LOAD LISTING, CALCULATIONS & GENERATOR SIZING

Absorbed Rated Load Nature Continous Intermittent Standby


Sr. Equipment Name Equip ID No Ef cos MCC Remarks
Power Power Factor of Load*
KW KVAR KW KVAR KW KVAR
1 Ana Motor M001 18 18 0.75 0.89 0.8 Main I 20.22 15.17 List
2 Aydnlatma M001 0.072 0.072 0.7 0.85 0.75 Main C 0.08 0.07 C
3 Istma M001 3 3 0.7 0.85 0.75 Main I 3.53 3.11 I
4 Kap Motor M001 0.75 0.75 0.7 0.85 0.75 Main S 0.88 0.78 S
150+KW

###
###
###

Sum 0.08 0.07 23.75 18.28 0.88 0.78

Maximum Load = 100% of continous load + 50% of Intermittent load + 10% of standby or biggest individual load (higher one)

KW KVAR KVA cos Amp Volts


Maximum of normal running load 12 9 15 0.7922 23 380
Peak load 13 10 16 0.7892 25 380

Maximum of normal running load with 10% Growth Factor 13.158 10.137 16.61 0.7922 25 380
Peak load with 10% Growth Factor 14.129 10.993 17.901 0.7892 27 380

Reccemended Generator Size when 70% loading 20.184 15.704 25.573 0.7892 39 380