Documente Academic
Documente Profesional
Documente Cultură
CODE OF PRACTICE
1. Introduction
The University has agreed the following Code of Practice in accordance with
the Dangerous Substances and Explosive Atmospheres Regulations (DSEAR).
The University is responsible for monitoring and reviewing the Code in the
light of further developments and it will be reviewed periodically by the
Health and Safety Committee.
Promote practical measures to minimise the risk to the health, safety and
welfare of staff, students, visitors and others who may be affected by the
work activities of the University
3. Implementation
Dangersubs0106.doc 1
Heads must identify who will be responsible for assessing the risks in their
Department under the Code. These individuals must be competent to carry out
the assessments, recognising their own limitations and seeking specialist
advice where necessary. In practice the person who creates a risk through the
use of a substance as defined in 2. above must at least be involved in the
assessment of that risk. Assessments may well be carried out by Research
Supervisors, Course Tutors, Departmental Safety Officers or line managers.
Those involved in the assessments must be familiar with the requirements of
the DSEAR Regulations and Approved Code of Practice and the Universitys
Code of Practice. They should know where to obtain information on
substances, how they are used and stored, what control measures are
necessary and when to consult others for help and advice.
Completed
Consistent and to a reasonable standard
Relate to the actual work being undertaken
Recorded and where appropriate proper records maintained
Reviewed
Staff and students must cooperate with their Head of Department in making
assessments. They must make full and proper use of any safe system of work,
and/or prescribed control measures, reporting any defects and where
appropriate participate in any monitoring. They must also participate in
training and make full use of information and instructions.
4. Arrangements
Step 1 - Check whether the substance or preparation has been classified under
the Chemicals (Hazard Information and Packaging for Supply) Regulations
(CHIP) as: explosive, oxidising, extremely flammable, highly flammable or
flammable.
Step 3 - Check to see if the work activity involves the creation or handling of
potentially combustible or explosive dusts.
Dangersubs0106.doc 2
Step 5 Provide controls to eliminate or reduce risks as far as is reasonably
practicable. Ensure the controls are implemented and maintained.
Step 7 Classify places where explosive atmospheres may occur into zones
and mark the zones where necessary
5. Assessment
In practice, the generic Risk Assessment form may be used to record the
assessment, but this will need to be supported by the specific DSEAR
assessment form (attached as Appendix 1).
Dangersubs0106.doc 3
The Regulations require that the safety risks from dangerous substances are
eliminated or, where this is not reasonably practicable, measures are taken to
control risks and reduce the harmful effects of any fire, explosion or similar
event, so far as is reasonably practicable. The Regulations identify a hierarchy
of types of protection that must be considered and applied in order of priority,
namely:
5.1 Substitution
This is involves replacing a dangerous substance with a substance or process
that totally eliminates the risk. In practice this may be difficult to achieve and
it is more likely that it will be more practicable to replace the dangerous
substance with one that is less hazardous (e.g. by replacing a low-flashpoint
solvent with a high-flashpoint one). An alternative is to design the process so
that it is less dangerous. This might include, for example, changing the manner
or sequence in which the dangerous substance is added. However, care must
be taken when carrying out these steps to ensure that no other new safety or
health risks are created or increased, which then outweigh the improvements
implemented as a result of DSEAR.
In reality, where the dangerous substance is handled or stored for use as a fuel,
there is often no scope for elimination and very little chance to reduce the
quantities handled. Where risk cannot be entirely eliminated control and
mitigation measures to reduce risk must be applied in the following order of
priority as follows:
Any measures taken to achieve the elimination or the reduction of risk should
take into account the design, construction and maintenance of the workplace
and work processes, including all relevant plant, equipment, control and
protection systems.
Dangersubs0106.doc 4
5.4 Explosive Atmospheres
Heads must ensure that control measures are implemented and maintained.
Controls must be kept in good working order and in good repair. Regular
Dangersubs0106.doc 5
checks should be made to ensure they continue to operate as intended. These
checks include visual checks, inspection, testing, servicing and remedial work
e.g. local exhaust ventilation must be tested at least once every 14 months or
earlier where necessary and a written record kept for at least 5 years.
Staff and students must co-operate and make full and proper use of prescribed
control measures, reporting any defects. They must also participate in training
and make full use of information and instructions.
6. Further Information
Dangersubs0106.doc 6
Dangerous Substances and Explosive Atmospheres Regulations
Specific Risk Assessment
This specific risk assessment process must be completed if the substances that you are
working with, handling or storing are flammable, extremely flammable, highly flammable,
oxidising, explosive, or capable of producing an explosive atmosphere. To be completed in
conjunction with any generic risk assessment for the task/activity being undertaken.
If a proprietary product, does the hazard information contained within the Material
Safety Data Sheet, or on the labelling on the product packaging denote that it is (tick
box):
Extremely Highly
Explosive Oxidising Flammable
flammable flammable
or has a flash point lower than 32oC
or that; release of vapour/gas may produce an explosive atmosphere
Extremely Highly
Explosive Oxidising Flammable
flammable flammable
or has a flash point lower than 32oC
or, could release of vapour/gas/dust produce an explosive
Yes No
atmosphere
If No has been answered to all of the above questions you may terminate the risk
assessment at this point, otherwise continue:
Note here how a work system, or activity could fail and give rise to fire or explosion, also note
any sources of ignition:
Process/activity
Where appropriate to the nature of the activity or operation:
Has the quantity of the dangerous substance held/used been reduced to a minimum?
Yes No
Have steps been taken to avoid, or minimise releases (intentional or unintentional)?
Yes No
Dangersubs0106.doc 7
Control measures (cont)
In the case of explosive atmospheres; (if not applicable tick here and proceed to
storage)
Have all such areas been classified in to zones in accordance with Schedule 2 to the
Regulations?
Yes No
Dangersubs0106.doc 8
Where necessary have such classified zones been marked at their entry points with the
specified EX hazard warning sign?
Yes No N/A
Are all areas classified into such zones appropriately protected from sources of ignition,
through the selection of equipment and protective systems compliant with the Equipment and
Protective Systems Intended for Use in Potentially Explosive Atmospheres Regulations 1996?
Yes No
Are employees working in zoned areas provided with clothing that does not create a risk of
electrostatic discharge?
Yes No
Have areas where explosive atmospheres may be present, before their first operation, been
verified as being safe by a person, or organisation competent in the field of explosion
protection?
Yes No
Storage
Are all flammable substances kept in suitable fire resistant storage and are all quantities in
excess of 50ltrs kept in dedicated and appropriately protected flammable stores?
Yes No
Are all petroleum spirits, or derivatives thereof, in excess of 50ltrs kept in dedicated and
appropriately protected petroleum spirit stores?
Yes No
Are incompatible substances stored apart (e.g. flammables, oxidisers, combustibles,
flammable gases, LPG)?
Yes No
Where appropriate have storage areas been designed to provide explosion relief/resistance?
Yes No N/A
Emergency procedures
Have suitable emergency procedures been developed and communicated to the workforce to
deal with adverse process conditions (e.g. exceeding limits of temperature, or other control
settings)?
Yes No N/A
Have suitable emergency procedures been developed and communicated to the workforce to
deal with fire and evacuation?
Yes No
Have suitable emergency procedures been developed and communicated to the workforce to
deal with the spillage of dangerous substances?
Yes No
Waste disposal
Have suitable procedures been developed, communicated to the workforce and implemented
to deal with the safe transport and disposal of dangerous substances?
Yes No
Where any question relevant to a dangerous substance being used, produced, handled or
stored has returned a No response, the subject area should be revisited to ensure that all
required and reasonably practicable risk reducing measures have been implemented.
Dangersubs0106.doc 9
Conclusion
The risk(s) from the hazard potential of the dangerous substances and/or explosive
atmospheres identified in this risk assessment must be reduced to the lowest level reasonably
practicable, are you satisfied that this is the case? Yes No
this including their handling, storage and ability, in the form that they present in the work
situation, to result in an explosive atmosphere, the following safe system of work (rules of
work) must be observed and adhered to at all times.
Dangersubs0106.doc 10
In the event of an emergency situation actions laid out in the safe system of work that are
designed to minimise damage to equipment or property should only be undertaken if this does
not put yourself or others at significant risk, personal safety and that of others must take
priority.
Dangersubs0106.doc 11