This document provides an air system sizing summary for a default system serving a 1000 square meter space in Chennai, India. Key details include:
- The central cooling coil is sized to handle a peak cooling load of 223.4 kW occurring in January, with a resulting supply air temperature of 14.4 degrees Celsius.
- The central heating coil is sized for a maximum heating load of 70.2 kW also occurring in January, with supply air leaving at 14.3 degrees Celsius.
- The supply fan is sized for a maximum airflow of 19,298 liters per second to deliver the required airflow, requiring a 47.93 brake horsepower motor.
This document provides an air system sizing summary for a default system serving a 1000 square meter space in Chennai, India. Key details include:
- The central cooling coil is sized to handle a peak cooling load of 223.4 kW occurring in January, with a resulting supply air temperature of 14.4 degrees Celsius.
- The central heating coil is sized for a maximum heating load of 70.2 kW also occurring in January, with supply air leaving at 14.3 degrees Celsius.
- The supply fan is sized for a maximum airflow of 19,298 liters per second to deliver the required airflow, requiring a 47.93 brake horsepower motor.
This document provides an air system sizing summary for a default system serving a 1000 square meter space in Chennai, India. Key details include:
- The central cooling coil is sized to handle a peak cooling load of 223.4 kW occurring in January, with a resulting supply air temperature of 14.4 degrees Celsius.
- The central heating coil is sized for a maximum heating load of 70.2 kW also occurring in January, with supply air leaving at 14.3 degrees Celsius.
- The supply fan is sized for a maximum airflow of 19,298 liters per second to deliver the required airflow, requiring a 47.93 brake horsepower motor.
Air System Name Default System Number of zones 1 Equipment Class CW AHU Floor Area 1000.0 m Air System Type SZCAV Location Chennai, India
Sizing Calculation Information
Zone and Space Sizing Method: Zone L/s Sum of space airflow rates Calculation Months Jan to Dec Space L/s Individual peak space loads Sizing Data Calculated
Central Cooling Coil Sizing Data
Total coil load 223.4 kW Load occurs at Jan 0100 Sensible coil load 220.4 kW OA DB / WB 25.7 / 19.5 C Coil L/s at Jan 0100 19298 L/s Entering DB / WB 20.8 / 14.5 C Max block L/s 19298 L/s Leaving DB / WB 11.3 / 10.6 C Sum of peak zone L/s 19298 L/s Coil ADP 10.0 C Sensible heat ratio 0.987 Bypass Factor 0.120 m/kW 4.5 Resulting RH 50 % W/m 223.4 Design supply temp. 14.4 C Water flow @ 5.6 K rise 9.62 L/s Zone T-stat Check 0 of 1 OK Max zone temperature deviation 0.1 K
Central Heating Coil Sizing Data
Max coil load 70.2 kW Load occurs at Jan 0900 Coil L/s at Jan 0900 19298 L/s W/m 70.2 Max coil L/s 19298 L/s Ent. DB / Lvg DB 11.3 / 14.3 C Water flow @ 11.1 K drop N/A
Supply Fan Sizing Data
Actual max L/s 19298 L/s Fan motor BHP 47.93 BHP Standard L/s 19262 L/s Fan motor kW 35.74 kW Actual max L/(s-m) 19.30 L/(s-m) Fan static 1000 Pa