Sunteți pe pagina 1din 24

FIRE APPARATUS MANUFACTURERS ASSOCIATION

Fire Pump Selection Guide


Contents
Introduction ..................................................................................................................................................................... 3
Overview ......................................................................................................................................................................... 3
Pump Types ..................................................................................................................................................................... 4
Centrifugal .......................................................................................................................................................... 4
Single Stage ............................................................................................................................................ 4
Multi-Stage ............................................................................................................................................. 4
Cast Construction.................................................................................................................................... 5
Fabricated Construction .......................................................................................................................... 5
Positive Displacement Pumps .............................................................................................................................. 5
Drive Methods ................................................................................................................................................................. 6
Midship Mounted Transfer Case Drive ................................................................................................................. 6
Overview: ............................................................................................................................................... 6
Typical Pump Sizes: ................................................................................................................................. 7
Power Take Off (PTO) Drive ................................................................................................................................. 8
Overview: ............................................................................................................................................... 8
Sizes available: ........................................................................................................................................ 8
Locations: ............................................................................................................................................... 8
Auxiliary Engine Driven (Direct Drive) .................................................................................................................. 9
Overview: ............................................................................................................................................... 9
Sizes available: ........................................................................................................................................ 9
Locations: ..............................................................................................................................................10
Pump Locations ..............................................................................................................................................................11
Pump Capacity Ratings....................................................................................................................................................11
Pump Intakes ..................................................................................................................................................................13

Page 1 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Intake Valve Types..............................................................................................................................................13


Internal (integral) intake valves ..............................................................................................................14
External valves .......................................................................................................................................14
Pump Discharges ............................................................................................................................................................15
Plumbing Size .....................................................................................................................................................15
Valve Construction and Controls.........................................................................................................................16
Valve Control Styles ...............................................................................................................................16
Discharge Instrumentation .................................................................................................................................17
Chemical Injection ..............................................................................................................................................18
Plumbing Material ..............................................................................................................................................18
Hose and Appliance Connections ........................................................................................................................18
Components ...................................................................................................................................................................19
Corrosion Prevention ......................................................................................................................................................20
Annual Pump and Related Equipment Testing .................................................................................................................20
Appendix A - Abbreviations .............................................................................................................................................21
Appendix B Pump Drive Mounting Diagrams ................................................................................................................22
Appendix C - Manufacturer Contacts ...............................................................................................................................24

Page 2 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Introduction
This guide is intended to provide fire service personnel with information about the various types of pumps,
their capacities, mounting locations on fire apparatus, drive systems, control and monitoring systems, and
valve types that are available for fire apparatus.

As with any engineered system design, there are pros and cons to each configuration and not all are
represented here. It is the responsibility of the purchaser to determine what best meets their needs and to
specify this information to prospective apparatus bidders, sellers, and manufacturers.

As technology is continually evolving, this guide is presented as a general information and educational
piece. The various options and auxiliary equipment presented may not be available from every
manufacturer, and some may be mutually exclusive.

For more information, contact the FAMA Member pump, equipment, and apparatus manufacturers listed
at www.fama.org.

The National Fire Protection Association Standards define voluntary minimum standards for automotive fire
apparatus. The two most widely used Standards are:
NFPA 1901, Standard for Automotive Fire Apparatus
NFPA 1906, Standard for Wildland Fire Apparatus

The current editions should be referenced when specifying new apparatus.


www.nfpa.org.

Within these Standards, pumps are divided into three main headings each with specific minimum
performance criteria:

1. Fire Pump,
2. Auxiliary Pump, and
3. Ultra-High Pressure (UHP) Pump.

In Canada, ULC S515 Standard for Automobile Fire Fighting Apparatus is the accepted standard to
reference.

Overview
Modern fire apparatus pump systems are comprised of many components utilized to move and
control water from a source. They use power to create or increase pressure to move the water

Page 3 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

through piping and valves, then discharge the water to hose lines or other appliances to be directed
to another location, applied to a fire, or other desired target.

This guide will present in general terms:

Pump Types
Drive Methods
Pump Locations
Pump Capacity Ratings
Intake Plumbing
Discharge Plumbing
Governor Types

Pump Types
CENTRIFUGAL
Centrifugal pump design is the most typical for Fire Pumps and Auxiliary Pumps in modern fire
apparatus and its proven design has been used in fire apparatus for well over a century. In a basic
centrifugal pump, typically a single casing, water enters through the pump inlet into the center (eye)
of the impeller which is spinning on a shaft. Water is spun outwardly through the impeller vanes and
into a volute casing resulting in increased pressure. The water is then discharged at a higher pressure
than when it entered the pump inlet. Centrifugal pumps have the ability to draft (draw) water from
an unpressurized water source with the aid of a primer. Centrifugal pumps are available as single
stage or multi-stage: such as two-stage and three-stage designs. Stages refer to the number of
impeller(s) and water path(s) within the centrifugal pump.

Single Stage

In a basic Single Stage Pump, water enters through the pump inlet and into a single spinning impeller.
Water then moves outward through the impeller vanes and into a volute casing. Pressure rises in the
casing resulting in a higher pressure out the pump discharge. A Single Stage Pump will not have a
Transfer Valve.

Multi-Stage

In a Multi Stage Pump, there are two or more impellers that work together to provide the pumps
required pressure and flow. Most designs have the impellers mounted on a single shaft, though,
occasionally, they may be separate. (See booster pumps below)

Page 4 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Multi-stage pumps are most typically used to develop high discharge pressures from 250 psi to 1500
psi. Each impeller adds to the pressure it receives from the stage before it, typically providing output
pressures significantly higher than that of a single stage pump.

Many multi-stage pumps, especially two-stage pumps, will be equipped with a transfer valve. The
transfer valve allows the different stages of the pump to operate in either a pressure or volume mode.
In the pressure mode, the stages are linked in series so that the output of the previous stage is routed
directly to the subsequent stages, compounding the pressure as described above.

In the volume mode, the stages are run in parallel so that the flow from each stage is basically
added together. Higher flows can be achieved.

Some pumps may be equipped with a high-pressure booster pump. The booster pump impeller will
likely have its own casing separate from the casing for the other stages, though it may still be driven
off a common gearbox. This pump may be plumbed in series with the other stage(s) for high pressure
flow, or it may be plumbed as a stand-alone pump allowing simultaneous high and low pressure flow.
A transfer case may be provided to switch between the modes.

Cast Construction

A single or two stage pump of cast construction typically has impeller inlet(s) and waterway(s) cast
into one complete cast pump casing. The transfer valve on a two stage pump is located in an area
of the pump body where water can be controlled to either flow from one stage to another (pressure
mode) or directly from each stage out the discharges (volume mode).Single stage and two stage
pumps are available with iron or bronze castings.

Fabricated Construction

A single or two stage pump of fabricated construction will typically have a separate pump casing
from the inlet and discharge piping. In the two stage pump, piping is used to connect one pump
stage to another and the transfer valve is in a location within the fabricated piping so water can be
controlled to either flow from one stage to another (pressure mode) or directly from each stage out
the discharge(s) (volume mode). Pump and apparatus manufacturers have the capability of
providing stainless steel intake and discharge plumbing / piping on certain pumps.

POSITIVE DISPLACEMENT PUMPS


Positive Displacement Pumps are most often used for Ultra High Pressure pump applications. A
positive displacement pump is different from a centrifugal pump in that these pumps operate by
drawing water into a chamber then squeezing it out under pressure. Examples of positive
Page 5 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

displacement pumps used in the fire service are piston pumps, rotary vane pumps, and gear pumps.
Each time the pump spins, a specific amount of water is moved. Because of this action, positive
displacement pumps are capable of delivering constant flow at very high pressures at a constant
speed.

Positive displacement pumps are restricted to low volumes (typically <50 gpm) due to size and
complexity. They are most commonly used for ultra-high pressure pumping systems that develop
pressures well in excess of 1,000 psi, for foam injection systems, or for priming the main centrifugal
pump.

Water supplied to a hose by a positive displacement pump will behave differently than a line
supplied from a centrifugal pump. For centrifugal pumps, reducing the backpressure (i.e. opening a
valve from half open to fully open) will result in a noticeable increase in flow (up to the capacity of
the pump). However, for a given pump speed, a positive displacement pump will maintain constant
flow, and it will do so regardless of the backpressure on the system. As an example, if the flow rate is
18 gpm at 1100 psi at the nozzle, the flow rate will remain about 18 gpm even after the nozzle is
removed. Positive displacement pumps are also likely to cause pulsations in the discharge line.

Drive Methods
The drive method is how the pump gets its power to turn the pump shaft thus creating water flow and
providing pressure.

MIDSHIP MOUNTED TRANSFER CASE DRIVE

Overview:

Midship split driveline pumps are typically located in the middle of the apparatus, between the
transmission and rear drive axle as part of the apparatus drive line. The pump and gear box are most
commonly mounted together as a single unit, and the pump is driven directly from the gear box, by
means of a chain, gears, or belt. A different configuration of a split driveline pump is to have the gear
box located in the driveline, and the pump mounted in the rear of the vehicle. The pump is driven by
means of a power shaft, similar to a power take off shaft, instead of a chain or a belt.

There are two, or more, drive shafts, connecting the engine transmission to the pump gearbox and
the pump gear box to the rear drive axle.

Page 6 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

A control must be installed inside the drivers compartment to select between Road Mode and
Pump Mode. When Road Mode is selected, power from the engine and transmission is
transmitted through the driveshafts, pump gear box and to the rear drive axle which propels the
vehicle. The pump is not engaged when in Road Mode. When Pump Mode is selected, the
power from the engine and transmission is transmitted through the driveshaft to the pump gear box
to drive the pump. The rear driveshaft is not engaged and the vehicle will stay stationary.

Consideration must be given to the ratings of the pump, engine horsepower and RPM requirements.

The pump power curve, available from the manufacture, will determine certain requirements of other
components. To ensure a reliable system, all components must work in conjunction with one another.
It is important to note driveline design is a critical aspect of a transfer split case pump installation.
Manufacturers of driveline components and, pump manufacturers should be consulted before any
driveline design is implemented on a fire apparatus to ensure the integrity and reliability of the
installation.

Typical Pump Sizes:

Pump sizes are determined by their flow capacity in Gallons per Minute (gpm). Common size ratings
of Midship Split Driveline pumps available include:500, 750, 1000, 1250, 1500, 1750, 2000, 2250, 2500,
2750, 3000, 3500, 4000, 5000, & 6000 gpm.

Note: Pumps with a size of 3000 gpm or more are often referred to as industrial pumps.
Pros:

Provides higher flow ranges, up to 6000 gpm, utilizing the power train to provide required
power.
Engine speed remains relatively constant to reduce fluctuations in pump discharge pressures.
Cons:

No pump and roll capabilities.


Pump gear box is part of the driveline, making some repairs more difficult.
If a problem occurs with a pump gear box, it may impede the vehicle from being driven.
Typically more expensive than other types of pump drives.
More difficult to install than other types of pump drives.
More space is required.

Page 7 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

POWER TAKE OFF (PTO) DRIVE

Overview:

There are two types of PTO drives. One receives power input from the main engine or transmission.
The other indirectly supplies power to the pump through a hydraulic pump. For a PTO driven by the
main engine or transmission, an appropriate PTO drive unit is mounted to one of the main engines or
transmissions PTO ports. A drive shaft is typically used to connect the PTO to the pump.
Consideration must be given to the ratings of the PTO port, PTO drive unit, duty cycle, pump
horsepower & RPM requirements. Inappropriate sizing of the PTO may lead to failures of the PTO drive
unit.

Some applications will utilize a PTO driven hydraulic pump that in turn drives a hydraulic motor to turn
the pump shaft. A control, typically located inside the drivers compartment, is used to engage and
disengage the PTO gear box.

The pump power curve, available from the manufacture, will determine some of the requirements of
the other components. Designing a reliable system requires all components work in conjunction with
each other. It is important to note the PTO is often considered the weakest link in a PTO drive system.
The PTO for the pump design should be verified with PTO suppliers as well as pump manufacturers to
ensure the reliability and integrity of the pump drive system.

Sizes available:

250, 350, 450, 500, 750, 1000, 1250, & 1500 gpm are the most common size ratings for the use in a PTO
Drive system.

Locations:

PTO driven pumps can be located in many positions on a fire apparatus. Typical locations are: front
mount pump; midship (non-split driveline) pump; rear mount pump.

Pros:

A PTO driven pump typically allows for pump and roll (pump & move) where the vehicle can
be driven using the vehicles normal chassis engine, transmission and drive train to propel the
vehicle, while the PTO powers the pump so that water, foam and/or Compressed Air Foam
System (CAFS) can be discharged while the vehicle is in motion.
Unlike a split shaft pump gearbox configuration, PTO driven pumps and drive components are
not integral with the drive train components between the transmission and drive axle(s).

Page 8 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

If a problem occurs with a PTO pump gear box, it is unlikely that this will impede the vehicle
from being driven.
Typically less expensive than other types of pump drives.
Easier to install in most applications.
Less space is required.

Cons:

For PTOs mounted to the main engine or transmission, during pump and roll operations, pump
pressure can vary greatly due to throttle position of apparatus, possibly causing variation in
water discharge pressure. A hydraulically driven PTO pump may reduce such variation as the
hydraulic pressure can be governed to maintain a more consistent water discharge pressure.
For PTOs mounted to the main engine during pump & roll the chassis engine may require a
higher RPM to maintain proper pump discharge pressure. This may be too high an RPM level
for the speed desired to drive the vehicle. If the vehicles brakes are utilized to maintain the
desired speed, over-heating and increased wear on the brake components may occur. A
hydraulically driven PTO pump may reduce or eliminate such issues.
Flows are typically limited to a maximum of about 1500 GPM.
Duty cycles of PTO components may increase service and maintenance requirements, and
may decrease component life.

AUXILIARY ENGINE DRIVEN (DIRECT DRIVE)

Overview:

Auxiliary engine driven pumps are coupled directly to their own engine which is separate from the
main engine. Auxiliary engine driven pumps are often used for Auxiliary Pumps. In cases where the
pump is rated less than 500 gpm, the pump may be directly connected to the engine output shaft so
the pump is spinning every time the engine is running. Some manufacturers will use a gear box
between the engine and pump that either increases or decreases the pump speed to engine speed.
Some pumps may be equipped with a clutch to disengage the pump from the engine.

Sizes available:

Most auxiliary engine driven pumps will be low horsepower pumps designed to flow relatively low
volumes (typically <500 GPM). Gasoline engines are available to drive pumps up to about 200 gpm
at 100 to 150 psi for mid-range pumps; 100 gpm at 100 to 250 psi and 50 gpm at 300 to 400 psi for
high pressure pumps. Small diesel engines are available to drive pumps within the same range as the
gasoline units, however, the higher horsepower offered by the diesel engines will typically allow the
Page 9 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

diesel units to provide greater flows in the same pressure ranges. These pumps are used primarily for
brush trucks or wildland/urban interface units built to meet the design practices identified in NFPA
1906 Standard for Wildland Fire Apparatus.

Larger capacity pumps up to 6000 gpm are also available, and are often used in industrial
applications. Keep in mind that as the flow increases, the power required to drive the pump
increases exponentially. Therefore, the size of the engine and the cost of the system will also increase
exponentially. For that reason, large engine driven water pumps are often mounted on trailers or
deployable pods for stand-alone specialty pumping systems.

Please see the pump capacity section for discussion on pressure.

Locations:

Auxiliary engine driven pumps are usually mounted in the rear of the apparatus behind the water
tank. Occasionally, the pumps are cross-mounted behind the cab or in the apparatus dunnage
area, either as a stand-alone pump module, or as an auxiliary pump to a chassis mounted PTO or
split-shaft driven pump system.
Pros:

Pump system is truly independent of the main engine allowing pump flow and pressure to be
independently regulated without impact to systems driven by the main engine.
Due to the independent nature of this system, it provides excellent pump and roll capabilities.
If a problem occurs to an auxiliary engine and pump, it is unlikely that it will impede the vehicle
from being driven.
Often easier to service due to ease of access.
Pump may have multiple control panels for in-cab and pump side operation.
Remote mount control panels allow the pump controls to be located almost anywhere on the
fire apparatus providing an optimum location for the pump operator to oversee the fire scene
as well as keeping him safe from discharge lines and equipment.

Cons:

An auxiliary engine driven pump may be more expensive than other types of pump drives.
When an auxiliary engine is used, useable space and payload capacity may decrease.
Increased maintenance costs may be incurred due to the separate engine.

Page 10 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Pump Locations
Depending on pump drive type, there are various locations where the pump can be mounted. For
split shaft/transfer case and PTO units the pump can be mounted in the:
Front of the apparatus, ahead of the engine and front axle;
Between the front and first rear axle, (Midship)
Rear of the apparatus, behind the first rear axle.

With auxiliary engine driven pumps, pump locations can be behind the cab, in the panel can be
located on top, on the side, and/or at the rear. The location doesnt necessarily need to be near the
actual pump. It is well advised to keep intake and discharge hose connections away from the pump
operator for improved safety, reducing the risks associated with pressurized hose lines and tripping
hazards. Each location has its advantages and disadvantages, depending on the departments
needs.

Pump Capacity Ratings


The size of the pump that is to be mounted on an apparatus is one of the most important decisions
when developing the specifications for a new pumping apparatus. Often purchasers will buy an
apparatus similar to what theyve purchased in the past. Thats not a bad practice assuming the
performance and operation of their existing fleet is adequate for the present and future needs.

Experienced purchasers believe most municipal pumper fire apparatus should be equipped with a
pump that is rated at 1500 gpm or larger. That may be a good rule of thumb, however, to maximize
the value of the apparatus you may wish to consider the following:

1. Understand how pumps are rated.


a. Fire pumps are rated per applicable standards from NFPA to deliver their rated capacity
at 150 psi from draft (20 of hose and 10 of lift)
The actual in-service pump performance from the water tank or a pressurized
water source may increase the pumps flow 10% or more compared with the same
pump at draft.
The guaranteed maximum pressure for a single stage structural pump is only 250
psi from draft, per applicable NFPA standards.
b. Many engine driven pumps, such as wildland pumps, are not necessarily rated at 150 psi
c. Ultra-High Pressure (UHP) pumps have ratings of 6 gpm at 1100 psi.
2. It is critical to define the pressure and flow so the best pump for your use can be selected.
Most fire pump discharges require 120-200 psi of pump discharge pressure for hose
lines, nozzles and appliances.
Low pressure nozzles allow for lower pump pressures to deliver the same flow rates.
Page 11 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Water supply lines may require as little as 40-50 psi of engine pressure, up to 185 psi
for large diameter supply hose.
Long forestry lines, or if supplying lines up hills, or to high rise standpipes, may
require 300 psi or higher pressure for adequate flow and acceptable nozzle
performance.
Ultra High Pressure (UHP) hoses, nozzles and appliances are specially designed to
be used at high pressures and low flows.
All hose, nozzles, and appliances should be selected appropriately to safely
deliver the flows and pressures anticipated.
It is not enough just to define flow. As an example, a 500 gpm pump rated at 150
psi is a very different pump from a 500 gpm pump rated at 40 psi.
a. Applicable NFPA standards only require pump performance up to 2,000 feet of elevation
above sea level. To maintain the rated performance above that elevation may require
more horsepower or a different pump.

3. Pump size should be based on actual flows needed in a typical operation.


a. NFPA 1901 Standard for Automotive Fire Apparatus defines generic ratings for what can
be expected out of any size discharge. Ensure the apparatus is equipped with enough
discharges to allow the pump to operate at capacity.
b. Review fire ground operation plans to determine what is needed from the pump.
Verify the sum of all flow rates for each attack line on the apparatus
Verify the maximum supply line volume expected for the apparatus. Note: if the
supply line is operated at less than 120 psi, then deduct approximately 10% for the
reduced pressure.
Add the rating for any master stream devices attached to the apparatus.
c. The pump rating will likely need not be any larger than the sum of items described above
that will be operated simultaneously.
d. If these ratings are to be maintained while being supplied from a pressurized source, the
required pump capacity may be reduced up to 10%.

4. Ensure the pump is not too large for the water supply.
a. If the pump is certified to applicable NFPA standards, it may have the potential to draft
at the rated capacity provided there is access to an adequate draft site and the
apparatus is equipped with properly sized suction hoses.
b. If the water supply to the pump is from a municipal or industrial water system, verify the
pump size against the rating of those systems.
c. When the apparatus is to be supplied exclusively by a tanker apparatus task force,
performance of the tanker (NFPA 1091 defined Mobile Water Supply Apparatus)
apparatus performance should be considered.
d. The required tank to pump performance in NFPA 1901 Standard for Automotive Fire
Apparatus is 500 gpm. If a larger flow from the on-board tank is needed, the apparatus
or pump manufacturer may need to install larger sized piping, valves and/or additional
line(s).
Page 12 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Pump Intakes
Any external connection that can be used to supply water to the pump is considered a pump intake.
Typically, a fire pump will include a minimum of two (2) intake connections: one (1) larger diameter
main inlet (sometimes called a steamer) connection and one (1) smaller auxiliary connection.

The steamer inlet size, and quantity, should be selected to supply the pumps full rated capacity
from draft. NFPA 1901 Standard for Automotive Fire Apparatus contains a table that lists the
maximum size and quantity of suction lines that may be used for testing of the pump from draft. Due
to the necessity to supply the pump from draft, the main inlet connection will be positioned as close
to the pump as possible with the shortest, straightest path possible into the pump impeller.

Auxiliary suctions are usually smaller connections used to feed the pump from a pressurized source
such as a hydrant. Most apparatus equipped with the auxiliary suction will be equipped with a 2.5
connection. Auxiliary suctions must also be equipped with a valve.

It is not unusual for an apparatus to be equipped with additional inlet connections based on the size
of the apparatus. For example, certain apparatus may include additional connections at the front
and/or rear to maximize the flexibility of the apparatus to be supplied with water while the apparatus
is positioned in the nominal location relative to the water supply. The key to remember is, the greater
the distance between the hose connection and pump impeller, the more pipe, elbows, and other
potential restrictions will be required in the plumbing. As a result, the draft capabilities of these
additional inlets may be significantly less than the main inlet. On a typical pumper apparatus, it is not
unusual for a front suction to have a draft capability of 70% or less compared to the main inlet.
Reducing the restriction(s) to improve the flow may not be feasible if the route of the plumbing is not
conducive for larger or straighter pipe runs.

INTAKE VALVE TYPES


It is good practice for the main inlet (or any inlet) to be equipped with an intake valve. The valve will
allow the operator to set up to supply the pump from an external water source while still being
supplied from the on board tank. When shifting between water sources, one valve can be opened
while another can be closed.

In general, there are two choices for the types of valves to be used, internal or external. An internal
valve is an integral component of the pump intake plumbing and typically a butterfly type valve.
An external valve is mounted outside the pump and pump panel. It can be either a ball, butterfly, or
piston type valve. Whether internal or external, these valves perform the same function in controlling
incoming water flow to the pump through one or more of the pumps primary water intakes. Both
Page 13 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

types of valves must have a means to expel air from the hose line when first charged. This prevents a
slug of air from moving through the pump and hose lines to reach the firefighters at the nozzle. Either
valve should also incorporate an automatic pressure relief feature to prevent unwanted pressure
surges in the supply hose over pressurizing the pump and discharge hose lines.

Internal (integral) intake valves


Pros:

Most can be controlled remotely from the pump operators position


Operates from a draft or pressurized water source
Protected from outside damage
Does not increase the width of the apparatus
Incorporates a manual override feature
Provided by the pump manufacturer
Cons:

More expensive than an external valve


Butterfly design partially blocks waterway
When repairs are needed, the apparatus, or pump, may need to be taken out of service
May not be easily accessible or serviceable

External valves
Pros:

Some can be controlled remotely from the pump operators position


Less expensive than an internal valve
Most will operate from either a draft or pressurized water source
Can be easily replaced or repaired without the pump or apparatus being out of service
Incorporates a manual override feature
Cons:

May not fit inside running boards, increasing the over-all width of the apparatus.
More prone to damage
Different manufacturer than the pump manufacturer

It is up to the purchaser to determine what is best for their operations, repair capabilities, and budget.

Page 14 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Pump Discharges
Discharges are any outlets on the apparatus that provide water flow under pressure from the pump.
Most discharges are classified by the size of the hose connection at the exterior of the apparatus.
Many departments may assume the valve and pipe sizes match the connection size. While this may
be true, there are exceptions. Therefore departments should make it clear if they are referencing
pipe or valve sizes rather than connection size. Discharges range in size from 1 to 8, though
common discharge sizes used on apparatus in North America are 1.5, 2.5, 3, 4, 5 and 6. The size
and location of the discharges are almost always selected based upon the anticipated use of the
apparatus (e.g. where hoses or master stream devices need to be connected on the truck while on
the fireground, including those lines that are going to be preconnected to the discharge).

Applicable standards from the NFPA have charts that identify the ratings of various discharges based
on the connection size. The sum of all the discharge ratings on the apparatus should equal, or
exceed, the total pump capacity ratings. Only discharges larger than 2.5 count towards the sum.
The actual capability of a given discharge usually exceeds its ratings. The actual flow of a given
discharge will be determined by the valve size, the plumbing size, restrictions in the plumbing (such as
flowmeters), and of course the hose and nozzle size connected to the discharge.

Ratings for discharges as identified by the applicable NFPA standards are:

2.5 = 250 gpm


3.0 = 375 gpm
4.0 = 625 gpm
5.0 = 1,000 gpm
6.0 = 1,440 gpm

No discharge larger than 2.5 is allowed on the operators pump panel. The flows listed for each
outlet size are minimum and are for rating purposes only. If piping and valving are sufficient, much
higher flows for a given outlet size might be achievable.

PLUMBING SIZE
One of the most important factors that determines the flow rate from a discharge is the plumbing size
which includes the valve size. Most departments will specify that the plumbing size should be equal
to, or greater than, the discharge connection size to reduce friction loss in the piping. However,
consulting with the manufacturer to ensure this does not create any problems is the recommended
approach. It is not unusual for smaller plumbing size(s) to be required to clear obstructions on the
Page 15 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

apparatus, particularly when the discharge is located a large distance from the pump (such as at
the front bumper). Additionally, it is not unusual for a smaller pipe size to be able to flow the
expected rating of the discharge, particularly if the pipe run is short and relatively straight.

Note: Some departments may attempt to define a maximum pressure loss in the discharge piping.
This may not be useful given the many variables to consider. Most manufacturers will design their
plumbing system to supply at least 150 psi pump pressure. When a higher flow rate is desired, the
specifications for the apparatus should state The discharge must be capable of supplying X gpm at
Y psi at Z engine speed.

VALVE CONSTRUCTION AND CONTROLS


Full flow ball valves (ball valves) are the most commonly used on fire apparatus. A ball valve is
manufactured with a ball which has a port machined through the center. When the ball turns one
way, it blocks flow. When turned approximately 90 degrees, the port aligns with the pipe and allows
flow. Because the diameter of the port is approximately equal to the inside diameter of the valve
pipe connections and there are no other restrictions in the flow path (such as a valve stem) there is
minimal friction loss.

These valve types usually require minimal maintenance such as replacing seals due to wear from
normal use and do not require any lubrication. Locating the valves where they are easily accessible
should be a consideration to allow for easy maintenance. Many of these valve types have what is
called a swing-out design in which the valve body can rotate away from the flanges connecting it
to the pipe so that seals may be accessed without having to disassemble much of the plumbing.

Valve Control Styles

Valve controls are available in three styles:


Manual: These may be push-pull (e.g. T-handle), crank/handwheel (rotational), or swing. The
common factor is a physical linkage between the operators control panel and the valve
itself. These are the least expensive controls available and are the most commonly used. The
main drawback to manual controls is the valves must be located relative to the control so that
the geometry of the linkage is effective (e.g. there is no binding during valve operation) and
the linkage is not blocked by other components. Manual controls may take up more panel
space than other types of actuators.
Air: These discharges use a pneumatic cylinder to open or shut the valve. The control is a
simple switch that provides air to one side of the cylinder or the other. Pneumatic valves
cannot be throttled.

Page 16 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Electric: These discharges utilize an electric motor mounted on the valve body to open and
close the valve. Operationally, these valves are the most flexible as the electric controls offer
very clear displays of valve position, and also allow the operator to actuate the valve to a
preset position at the touch of a button. These types of valves are equipped with a manual
connection on the end of the actuator gear shaft that may be used to open or shut the valve
in the event of a loss of electrical power. One advantage of using electric valves is the
allowance of increased flexibility in apparatus design. Controls may be located without regard
to where the valve is located, even if they are at opposite ends of the apparatus. Some
designs allow controls in multiple locations. As a result, the plumbing may be designed to
make the most effective use of the available space, thus allowing more space on the
apparatus for other purposes. However, a disadvantage of these valve types may be that the
upfront cost which are typically higher than manual actuators. However, the total cost (e.g.
upfront versus warranty and maintenance) between electric actuators versus manual
actuators should be considered.

DISCHARGE INSTRUMENTATION
Per NFPA 1901 Standard for Automotive Fire Apparatus, certain fire apparatus under the standard
require, all discharges 1.5,or larger, to have an individual discharge gauge that visually indicates the
hose inlet pressure immediately downstream of the valve. There is some variation allowed on other
fire apparatus types not covered by the standard. (e.g. wildland fire apparatus)

There are many types of gauges that include, but are not limited to, simple coil-tube mechanical
gauge and electronic transducers that provide a signal to a digital display. Regardless of gauge
type, if the apparatus is to be operated in cold climates where ambient temperatures can fall below
freezing for sustained periods of time, the gauges must be protected to prevent water from getting
trapped in the gauge sensor and freezing. Freezing will damage the gauge. Digital pressure gauges
are also available. These can be easily installed in the plumbing and the pressure can be displayed
on the same controller that is used for operating the electric valve. This can simplify the pump panel
design and layout.

Flow meters are becoming more common in the fire service. Flow meters use a mechanical or
electronic device, usually a paddlewheel, to provide a visual indication of the flow rate through a
discharge. This allows the operator to know exactly how much water is flowing at a given time.
Electronic flowmeters can also allow cumulative measurement of all the water flowed through a
given discharge over the course of a sustained period of time. If a mechanical and electronic flow
meters are networked together, they can provide the total water flowed through all discharges that
have a flow meter installed.

Page 17 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

There are two potential disadvantages to flowmeters. First, they are often expensive relative to stand-
alone pressure gauges. Second, they may require additional plumbing space since the inlet
plumbing must be straight for a sufficient distance to guarantee smooth flow at the flowmeter so the
flow measurements are accurate.

CHEMICAL INJECTION
Some discharges will require the introduction of firefighting chemicals such as foam concentrate.
There are several methods to do this; from simple injection ports to full body eductors. The common
feature of all methods is they will introduce additional flow restrictions into the discharge.
Direct injection foam systems introduce foam at a single point that feeds multiple discharges and
mitigates additional restrictions in the flow. Therefore, this single injection point becomes the main
flow restriction for all the discharges it feeds and must be sized to find the balance between injection
accuracy and minimizing the flow restriction.

PLUMBING MATERIAL
The plumbing material should be designed for the agent that flows through it. Stainless steel is in
common use and valves are typically made with a stainless steel or composite polymer balls and
brass, or bronze, bodies. These materials provide excellent corrosion resistance for both foam and
water. Steel piping is becoming rare and is usually only used to minimize expense.

Steel may be suitable for water even though the effects of corrosion may become evident much
more quickly than for other materials. However, it should not be used for foam. Aluminum piping is
not typically used for fire apparatus, except on waterways for aerial devices.

Regardless of the material, the plumbing system must be able to withstand the expected pressure
rating of the pump with a sufficient safety margin (500 psi for normal pressure pumps, and higher for
high pressure and ultra-high pressure pumps.)

HOSE AND APPLIANCE CONNECTIONS


The hose connections must be selected based upon the operational practices of the department.
The most common connection on any discharge is a male National Hose Thread (NH). NH threads
are required to allow full interoperability between departments in other regions.

Some jurisdictions specify other connections, such as Storz, for large diameter discharges. Some
jurisdictions may still have custom threads on their hose based upon the history of their water system.
If custom discharge threads are desired, it is required by NFPA 1901 that they be added in the form of
Page 18 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

adapters on the NH threads if the apparatus is to be used in the United States. This will maximize
interoperability and allow the apparatus to be restored to the latest industry standards if it is ever sold.

Any discharge connection higher than 42 inches above the ground should be equipped with a
turndown adapter to prevent kinking of the hose. All discharges should be equipped with a cap to
protect the threads and prevent leakage when not in use. The caps should remain secured to the
apparatus when removed from the connection using a restraining cable or chain.

Certain exceptions may, such as a deck gun or master stream device that is designed to be
mounted directly to the apparatus. Some models allow easy removal of the device so that it may be
connected to a ground base supplied by one or more hose lines.

Purchasers of fire apparatus must confirm the connection type for deck guns. Deck gun
manufacturers can supply their products with several different inlets from pipe thread to flanges, so it
is important to make sure they match.

Drains should be supplied on any discharge larger than 1. This will allow pressure to be drained from
the hoseline regardless of what the pump is doing and without having to open the nozzle. Additional
drains should be provided as necessary to allow full draining of all low points in the plumbing to
provide protection against freezing.

Components
With any type of pump, there are several components that are common, and perform common
functions. Some of these include:

Various intake manifolds, piping and valves to control and direct water coming into the pump,
Various discharge manifolds, piping, and valves to control and direct the water output
Intake Pressure Relief Valves (PRV) to discharge excess pressure coming into the pump and
protect the intake side of the pump and piping
Discharge pressure relief valves and pressure governors to limit discharge pressures to protect
discharge components and hose lines but also protect firefighters from undesirable pressure
surges,
Drain controls to drain water from the pump intake and discharge plumbing
Pump control devices, throttle, governor, primer, pump cooler, engine cooler, drains, and
thermal relief valves

Page 19 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Pump monitoring devices and pump-engaged indicators, master intake and discharge
pressure gauges, dedicated inlet and discharge pressure gauges, and flow meters (if so
equipped)
Engine monitoring devices such as engine speed, fuel level, oil pressure, cooling system
temperature, electrical charging system
Foam system valves, controls, and monitoring devices (if so equipped)

Corrosion Prevention
Corrosion and material deposits can be an issue depending on the pump, plumbing, and valve
materials utilized. The mineral and salt content of the water source can also accelerate corrosion or
build-up of deposits. A sacrificial anode helps reduce galvanic corrosion within the pump body by
attracting the corrosion away from the main parts of the pump. In simple terms, galvanic corrosion
is an electric circuit, like a battery. The anode is more active electrically than the pump components,
and therefore provides the electric flow that attracts corrosive material away from the parts you
want to protect. Because it is sacrificial, the anode will experience decay and will have to be
replaced periodically. If the anode is not replaced, once it is depleted, corrosion will likely attack
pump components.

Anodes do not provide protection against other forms of corrosion such as general oxidation, stress
corrosion, etc. All pumps, valves, appliances, and related components must be tested at least
annually in order to assure continued safe and reliable operation.

Annual Pump and Related Equipment Testing


The pumps and associated equipment should be tested annual per the NFPA 1911 Standard for the
Inspection, Maintenance, Testing, and Retirement of In-Service Automotive Fire Apparatus. Test
procedures for external valves and appliances can be found in the NFPA 1962 Standard for the Care,
Use, Inspection, Service Testing, and Replacement of Fire Hose, Couplings, Nozzles, and Fire Hose
Appliances.

Often a thorough Preventative Maintenance Program will detect issues early before they become
major, expensive problems that may take the apparatus out of service.

Page 20 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Appendix A - Abbreviations
PTO Power Take Off A gear-drive mounted on the side of an
engine flywheel or transmission that
transfers power to a shaft which can
provide rotating power to another device.
GPM Gallons Per Minute A rate measurement of liquid flow in U.S.
gallons.
LPM Liters Per Minute A rate measurement of liquid flow in
metric.
RPM Revolutions Per Minute A rate measurement of a rotating object,
such as an engine crankshaft.
NFPA National Fire Protection An internationally recognized standards
Association organization
FAMA Fire Apparatus A North American fire apparatus and
Manufacturers related component manufacturers
Association organization
PSI Pounds per Square Inch A measurement of pressure in U.S. pounds
kPa Kilo Pascals A measurement of pressure in metric
HP Horsepower A measurement of engine output
UHP Ultra High Pressure A general rating of pump pressure output
CAFS Compressed Air Foam A system used to proportion foam
System concentrate to water, then add
pressurized air to create compressed air
foam
CAF Compressed Air Foam An extinguishing or pre-treatment agent
created with a Compressed Air Foam
System
RPM Revolutions Per Minute A measurement of rotation of an engine
output shaft, or other rotating object.

Page 21 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Appendix B Pump Drive Mounting Diagrams

Direct Engine Mounting

PTO Mounting

Front Mounting

Page 22 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Midship Mounting

Rear Mounting

Page 23 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16
FIRE APPARATUS MANUFACTURERS ASSOCIATION

Appendix C - Manufacturer Contacts

For further information on apparatus and component manufacturers, refer to the


FAMA Buyers Guide.
http://www.fama.org/members/buyers_guide/

Page 24 of 24

Fire Apparatus Manufacturers Association TC024 - FAMA Pump Selection Guide 160324 DRM - FINAL 3-25-16

S-ar putea să vă placă și