TERTIARY-WINDING OVERCURRENT
PROTECTION BASIC INFORMATION
During external system ground faults, tertiary windings may carry very heavy currents.
Hence, to guard against failure of the primary protection for external ground faults,
separate tertiary overcurrent protection may be desirable.
The method selected for protecting the tertiary generally depends on whether or not the
tertiary is used to carry load. If the tertiary does not carry load, protection can be provided
by a single overcurrent relay connected to a CT in series with one winding of the .
This relay will sense system grounds as well as phase faults in the tertiary or in its leads.
When tertiary windings are connected by cables, the overcurrent protection provided to
the tertiary winding should account for the thermal withstand of the cables.
Alarming and tripping as a result of a prolonged unbalance condition or load tap changer
malfunction should prevent damage to cables. If the tertiary is used to carry load, partial
protection can be provided by a single overcurrent relay supplied by three CTs, one in
each winding of the and connected in parallel to the relay.
This connection provides only zero sequence overload protection and does not protect for
positive and negative sequence overload current. In this case, the relay will operate for
system ground but will not operate for phase faults in the tertiary or its leads.
Where deemed necessary, separate relaying such as differential type should be provided
for protection for phase faults in the tertiary or its leads. The setting of the tertiary
overcurrent relay can normally be based on considerations similar to those in line time
overcurrent.
However, if the tertiary does not carry load, or if load is to be carried and the
three CT, zero sequence connection is used, the associated overcurrent relay can
be set below the rating of the tertiary winding. This relay should still be set to
coordinate with other system relays.
No comments:
Post a Comment
Previous Articles
2013 (1)
November (1)
2012 (166)
November (11)
TERTIARY-WINDING OVERCURRENT PROTECTION BASIC INFO...
DIFFERENTIAL PROTECTION OF AUTOTRANSFORMERS USING ...
PROTECTIVE RELAY CURRENTS EXPERIENCED BY POWER TRA...
TYPES OF POWER TRANSFORMER FAULTS BASIC INFORMATIO...
POWER TRANSFORMER RELAYING PHILOSOPHY AND ECONOMIC...
PHASE SHIFTING TRANSFORMER SHORT CIRCUIT CHARACTER...
PHASE SHIFTING TRANSFORMER CONSTRUCTION
PHASE SHIFTING TRANSFORMER RATING DATA REQUIREMENT...
PHASE SHIFTING TRANSFORMER UNUSUAL SERVICE CONDITI...
USUAL SERVICE CONDITION OF PHASE SHIFTING TRANSFOR...
PHASE SHIFTING TRANSFORMER DESIGN CRITERIA
October (5)
September (12)
August (13)
July (6)
June (18)
May (17)
April (18)
March (23)
February (28)
January (15)
2011 (4)
December (4)
TOP COUNTRIES
Free counters
Followers
Visitors
Angular Displacement
Audible Sound
Autotransformers
BH Curve
Booster Transformer
Buchholz Relay
Cabinets
Calculations
Coils
Connection
conservator
Coolants
cooling classes
cooling system
Core
Current Transformer
CVT
Design
Diagrams
Differential Relay
Distribution Transformer
Eddy Current
Fault
GIS
Grounding
Harmonics
HVDC Transformers
Hysteresis
Impact Indicator
Impedance
Instrument Transformers
Insulating Liquids
Insulation
Isolation Transformer
Liquid Filled
Nameplate
Open Delta
Pad Mounted
Parallel Operations
Polarity
Power Transformer
Reactors
Relay
Rogowski Coil
Scott Connection
Short Circuit
specifications
Standards
Substation
Surge Arresters
T Connection
Tanks
Tap Changers
Temperature Rise
Tertiary Winding
Tests
Three Winding
Transducers
Transformer Banking
Transformer Bushing
Transformer Failure
Transformer Heating
Transformer Life
Transformer Loading
Transformer Losses
Transformer Maintenance
Transformer Measurements
Transformer Oil
Transformer Protection
Transformer Studies
Transient
Transport of Transformer
Tutorials
Video
Voltage Regulation
Voltage Transformer
Windings
Wye Delta
Zigzag Transformers