CONNECTION DESIGN FOR HANDRAIL BASE PLATE TO CONCRETE USING HILTI KB3 ANCHORS
References:
1. Appendix D, ACI CODE 318-08
2. ICC ESR 2302 Reissued December 1, 2011
Given:
Hilti KB3 Concrete Anchors
5
d in h 4 in s 4 in H 3.5 ft
a 8 ef
fc' 5000 psi (For Structural Slabs, per Design Drawing S-1.0)
Assumptions:
1. Cracked concrete conditions assumed.
2. Anchors are considered ductile steel elements. Per ACI D.4.4 Item a,
0.75 0.65
t v
Ultimate Loads:
T 1.6 T V 1.6 V
u u
T 3360 lbf V 320 lbf
u u
N 27030 lbf
t sa
A.2 Concrete Breakout Strength of Anchor in Tension
Verify minimum concrete thickness, edge distance and bolt spacing,
Slab thickness h>8" > min h=8" per Table 3, ESR 2032, OK!
From ESR 2032 Figure 3 and Table 3,
c 1.75 for bolt spacing s 4
min
c c Connection not placed near Edge of concrete, OK!
a min
25 May 2012 16:21:19 - broadway hilti kb3 - handrail base units.sm
2
A 9 h A 3 h 3 h s
NCO ef NC ef ef
2 2
A 144 in A 192 in
NCO NC
N 9616.6522 lbf
b
c 1.5 h 1.0
a ef edN
A
NC (ACI Eqn D-5)
N N
cbg A ecN edN cN cpN b
NCO
N 12822.203 lbf
cbg
V 31798 lbf
v sa
25 May 2012 16:21:19 - broadway hilti kb3 - handrail base units.sm
V 0.2 V 1
u cV cpg Hence, full strength in tension shall be permitted.
Verify if full strength in shear can be permitted,
.2 N 1666.8864 lbf T 3360 lbf
cT cbg u
T .2 N 0
u cT cbg Hence, full strength in shear cannot be permitted.
Interaction Equation,
T V
u u
0.421 1.2 (ACI Eqn D-32)
N V
cT cbg cV cpg