Sunteți pe pagina 1din 13

This article was originally published in a journal published by

Elsevier, and the attached copy is provided by Elsevier for the


authors benefit and for the benefit of the authors institution, for
non-commercial research and educational use including without
limitation use in instruction at your institution, sending it to specific
colleagues that you know, and providing a copy to your institutions
administrator.
All other uses, reproduction and distribution, including without
limitation commercial reprints, selling or licensing copies or access,
or posting on open internet sites, your personal or institutions
website or repository, are prohibited. For exceptions, permission
may be sought for such use through Elseviers permissions site at:

http://www.elsevier.com/locate/permissionusematerial
John Kueck has been an electrical
engineer with Sargent and Lundy
Engineers, Combustion Engineering,
and Carolina Power and Light. From
1992 to present, he has been a researcher
at the Oak Ridge National Laboratory in
issues regarding grid reliability,
restructuring, and distributed energy.

py
Brendan Kirby is a senior power
system researcher at the Oak Ridge
National Laboratory with 30 years
Reactive Power from

co
experience and over 100 publications,
including many in The Electricity
Distributed Energy
Journal. His research interests include
bulk power system reliability, demand
response, and wind integration.
Distributed energy is an attractive option for solving
reactive power and distribution system voltage problems

al
D. Tom Rizy is a senior research
electrical engineer at Oak Ridge because of its proximity to load. But the cost of retrofitting
National Laboratory and a reviewer for DE devices to absorb or produce reactive power needs to be
on
the IEEE Transactions on Power
Systems. He has over 28 years reduced. There also needs to be a market mechanism in
experience in power systems R&D and place for ISOs, RTOs, and transmission operators to
received his MSEE and BSEE from
rs

Virginia Tech and the University of procure reactive power from the customer side of the meter
Virginia, respectively. where DE usually resides.
pe

Fangxing (Fran) Li received his Ph.D.


from Virginia Tech in 2001 and worked John Kueck, Brendan Kirby, Tom Rizy, Fangxing Li and
at ABB in Raleigh, North Carolina, as Ndeye Fall
a Senior and then a Principal R&D
Engineer. He has been an Assistant
Professor at The University of
Tennessee (UT) at Knoxville, and an
r's

I. Introduction voltage droop. To correct this


adjunct researcher at Oak Ridge
lagging power flow, leading
National Laboratory since August
2005. Reactive power, measured in reactive power (current leading
volt-amperes reactive or VARs, is voltage) is supplied to bring the
o

Ndeye K. Fall is an electrical engineer one of a class of power system current in phase with voltage.
th

with Energetics Incorporated, a


technical and management consulting
firm headquartered in Columbia,
reliability services collectively
known as ancillary services.
Ancillary services are essential for
R eactive power can be sup-
plied from either static or
dynamic VAR sources. Static
Maryland. She conducts on-site
Au

assessments of distributed energy the reliable operation of the bulk sources are typically transmission
applications in the United States and power system. Reactive power and distribution equipment, such
around the world and has written over flows when current leads or lags as static VAR compensators or
75 articles on electric transmission and
behind the voltage; typically, the capacitors at substations, and
distribution.
current lags because of inductive their cost has historically been
loads like motors. Reactive power included in the revenue require-
flow wastes energy and trans- ment of the transmission owner
mission capacity, and causes (TO), and recovered through

December 2006, Vol. 19, Issue 10 1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007 27
system sales. The role of reactive
power in maintaining system
reliability, especially during
unforeseen system contingencies,
is the reason for the growing
interest by regulators and system
operators alike in alternative
reactive power supplies.

py
In order to study the economic
benefits of using DE for reactive
power support service, it is nece-

co
ssary to know their capabilities,
their cost, and the possible revenue
Figure 1: Total Installed Capacity by DE Technology2 Smaller than 5 MW3
stream from consumers of reactive
power services. The cost of pro-
cost-of-service rates. By contrast, static devices like capacitors can- viding reactive power includes
dynamic sources are typically not match. In addition, DE sup- capital costs as well as operating

al
energy producers, including plies are usually located near costs, such as for operations and
generators capable of producing loads, which is the most effective maintenance (O&M). Although
on
both real and reactive power, and place to supply reactive power. the capital costs of capacitors and
synchronous condensers, which Improving the power factor of the other static devices are much lower
produce only reactive power. The load significantly improves the than for generators and network
rs

equipment may be owned either reliability and efficiency of power VAR devices, they are far less
by TOs or independent entities.1 system operation. Adequate local, functional, cannot adapt to rapid
Figure 12,3 shows that there is a dynamic reactive supply can changes during system contin-
pe

surprisingly large amount of dis- greatly increase the margin to gencies, nor provide variable
tributed energy installed in the voltage collapse. reactive power.
United States. If we conserva-
tively assume that 5 percent of the
total is available for conversion to
Evaluating the economics of
reactive power compensation is
complex, since there are no stan-
S ome small generators have
been tested and have the
capability to be dispatched as a
r's

supply reactive power, we would dard models or analysis tools and source of reactive power supply if
have over 10,000 MVAR of reac- no fully functioning markets for appropriately modified. There are
tive power capability. For com- reactive power in the U.S., mean- also some instances, typically in
parison purposes, the entire New ing data on costs and benefits is urban centers, where there is a
o

England Independent System difficult to find. It is an emerging need for dynamic reactive power
th

Operator has approximately area of analysis that is just begin- supplies and DE-based reactive
12,000 MVAR of available reactive ning to attract the attention of power service shows competitive
power capacity. researchers and analysts. This is payback periods.
Au

W hile the potential for DE-


based reactive supply is
great, presently the costs are
not surprising, given that the rev-
enue flow associated with reactive
power is less than 1 percent of the
For DE to become widely used
as a reactive power resource, the
cost of modifying these devices to
higher than other readily avail- total U.S. electricity market. provide reactive power needs to
able technologies, such as capa- However, the importance of reac- be reduced and system operators
citors. However, DE-based tive power as a component of a must develop a compensation
reactive supplies can provide reliable power grid is not mea- plan for a local voltage regulation
dynamic support capabilities that sured by its market share of power service.

28 1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007 The Electricity Journal
A. Hidden economic
benefits. Other hidden
economic benefits are briefly
discussed here. To help the reader
understand these benefits, a
simple two-bus system shown in
Figure 2 is used to illustrate the
benefits. In the figure there is a

py
generation bus, a load bus, and a
line connecting the two buses. The Figure 3: The Original and New Transfer Capability Considering a Certain Security Margin
generation bus represents a

co
generation center, the load bus output from the expensive IPP Interest in voltage support and
represents a load center, and the generator may be reduced. Thus, reactive power compensation
line represents an inter-tie or an the total system cost will be issues increased considerably as a
interface between the two areas. reduced and the LSE utility will result of the August 2003 blackout
The tie line is congested due to the pay less to serve the same load. affecting the Northeast and Mid-
maximum transfer capability
F urther, the local VAR injec- west, which identified failure of

al
between two areas. We assume tion may benefit the LSE the LSEs to monitor and manage
the generation center has a cheap utility because the transfer cap- reactive reserves for various con-
on
unit with a cost of $20/MWh. The ability of the tie line will be tingency conditions as a causative
load center has a large amount of increased due to the local VAR element.4 Based on this analysis
load, served by a utility as a load- compensation. As indicated in the Federal Energy Regulatory
rs

serving entity (LSE), and an Figure 3, the local VAR compen- Commission (FERC) staff under-
expensive unit, owned by an sation in the stressed area may took a more detailed analysis of
independent power producer increase the maximum transfer reactive power compensation
pe

(IPP), with a cost of $25/MWh. capability constrained by voltage issues, an effort that recently
The original import into the stability. This increase of transfer culminated in release of a report
load center is Pim + jQim. If there is capability indicates that addi- entitled Principles for Efficient and
a local VAR injection (Qc in the tional cheap MW can be delivered Reliable Reactive Power Supply and
figure), the flow at the receiving from the generation center with- Compensation1
r's

end will be reduced to Pim + out compromising the tie line Dynamic reactive power may
j(Qim QC). If the same MVA stability. Hence, the expensive be provided by devices in the
transfer limit is maintained, then unit may be dispatched at lower following three categories:
we can send more real power over output achieving lower overall  Pure reactive power compen-
o

the tie-line since the reactive cost. The total production cost sators such as synchronous con-
th

power flow has been reduced. will be reduced further and, densers and solid-state devices
Therefore, more MW can be eventually, the LSE utility such as static VAR compensators
dispatched from the cheap will pay less money to purchase (SVC), static compensators
Au

generation center. Hence, the electricity. (STATCOM), D-VAR, and


SuperVAR. These are typically
considered as transmission
service devices.
 DE with oversized generators
or inverters to provide a broader
range of reactive power. These DE
Figure 2: A Two-Bus System Technologies include diesel

December 2006, Vol. 19, Issue 10 1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007 29
engine generators, fuel cells,
microturbines, etc. Convention-
ally, they are purchased to pro-
vide backup real power (MW)
supply under emergency with a
limited range of reactive power
output. To increase the capability
of supplying reactive power,

py
some upgrades are necessary
such as oversizing the generator
for diesel engine generators and

co
oversizing the inverters for fuel
cells and microturbines.
 Adjustable-Speed Motor
Drives (ASDs) to supply reactive
power. Adjustable-speed drives
Figure 4: Average Costs of Reactive Power Technologies
are inverter-based devices that

al
change the voltage magnitude
and frequency at the motor tors drops off when it is most dynamic reactive power. An
on
terminals. Adjustable-speed needed. The cost of providing estimate of cost of these technol-
drives save energy because reactive power from non-gener- ogies is also given.
motors that drive pumps or fans ating reactive power devices is
rs

can be easily controlled to supply basically their capital cost and A. Synchronous condensers
a precise amount of water or air O&M expense, as they have no
that is needed, without wasted fuel requirements. In the case of A synchronous condenser is a
pe

energy. New ASD designs can adjustable-speed drives, or gen- synchronous motor that can be
control their power factor. ASDs erators used in CHP or back up controlled to generate or absorb
can draw a leading power power applications, the capital reactive power by changing its
factor and still provide full power cost may have already been field excitation. The synchronous
output to the motor without a amortized in the purchase of the condenser can also dynamically
r's

reduction in service if they equipment for its primary pur- supply reactive power and adjust
are designed to carry extra pose, that is, controlling pump its output depending on system
current. motor speed, combined heat and conditions. The synchronous

A s far as costs go, the capital power, or back-up generation. machines are costly to purchase
o

costs of static power Figure 4 is an estimate of the initially, and they have internal
th

sources such as capacitors are cost regimes for various losses, which present a continu-
much lower than the capital costs nongeneration reactive power ous operating cost. Generally, an
of dynamic sources such as the sources. average cost for synchronous
Au

SVC or D-VAR; however, a condensers varies from $10 to $40


capacitor is limited since it will per kVAR and maintenance runs
only supply or absorb reactive II. Dynamic Reactive about from $0.4 to $0.8/kVAR per
power in set quantity steps or Power Technologies year. Existing synchronous
increments. In addition, its reac- motors in industrial applications
tive power production drops with This section identifies and could be used for this service
the square of any voltage reduc- describes several of the technol- if they are no longer needed for
tion; reactive power from capaci- ogies capable of producing a process or have excess kVA

30 1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007 The Electricity Journal
capacity. Also, the generator
on existing distributed generators
(DGs) could be used as a syn-
chronous condenser as described
below.

B. Retrofit of engine
generators to a synchronous

py
condenser

Engine generators installed by

co
utilities or end-users for emer-
gency, standby, or peaking pur-
poses have the potential to operate
as synchronous condensers and
provide dynamic reactive power
to the grid. A large portion of these

al
generators are underutilized, as
they are called upon to produce
on
real power output only a portion of
Figure 5: 44.5 kVA Generator D Curve. Source: SSS Clutch Company
the time, e.g., during emergencies
or blackouts. Thus, there may be a
rs

real opportunity to increase their shows an example of a generator attributable to reactive power
utilization and benefit the power D curve. The blue lines projecting production.
grid by enabling dual operation of out from the D curve are used to Several companies make
pe

the generator as a real and reactive calculate the generators reactive clutches that can be installed
power producing technology. power output capability at dif- between generators and
Also, engine generators could ferent power factors (0.4 lagging drivers such as reciprocating
be equipped with oversized to 0.4 leading is shown) given a engines, steam and combustion
generators so that they can supply real power output. turbines. The clutch operates
r's

the needed real power and still


have the capacity to supply reac-
tive power. Technology is avail-
W hen a generator operates
at a lagging or leading
power factor (not unity or 1.0),
by completely disengaging the
prime mover and the generator
when only reactive power is
able to allow many types of higher currents are produced in needed. When active or real
o

generators to be converted into the generator and generator step- power is needed, the clutch
th

synchronous condensers, i.e., up transformer. These higher engages for electric power
sources of reactive power, by currents cause significant losses to generation. When the turbine is
using a clutch. occur from resistive heating or I2R shut down, the clutch disengages
Au

G enerators have limits in


their reactive power cap-
ability set by the different thermal
losses associated with the arma-
ture winding and field winding of
the generator, as well as increased
automatically leaving the
generator rotating to supply
reactive power only for power
limits of their armature, field and eddy currents or stray losses. factor correction, voltage control,
core. These limits are outlined in These losses can be calculated as or spinning reserve. Throughout
the generators capability curve. the real power that is consumed to these changing modes, the
The curve is also called a D produce reactive power and, generator can remain electrically
curve, due to its shape. Figure 5 therefore, a cost that is directly connected to the grid, thus

December 2006, Vol. 19, Issue 10 1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007 31
providing a quick response to smaller footprint than SVCs most important features of the
system demands. because they use power electronics D-VAR system is its overload
instead of capacitors and reactors. ability, which enables it to inject
C. Static VAR compensators STATCOMs have a response time anywhere up to three times its
in the order of microseconds. continuous rating for several
Static VAR Compensators seconds. This feature is particu-
(SVCs) are shunt capacitors and E. Dynamic VAR (D-VAR) larly useful in addressing trans-
reactors connected via thyristors system mission voltage stability

py
that operate as power electronic problems or to improve power
switches. They can consume or The Dynamic VAR (D-VAR1) quality and correct voltage sags of
produce reactive power at speeds system is an advanced STATCOM incoming power sources. D-VAR

co
in the order of milliseconds. One systems can range anywhere from
main disadvantage of the SVCs is 2 MVA to over 100 MVA in size
that their reactive power output and the smallest units cost
varies according to the square of approximately $200,000. The
the voltage they are connected to, price per kVAR varies from
similar to capacitors. So, their $80/kVAr to $100/kVAr for the

al
reactive power capability drops total installed cost depending on
off with the lower voltage. As a the site specifics, and the price
on
result, an SVC has limited ability becomes more competitive as the
to mitigate voltage instability, unit gets larger in size.
leading to voltage collapse situa-
rs

tions. An average cost for SVCs F. SuperVAR


that allow rapid switching
between capacitors and reactors The SuperVAR7 is a high-tem-
pe

varies from $40 to $60 per kVAR. technology, developed by Amer- perature superconductor (HTS)
An SVC with only capacitors cost ican Superconductor.5 The dynamic synchronous condenser
less at $30 to $50 per kVAR. D-VAR is a dynamic FACTS meant to run continuously, cost-
(flexible AC transmission system) ing between $1 million and $1.2
D. Static compensator device with specialized software million. The SuperVAR machine,
r's

(STATCOM) to control reactive power output developed by American Super-


in several sophisticated ways. conductor, dynamically absorbs
STATCOMs are power electro- Its price depends on size. The or generates reactive power,
nics-based SVCs. They use gate D-VAR responds to voltage dips depending on the needs of the
o

turnoff thyristors or insulated gate by dynamically injecting exact grid. The SuperVAR will be rated
th

bipolar transistors (IGBT) to con- amounts of reactive power. The at 10 MVA, but its first prototype
vert a DC voltage input to an AC system can prevent voltage col- being demonstrated at the Ten-
signal chopped into pulses that are lapse and uncontrolled loss of nessee Valley Authority (TVA) in
Au

recombined to correct the phase load when critical transmission Gallatin, Tennessee, is 8 MVA.8
angle between voltage and current. elements fail. It can control The device responds instantly to
While capacitors and reactors cost capacitors and regulate steady- disturbances such as lightning,
$10 to $20 and $20 to $30 per kVAR, state voltages and provides reac- short circuits, and equipment
respectively, STATCOMs cost $55 tive power support to wind failures. It allows pure voltage
to $70 per kVAR in large systems farms.6 The D-VAR also protects regulation on a continuous basis,
sized at 100 MVAR or more. critical manufacturing operations mitigates voltage flicker, and
STATCOMs have a slightly from voltage sags. One of the provides power factor correction.

32 1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007 The Electricity Journal
TVA installed the first prototype
of the machine to mitigate a flicker
problem from a steel mill.
The cost of installing adjustable-
speed drives is usually amortized
by the energy savings realized by
T he range of payment meth-
ods include: (1) pay nothing
to generators, but require that
the reduction of losses in the air or each generator be obligated to
G. Oversizing the inverter of water flow. Adjustable-speed provide reactive power as a con-
a distributed energy device drives are often paid back in six dition of grid connection; (2)
months or less because of their include within a generators
An inverter that is connected energy savings. Some utilities installed capacity obligation an

py
with a distributed energy device offer rebates for the installation of additional requirement to pro-
such as a fuel cell or a microtur- adjustable-speed drives. To sup- vide reactive power, with the
bine can provide dynamic control ply meaningful levels of reactive generators compensation

co
of real and reactive power. The included in its capacity payment;
solid-state inverters have quicker (3) pay nothing to generators (or
response and a larger reactive include their reactive power
power adjustment range at rated obligations as part of their general
real power than the excitation capacity obligation), but com-
circuit of the synchronous pensate transmission owners and

al
machines. Although convention- load-serving entities for the rev-
ally the range of the reactive enue requirements of transmis-
on
power supply from such devices sion-based solutions; (4)
is limited, it is possible to upgrade determine prices and quantities
the inverters to supply reactive for both generator-provided and
rs

power in a much larger range. transmission-based solutions


Oversizing of the inverter can through a market-based approach
significantly increase the range of such as a periodic auction (for
pe

reactive power supply. Basically, power, the inverter would need to reactive power capability) or an
the approximate marginal cost be oversized as described above. ongoing spot market (for short-
per kVAR is about $56 to $93/ term reactive power delivery);
kVAR and this marginal cost and (5) centrally procure (such as
increases as the reactive power III. Compensation for on a zonal basis) reactive power
r's

capability is increased. Reactive Power capability and/or supplies


according to a cost-based10 pay-
H. Adjustable-speed drives The nature of the market for ment schedule set in advance.11
participants providing reactive
P rovision of static reactive
o

Adjustable-speed drives are power supply e.g., generator, power supply through
th

devices that use inverters to transmission owner, load-serving capacitors and load tap changers
change the voltage magnitude entity (LSE), or end-use customer is generally arranged for by
and frequency at the motor will determine whether a solid LSEs/electricity distribution
Au

terminals. Adjustable-speed business case can be made for companies (EDCs) as a normal
drives are excellent energy savers entering the reactive power sup- part of distribution network
because motors that drive pumps ply market. This discussion planning and operations. The
or fans can be controlled to supply focuses on regions of the country institutional arrangements for
just the flow of water or air that is that have implemented wholesale providing reactive power supply
needed, with tremendous energy competition and created system/ from static devices are straight-
savings.9 Reactive power could be transmission operation organiza- forward, as they are an asset
supplied at the drive terminals. tions (Table 1). owned by LSEs or EDCs. These

December 2006, Vol. 19, Issue 10 1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007 33
py
34
1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007

co
Table 1: Regional Comparison of ISO/RTO Arrangements for Reactive Power Compensation
Required Power Factor
Method of Compensating Provisions for Testing/Confirming Capability Range Compensation for Annual Reactive
Generators for Reactive Power Capability of for Generators Annual Payment to Lost Profits on Power Service
Region Reactive Power Supply Generators and Other Facilities (leading/lagging) Generator Real Energy Sales Requirement

al
PJM Payment equal to revenue Capability test every 5 years 0.95/0.90 $2,430/MVARa Yes $185,957,688b
requirement
approved by FERC
on
NYISO Capacity Capability test once a year 0.95/0.90 $3,919/MVAR Yes $61,000,000c
d
CAISO No compensation for Tests are not normally run unless 0.95/0.90 None Yes None
operating within ISO detects a problem
power factor range
rs

ISO-NE Capacity Capability test every 5 years 0.95/0.90 $1050/MVAR Yes $12,514,950e
SPP Pass-through of revenues collected Control area operators negotiate Not available Not available Not available Not available
by control area operators with generators
pe

MISO Payment equal to revenue Control area operators negotiate 0.95/0.95 Generator revenues are No Not available
requirement approved by FERC with generators aggregated by
pricing zone
ERCOT No capacity payment Capability test every 2 years 0.95/0.95 Paid the avoided Yes None
cost of DVAR
or equivalent equipment
a
Dividing the total zonal revenue requirement by the total gross lagging MVAR capability at maximum power output for all generators in the zone yields rates ranging from $1005/MVAR-year to $5907/MVAR-year with an average zonal rate
or $2,430/MVAR-year. Source: http://www.pjm.com/committees/working-groups/rswg/downloads/20050520-item-1-reactive-compensation.pdf.
r's

b
Available at http://elibrary.ferc.gov/idmws/common/OpenNat.asp?fileID=10443890.
c
F. Alvaredo et al., Reactive Power as an Identifiable Ancillary Service, Mar. 2003, available at http://web.ta-alberta.ca/tar/ReactivePowerasIdentifiableAncillaryService.pdf.
d
The Electricity Journal

The only true VAR support payment from the ISO to a VAR provider is a special contract covering some privately owned synchronous condensers near Contra Costa, California. Source: Email communication with Dave Timpson, CAISO.
e
ISO-NE VAR Status Report Aug. 1, 2005, states there are 11,919 MVAR of qualified generator VARs. The capacity payment is $1050/MVAR-year for a total of $12,514,950; see http://www.iso-ne.com/stlmnts/iso_rto_tariff/schd2/
var_status/2005/VAR%20Status_08_2005.rtf.
o
th
Au
devices are simply put into the from generators and the arrange- must rely on retail regulator
utilitys rate base and fixed and ments for acquiring reactive approval of a rate base for
variable costs are recovered via power supply from transmission- recovery of the investment and
retail rates of the customers based sources owned by trans- variable costs. A DG or other DE
served. A similar arrangement mission owners/providers. A device would have to either be
can be used for the capital costs of transmission owner who mitigates approved as a source of reactive
dynamic transmission-based a reactive power compensation power supply under Schedule 2,
devices (STATCOMs and SVCs) problem by investing in a trans- including testing requirements

py
placed in operation by transmis- mission-based reactive power and automatic voltage regulation
sion owners. provision will be able to rate base (AVR), or rely on negotiations

G enerally speaking, ISOs, the investment, but at the present with their LSE for a compensation

co
RTOs, and TOs do com- arrangement. Each situation will
pensate generators (both affiliates call for a different economic eva-
of vertically integrated utilities luation framework.
and independent power produ-
cers, or IPPs) for providing reac-
tive power. The institutional
S everal of the RTOs notably
ISO-NE, PJM, NYISO are
addressing this disparity in pay-

al
arrangement provides compen- ment provisions for generators
sation using a cost-based sche- and all other sources of reactive
on
dule set in advance, usually a power supply. These RTOs are
payment equal to the generation attempting to create a more level
owners monthly revenue playing field by applying the
rs

requirement. In exchange, the principle of consistent compen-


generators must be under the sation for similar supply types.
control of the control area opera- The objective is a single and
pe

tor and be operated as dispatch- may not receive any Schedule 2 consistent compensation
able to produce or absorb reactive compensation from the RTO. This approach for all types of reactive
power. In some cases, when there is despite the possibility that power sources that would replace
is a reduction in real power out- transmission-based solutions may the generator-specific Schedule 2
put due to a request for reactive be a least-cost alternative for now in effect.
r's

power production, the RTO will reactive power supply and be


provide an additional payment to more valuable during system
compensate the generator for the contingencies. The situation for IV. Locational Pricing
lost opportunity of delivering real reactive power producing DE is for Reactive Power?
o

power into the network. Cost- even more ambiguous.


th

based compensation to generators Institutional arrangements Locational reactive power pri-


for providing reactive power directly affect the economic fra- cing should encourage efficient
supply is regulated by FERC, and mework for evaluation of invest- locational siting of new distribu-
Au

all ISOs/RTOs must provide a ments in providing reactive ted energy. New generation siting
Schedule 2 tariff for reactive power supply. Although a gen- decisions are often based on real
supply and voltage control as part erator can rely on a stream of power prices and incentives.
of their Open Access Transmis- Schedule 2 capacity payments However, new real power gen-
sion Tariff (OATT). based on the revenue required for eration that displaces existing real
There is a significant disconnect their reactive power supply power resources may place an
between the arrangements for operations, a transmission provi- increased burden on the systems
procuring reactive power supply der installing a STATCOM or SVC need for reactive power due to its

December 2006, Vol. 19, Issue 10 1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007 35
location on the network. Alter- considered by some ISOs is a preparation of the report upon
natively, new generation might single, blanket price to be paid for which this article is based; com-
choose locations that reduce sys- reactive power regardless of pensation methods for reactive
tem reactive power needs if the location, and then dispatching the power are changing quickly, and
reactive power pricing incentives reactive power as needed by the the reader should not be sur-
are apparent. Because reactive system operator to control voltage prised to find that specific pay-
power losses in transmission lines and ensure adequate reactive ments for his location differ from
are very high, generators near reserves. This approach certainly the methods provided here.

py
loads can supply reactive power simplifies the market operation,
with much lower losses than but it loses the incentive men- A. PJM
generators located long distances tioned above to place new gen-

co
from loads. The systems reactive PJM Interconnection, LLC (PJM)
power needs and costs might be compensates all generators (affili-
addressed through improved ates of investor-owned utilities
pricing mechanisms that encou- and independent power produ-
rage siting decisions that are cers) with a payment equal to the
consistent with the systems generation owners monthly rev-

al
reliability needs. enue requirements as accepted or
approved by FERC.13 Dividing the
T he system operator could
on
hold an auction for reactive total zonal revenue requirement
power capacity in which suppli- by the total gross lagging MVAR
ers would be compensated for a capability at maximum power
rs

commitment to make reactive output for all generators in the


power capacity available to the zone yields rates ranging from
system. This approach allows $1,005/MVAR-year to $5,907/
pe

competition among generation eration with the ability to supply MVAR-year with an average zonal
and transmission elements to reactive power in locations where rate of $2,430/MVAR-year. PJM
supply reactive power needs. it is most needed. also provides lost-opportunity
Requirements would likely be set cost payments when there is a
locally, based on the needs reduction in real power output.
r's

determined by the system opera- V. Examples of Reactive These costs are filed with and
tor. This would allow prices to Power Compensation approved by FERC and are allo-
reflect the locational value of cated to network transmission
reactive power capacity and This section identifies and service customers in the zone
o

avoid paying for excess capacity documents examples of reactive where the generator is located.
th

in areas that do not need it.12 The power compensation service


locational zones for reactive market development, adminis- B. ISO-NE
power would most likely be trative solutions, or regulatory
Au

smaller than the zones for real frameworks in wholesale markets ISO New England Inc. (ISO-
power because reactive power (transmission level). In particular, NE) compensates generators
does not travel well and the need it identifies well-developed based on four components: (1)
is locational in nature. Smaller examples/designs for obligatory capacity costs: the fixed capital
zones would mean that a larger reactive power service or market- costs incurred by a generator
number of zones would be based reactive power services. associated with the installation
required, and this adds to market Please note that these examples and maintenance of the capability
complexity. An option being were correct at the time of the of providing reactive power; (2)

36 1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007 The Electricity Journal
lost opportunity costs: the value transmission owners for provid- least the range of power factors of
of the generators lost opportunity ing reactive power, but has no 0.95 leading or lagging, measured
cost in the energy market where a mechanism to compensate IPPs.16 at the units main transformer
generator would otherwise be high-voltage terminals. There is no
dispatched by ISO-NE to reduce D. NYISO compensation for reactive power
real power output to produce service within this range. Genera-
reactive power; (3) cost of energy The New York Independent tors receive a variable payment of
consumed: the cost solely to pro- System Operator Inc. (NYISO) $2.65 per MVAR-hr for MVARs

py
vide reactive power support, such compensates all large, conven- beyond 0.95 leading/lagging.18
as the energy for motoring a tional generators for reactive
hydroelectric generating unit; and power, but those owned by utili- F. SPP

co
(4) cost of energy produced: the
portion of the amount paid to The Southwest Power Pool
market participants for the hour Inc.s (SPP) compensation for
for energy produced by a gener- reactive power is a pass-through
ating unit that is considered of the revenues collected by
under the Schedule 2 to be paid individual control operators.19

al
for VAR support. ISO-NE pro- Each control area operator shall
vides $1,050 per MVAR-year for specify a voltage or reactive
on
reactive compensation and cur- schedule to be maintained by each
rently has 11,919 MVARs avail- synchronous generator at a spe-
able to receive capacity payments. cified bus. Generators shall be
rs

This translates to an annual able to run at maximum rated


compensation of $12.5 million.14 reactive and real output accord-
ing to each units capability curve
pe

C. MISO ties are compensated differently during emergency conditions for


from non-utility generators (or as long as acceptable frequency
The Midwest Independent IPPs) under purchased power and voltages allow the generator
Transmission System Operator agreements. Payments are made to continue to operate. Generators
Inc. (MISO) compensates genera- from a pool consisting of total shall be exempt from this if they
r's

tors owned by transmission costs incurred by generators that meet the following criteria:20
owners for providing reactive provide voltage support service,  Generator output is less than
power. Rates are based on control and 2004 rates were calculated by 20 MW.
area operator rates filed at FERC dividing 2002 program costs of  Generation is of intermittent
o

and are paid where the load is $61 million by the 2002 generation variety (wind generation).
th

located (zonal basis) and loads capacity expected of 15,570


outside MISO are charged an MVAR, resulting in a compensa- G. CAISO
average system-wide rate. MISO tion rate of $3,919 per MVAR-
Au

does not provide for lost-oppor- year.17 In the California Independent


tunity costs for producing reac- Service Operator Corporations
tive power instead of real power. E. ERCOT (CAISO) service territory genera-
Compensation for reactive power tors are required to provide
is treated as a pass-through of In the Electric Reliability Coun- reactive power by operating
revenues from individual control cil of Texas (ERCOT) region, gen- within a power factor range of
area operators.15 MISO compen- erators must be capable of 0.90 lagging and 0.95 leading. The
sates generators owned by providing reactive power over at CAISO tariff states that generators

December 2006, Vol. 19, Issue 10 1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007 37
receive no compensation for  Novel compensation 20drive%20energy%20savings%
20doe%22.
operating within this range. methods need to be introduced
10. The cost basis could be actual costs
Generators that are producing real to encourage the dispatch of
for reactive power provision or could
power are required, upon the dynamic resources close to be based on the opportunity costs of
ISOs request, to provide reactive areas with critical voltage providing reactive power in lieu of real
energy output outside their stan- issues.& power.

dard obligation range, for which 11. Principles for Efficient and Reliable
Reactive Power, supra note 1.
they receive lost opportunity costs.

py
Endnotes: 12. Id.
13. Available at http://www.pjm.
1. Principles for Efficient and Reliable com/documents/ferc/documents/
VI. Conclusion Reactive Power Supply and 2005/march/20050311-er05623.pdf.

co
Compensation, FERC Staff Report,
14. Comments from ISO-NE and
Distributed energy or DE is an Docket No. AD-05-01-1000,
NEPOOL Committee to FERC, Apr.
Feb. 4, 2005, available at http://
attractive option for solving www.ferc.gov/EventCalendar/Files/
2005, Docket No. AD05-1-000,
reactive power and distribution available at http://www.iso-ne.com/
20050310144430-02-04-05-reactive-
regulatory/ferc/filings/2005/apr/
system voltage problems because power.pdf.
ad05_1_000_04_04_05isonepool.pdf.
of its proximity to load. Providing 2. Graph includes DE Installations

al
15. FERC Report on Supply and
dynamic reactive power near the smaller than 5 MW only. Source: The
Consumption, Docket AD05-1-000, Feb.
Installed Base of U.S. Distributed
load provides significant eco- Generation, Resource Dynamics
4, 2005, available at http://
on
nomic benefits such as reduced www.ferc.gov/EventCalendar/Files/
Corporation, 2005 Edition.
20050310144430-02-04-05-reactive-
losses, increasing availability of 3. Id. power.pdf.
local generation, and improved
4. U.S.-Canada Power System Outage 16. MISO filed with FERC to
rs

local voltage control. Several Task Force Final Report on the August 14, add a new Schedule 21 to compensate
technology options are available 2003, Blackout in the United States and IPPs separately from Schedule 2
to supply reactive power from Canada: Causes and Recommendations, compensation of utility-owned
pe

Joint US-Canada Power System generation. On June 25, 2004,


DE; these include small genera- Outage Task Force, April 2004, at 17, FERC rejected the specific proposal for
tors, synchronous condensers, available at ftp://www.nerc.com/ Schedule 2 while agreeing that
fuel cells, and microturbines. pub/sys/all_updl/docs/blackout/ generators providing reactive power to
ch1-3.pdf. support the transmission system
They can provide continuous/ should be compensated. This issue is
variable dynamic reactive power 5. Available at http://www.amsuper.
still under adjudication. Midwest
com/products/library/PES_DVR_
r's

which can respond quickly to Independent System Transmission


01_0804a.pdf.
Operator, Inc., Docket No. ER04-961-
reactive power demand.
6. Available at http://www. 000 109 FERC 61,005.

S everal criteria need to be met


for DE to become widely
amsuper.com/products/
applications/windEnergy/
17. Available at http://www.nyiso.
o

com/services/documents/b-and-a/
integrated as a reactive power documents/AMSC_EDF_ rate_2/2005_oatt_mst_sched2_vss_
SuperVARResults2006FINAL.pdf.
th

resource. rates.pdf.
7. Available at http:// 18. Available at http://pjm.com/
 The overall costs of retrofit-
www.amsuper.com/products/ committees/working-groups/rswg/
ting DE devices to absorb or motorsGenerators/quickVAR.cfm.
Au

downloads/20050713-item-2-reactive-
produce reactive power need to 8. Available at http:// compen-comp.pdf.
be reduced. www.amsuper.com/products/ 19. FERC Report on Supply and
 There needs to be a market motorsGenerators/documents/ Consumption, Docket AD05-1-000,
IEEESuperVAR-030910-Paper.pdf. Feb. 4, 2005, available at http://www.
mechanism in place for ISOs/
9. Screening Pumping Systems for ferc.gov/EventCalendar/Files/
RTOs/TOs to procure reactive 20050310144430-02-04-05-reactive-
Energy Savings Opportunities, available
power from the customer at http://eetd.lbl.gov/ea/indpart/ power.pdf.
side of the meter where DE publications/lbnl_53054.pdf 20. Available at http://www.spp.
resides. #search=%22adjustable%20speed% org/Publications/SPP_Criteria.pdf.

38 1040-6190/$see front matter # 2006 Elsevier Inc. All rights reserved., doi:/10.1016/j.tej.2006.10.007 The Electricity Journal

S-ar putea să vă placă și