Air System Sizing Summary for Default System

Project Name: sample project 12/30/2014


Prepared by: Mott MacDonald 12:44PM

Air System Information


Air System Name Default System Number of zones 1
Equipment Class CW AHU Floor Area 1000.0 m
Air System Type SZCAV Location Chennai, India

Sizing Calculation Information


Zone and Space Sizing Method:
Zone L/s Sum of space airflow rates Calculation Months Jan to Dec
Space L/s Individual peak space loads Sizing Data Calculated

Central Cooling Coil Sizing Data


Total coil load 223.4 kW Load occurs at Jan 0100
Sensible coil load 220.4 kW OA DB / WB 25.7 / 19.5 C
Coil L/s at Jan 0100 19298 L/s Entering DB / WB 20.8 / 14.5 C
Max block L/s 19298 L/s Leaving DB / WB 11.3 / 10.6 C
Sum of peak zone L/s 19298 L/s Coil ADP 10.0 C
Sensible heat ratio 0.987 Bypass Factor 0.120
m/kW 4.5 Resulting RH 50 %
W/m 223.4 Design supply temp. 14.4 C
Water flow @ 5.6 K rise 9.62 L/s Zone T-stat Check 0 of 1 OK
Max zone temperature deviation 0.1 K

Central Heating Coil Sizing Data


Max coil load 70.2 kW Load occurs at Jan 0900
Coil L/s at Jan 0900 19298 L/s W/m 70.2
Max coil L/s 19298 L/s Ent. DB / Lvg DB 11.3 / 14.3 C
Water flow @ 11.1 K drop N/A

Supply Fan Sizing Data


Actual max L/s 19298 L/s Fan motor BHP 47.93 BHP
Standard L/s 19262 L/s Fan motor kW 35.74 kW
Actual max L/(s-m) 19.30 L/(s-m) Fan static 1000 Pa

Outdoor Ventilation Air Data


Design airflow L/s 0 L/s L/s/person 0.00 L/s/person
L/(s-m) 0.00 L/(s-m)

Hourly Analysis Program v4.50 Page 1 of 1