Technical data www.weidmueller.com
Temperatures
Ambient temperature -25 C...+70 C (derating
from 60 C)
Input
Connection range AWG26-12 (0.1-4.0 mm) Input frequency 50/ 60 Hz
Input fuse Fusible link 6 A (T) / 250 V Input fuse (internal) Yes
Input voltage (voltage mode input) 88...132 V AC/176...264 Surge protection
V AC selectable; 250...370
V DC Varistor
Wire connection method Screw connection
output
Connection range AWG26-12 (0.1-4.0 mm) Control at 10...100% load 1%
Mains failure bridge-over time for 115 V Mains failure bridge-over time for 230 V
AC 10 ms AC 15 ms
Max. capacitance at output Max. residual ripple < 100 mVPP / bandwidth
40000 F 20 MHz
Output power 300 W Output voltage type DC
Overload protection 120 % Iconst of max. Parallel connection option
output load; automatic Recommended with diode
reset module
Status relay / CO contact 250 V AC (max. 30 V Surge protection
DC) / 1 A 30...36 V
Wire connection method Screw connection
General data
Ambient temperature -25 C...+70 C (derating DIN Rail compatibility
from 60 C) TS 35
Degree of efficiency at max. load EMC standards EN 55011, EN 55022, EN
55024, EN 61000-6 /-2,
84% -3
Installation advice Clearance: above/below Low Voltage Directive
3 cm 73/ 23/ EWG
Mounting position, installation notice horizontally, on terminal Standards
rail TS 35 DIN EN 60950
Status indication Green LED Weight 1,600 g
Insulation coordination
electrical isolation, input-earth 1.5 kV electrical isolation, input-output 3 kV
electrical isolation, output-earth 0.5 kV
Technical data www.weidmueller.com
Signalling
Status indication Green LED