Sunteți pe pagina 1din 23

SECTION - 31

DISTRIBUTION TRANSFORMERS

1. The Distribution transformer to be supplied and erected along with suitable


galavanised 6pole structure (RS Joist, HG Fuse set; AB Switch , two number
outdoor 6 way pillar box for each transformer etc.,)

2. STANDARD:
Except where modified by this specification, the transformer shall comply
with the requirements of IS-2026. IS-1180, IS.3347. IS.7421. IS.2099 and IS.335 of
the latest issue.

3. MATERIALS AND WORKMANSHIP:


All the materials used in the construction of the transformers and
accessories shall be of the highest quality. The entire design and construction
should be capable of withstanding the severest stresses likely to occur in actual
services and capable of resisting rough handling during transport. The workmanship
shall be of the highest grade and entire construction in accordance with the best
modern practice.

4. CAPACITY:

The transformers shall have a maximum continuous rating as per IS.2026 at


the secondary terminals of the specified KVA output as per Schedule-A.

5.TYPE:

The distribution transformers shall be of the double wound type with three phase,
oil immersed, naturally cooled core type suitable for outdoor installation and for
operation in highly humid tropical climate and in lightning or non-lightning areas
and at an altitude of 0 to 1000 meters with range of temperatures varying from 5
to 50 Deg.C.

6.FREQUENCY:

The distribution transformer shall be designed to work at a standard


frequency of 50 cycles per second and must be capable of operating satisfactorily
at any frequency between 48.5 and 51.5 cycles per second.

7.FLUCTUATION IN VOLTAGE:

The transformers shall be rated suitable for operation for voltage upto plus
or minus 12% on the H.V side and frequency variation plus or minus 3%.

761

8.NATURE OF LOAD:

The Distribution Transformer will be used for supplying a mixed power and lighting
loads.

9.TEMPERATURE RISE:

The maximum temperature rise shall not exceed the limit of 55 Degree C.
(measured by resistance) for the transformer winding & core and 45 Degree C.
(measured by thermometer) in top oil over an ambient temperature of 50 Deg.C,
when tested in accordance with IS.2026.

10.OVER LOAD CAPACITY OF THE TRANSFORMER:

The transformer shall be capable of carrying without injury, momentary and


alternatively sustained overloads of duration as per Indian Standards under various
conditions of operation, rated voltage and frequency being maintained. The
overload capacity of transformer for two hours (i) Starting from cold and (ii) after
continuous full load run shall be clearly stated.

11. VOLTAGE RATIO:

The normal no load operation voltage ratio shall be as stated in the


Schedule-A and the tolerance is as per IS.2026.

12. CONNECTIONS AND GROUP SYSTEM:

The transformer windings shall be delta connected on the HV side and star
connected on the LV side. The group symbol of the transformers shall be DY11, as
specified in IS 2026 of latest issue so as to produce a positive displacement of 30
Deg. from the primary to the secondary vector of the same phase. The neutral of
the secondary winding shall be connected to a separate insulated terminal.

13. LOSSES & IMPEDANCE:

The losses and impedance at rate voltage shall be as specified in Statement


of Schedule-F subject to tolerance as per IS.2026. The full load losses and
impedance shall be calculated at 75 Deg. C for this purpose.

15.NEUTRAL CURRENT:

The neutral current shall not be more than 2% of the rated full load
current in respect of 1000 KVA capacity transformer.

16. REGULATION: The inherent regulation at normal balance load at


unity and 0.8 (lag) power factors at a temperature of 75 Degree C. shall be stated
in the tender and the tenderers shall guarantee these performance figures. .

762

17.0. TRANSFORMER CORE :

17.1. The transformer core shall be built up of high grade cold rolled grain
oriented annealed (CRGO) laminations, having low loss and good grain properties,
coated with hot oil proof lamination insulation, bolted together and to the frame
firmly to prevent undue vibration or noise. The complete design of the core must
ensure permanency of the core losses with continuous working of the
transformers. The value of flux density allowed in the design shall be clearly
stated in the offer.

17.2. The tenderers should indicate in their tender the type and grade of core
materials used for manufacture of the transformers. They should also indicate
their concurrence ( in case the purchase orders are placed on them to furnish the
proof of purchase of such core material (invoice copy) along with the Certificate
for having availed the CENVAT benefits if availed. They should also furnish the
calculations for arriving at the maximum flux density and the losses for such core
materials proposed to be used by them.

17.3. Flux density: The maximum flux density at any point shall not exceed 1.55
webers/sq.m. at normal voltage and frequency.

17.4. The transformer core shall not be saturated for any value of V/f ratio to the
extent of 112.5% of the rated value of V/f ratio (i.e. 11000/50 or 22000/50 due to
the combined effect of voltage and frequency) upto 12.5% without injurious
heating at full load conditions and will not get saturated. The tenderer shall furnish
necessary design data in support of this situation.

17.5. The no load current at rated voltage and at 112.5% of rated voltage shall
not exceed the values given in the Statement of Schedule-F of this specification.

17.6. The test for magnetic balance by connecting the LV phase by phase to
rated phase voltage and measurement of an-bn-cn voltages will be carried out and
test results furnished.

17.7. The number of steps of core, Diameter of the core and the Effective Area of
the core should be as per the values given in Schedule-F of this specification.

17.8. The weight of core only and weight of core and windings should be furnished
in the guaranteed technical particulars failing which the tender is liable for
rejection.

17.9. 1% tolerance is permissible for core dimensions.

763

18CORE CLAMPING:

18.1 The core clamping channel shall be of size as specified in Schedule-F with 2
Nos. MS nut bolts for efficient clamping.

18.2. The top yoke channels to be reinforced by adequate size of MS flat with
thickness not less than 6 mm, at equidistant if holes/ cutting is done for LT lead so
as to avoid bending of channel.

18.3. MS channels shall be painted with oil and corrosion resistant paint before use.

18.4. MS rods shall be used as tie rods and key studs as specified in Schedule-F and
shall be efficiently insulated.

18.5. Core base and bottom yoke shall be supported with MS channel as specified in
Schedule- F with proper bolting together. In no case, flat or cut channels shall be
accepted.

18.6. All bottom & top yoke key studs, tie rods shall be painted with oil and
corrosion resistant paint before use.

18.7. Suitable eyes or lugs shall be provided in the channels abetting the top yoke
for lifting the core and windings out of the tank. The core shall be effectively
earthed to the tank.

19.0 WINDINGS AND INSULATION:

19.1 Both H.T. and L.T. windings should be double paper covered insulated with
aluminium windings / Copper windings as indicated in Schedule-F.

19.2. The insulation materials to be used for the windings shall be suitable for
satisfactory service in tropical climates in this country and for full load operation as
per ISS. DPC insulation shall be provided for high voltage as well as low voltage
windings.

19.3 Electrical grade plain insulation Kraft paper shall be used for inter layer
insulation of the HV and LV coils. Press Board blocks shall be used for top and
bottom yoke insulation.

a. The conductor cross section of the windings for H.V. and L.V.
should not be less than as furnished in Schedule-F. 1% tolerance is permissible
for the dimensions for the windings.

b. Current density: The current density for HV and LV should not be more
than 2.8 A/sq.mm. for Copper and 1.6 A/sq.mm for Aluminium conductor.
c. The L.T. windings shall be cylindrical and concentric with H.T.windings on
the outer side. The arrangements of the windings must be such that there is

764

electrical and magnetic balance under all conditions of operation. The


arrangements shall permit free circulation of the oil to ensure the absence of
hot spots. All similar coils shall be interchangeable. It is essential that the
windings shall be subjected to thorough shrinking at factory site. Adjustable
devices shall be provided for taking up any possible shrinking of windings in
service. The general design and construction of the transformers and
bracings of the windings shall be such that no mechanical movements of the
coils will be possible with dead short on either side of the transformer. The
short circuit ratings of the transformers shall be as per IS.2026 of latest
issue.
d. The LV winding shall be in even layers so that the neutral formation will be at
top.
e. If the axial length of HV/LV coils is required to be on the higher side due to
practical problems during manufacture, the increase in axial length is
accepted and this shall be accommodated by the end insulation space of 50
mm (22 KV) provided for both at the top & bottom. It may be ensured that
sufficient increased end insulation is provided both at top & bottom.

20.0. END TURNS INSULATION:

The insulation of the end turns of HV windings shall be so designed as to


withstand the Impulse Voltage test as per IS.2026-1977. It may clearly be indicated
as to whether reinforcement to the end turns insulation is provided or not and if
provided, the extent of end turns for which insulation reinforcement is provided shall
be furnished.

21.0. INTERNAL CONNECTIONS:


21.1. H.V. Windings :
21.1.1. In case of H.V. Winding ,all jumpers from winding to bushing shall
have cross section larger than winding conductor.
21.1.2. In case of Al./Cu winding, Delta joints shall be with brazing only.
21.1.3. Lead from delta joint shall be brazed to the lug strip which in
turn is to be connected to bushing rod.

21.2. L.V.Winding:
21.2.1 L.T. Star point shall be formed of Al./Cu. flat of sufficient length. Lead
from winding shall be connected to the flat by brazing.

21.2.2 Firm connections of L.T.Winding to bushing shall be made of adequate


size of 'L' shaped flexible sheet. Connection of L.T.Coil lead to "L" shape
flexible sheet shall be by brazing.

21.2.3 "L" shape flexible sheet shall be clamped to L.V.Bushing metal part by
using nut, locknut and washers.

765

21.2.4 For Aluminium windings, L & T Alkapee aluminium brazing rods with
suitable flux shalll be used. For copper windings, silver brazing alloy shall
be used.

22.0. CLEARANCES:
The clearances in respect of the following shall not be less than the
values specified in Schedule-F and standards such as I.S.2026 Part-III etc.,

23.0. TANK:

23.1. The transformer tank shall be of robust construction and shall be built of
electrically welded M.S.plate of suitable thickness not less than 5 mm for the
bottom and top and not less than 3.15 mm for the sides. The tank should be
sand blasted or cleaned by Chemical process and then coated with paint
conforming to No.632 of IS.5-1961 or the latest issue. For inside of the tank
suitable varnish coating shall be provided. The Tank should be pressure
tested and should withstand the value indicated in the Statement of the
Schedule F of the Contract. Welding should be done on both sides of the
plates forming the side walls, top and bottom of the transformer tank.

23.2. All joints of the transformer tank and fittings shall be hot oil tight and no
bulging shall occur during service. In order to facilitate easy removal of the
core and windings, the transformer core and windings shall be positioned
such that it can be lifted easily from the tank. The tank plate and the lifting
lugs shall be of such strength that the complete transformer when filled with
oil may be lifted by means of the lifting shackle.

23.3. Top cover plate shall be slightly sloping approximately 6 mm towards HV


bushing downwards so as to avoid entry of water through the cover plate
gasket. The top cover shall have no cut at point of lifting lug. The tank
shall be fabricated by welding with not more than two joints for the tank.
No horizontal or vertical joints in tank side walls and its bottom or top cover
will be allowed. In addition, the cover of the main tank shall be provided
with an air release plug.

23.4. Stiffners: The tank shall be reinforced by welded angle on the outside
walls on the edge of the tank to form two equal compartments for 500 KVA
rating and three equal compartments for 200, 250 & 500 KVA ratings. If
necessary, vertical stiffners shall be provided for the required rigidity. The
permanent deflection is not more than 5 mm upto 750 mm length and 6

766

mm up to 1250 mm length with transformer tank without oil subjected to a


pressure of 0.35 kg/sq mm.

23.5. Lifting Lugs: Two Nos. welded heavy duty lifting lugs of MS plate 8 mm
thick suitably reinforced by vertical support flat of same thickness as of lug
welded edgewise below the lug on the side wall up to reinforcing angle shall
be provided to lift the transformer complete with oil. The lugs may be
positioned in such a way that when a sling is used it does not foul the
bushings or conservator.

23.6. Lifting Hooks for top cover : 2 Nos. hooks on MS plate of adequate size may
be provided to lift the tank cover.

23.7. Top cover fixing bolts: GI nut bolts of 1/2" dia with one plain washer shall
be used for top cover fixing spaced at 4" apart.

23.8. Gaskets & Sealing washers: 5 mm thick (for 500 KVA capacity) and 6 mm
thick ( for 200, 250 & 500 KVA capacities) oil and heat resistant Neoprene
rubberised corksheets, conforming to type B/C Part-II, I.S. 4253 will be
placed between the tank and cover plate. Accordingly sealing washers for
items like drain plug etc are to be provided.

24.0. PARELLEL OPERATION:


All the transformers of the same voltage ratio shall be exactly the same
design and operating characteristics such that they shall give perfectly
satisfactory operation when run in parallel and share the load in proportion
of their rated KVA within the limits of tolerance laid down in IS.2026 of latest
issue. Transformers of the same rating shall be absolutely identical and
inter-changeable in all respect

25.0. HEAT DISSIPATION:


Heat dissipation by tank walls excluding top and bottom should not be

less than 500 W/sq.m.

26.0 CONSERVATOR:

1.1. The total volume of conservator shall be such as to contain 10% of total
quantity of oil. Normally 3% quantity of the total oil will be contained in the
conservator. Dimension of the conservator shall be indicated in the General
Arrangement Drawing.

767

1.2. Oil level indicator with minimum oil level marking shall be provided on the
side which will be with fully covered detachable flange with single gasket
and tightened with MS nut-bolt.

1.3. The conservator shall be provided with the drain plug and a filling hole (30
mm dia) with cover)

1.4. The cover of the main tank shall be provided with air release plug to enable
trapped air to be released unless the conservator is so located as to
eliminate the possibility of air being trapped within the main tank.

1.5. The Pipe from conservator tank connecting to main tank shall be of 30mm
to 50 mm dia, according to the capacity of the transformer.

1.6. The inside diameter of the pipe connecting the conservator to the main
tank shall be within 30 mm to 50 mm according to the capacity of the
transformer and it should project into the conservator in such a way that its
end is approximately 20 mm above the bottom of the conservator so as to
create a sump for collection of impurities. The minimum oil level
corresponding to (-) 5 Degree C. should be above the sump level.

27.OIL:

27.1. The insulating oil used in the transformers shall comply with the requirements
such as the characteristics of oil, specific resistance, dielectric dissipation factor and
flash points electrical strength, etc. specified in IS.335 of latest issue. All the
transformers shall be supplied with the necessary quantity of oil. The oil content
should not be less than that prescribed in the Statement of Schedule-F, after
absorption by the core and windings. The following shall also be included:

(a) Schedule of Deviation from specified standards.


(b) Schedule of deviation from specified test requirements specified in
the relevant and present specifications.

28. RADIATORS:

28.1 Heat dissipation by fin type radiator 1.25 mm thick shall be worked out on the
basis of manufacturers data sheet. The tenderer should submit the calculation
sheet.

768

28.2 The radiators may be fixed at right angle to the sides or diagonally. The size of
the radiator shall be such that it covers atleast 50% of bottom yoke, full core &
complete top yoke.

28.3 The radiators provided must be adequate. There should be a clear gap
of 75 mm between the tank / stiffner if any and the radiators, so that the belting
angles one on each longer side of the tank can be fixed. The radiators shall not
hinder the passage of belting angles.

29. BUSHINGS:

The transformer shall be of the outdoor type with bushing insulator terminals
on the HV and LV sides as specified in the Drawing & Statement of Schedule-
F attached hereto and should be provided on the sides of the tank. The
bushings should be of porcelain, brown glazed type, H.V. conforming to
IS.2099 of latest issue and L.V. conforming to IS.7421-1974 of the latest
issue.

The HV Bushings rods and other metal parts shall be of brass. LV bushings
rods shall be of copper and the other metal parts of brass. Bushing rods are
to be firmly mounted with three nuts inside and also outside the tank. The
dimensions shall conform to I.S.3347 of latest issue.

HV Bushings shall be of single piece type and LV bushings may be of double


piece. For 11 KV, 12 KV rating bushings and for 22 KV, 24 KV rating
bushings shall be used. For 433 volts, 1.0 KV terminal bushing shall be
used. Bushings of the same voltage class shall be interchangeable. The
bushings shall be mounted on the side of the tank and not on the top cover.
Only one sheet metal pocket with turret shall be provided for mounting of HV
bushings. Sheet metal pocket shall be designed in such a way that all HV
bushings shall remain at equidistance. Bushings having type tested as per
IS:3347 shall only be acceptable.

30. BUSHING TERMINALS:

Copper rods of 30 mm dia for LT shall be provided for 1000 KVA capacities
for 22 KV rating.

HT/LT bimetallic connectors conforming to IS.5561 shall be provided.

769

31.BUSHING METAL PARTS & TERMINALS:

The bushing porcelain and metal parts shall conform to the following
specifications:

------------------------------------------------------------------------------------

Voltage Indian Standard Indian standard for

Class for porcelain parts metal parts

------------------------------------------------------------------------------------

UP to 1 KV IS.3347 (Part-1 Sec.I IS.3347 (Part-I Sec.I)

Bushings 1979 or the latest 1979 or the latest

ISS if any. ISS if any.

24 KV IS.3347 (Part-IV IS.3347 (Part-IV

Bushings Sec-I) 1972 or the Sec.2) 1967 or the

Latest issue, if any. Latest issue, if any.

32.0TAPPINGS:

32.1 Tappings shall be provided on the H.V.windings for variation of voltage on the
L.V.side from -9% to +3% of the rated voltage in five steps of 3% and shall be
controlled by an externally hand operated off-circuit tap changing switch. The tap
changing gear should be provided with an indicator arrangement in aluminium
anodised plate to show the tap position. Switch position 1 shall correspond to the
maximum plus tapping. Provision shall be made for locking the tapping switch
handle in position.

32.2. The operating lever of Tap switch should be provided at the side of the tank
and not on top of the tank cover.

33.0 EXPLOSION VENT:

33.1 The explosion vent like swan's neck is to be fitted at an angle of about 75 deg.
to the horizontal to avoid direct splashing of rain water on the diaphragm. The
diaphragm shall be made of Hylam Sheet of thickness 0.3 mm to avoid absorption of
moisture.

33.2 Steel net with bigger holes may be provided before the diaphragm and the
distance shall be 12 mm minimum. The pipe dia of the explosion vent shall be 70

770

mm fixed by welding on sufficient size of hole on the top of the tank to handle more
oil to flow out in quicker time and to reduce pressure inside the tank.

33.3 The thickness of pipes in the case of vent pipe and the conservator shall be
sufficient to avoid weak metal parts which would give way under pressure. The
inside of the vent pipe shall be treated with anti corrosive paints as done in the case
of main tank.

34. BREATHER:

The breather should be plain breathing device comprising an inverted "U"


pipe with silicagel type. The breather joints will be screwed type. It shall have die
cast aluminium body or Propyline materials and inside container for silicagel shall be
tin sheet in case of Aluminium die cast breather. The volume of breather shall be as
per Statement of Schedule-F.

35. TANK BASE CHANNEL:

The tank base channels shall be of sufficient length so as to facilitate for pole
mounting and plinth/platform mounting. Base channel shall be welded to the
bottom of the tank across the longitudinal side of the tank.

36. PAINTINGS:

The tank should be sand blasted or cleaned by chemical process beforepainting.


The transformers should be given a primary coat of red lead (not red oxide) or other
suitable anticorrosive paints and finished with two coats of colour paint of dark
admiralty grey shade of oil & weather resistant quality.

The above paints should conform to No.632 of IS.5 /1961 or latest issue.

37. TERMINAL LEAD AND MARKINGS:

1. The transformers shall have suitable terminals on both the HV and LV sides.
2. All leads including tapping and neutral shall be insulated and rigidly supported
and shall be easily accessible without need for removing the windings from
the tank.
3. Unless otherwise specified, the phase and neutral leads shall be brought out
of the tank through porcelain bushing insulators which must be of suitable
design to prevent failure due to line or lightning surges, system faults or
switching operation.

771

3. The physical positions of terminals relative to one another shall be as per


IS.2026 of latest issue.
4. The high voltage phase windings shall be marked both on the terminal Board
inside the tank and on the outside with capital letters 1U, 1V & 1W and the
low voltage windings of the same phase marked by corresponding letters 2U,
2V & 2W and neutral point terminal being indicated by the letter 'N'.
5. These letters shall be assigned to the windings respectively from the left to
the right facing the side carrying high voltage terminals.
6. The vector diagram plate shall clearly indicate the methods adopted for
making the terminals, both outside and interior.

38. FITTINGS:

Standard fittings in line with the manufacturer's practice shall be provided on


each transformer including the following.

Two earthing terminals (with lugs & markings)

Oil level guage with minimum oil level marking

Lifting Lugs & Hooks

Name plate of aluminium anodised material with non-detachable terminal marking


plate, showing the relative physical position of the terminal and their markings as
marked on plate shall be filled in a visible position. The transformer shall also be
provided with non-detachable rating plate of aluminium anodised material fitted in a
visible position. The relative position of the tapping switch and corresponding
voltages may also be shown on the rating plate. The entries of the rating plate
shall be indelibly marked (for example by etching, engraving or stamping). The
above shall be as given IS.1180/ Part-I.

Silicagel Breather

Drain cum sampling valve of Dia 20 mm or 32 mm as applicable with steel plug of


Dia 20 mm or32 mm as applicable.

A filtration valve of Dia 20 mm or 32 mm with a steel plug of 20 mm or 32 mm as


applicable.

Thermometer pocket, with a cover to avoid collection of rain water

Conservator with drain plug

Oil filling hole with cap on conservator

Air Release Plug

772

Radiators

Explosion Vent

Off-Circuit Tap changing switch.

39.0 DRAWING:

One copy of the Dimensional Drawing and Internal Assembly


Drawing of the transformer complete with all fittings and accessories and all the
rated guaranteed technical parameters shall be submitted along with the tender.

40.0 TOLERANCES:

Unless otherwise specified herein, values of the parameters of the


transformers should be within the tolerance permitted in IS-2026 & IS-1180 and
other IS. as per clause-1.

41.0INSPECTION:

All tests and inspection shall be made at the place of manufacturer, unless
otherwise specifically agreed upon by the manufacturer and purchaser at the time
of purchase. The manufacturer shall afford the inspector representing the
purchaser all reasonable facilities without charge, to safisfy him that material is
being supplied in accordance with the Technical Terms specified. The purchaser
has the right to have the tests carried out at his own cost by an independent
agency, whenever there is a dispute regarding quality of supply.

42.0. QUALITY PLAN: STAGE INSPECTION FOR ENFORCEMENT:

42.1. Stage inspection will be carried out by the purchaser's representative at the
following consumer's hold points.

On completion of core & winding assembly

After fabrication of tank.

At the time of these inspections, the raw materials such as core sheets, winding
conductor, insulating paper, oil and M.S.plate will be verified for quality, by scrutiny
of the documentary evidences for the purchase of these materials from the standard
manufacturers and along with the test certificates.

15 days advance intimation should be given for arranging these inspections.

773

1. TEST AND TEST CERTIFICATE:

43.1. ACCEPTANCE TEST:

The Tenderer should have adequate testing facility at the manufacturer's works so
also arrangement for measurement of losses, resistances, details of which will be
furnished by the tenderer.

All transformers shall be subjected to the tests detailed in Schedule-C at the


manufacturer's works as per IS.2026 and IS.1180, IS.2099, IS.335 & IS.7421 of the
latest issue.

43.2.0. TYPE TESTS:

43.2.1.

(i) Impulse voltage withstand Test as per clause No.13 of IS.2026


(Part-III) / 81.

Impluse voltage withstand test shall be for 125 KV for

22 KV class transformers .

(ii) Dynamic Short Circuit Withstand Test showing No load losses & load
losses at 75 Deg.C.

The above Type Test Certificates should not be dated earlier than
five (5) years as on the date of tender opening.

43.3. ROUTINE TESTS:

The routine test certificate in duplicate for each of the transformer shall be
furnished to the purchaser for approval.

43.4. STRIP TESTS:

43.4.1 One Unit will be subjected to strip test at supplier's premises during the
course of Stage Inspection in accordance with Schedule-C.

43.4.2 2% of the ordered quantity will be subjected to strip test at the


Corporations premises in accordance with Schedule C

43.5. SPECIAL TESTS:

The transformers shall be subjected to any other special tests considered by


the purchaser during the contract period. Cost of such special tests will be borne by
the Purchaser. If the results are not satisfactory, the cost of testing will be
recovered from the supplier besides rejection of the materials.
774

44.0.SCHEDULES

The Tenderer shall fill in the following Schedules which form part of the Tender
Specification & Offer. If the Schedules & Drawings are not submitted duly filled in
with the offer, the offer shall be liable for rejection.

Schedule-A :

Schedule-B : Guarantee Performance Particulars.

Schedule-C : Tests to be carried out including Quality Plan Enforcement.

Schedule-D : Declaration Form.

Schedule-E : Statement of Supply orders executed/under execution during the


past three years

Schedule-F : Guaranteed Values to be adopted by the Tenderer, comprising 4


Drawings & One Statement.

Schedule-G : Questionnaire-A & B

Schedule-H : Measurement of Core & Winding for 500 KVA/11 KV/433V


Distn.Transformer

45. DRAWINGS:

Actual dimensional General Arrangement Drawing and Internal Assembly


Drawings in line with Schedule-F should be furnished along with the tender.

****

775

TESTS TO BE CARRIED OUT INCLUDING QUALITY PLAN ENFORCEMENT

The completely assembled transformers & accessories shall be subjected


to the following tests at manufacturer's works. Government Institutes/Undertaking
before supply, except where otherwise stated, in accordance with I.S.2026. I.S.1180
(Part-I). I.S.2099 and I.S.335 of the latest issue.

iii) ROUTINE TESTS:


(A) Test for polarity
(B) Measurement of winding resistance. (HV & LV)
(C) Measurement of voltage ratio and check of voltage vector relationship
(D) Measurement of Impedance voltage/short circuit impedance (Principal
Tapping) and load loss.

(E) Measurement of No Load Loss and current


(F) Measurement of insulation resistance
(G) Induced over voltage withstand test
(H) Separate source voltage withstand test.

iv) TYPE TESTS :


i.Air pressure test as per I.S.1180/Part-I
ii.Unbalanced current Test. The values of unbalanced current indicated
By the ammeter shall not be more than the percentage limit furnished
In Schedule-F.
iii.Temperature rise test
iv.Lightning Impulse test
v.Dynamic Short Circuit withstand test, showing the No Load Losses and
Load Losses at 75 Deg. C.

The test certificates shall include a statement of efficiency of the transformers


of various loads at unity and 0.8 power factor lag.

TESTS AT SITE:

The purchaser reserves the right of conducting any or all the tests on the
transformers after arrival at site and the contractor shall guarantee the test
certificate figures under actual service conditions.

A. STRIP TEST :
(1) One Unit will be subjected to strip tests at supplier's promises during the course
of stage inspection by the Third party inspection agency / Corporation Inspection
Engineers authorised by the Corporation. The transformers are liable to be rejected
if purchase order requirement are not met in respect of the minimum / maximum
values specified in the P.O. or Guaranteed Technical & Performance particulars.

776

(2) Corporation is at liberty to conduct strip test for 2% of the ordered quantity
subject to a minimum of one number at Corporations site in the presence of
suppliers representative and the special committee constituted by the Corporation
within 15 days from the date of receipt of intimation from the Superintending
Engineer/MM-II. If it is found that the distribution transformer is not meeting the
Specification requirements and the values specified in the Purchase order or
Guaranteed Technical & Performance particulars, all the transformers in that
particular consignment are liable to be rejected.

(3) Dismantling and reassembling charges will be borne by the supplier. However
minor facilities such as drying oven , oil filters, cranes etc., needed for conducting
the strip test and subsequent reassembly by the supplier shall be provided by the
consignee Superintending Engineers free of cost.

QUALITY PLAN:

Stage inspection will be carried out by the purchaser's representative at the


following consumer's hold points.

(d) On completion of core & winding assembly


(e) After fabrication of tank

At the time of these inspections, the raw materials such as core sheets,
winding conductor, insulating paper, oil and M.S.Plate will be verified for quality, by
scrutiny of the documentary evidences for the purchase of these materials from the
standard manufacturers and along with the test certificates.

15 days advance intimation should be given for arranging these inspection.

777

GUARANTED VALUE TO BE ADOPTED BY THE TENDERERS:

-----------------------------------------------------------------------------------------------------

Sl. Details Value

No. 1000 KVA/22 KV

-------------------------------------------------------------------------------------------------------

1. a) No-Load Losses (watts) (*) :

with IS. tolerance

b) Magnetising current in percentage of

rated full load current at rated voltage.

(with IS tolerance) : 1.5 %

(i) Magnetising current in percentage of


rated full load current at 112.5 %

of rated voltage. (with IS tolerance) : 3%

(ii) Power factor of magnetising current


(lag - maximum) : 0.2

(iii) Neutral current measured by Ammeter.


(max) in % of full load current : 2%

2. Full load loss at rated (*)


full load current at 75 Deg. C : + IS Tolerance

at Principal tapping (watts) :

3. Percentage impedence at 75 Deg.C. : 5 % + IS Tolerance

4. Minimum qty of oil for first filling after


absorption by core & windings. (litres) :

5. External Clearance of Bushing Terminals

in mm (minimum)

778

(a) HV Phase to Phase :

(b) HV Phase to Earth :

LV Phase to Phase :

(d) LV Phase to Earth :

6. Maximum flux density at normal voltage

and frequency at any point.

(weber /sq. m) (max) : 1.55

7. Maximum temperature rise of

a) Windings by resistance Deg. C : 55

b) core by thermometer : 55

c) Oil by thermometer : 45

d) Ambient temperature over which

Temperature rise is calculated : 50

--------------------------------------------------------------------------------------------

Sl. Details Value

No. 1000 KVA/22 KV

----------------------------------------------------------------------------------------------------

8. Tank test pressure (Kg/sq cm) (minimum) : 0.35

9. Thickness of paper insulation for tap lead

in mm (minimum) : 1.5

10. Weight of the following (Kg)

(a) Core (tolerance 1 % ) :

779

(b) Windings (tolerance 1 %) :

a. Dimensions of the inter connecting pipe


between conservator & Tank (Nominal) : 50 mm

b. Explosion vent :
a) Pipe Dia (Nominal) : 70 mm

b) Diaphragm material : Hylam

c) Diaphragm thickness (maximum) : 0.3 mm

d) Distance between wiremesh and the

Diaphragm (Minimum) : 12 mm

e)Breather:

Capacity in Grams : 500 Gram

Body material : Diecast aluminium or Poly

propylene

Inside container material : Tin sheet

14. Bushing Rod :

a) HV material : brass

HV dia : mm

b) LV material : copper

LV dia : mm

23. Nuts for bushing rods


HV materials : brass

HV Nos. : 3+3

LV materials : brass

LV Nos. :4+4

780

15. Number of Turns

a) LT :

b) HT :

SIGNATURE OF THE TENDERER

781

MEASUREMENTS OF CORE & WINDINGS

FOR 1000 KVA/ KV /433V DISTRIBUTION TRANSFORMER

DESCRIPTION As per Technical As per offer


Specification

CORE

A LEG CENTRES mm

B WINDOW HEIGHT mm

C CORE CIRCLE mm

D NO OF STEPS

EFFECTIVE CORE AREA sq.mm

LV COIL

E/F OUTER / INSIDE DIAMETER mm

G AXIAL LENGTH mm

CONDUCTOR CROSS SEC. Sq.mm

LV STRIP SIZE (BARE) AXIAL (a) mm

BREADTH(b) mm

NO OF CONDUCTORS IN LV

LV INTERLAYER CLEARANCE mm

LV STRIP ARRANGEMENT

HV COIL NO. OF HV COIL PER PHASE

H/I OUTER /INSIDE DIAMETER MM

J AXIAL LENGTH mm

CONDUCTOR CROSS SEC. Sq.mm

HV/LV CONDUCTOR INSULATION


COIL
INSULATION BETWEEN TAP COILmm
K
BASE FLAT INSULATION mm

782

L RADIAL CLEARANCE BETWEEN CORE

M AND LV COIL mm

WEDGES BETWEEN HV & LV COILS


NO.
N
GAP BETWEEN HV & LV mm
O
FRAME CHANNEL INSULATION mm
P
PHASE BARRRIER mm
Q
END INSULATION BLOCK mm
R
CLEARANCE TO TANK WALL FROM HV
S
WDG

BOTTOM FRAME SIZE mm x mm


T
BASE CHANNEL SIZE mm x mm
U
NO OF SPACERS BET HV COIL /
V CIRCLE

THICKNESS OF SPACERS mm

W INTER PHASE CLEARANCE mm

X TIE RODS SIZE & No.

Y KEY STUD SIZE & No.

Z TAP CHANGER +3 TO (-) 9 %

SIGNATURE OF TENDERER.

783

S-ar putea să vă placă și