Sprinkler Flow:-

Total flow = Total area x Density


= 139 x 6.1
= 847.9
Per sprinkler flow = Total flow / No sprinkler

Q =

.
=( )

= 847.9/14
= 60.5 Lpm
Flow = A x D
= 10 x 6.1
= 61 Lpm

6.2.3 Duration.
6.2.3.1*Water supplies shall be designed to meet the fixed fire
protection demand plus 250 gpm (946 L/min) for inside and
outside hose streams for at least 60 minutes, unless otherwise
specified in the occupancy standards.
If pump pressure is more than 12.1 bar than source pressure should be as per jockey pump mean 10 psi more than
main pump this rule should follow if you want to take prv input pressure otherwise no need if pump pressure is
below 12.1 bar.