PROJECT Substation Package-S1 for 33/11kV Infocity Susbstation (New) under OPTCL.
The purpose of the document is to design the Earthmat for the 33/11kV AIS Substation. The important aspect is that the design should achieve
"Tolerable Touch and Step potential " with the Earth grid resistance less than 1 ohm.
2.3.5 No of electrodes
Transformer = 2 (2# Neutral)
Lightning Arrester = 3 (3 No. x 1)
PT/CVT = 3 (3 No. x 1)
Tower with Peak = 3 (3 No. x 1)
Outer Fence = 15 (4 No. x 1)
2.3.5 No of electrodes nR = 26
Lx
3.1.1 Area of Switchyard Ag = Lx*Bx
= 14 x 14
Bx
= 196 Sq.m
= 014/2+1
= 8
= 014/2+1
= 8
= 224
= 52 m
= 2 x ( 14 + 14 )
= 56 m
= ( 14 + 14 )
= 20 m
3.1.5 Geometric factor n
= 2 x 224 / 56
= 8.0
SWITCHGEAR AND CONTROL PVT. LTD.
PROJECT Substation Package-S1 for 33/11kV Infocity Susbstation (New) under OPTCL.
= 1.0
= 1.0
= 1.0
= 8.0
= 1-0.09*(1-009/3000)/(2*0.10+0.09)
= 0.6906
= 476.49 V
= 1557.94 V
SWITCHGEAR AND CONTROL PVT. LTD.
PROJECT Substation Package-S1 for 33/11kV Infocity Susbstation (New) under OPTCL.
= 224+52
= 276 m
Km = 1 . ln Ds2 + (Ds + 2h ) 2
-h + Kii ln 8
2p 16 hd 8 Ds d 4d Kh p (2n-1)
1.00 for grids with ground rods in perimeter / all along the grid
Kii =
2/n
1/(2n) for grids with no ground round rods or grids with only a few ground rods
= ( 1 + 0.6 / 1.0 )
= 1.2649
= 0.3147
= 1.8280
= 468.91 V
SWITCHGEAR AND CONTROL PVT. LTD.
PROJECT Substation Package-S1 for 33/11kV Infocity Susbstation (New) under OPTCL.
= 212.2 m
n = 8
= 0.5444
Estep = r Ks Ki I / Ls
= 1055.10 V
Re = r ln (4 LR/b ) - 1 + 2 K1 LR (nR-1)2
2p nR LR Ag (Eqn. 55 in page 66)
H = 0.6 m
K1 = 1.41-0.04x
= 1.41-0.04(L/B)
= 1.41-0.04*14.00/14.00
= 1.3700
K2 = 5.50+0.15x for H = 0
K2 = 4.68+0.10x
= 4.68+0.10(L/B)
= 4.68+0.10*14.00/14.00
= 4.78
= (0.03 * 0.6)
= 0.136 m
Rse = r ln (2 Lc / Lr) + K1 Lc - K2 +1
p Lc Ag (Eqn 56 in page 66)
= 0.3126 Ohm
THIS IS LESS THAN THE RECOMMENDED VALUE OF LESS THAN 1.0 OHM
SWITCHGEAR AND CONTROL PVT. LTD.
PROJECT Substation Package-S1 for 33/11kV Infocity Susbstation (New) under OPTCL.
5.1.7 Combined resistance of Grid & ground rods = 0.3126 ohm < 1.0 ohm
6 CONCLUSION
Permissible Spacing of conductors for the present layout is 2m. Hence, Earthmat layout shall be prepared with spacing
lesser or equal to 2m.