Accionamientos LCI
Interaccin armnica
Power Inverter
Ref.: Technical Evaluation and Practical Experience of High Power Grinding Mill Drives in Mining
Applications, J. Rodrguez, J. Pontt, P. Newman, L.Moran, G.Alzamora
Voltage waveform at the rectifier input side of an 18000 HP
LCI SAG Mill Drive. (a) Line to line bus voltage waveform
(11270 V peak). (b) Average rms value of the associated frequency
spectrum versus order of the harmonic component.
Current waveform at the rectifier input side of an 18000 HP LCI SAG Mill
Drive. (a) Rectifier input line current (800 A peak). (b) Average rms value
of the associated frequency spectrum versus order of the harmonic.
Gearless motor for a high power mill
supply system
excitation
i L1 i L2 i L3
v L1 v L2 v L3
i L1,L2,L3 M
open and closed
loop controls v 3-
L1,L2,L3
Reference value Actual value
Power circuit of a cycloconverter-fed mill drive with 2 three-phase windings
iu ia iv ib iw ic
b v
a w
u c
Principio de operacin del
control vectorial
Currents generated by the Currents generated by the
cycloconverter with large cycloconverter with reduced
dead time dead time
iL1
iL1
iL2 iL2
iL3 iL3
iq
id
30 ms
MN - 06 Filtro pasa-altos
R
S
T
L1 R1 L2 R2 L3 R3
C1 C2 C3 C4 C5 C6
Rel de desbalance
Centro Tecnolgico de Molienda SAG y Sistemas Elctricos - Universidad Tcnica Federico Santa Mara
Filtros tipo C, h=2,3,4
Input currents and frequency spectrum in a 12-pulse
cycloconverter feeding a 38-foot SAG mill
I [Amp].
I Amp.
400
300
200
100
0
-100 0 10 20 30 40 50 60 70 80
-200
-300
-400
Frequency spectrum
6.00%
5.00%
4.00%
3.00%
2.00%
1.00%
0.00%
1100
1238
1375
1513
1650
1788
1925
2063
2200
2338
2475
2613
2750
2888
3025
3163
138
275
413
550
688
825
963
0
Single line diagram of the cycloconverter drives at a
Concentartor 110 ktpd
Multibranch 20 MVAR Harmonic Filter Module
Comentarios
LCI 12-pulse
Capacidad de up-rating de
trafos
Rango
12000-27000 Hp
9-11 rpm
Caso 1: Accionamiento LCI
LCI 12-pulse
Esquema
Unilineal
Planta14.000 mtd (1st stage) and 20.000 mtd (2nd stage), near 4.000
meters a.s.l.
The circuit includes a 12-pulse Load Commutated Inverter (LCI).
The LCI drives the SAG Mill and 2 BALL MIlls..
El Problema
Problemas operacionales por fallas en sistemas electrnicos
Nutridas downtimes en circuito de molienda
Fuertes prdidas de produccin
Destruccin de SCRs
Destruccin de tarjetas de disparo
Objetivo del trabajo
Procedimientos de Mantencin
Uso de instrumentacin
Reduccin de riesgos
Load Commutated Inverter (LCI)
estator Polo
SAG mill is controlled to 11.2 -11.5 rpm with the LCI.
LCI 12-pulse
Unexpected Shutdown
Cacractersticas de una falla (trip)
Measurements show
DC-LINK overcurrents
Overcurrent in transformer windings
Hiptesis
Problemas durante conmutacin
Comportamiento del LCI bajo condiciones de falla
de conmutacin
Possible Causes
Fault in the thyristor. Loss of block capability.
Loss of input voltage
Loss of gate pulse
False pulse in the thyristors
Comportamiento del LCI bajo condiciones
de falla de conmutacin
Simulation results
(8.5rpm)
DC-LINK current
Field measurements
DC-LINK current
The Protection System of the LCI stops the pulses to the thyristors if
the DC-LINK current reaches 2 pu during a half period of 50Hz.
Accionamiento LCI y motor 6500 Hp motor de SAG mill
Simulacin
SCR Voltage (Motor side Converter)
SCR 1 SCR Current (Motor side Converter)
SCR 1
Voltage [V]
2000
Current [A]
0
5000
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12 0
SCR 2 0 0.02 0.04 0.06 0.08 0.1 0.12
Voltage [V] Voltage [V] Voltage [V] Voltage [V] Voltage [V]
2000 SCR 2
Current [A] Current [A] Current [A] Current [A] Current [A]
0
5000
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12 0
SCR 3 0 0.02 0.04 0.06 0.08 0.1 0.12
2000 SCR 3
0
5000
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12 0
SCR 4 0 0.02 0.04 0.06 0.08 0.1 0.12
2000 SCR 4
0
5000
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12 0
SCR 5 0 0.02 0.04 0.06 0.08 0.1 0.12
2000 SCR 5
0 5000
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12 0
SCR 6 0 0.02 0.04 0.06 0.08 0.1 0.12
SCR 6
2000
0 5000
-2000 0
0 0.02 0.04 0.06 0.08 0.1 0.12 0 0.02 0.04 0.06 0.08 0.1 0.12
Time [s]
a) c) Time [s]
2000
DC-Link Voltage (Line side Converter) Overcurrent
Voltage [V]
1000
-1000
0 0.02 0.04 0.06 0.08 0.1 0.12
DC-Link Voltage (Motor side Converter)
2000
Voltage [V]
0
Fig.3 Simulation Model of the LCI - Drive
-2000
0 0.02 0.04 0.06
Reactor Voltage
0.08 0.1 0.12 a) Thyristors Voltages
5000
b) DC-Link variables
Voltage [V]
c) Thyristors currents
0
-5000
0 0.02 0.04 0.06 0.08 0.1 0.12
DC-Link Current.
10000
Current [A]
5000
0
0 0.02 0.04 0.06 0.08 0.1 0.12
b) Time [s]
DC-Link Voltage (Line side Converter)
2000
Voltage [V]
1000
-1000
0 0.02 0.04 0.06 0.08 0.1 0.12
DC-Link Voltage (Motor side Converter)
2000
Voltage [V]
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12
Reactor Voltage
5000
Voltage [V]
-5000
0 0.02 0.04 0.06 0.08 0.1 0.12
DC-Link Current.
10000
Current [A]
5000
0
0 0.02 0.04 0.06 0.08 0.1 0.12
Time [s]
SCR Current (Motor side Converter)
Current [A] SCR 1
5000
0
0 0.02 0.04 0.06 0.08 0.1 0.12
SCR 2
Current [A] Current [A] Current [A] Current [A] Current [A]
5000
0
0 0.02 0.04 0.06 0.08 0.1 0.12
SCR 3
5000
0
0 0.02 0.04 0.06 0.08 0.1 0.12
SCR 4
5000
0
0 0.02 0.04 0.06 0.08 0.1 0.12
SCR 5
5000
0
0 0.02 0.04 0.06 0.08 0.1 0.12
SCR 6
5000
0
0 0.02 0.04 0.06 0.08 0.1 0.12
Time [s]
SCR Voltage (Motor side Converter)
SCR 1
2000
Voltage [V]
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12
SCR 2
Voltage [V] Voltage [V] Voltage [V] Voltage [V] Voltage [V]
2000
0
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12
SCR 3
2000
0
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12
SCR 4
2000
0
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12
SCR 5
2000
0
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12
SCR 6
2000
0
-2000
0 0.02 0.04 0.06 0.08 0.1 0.12
Time [s]
DC-Link Current. Comportamiento medido bajo
falla
Solucin
I+D
Hardware
Trabajo de terreno
Solucin
Ncesidad de fabricar tarjetas de repuesto
Necesidad de sistema de moinitoreo
Necesidad de servicios
Problema
Descripcin
Solucin
Case2: Up-rating de un accionamiento GMD
Capacidad de up-rating de
trafos
Rango
12000-27000 Hp
9-11 rpm
I network OK!
Prdidas
importantes!
Process control
improvement
Patented
Spin-off ETT Ltda.
4.3Km
27Km
El problema
Aspectos elctricos
Aspectos de proceso
Aspectos mecnicos
Resumen
PROCESOS DE FLOTACION
Definen la recuperacin metalrgica
EQUIPOS DE GRAN TAMA0
250 m3
130 m3
300 m3
100 m3
Primary Currents
Currents Waveforms
1
[pu]
-1
1
[pu]
-1
Secondary Currents
1
[pu]
-1
1.5 1.6 1.7 1.8 1.9 2
[s]
Secondary Currents
(Simulaton) Measurements
Operacin bajo
condiciones normales
Field measurement
Ref.: J. Rodrguez, J. Pontt, K. Tischler, N.Becker, J.Rebolledo, ''Operation of
High Power Cycloconverter-Fed Gearless Drives under Abnormal Conditions'' ,
IEEE Trans. On Ind. Appl., Vol.43, Nr.3, pp.814-820.
Efectos de cortocircuito en el
cicloconversor
Fuertes componentes alternas de fuerza vertical
(hasta 6 p.u.) . Si no estn consideradas, el motor se
puede mover.
El perno se
elonga
La fuerza de friccin se
reduce y el frame del motor
puede desplazarse
Aspectos de
Proceso
Para evitar quiebre de revestimientos y
quiebres de bolas
Impactmeter
MonSAG
Para el control de llenado y
eficiencia
Monsag System
Fuente:
Fuente: National Instruments
0 ,8 0
0 ,7 0
0 ,6 0
0 ,5 0
0 ,4 0
0 ,3 0
0 ,2 0
0 , 10
0 ,0 0
0 0,5 1 1, 5
B [ T e s la]
Frequency
Position
Posibles mecanismos
de fallas
Torques oscilatorios causados por
armnicas de flujo y corrientes
Pull magntico (des)balanceado
causado por entrehierro asimetrico.
Deformacin del estator causado por
combinacin de fuerzas trmicas y
fuerzas oscilatorias de origen
electromagnetico
Experiencia funcional para
deteccin de deformacin y
vibraciones
La misin de reconocimiento de
patrones se calibra segun los valores
esperados de frecuencias naturales
del estator y rotor.
Caractersticas de sistema
de instrumentacin
Para funciones de monitoreo, vigilancia y
supervisin.
A nivel de terreno
Robusta frente a interferencias
electromagnticas
Robusta frente al ambiente industrial
Confiabilidad
Especialistas de CASIM han tenido la
tarea de anlisis de causa raz de
varias de las fallas que han provocado
perdidas importantes en equipos
crticos de plantas mineras, como
GMDs de Codelco y otras empresas en
Chile y extranjero.
Se ha desarrollado sistemas, mtodos
e innovaciones tecnolgicas para
diagnstico.
Resumen
Tendencia a grandes equipos por
economa de escala.
En el escalamiento de molinos GMD de 38-
40 pies han aparecido fenmenos nuevos.
Los fabricantes se han visto sorprendidos.
Las manifestaciones de fallas son
mecnicas, pero con origen combinado de
diversos fenmenos.
Lecciones
aprendidas
Importante el Know-how, I+D+I para mejor
diseo, operacion de grandes GMDs.
Problemas complejos requieren un enfoque
multidisciplinario.
Necesidad de capacidades de Innovaciones
Capacidad de innovar
Desarrollo de Pymes de base
tecnolgica cluster minero
hacia clase mundial
Encadenamiento productivo
Nuevos modelos de negocios
Ref.: Prog. Innovacion en Minera, Omar Hernndez, Subdirector
minera, medioambiente e infraestructura, CORFO-Innova, 28.05.2010
Ref.: Prog. Innovacion en Minera, Omar Hernndez, Subdirector minera, medioambiente e
infraestructura, CORFO-Innova, 28.05.2010
Camino de solucin?
Know-how
Colaboracin Intl
Universidad Tcnica Federico
Santa Mara
Centro de Automatizacin y
Supervision para la Industria Minera
Muchas Gracias !