAAAAAAA#
MMMM: setup administrator password
XX: serial number of switch value, 00-05
AAAAAAAAAAAA: alarm SMS contents need to setup

29)Inquiry relay output parameters


NNNN#E4#
Return:
#E4:station number; AOUT1:closed time(unit is second); AOUT2:closed time(unit is second); AOUT3:closed
time(unit is second); AOUT4:closed time(unit is second); TOUT1:closed time(unit is second); TOUT2:closed
time(unit is second); TOUT3:closed time(unit is second); TOUT4:closed time(unit is second); COUT1:closed
time(unit is second); COUT2:closed time(unit is second); COUT3:closed time(unit is second); COUT4:closed
time(unit is second);POUT1:closed time(unit is second); POUT2:closed time(unit is second); POUT3:closed
time(unit is second); POUT4:closed time(unit is second);#

Page 37 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 37 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

AOUT: alarm linked output parameters


TOUT: timing output parameters
COUT: SMS control output parameters
POUT: dialing control output parameters

30)Setup relay alarm linked output parameters


MMMM#ATMX:AAAA#
X: relay serial number, 1-4
AAAA: relay closed time, 4 digits(unit is second)

31) Setup relay timing output parameters


MMMM#TTMX:AAAA#
X: relay serial number, 1-4
AAAA: relay closed time, 4 digits(unit is second)

32)Setup relay SMS control output parameters


MMMM#CTMX:AAAA#
X: relay serial number, 1-4
AAAA: relay closed time, 4 digits(unit is second)

33)Setup relay dialing control output parameters


MMMM#PTMX:AAAA#
X: relay serial number, 1-4
AAAA: relay closed time, 4 digits(unit is second)

34)Setup RS485 communication port parameters


MMMM#MR4B:X,Y,AAA#
X: band rate, 1-1200, 2-2400, 3-4800, 4-9600
Y: odd-even check, 0-None, 1-Odd, 2-Even
AAA: inquiry instruction interval time, 3 digits, unit is ms

35)Setup RS485 communication port working mode


MMMMM#MR4N:A0B#
A: 0-Special Meters AIN15-AIN18 PIN9-PIN12
1-Modbus Meters AIN15-AIN18 PIN9-PIN12
2-Special(AIN15 AIN16 PIN9 PIN10)+Modbus(AIN17 AIN18 PIN11 PIN13)
B: 0-No Meters
1-ABB
2-KL
3-HHE

36)Setup RS485 communication port collected AIN data parameters


MMMM#ADNXX:A,BBB,CCCCC,D,E.EEE,F.FFF,GGGG,HHHHHH#
XX: stand for AIN serial number, 15-18
A: process mode, 0-no collected, 1-only collected, 2-collected and alarm

Page 38 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 38 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

BBB: inferior intelligent electric meter Modbus protocol site


CCCCC: register address of these datas localed in inferior intelligent electric meter
D: data storage format, 0-32 Bits Floating Point Data FFH4 FFH3 FFH2 FFH1
1-32 Bits Floating Point Data FFH3 FFH4 FFH1 FFH2
2-32 Bits Floating Point Data FFH1 FFH2 FFH3 FFH4
3-32 Bits Floating Point Data FFH2 FFH1 FFH4 FFH3
4-32 Bits Integer Data FFH4 FFH3 FFH2 FFH1
5-32 Bits Integer Data FFH3 FFH4 FFH1 FFH2
6-32 Bits Integer Data FFH1 FFH2 FFH3 FFH4
7-32 Bits Integer Data FFH2 FFH1 FFH4 FFH3
E.EEE: alarm high threshold
F.FFF: alarm low threshold
GGGG: separately cooresponding Relay1-Relay4 4 relays, 0-no linked, 1-linked
HHHHHH: separately cooresponding Tel No.1-Tel No.6 6 pre-set phone numbers. 0-no alarm aim at this
number, 1-send alarm SMS to this number when alarming, 2-dial to this number when alarming, 3- send SMS
and dial to this number when alarming.

37)Setup RS485 communication port collected PIN data parameters


MMMM#PMEX:A,BBB,CCCCC,D#
X: stand for PIN serial number, 3-PIN9, 4-PIN10, 5-PIN11, 6-PIN12
A: process mode, 0-no collected, 1-collected
BBB: inferior intelligent electric meter Modbus protocol site
CCCCC: register address of these datas localed in inferior intelligent electric meter
D: data storage format, 0-32 Bits Floating Point Data FFH4 FFH3 FFH2 FFH1
1-32 Bits Floating Point Data FFH3 FFH4 FFH1 FFH2
2-32 Bits Floating Point Data FFH1 FFH2 FFH3 FFH4
3-32 Bits Floating Point Data FFH2 FFH1 FFH4 FFH3
4-32 Bits Integer Data FFH4 FFH3 FFH2 FFH1
5-32 Bits Integer Data FFH3 FFH4 FFH1 FFH2
6-32 Bits Integer Data FFH1 FFH2 FFH3 FFH4
7-32 Bits Integer Data FFH2 FFH1 FFH4 FFH3

38)Inquiry communication port patameter setup


NNNN#E6#(NNNN is inquiry password)
Return:
#E6:station number; MR2E(RS232 parameter):XX(model of external electric meter); AD13: process mode,
alarm high threshold, alarm low threshold, linked status of 4 relay, process mode of 6 alarm phone;
AD14:process mode, alarm high threshold, alarm low threshold, linked status of 4 relay, process mode of 6
alarm phone; PU07:process mode;PU08:process mode;ER4E(RS485):workingmode, BT(communication
basic parameters):BaudRate, Parity, Control Delay Time;AD15:process mode, inferior intelligent electric meter
Modbus protocol site, register address of these datas localed in inferior intelligent electric meter, data storage
format , alarm high threshold, alarm low threshold, linked status of 4 relay, process mode of 6 alarm phone;
AD16:process mode, inferior intelligent electric meter Modbus protocol site, register address of these datas
localed in inferior intelligent electric meter, data storage format , alarm high threshold, alarm low threshold,
linked status of 4 relay, process mode of 6 alarm phone; AD17:process mode, inferior intelligent electric meter

Page 39 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 39 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

Modbus protocol site, register address of these datas localed in inferior intelligent electric meter, data storage
format , alarm high threshold, alarm low threshold, linked status of 4 relay, process mode of 6 alarm phone;
AD18:process mode, inferior intelligent electric meter Modbus protocol site, register address of these datas
localed in inferior intelligent electric meter, data storage format , alarm high threshold, alarm low threshold,
linked status of 4 relay, process mode of 6 alarm phone; PU09:process mode, inferior intelligent electric meter
Modbus protocol site, register address of these datas localed in inferior intelligent electric meter, data storage
format; PU10:process mode, inferior intelligent electric meter Modbus protocol site, register address of these
datas localed in inferior intelligent electric meter, data storage format; PU11:process mode, inferior intelligent
electric meter Modbus protocol site, register address of these datas localed in inferior intelligent electric meter,
data storage format; PU12:process mode, inferior intelligent electric meter Modbus protocol site, register
address of these datas localed in inferior intelligent electric meter, data storage format;#

39)Setup INTERLOCK
MMMM#ACX:AA,BB,CC,DD,EEEE#
X: INTERLOCK group, 1-4
AA: signal name, 00-False, 01-True, 02-19 in turns corresponding with AIN1-AIN18, 19-25 in turns
corresponding with DIN1-DIN6
BB,CC and DD: same as AA
EEEE: separately cooresponding Relay1-Relay4 4 relays, 0-no linked, 1-linked
Note: when AA BB CC and DD all satisfy alarm conditions, can linked relay.

40)Setup pulse alarm parameters


MMMM#ATX:AAAAA,BBBBBBBB,CCCCCC,D#
X: pulse signal serial number, 1-6
AAAAA: interval number of pulse internal alarm
BBBBBBBB: total amount of pulse total amount alarm
CCCCCC: separately cooresponding Tel No.1-Tel No.6 6 pre-set phone numbers. 0-no alarm aim at this
number, 1-send alarm SMS to this number when alarming, 2-dial to this number when alarming, 3- send SMS
and dial to this number when alarming.
D: alarm or not alarm, 0-alarm, 1-not alarm

41)Inquiry INTERLOCK and pulse alarm parameters


NNNN#E8# (NNNNis inquiry password)
Return:
#E8:station number; AC1:signal name, signal name, signal name, signal name, linked status of 4 relay;
AC2:signal name, signal name, signal name, signal name, linked status of 4 relay; AC3:signal name, signal
name, signal name, signal name, linked status of 4 relay; AC4:signal name, signal name, signal name, signal
name, linked status of 4 relay; AT1: interval number of pulse internal alarm, total amount of pulse total amount
alarm, process mode of 6 alarm phone, alarm or not alarm; AT2: interval number of pulse internal alarm, total
amount of pulse total amount alarm, process mode of 6 alarm phone, alarm or not alarm; AT3: interval number
of pulse internal alarm, total amount of pulse total amount alarm, process mode of 6 alarm phone, alarm or not
alarm; AT4: interval number of pulse internal alarm, total amount of pulse total amount alarm, process mode of
6 alarm phone, alarm or not alarm; AT5: interval number of pulse internal alarm, total amount of pulse total
amount alarm, process mode of 6 alarm phone, alarm or not alarm; AT6: interval number of pulse internal
alarm, total amount of pulse total amount alarm, process mode of 6 alarm phone, alarm or not alarm;#

Page 40 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 40 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

42)Setup day timing operation parameters


MMMM#STMX:HH,MM,A,BBBB#
X: timer serial number, 1-4
HH: hour, 00-23
MM: minute, 00-59
A: timing period, 0-not timing, 1-every day, 2-every hour
BBBB: separately cooresponding Relay1-Relay4 4 relays, 0-no action, 1-action

43)Setup week timing operation parameters


MMMM#WTMX:W,HH,MM,BBBB#
X: timer serial number, 1-7
W: what day, 0-not timing, 1-Sunday, 2-7 in turns corresponding with Monday to Saturday
HH: hour, 00-23
MM: minute, 00-59
BBBB: separately cooresponding Relay1-Relay4 4 relays, 0-no action, 1-action

44)Inquiry timing operation parameters


NNNN#E5#
Return:
#E5:station number; DTM1(day timing): timing period, hour: minute, linked status of 4 realy DTM2(day timing):
timing period, hour: minute, linked status of 4 realy; DTM3(day timing): timing period, hour: minute, linked
status of 4 realy; DTM4(day timing): timing period, hour: minute, linked status of 4 realy; WTM1(week
timing):what day, hour: minute, linked status of 4 realy; WTM2(week timing):what day, hour: minute, linked
status of 4 realy; WTM3(week timing):what day, hour: minute, linked status of 4 realy; WTM4(week
timing):what day, hour: minute, linked status of 4 realy; WTM5(week timing):what day, hour: minute, linked
status of 4 realy; WTM6(week timing):what day, hour: minute, linked status of 4 realy; WTM7(week
timing):what day, hour: minute, linked status of 4 realy;#

45)Setup phone calling operation parameters


MMMM#OPHNX:AAAAAAAAAAA!#
MMMM#OPHUX:BBBB#
X: serial number, 1-4
AAAAAAAAAAA: calling phone number, not fill or NUL marks no number
BBBB: separately cooresponding Relay1-Relay4 4 relays, 0-no action, 1-action

46)Inquiry phone calling operation parameters


NNNN#E7#
Return:
#E7:station number;OPN1:phone number, linked status of 4 realy; OPN2:phone number, linked status of 4
realy; OPN3:phone number, linked status of 4 realy; OPN4:phone number, linked status of 4 realy;#

47)Inquiry real time data


NNNN#EE#
Return:

Page 41 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 41 of 42 Ver 1.10 File No.:KPS20011
A Professional GSM Alarm System designer and manufacturer!
GSM SMS Controller Alarm &GSM House Alarm System&
GSM Telemetry Units & GSM GPRS Telemetry Data Logger
Http://www.GSMalarmsystem.com www.KingPigeon.Com.Cn

#STA:station number;TM:current date,current time; C:73; V:battery voltage; all collected AIN data; all collected
pulse value data; DI:input status of switch value; DO:relay status;#
Note: 1. All AIN data format is: ADXX:data;(XX:01-18)
2. Input status of switch value:0-open, 1-closed, 3-pulse count
3.Relay status:0-open,1-closed

Page 42 of 42 King Pigeon Hi-Tech. Co., Ltd. Page 42 of 42 Ver 1.10 File No.:KPS20011