Generator engines
By
Ribe Mrsk
The engines are four-stroke medium-speed turbocharged engines and run on diesel or
heavy fuel oil. Each of the engines drives a synchronous alternator.
The procedure for manually starting up a generator, paralleling it and shutting it down is as
follows:
Manual start-up:
Ensure Remote Control is selected on the generators local panel
Switch the generator in question and running generators into manual mode
Start the engine from the generator panel
Manual paralleling:
Confirm that a voltage of 440 V has been acquired
Align the frequency of the incoming generator with that of the running generator(s)
means of its governor raise/lower switch
When the voltage and frequency of the incoming generator matches the net,
change over the synchroscope to the incoming generator
Use the governor raise/lower switch to adjust the frequency of the incoming
generator so it is slightly faster than the net (to prevent it engaging as a motor)
When the synchroscope indicates the incoming generator as in the 12 oclock
position (= its synchronous with the net), engage its circuit breaker
Equalise the load on the running generators by means of their governor raise/lower
switches, maintaining a frequency of 60 Hz
Manual shutdown:
Remove load from the generator in question by means of the governor raise/lower
switches, maintaining a frequency of 60 Hz.
Disengage the circuit breaker of the generator
Stop the engine from the generator panel
Generator readings:
During a sea passage with one auxiliary engine running, the following readings have been
gathered:
Current:........................................................................................................................0.69 kA
Power:..........................................................................................................................460 kW
Frequency.......................................................................................................................60 Hz
Voltage:...........................................................................................................................448 V
Oil specifications:
The lubrication oil specification has been gathered from the ships lubrication plan, by
ExxonMobile. The fuel oil specification is from a laboratory analysis of fuel oil bunkered on
November 3rd 2005.
Name:.............................................................................................................Mobilgard M330
Density at 60F (16C):..........................................................................................894 kg/m3
Viscosity:......................................................................................................................30 SAE
Kinematic viscosity at 40C:........................................................................................108 cSt
Kinematic viscosity at 100C:......................................................................................11.8 cSt
Pour point:......................................................................................................Maximum -15C
Flash point:...................................................................................................Minimum +229C
TBN:......................................................................................................................5 mgKOH/g