42TXP Fan Coil Units 60Hz

Quality Assurance
Certificate Reg. No:
04 100 950420

Subject to change without notice Product Data Catalog


Manufacturers Name: Saudi Airconditioning Manufacturing Co. Ltd.
Country of origin : Jeddah, Saudi Arabia
Nearest port of embarkation: Jeddah Islamic port
Product classification: Commercial and Residential

42TXP 60Hz
Nominal Cooling Capacity 1.5 5.0 Tons
HFC R -410A Refrigerant
42TX Direct Expansion fan coil units are available in 6 sizes with nominal cooling capacity range from 1.5 to 5.0 Tons.
Each unit is designed to occupy a minimum space. No complex system controls are required for Carrier fan coil units.
Piping, drain, and wiring connections are readily accessible and mounting holes and slots are predrilled to save
installation time and field labor expense.

Contact your local Carrier representative for additional reference materials.

Page 1
Table of Contents
Features / Benefits .......................................................................................................................................................... 2
Model Number Nomenclature ......................................................................................................................................... 3
Physical Data .................................................................................................................................................................. 4
Base Unit Dimensions ................................................................................................................................................... 5
Combination Matrix and Ratings ..................................................................................................................................... 6
Electrical Data ................................................................................................................................................................. 6
Typical Wiring Schematic ............................................................................................................................................... 7
Detailed Performance Data ............................................................................................................................................ 7
Fan Performance / Sound Pressure ............................................................................................................................. 10
Controller For Ducted Fan Coil Units ............................................................................................................................ 11
Application Data ............................................................................................................................................................ 13
Options and Accessories .............................................................................................................................................. 14
Guide Specification ....................................................................................................................................................... 15

Features / Benefits
Every compact one-piece unit arrives fully assembled, tested, and ready to run
Designed especially for high ambient environment
EER (Energy Efficiency Ratio) ratings of up to 11.5
Standard wired control board kit to control the unit functions, with additional remote control
The drain pan is polyester powder coated for extra protection
Piping connection are field exchangeable; standard factory setup right hand side
Direct drive forward curved centrifugal fan
3 speed motor
Standard galvanized sheet metal casing
Low unit height suitable for low false ceiling application
Washable aluminum filter
Easy installation and maintenance
inch thickness internal insulation with 24 kg/m^3 density
Low noise level suitable for all application
Sweat connections for easy installation and maintenance

Carriers 42TXP direct expansion fan coils are designed to cover low to medium range of air handling requirements.
They are compact and ready to fit in the under ceiling application. All units come with solid-state fan controls, 1/2-in.
insulation, quiet multi-speed motors, and fully wet coils. Units can accommodate factor supplied field installed
heaters from 2 to 4kw. 42TXP are designed for ease of service in under ceiling applications. A carton template for
easy location of mounting hardware simplifies installation. Coils are made of double wavy aluminum fins
mechanically bonded to copper tubes for superior heat transfer.

Direct drive forward curved centrifugal fan attached to 3-speed high efficiency motors. Galvanized sheet metal
casing protects against rust and drain pan is polyester powder coated for extra protection. Electrical heater is
available option while the control board with the integrated thermostat, remote control and washable Aluminum filters
are standard feature. Piping connections position (RH/LH) is optional, and field interchangeable for various
applications.

Page 2
Model Number Nomenclature - 42TXP - R410A Series
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15
4 2 T X P 0 1 8 - 3 3 1 C R E

Controls
A = None
E = Electronic

Connection Side
R = Right Hand
Model Type L = Left Hand
42 Series Low Height
Fan Coils
Factory Installed Option
C = Cool Only
Model Series
TX = Direct Expansion

Packaging
1 = Standard

Refrigerant Type
P = R-410A Series Design Series
2 = 2nd Design Series
3 = 3rd Design Series

Unit Size Power Supply (V/Ph/Hz)


018 = 18,000 Btuh 3 = 230/1/60
024 = 24,000 Btuh 7 = 220/1/50
030 = 30,000 Btuh
036 = 36,000 Btuh
048 = 48,000 Btuh Design Review
060 = 60,000 Btuh = Factory Assigned

* FIH - Factory Supplied - Field Installed Electic Heaters Available - See Options and Accessories.

Page 3
Physical Data - 42TXP Series
Unit Model 42TXP18 42TXP24 42TXP30 42TXP36 42TXP48 42TXP60-32
Unit size (Tons) 1.5 2.0 2.5 3.0 4.0 5.0
Power Supply 230V-1Ph-60Hz
Motor HP 1/10 1/15 1/10
Number of Motors, Speeds 1, 3 Speed 2, 3 Speed
Evaporator Coil
Coil Material (HP Tube) 3/8" Grooved copper tubes
Coil Material (Finplate) Al fins, DW Al fins, LSW Al fins, DW Al fins, LSW
Coil Face Area, m^2 0.21 0.26 0.31 0.44 0.52
Number of Rows 3
Fin Denisty/ Inch 15 14
Coil Connection Type Sweat Type
Coil Connection Size (Suction, Liquid) Inch 5/8, 3/8 3/4, 3/8
Drain Diameter Inch 1
REFRIGERANT METERING DEVICE AccuRater
Size 52 55 65 70 70 84
Blower Direct drive forward curved centrifugal fan
Blower Diameter / Width, mm 156 / 220 156 / 170 156 / 220
Filter Type Washable Aluminum Filter
Filter Qty. / Size (mm) 1 / 847x262 2 / 525x262 2 / 630x262 2 / 630x365 2 / 735x365
Unit Dimensions
Width, mm 1052 1262 1472 1682
Depth, mm 600
Height, mm 275 375
Net Weight, kg 32 39 43 49 56

Page 4
Base Unit Dimensions
Notes:
- The piping connections drain pan outlet and control box are located on the right hand side facing the airflow as
factory standard. They however can be relocated to the left hand side facing air flow in the field when needed.
- Unit should be installed for horizontal discharge only. Suspend horizontally using the factory-provided holes
located at the topside flanges of the unit.

All Dimensions in mm A B C D E F H I J K W
42TXP018-33 814 906 219 255 600 447 275 228 160 211 1052
42TXP024-33 1024 1116 219 255 600 447 275 228 160 211 1262
42TXP030-33 1234 1326 219 255 600 447 275 228 160 211 1472
42TXP036-33 1234 1326 319 355 600 447 375 228 160 211 1472
42TXP048-33 1444 1536 319 355 600 447 375 228 160 211 1682
42TXP060-32 1444 1536 319 355 600 447 375 228 160 211 1682

Page 5
Combination Matrix and Ratings
Cooling Only At T1 Condition*
Capacity Annual
Unit Size Outdoor Model Indoor Model Indoor Type CFM Input Watts AMPS E.E.R
(Btu/hr) Consumption (kW)
18 38PKS18DS30-01 42TXP018-33 Ducted Split 19000 594 1645 7.5 11.55 4441
24 38PKS24DS30-01 42TXP024-33 Ducted Split 25000 708 2165 9.5 11.55 5846
30 38PKS30DS30-01 42TXP030-33 Ducted Split 31000 944 2684 12.2 11.55 7247
36 38PKS36DS30-01 42TXP036-33 Ducted Split 35000 1143 3030 13.5 11.55 8181
38PKS48DS30-01 Ducted Split 45000 1413 3896 17.0 11.55 10519
48 42TXP048-33
38PKS48DS20-01 Ducted Split 45000 1460 3896 6.8 11.55 10519
38PKS60DS30-01 Ducted Split 54000 1407 4675 20.5 11.55 12623
60 42TXP060-32
38PKS60DS20-01 Ducted Split 54000 1422 4675 8.0 11.55 12623

Cooling Only At T3 Condition**


Capacity
Unit Size Outdoor Model Indoor Model Indoor Type CFM Input Watts AMPS E.E.R
(Btu/hr)
18 38PKS18DS30-01 42TXP018-33 Ducted Split 17000 625 2000 9.0 8.50
24 38PKS24DS30-01 42TXP024-33 Ducted Split 21500 735 2590 11.5 8.50
30 38PKS30DS30-01 42TXP030-33 Ducted Split 27500 1003 3235 14.5 8.50
36 38PKS36DS30-01 42TXP036-33 Ducted Split 31000 1173 3647 16.0 8.50
38PKS48DS30-01 Ducted Split 40000 1448 4706 20.5 8.50
48 42TXP048-33
38PKS48DS20-01 Ducted Split 40000 1468 4706 8.0 8.50
38PKS60DS30-01 Ducted Split 47000 1405 5662 24.7 8.30
60 42TXP060-32
38PKS60DS20-01 Ducted Split 47000 1407 5662 9.5 8.30

Legend:
1 . CFM Cubic Feet per Minute
2 . EER Energy Efficiency Ratio
3 . Notes:As per SASO 2682/2007 testing standard below:
a) * T1 Cooling Standard: 80.6F db, 66.2F wb indoor entering-air temperature and 95.0F db, 75.2F wb air entering outdoor unit.
c) ** T3 Cooling Standard: 84.2F db, 66.2F wb indoor entering-air temperature and 114.8F db, 75.2F wb air entering outdoor unit.
4 . Annual consumption is rated at 2700 hours x Input kW.

Electrical Data
42TXP Series
Nominal Voltage Fan
Model No. Condenser Control Input Power Supply
Capacity Ton Min Max FLA
42TXP018-33 1.5
1.0
42TXP024-33 2
42TXP030-33 2.5
24V 230/1/60 207 253 1.5
42TXP036-33 3
42TXP048-33 4
2.0
42TXP060-32 5

Legend:
1. FLA - Full Load Amps

Page 6
Typical Wiring Schematic

Page 7
Detailed Performance Data
Matching 38P with 42TXP
Evaporator Condenser Air Entering Deg. F
Nom Air 75 85 95 105 115 120
Cap.
Mbtuh Cap. MBH Cap. MBH Cap. MBH Cap. MBH Cap. MBH Cap. MBH
CFM EWB kW* kW* kW* kW* kW* kW*
Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen
72.0 21.7 10.8 1.3 20.8 10.5 1.5 19.8 10.1 1.6 18.2 9.4 1.8 16.7 8.8 2.0 15.9 8.5 2.1
66.2 19.7 13.5 1.4 18.8 13.1 1.5 17.4 12.5 1.7 15.9 11.8 1.8 14.4 11.2 2.0 13.6 10.8 2.1
400
62.0 18.0 15.3 1.4 17.1 14.9 1.5 16.2 14.4 1.6 14.3 13.5 1.8 12.9 12.7 2.0 12.2 12.2 2.0
57.0 16.8 16.8 1.4 16.1 16.1 1.5 15.4 15.4 1.6 13.9 15.4 1.8 12.8 12.8 2.0 12.2 12.2 2.0
72.0 22.4 11.7 1.3 21.5 11.3 1.5 20.5 11.0 1.6 19.0 10.4 1.8 17.4 9.8 2.0 16.5 9.5 2.1
66.2 20.5 15.1 1.3 19.5 14.6 1.5 18.1 14.0 1.6 16.6 13.4 1.8 15.1 12.7 2.0 14.3 12.4 2.1
18 500
62.0 19.1 17.4 1.3 18.2 16.9 1.5 16.9 16.3 1.7 15.4 15.4 1.8 14.2 14.2 2.0 13.6 13.6 2.1
57.0 18.4 18.4 1.4 17.7 17.7 1.5 16.7 16.7 1.7 15.4 15.4 1.8 14.2 14.2 2.0 13.6 13.6 2.1
72.0 22.9 12.5 1.3 22.0 12.1 1.5 21.0 11.7 1.6 19.5 11.2 1.8 17.8 10.6 2.0 17.0 10.3 2.1
66.2 21.1 16.5 1.3 20.0 16.0 1.5 19.0 15.5 1.6 17.2 14.8 1.8 15.6 14.1 2.0 14.8 13.8 2.1
600
62.0 19.9 19.2 1.4 18.9 18.7 1.5 17.7 17.7 1.6 16.4 16.4 1.8 15.1 15.1 2.0 14.5 14.5 2.1
57.0 19.7 19.7 1.4 18.9 18.9 1.5 17.7 17.7 1.6 16.4 16.4 1.8 15.1 15.1 2.0 14.5 14.5 2.1
72.0 28.8 14.3 1.8 27.6 13.8 2.0 26.3 13.2 2.2 24.9 12.7 2.4 23.3 12.0 2.6 22.3 11.7 2.7
66.2 26.0 17.7 1.8 24.8 17.1 2.0 23.5 16.5 2.2 22.2 15.9 2.4 20.2 15.0 2.6 19.3 14.6 2.7
500
62.0 23.8 19.9 1.8 22.6 19.3 2.0 21.4 18.7 2.1 20.2 18.1 2.3 18.1 17.0 2.5 17.1 16.5 2.6
57.0 22.0 22.0 1.8 21.1 21.1 1.9 20.1 20.1 2.1 19.2 20.1 2.3 17.6 17.6 2.5 16.8 16.8 2.6
72.0 29.8 15.2 1.8 28.5 14.7 2.0 27.1 14.2 2.2 25.6 13.6 2.4 24.0 13.0 2.6 23.2 12.6 2.7
66.2 27.1 19.3 1.8 25.7 18.7 2.0 24.4 18.1 2.2 23.0 17.5 2.4 21.1 16.7 2.6 20.1 16.2 2.7
24 600
62.0 25.0 22.1 1.8 23.8 21.4 2.0 22.5 20.8 2.2 21.2 20.2 2.4 19.2 19.1 2.6 18.4 18.4 2.7
57.0 23.8 23.8 1.8 22.8 22.8 2.0 21.8 21.8 2.1 20.8 20.8 2.4 19.2 19.2 2.6 18.4 18.4 2.7
72.0 30.4 16.0 1.8 29.1 15.5 2.0 27.7 15.0 2.2 26.2 14.4 2.4 24.5 13.8 2.6 23.6 13.4 2.7
66.2 27.8 20.8 1.8 26.4 20.1 2.0 25.0 19.6 2.2 23.6 18.9 2.4 21.9 18.2 2.6 20.7 17.7 2.7
700
62.0 25.9 24.1 1.8 24.7 23.4 2.0 23.3 22.7 2.2 22.0 22.0 2.4 20.4 20.4 2.6 19.6 19.6 2.7
57.0 25.3 25.3 1.8 24.3 24.3 2.0 23.2 23.2 2.2 22.0 22.0 2.4 20.4 20.4 2.6 19.6 19.6 2.7
72.0 36.1 18.0 2.2 34.4 17.3 2.4 32.7 16.6 2.7 30.9 15.9 2.9 28.6 15.0 3.2 27.3 14.5 3.3
66.2 32.7 22.4 2.2 31.3 21.7 2.5 29.6 20.9 2.7 27.4 19.9 2.9 24.8 18.8 3.2 23.4 18.2 3.3
700
62.0 29.9 25.3 2.2 28.5 24.6 2.4 27.1 23.9 2.7 24.7 22.7 2.9 22.3 21.5 3.1 21.1 20.9 3.3
57.0 28.2 28.2 2.2 27.1 27.1 2.4 25.9 25.9 2.7 24.0 25.9 2.9 22.1 22.1 3.1 21.1 21.1 3.3
72.0 36.9 18.8 2.2 35.1 18.0 2.4 33.3 17.3 2.7 31.6 16.6 2.9 29.3 15.8 3.2 28.0 15.3 3.3
66.2 33.7 23.8 2.2 32.1 23.1 2.5 30.3 22.2 2.7 28.2 21.3 2.9 25.6 20.2 3.2 24.1 19.6 3.3
30 800
62.0 30.9 27.1 2.2 29.5 26.4 2.4 28.1 25.7 2.7 25.7 24.5 2.9 23.3 23.3 3.1 22.3 22.3 3.3
57.0 29.7 29.7 2.2 28.5 28.5 2.4 27.3 27.3 2.7 25.4 25.4 2.9 23.3 23.3 3.1 22.3 22.3 3.3
72.0 37.7 19.8 2.2 35.9 19.0 2.4 34.1 18.3 2.7 32.2 17.5 2.9 30.1 16.9 3.2 28.8 16.4 3.3
66.2 34.6 25.7 2.2 32.9 24.8 2.5 31.0 23.9 2.7 29.0 23.2 2.9 26.4 22.2 3.2 25.1 21.6 3.3
950
62.0 32.2 29.7 2.2 30.7 29.0 2.5 29.2 28.2 2.7 27.0 27.0 2.9 24.9 24.9 3.2 23.8 23.8 3.3
57.0 31.5 31.5 2.2 30.3 30.3 2.5 29.0 29.0 2.7 27.0 27.0 2.9 24.9 24.9 3.2 22.3 22.3 3.3

Notes:
1. kW* Total System Power Input
2. Ewb Entering Wet-Bulb
3. SHC Sensible Heat Capacity (1000 Btuh) Gross
4. Bold, Italics, Underlined - Standard Ratings
5. Formulas:
a) Leaving db = Entering - Sensible Heat Cap / (1.09 x CFM)
b) Leaving wb = wb corresponding to air leaving coil (hwb)
c) hwb Leaving = hwb entering - total cap(Btuh)/(4.5 X CFM)
6. Direct interpolation is permissible. Do not extrapolate.

Page 8
Detailed Performance Data (Continued)
Matching 38P with 42TXP
Evaporator Condenser Air Entering Deg. F
Nom Air 75 85 95 105 115 120
Cap.
Mbtuh Cap. MBH Cap. MBH Cap. MBH Cap. MBH Cap. MBH Cap. MBH
CFM EWB kW* kW* kW* kW* kW* kW*
Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen Tot Sen
72.0 40.1 20.1 2.3 38.2 19.4 2.6 36.3 18.6 3.0 33.6 17.5 3.3 30.7 16.4 3.7 29.1 15.8 3.9
66.2 36.4 24.1 2.3 34.7 23.4 2.6 32.7 22.5 3.0 29.6 21.1 3.3 26.6 19.8 3.7 25.1 19.2 3.9
800
62.0 32.7 27.9 2.3 31.0 27.1 2.6 28.7 25.9 2.9 25.8 24.4 3.3 23.1 22.8 3.6 21.7 21.7 3.8
57.0 30.0 30.0 2.3 28.8 28.8 2.6 26.9 26.9 2.9 24.8 24.8 3.2 22.8 22.8 3.6 21.7 21.7 3.8
72.0 41.4 21.4 2.3 39.4 20.5 2.6 37.5 19.7 3.0 34.9 18.8 3.3 31.9 17.7 3.7 30.3 17.1 3.9
66.2 37.9 26.1 2.3 36.1 25.3 2.6 34.1 24.5 3.0 30.8 23.1 3.3 27.7 21.8 3.7 26.1 21.1 3.9
36 950
62.0 34.0 30.5 2.3 32.3 29.6 2.6 30.0 28.4 2.9 27.0 26.6 3.3 24.5 24.5 3.6 23.4 23.4 3.8
57.0 32.1 32.1 2.3 30.8 30.8 2.6 29.0 29.0 2.9 26.7 26.7 3.3 24.5 24.5 3.6 23.4 23.4 3.8
72.0 42.3 22.4 2.3 40.3 21.6 2.6 38.3 20.8 3.0 35.9 20.0 3.4 32.8 18.9 3.7 31.1 18.3 4.0
66.2 38.9 27.9 2.3 37.0 27.0 2.6 35.0 26.1 3.0 31.7 25.0 3.3 28.5 23.6 3.7 26.9 22.9 3.9
1150
62.0 35.1 32.9 2.3 33.3 31.9 2.6 31.2 30.6 3.0 28.3 28.3 3.3 26.0 26.0 3.7 24.8 24.8 3.9
57.0 33.9 33.9 2.3 32.5 32.5 2.6 30.7 30.7 3.0 28.3 30.7 3.3 26.0 26.0 3.7 24.8 24.8 3.9
72.0 52.0 52.0 3.1 49.8 25.1 3.5 47.0 23.8 3.9 43.8 22.4 4.3 40.4 21.0 4.8 38.6 20.5 5.0
66.2 48.3 26.0 3.1 45.7 30.0 3.5 42.6 28.5 3.9 39.5 27.1 4.3 36.1 25.4 4.8 34.2 25.0 5.0
1050
62.0 44.5 33.3 3.1 41.3 34.7 3.4 38.0 32.8 3.8 34.7 31.1 4.2 31.3 29.0 4.6 29.4 28.5 4.9
57.0 40.6 40.6 3.1 37.9 37.9 3.4 35.5 35.5 3.8 33.1 35.5 4.2 30.5 30.5 4.6 29.2 29.2 4.9
72.0 53.5 53.5 3.1 51.2 26.4 3.5 48.5 25.2 3.9 45.1 23.8 4.3 41.6 22.4 4.8 39.7 22.0 5.0
66.2 49.7 27.9 3.1 47.3 32.3 3.5 44.1 30.7 3.9 40.9 29.3 4.3 37.3 27.7 4.8 35.4 27.4 5.0
48 1250
62.0 46.0 36.5 3.1 43.1 37.9 3.5 39.7 36.0 3.8 36.4 34.1 4.3 32.9 32.0 4.7 31.5 31.5 4.9
57.0 43.4 43.4 3.1 40.8 40.8 3.4 38.2 38.2 3.8 35.6 35.6 4.2 32.9 32.9 4.7 31.5 31.5 4.9
72.0 54.4 42.3 3.1 52.0 27.3 3.5 49.3 26.1 3.9 46.0 24.8 4.3 42.3 23.4 4.8 40.4 23.0 5.0
66.2 50.6 29.3 3.1 48.4 33.9 3.5 45.0 32.0 3.9 41.7 30.9 4.3 38.1 29.2 4.8 36.1 29.0 5.0
1400
62.0 46.8 38.7 3.1 44.0 39.9 3.5 40.7 38.2 3.9 37.5 36.2 4.3 34.4 34.4 4.7 32.9 32.9 5.0
57.0 45.0 45.0 3.1 42.6 42.6 3.5 39.9 39.9 3.9 37.3 37.3 4.3 34.5 34.5 4.7 33.0 33.0 5.0
72.0 61.8 30.6 3.8 59.4 29.6 4.2 56.7 28.4 4.7 53.9 27.3 5.2 50.1 25.8 5.7 47.9 24.8 6.0
66.2 55.7 37.0 3.8 53.2 35.9 4.2 50.7 34.7 4.6 47.4 33.2 5.1 42.7 31.1 5.5 40.5 30.1 5.8
1050
62.0 50.9 41.3 3.7 48.6 40.1 4.1 46.1 38.8 4.5 42.2 37.0 5.0 38.0 34.9 5.4 36.0 33.9 5.6
57.0 46.4 46.4 3.7 44.6 44.6 4.0 42.7 42.7 4.5 39.5 42.7 4.9 36.5 36.5 5.4 34.9 34.9 5.6
72.0 63.9 32.4 3.8 61.4 31.4 4.3 58.7 30.3 4.7 55.7 29.1 5.2 52.0 27.7 5.7 49.9 26.9 6.0
66.2 58.0 40.2 3.8 55.5 39.0 4.2 52.8 37.8 4.7 49.9 36.5 5.2 44.9 34.4 5.6 42.5 33.4 5.8
60 1250
62.0 53.5 45.4 3.8 51.0 44.2 4.2 48.4 42.9 4.6 44.7 41.1 5.0 40.2 38.9 5.5 37.8 37.8 5.7
57.0 50.0 50.0 3.7 48.1 48.1 4.1 46.1 46.1 4.5 43.0 43.0 5.0 39.6 39.6 5.4 38.0 38.0 5.7
72.0 65.1 33.6 3.8 62.6 32.7 4.3 59.8 31.6 4.7 56.7 30.4 5.2 53.1 29.0 5.8 50.9 28.3 6.0
66.2 59.3 42.3 3.8 56.8 41.2 4.2 54.0 39.9 4.7 51.0 38.7 5.2 46.1 36.7 5.6 43.7 35.6 5.9
1400
62.0 55.0 48.3 3.8 52.5 47.0 4.2 49.8 45.7 4.6 46.3 44.0 5.1 41.7 41.7 5.5 40.0 40.0 5.8
57.0 52.4 52.4 3.7 50.3 50.3 4.1 48.2 48.2 4.6 45.3 45.3 5.0 41.6 41.6 5.5 39.9 39.9 5.8

Notes:
1. kW* Total System Power Input
2. Ewb Entering Wet-Bulb
3. SHC Sensible Heat Capacity (1000 Btuh) Gross
4. Bold, Italics, Underlined - Standard Ratings
5. Formulas:
a) Leaving db = Entering - Sensible Heat Cap / (1.09 x CFM)
b) Leaving wb = wb corresponding to air leaving coil (hwb)
c) hwb Leaving = hwb entering - total cap(Btuh)/(4.5 X CFM)
6. Direct interpolation is permissible. Do not extrapolate.

Page 9
Fan Performance/Sound Pressure
Fan Performance English - 42TXP Air Flow (CFM)
Ex. Static Pres. in.wg 0 0.05 0.1 0.15
Unit H M L H M L H M L H M L
42TXP018-33 692 586 548 666 555 497 640 524 447 603 466 373
42TXP024-33 780 691 607 756 642 552 732 592 497 682 527 443
42TXP030-33 1181 995 815 1106 895 740 1031 796 665 935 706 557
42TXP036-33 1385 1172 1096 1333 1110 995 1281 1048 893 1205 931 746
42TXP048-33 1572 1383 1214 1512 1283 1104 1452 1184 995 1363 1054 885
42TXP060-32 1572 1383 1214 1512 1283 1104 1452 1184 995 1363 1054 885

Fan Performance English - 42TXP Air Flow (CFM) - Continued


Ex. Static Pres. in.wg 0.2 0.25 0.3
Unit H M L H M L H M L
42TXP018-33 541 421 294 434 318 329
42TXP024-33 607 464 373 524 383 453
42TXP030-33 846 637 457 736 517 617
42TXP036-33 1082 842 587 846 621 642
42TXP048-33 1214 927 746 1042 762 901
42TXP060-32 1214 927 746 1042 762 901

Fan Performance SI - 42TXP Air Flow (m^3/hr)


Ex. Static Pres. In.Pa 0 12.5 25 37.5
Unit H M L H M L H M L H M L
42TXP018-33 1176 995 931 1132 943 845 1088 891 759 1024 791 634
42TXP024-33 1326 1174 1032 1284 1091 938 1243 1006 844 1159 896 752
42TXP030-33 2007 1690 1385 1879 1521 1257 1751 1352 1129 1589 1200 946
42TXP036-33 2353 1991 1862 2265 1886 1690 2177 1781 1518 2048 1582 1268
42TXP048-33 2671 2349 2062 2569 2180 1876 2467 2011 1690 2315 1791 1504
42TXP060-32 2671 2349 2062 2569 2180 1876 2467 2011 1690 2315 1791 1504

Fan Performance SI - 42TXP Air Flow (m^3/hr) - Continued


Ex. Static Pres. In.Pa 50 62.5 75
Unit H M L H M L H M L
42TXP018-33 919 715 499 737 541 559
42TXP024-33 1032 788 634 890 651 769
42TXP030-33 1437 1082 777 1251 879 1048
42TXP036-33 1839 1430 997 1437 1055 1091
42TXP048-33 2062 1575 1268 1770 1295 1530
42TXP060-32 2062 1575 1268 1770 1295 1530

Sound Pressure - 42TXP - English


Ex. Static Pressure dBA @ 0 in.wg ESP dBA @ 0.1 in.wg ESP dBA @ 0.2 in.wg ESP
Unit H M L H M L H M L
42TXP018-33 50.0 48.0 46.0 49.0 46.5 45.0 48.0 45.0 43.5
42TXP024-33 50.5 48.5 46.5 49.5 47.0 45.5 48.5 45.5 44.0
42TXP030-33 51.0 49.0 47.0 50.0 47.5 46.0 49.0 46.0 44.0
42TXP036-33 51.0 49.0 47.0 50.0 47.5 46.0 49.0 46.0 44.5
42TXP048-33 51.5 49.5 47.5 50.5 48.0 46.5 49.5 46.5 45.0
42TXP060-32 51.5 49.5 47.5 50.5 48.0 46.5 49.5 46.5 45.0

Sound Pressure - 42TXP - SI


Ex. Static Pressure dBA @ 0 Pa ESP dBA @ 25 Pa ESP dBA @ 50 Pa ESP
Unit H M L H M L H M L
42TXP018-33 50.0 48.0 46.0 49.0 46.5 45.0 48.0 45.0 43.5
42TXP024-33 50.5 48.5 46.5 49.5 47.0 45.5 48.5 45.5 44.0
42TXP030-33 51.0 49.0 47.0 50.0 47.5 46.0 49.0 46.0 44.0
42TXP036-33 51.0 49.0 47.0 50.0 47.5 46.0 49.0 46.0 44.5
42TXP048-33 51.5 49.5 47.5 50.5 48.0 46.5 49.5 46.5 45.0
42TXP060-32 51.5 49.5 47.5 50.5 48.0 46.5 49.5 46.5 45.0
Notes: Sound pressure assumes "standard room", 3 meters from exit, no ducts, ducts will further reduce sound.

Legend:
CFM - Cubic Feet per Minute
in.wg - Inch Water Gage
Pa - Pascal
dBA - Decibel

Page 10
Controller For Ducted Fan Coil Units
Features: The controller is used to control air cooled ducted split unit, supports the following functions:
- Modes: Cool, Dry, Fan, Heat
- Indoor fan speed: Auto, High, Medium, Low
- Sleep mode
- Compressor protections:
Comp 3 minutes restart protection
Indoor coil anti-freeze
Room sensor and indoor coil sensor failure monitoring
- Non volatile memory keep system settings
- Programmable On/Off timer
- Random restart to minimize voltage dip during compressor first cut in cycle upon power up.

Hardware Setting: A 2 way DIP switch is used to configure: DIP Switch On Off
SW1 Cool Cool-Heat
SW2 Water System DX System

Error Code: If multiple faults happen at the same time, the corresponding error code will be shown one after
another
Fault Error code
Room sensor fault E1
Indoor coil sensor fault E2
Comp fault E4

Split System Description


Wireless Room Controller
Wired Room Controller

Wired Room
Controller (Standard)

Notes: The wired room controller is mounted on the wall and can control all system functions without wireless remote control.

1) On/Off Key: If you press this key, the system will begin operation, Press the key again, and operation stops.
(You can hear a receiving beep). If you press this key immediately after turning off the system, the compressor will
not operate for 3 minutes to prevent overloading.

2) Operation Mode Selection Key: Toggles the operation mode: Cool, Dry, Heat, or Fan only
COOL Led Lights on when selecting COOL mode.
DRY Led Lights on when selecting DRY mode.
HEAT Led Lights on when selecting Heat mode.
FAN Led Lights on when selecting FAN mode.

3) Fan Speed Selection Key: Toggles the fan speed: Auto, High, Medium, or Low, Note: Fan key is invalid in Dry
mode.

4) Temperature Up Key: By pressing Temperature up Key, the setting temperature increases by 1C with each
press.

5) Temperature Down Key: By pressing temperature down key, the setting temperature decreases by 1C with
each press. If you set the desired room temperature, then system will maintain the room temperature as set. Upon
setting the desired room temperature the system will maintain the room temperature

Page 11
Cool Mode: If the room temperature is higher than the setting, the compressor will automatically turn on provide a
cooling effect. On the hand, if the room temperature is lower than the setting, the compressor will automatically turn
off to stop cooling operation. If indoor fan is programed to be turned off with comp signal, it will turn off once comp
is cut off
Heat Mode: If the room temperature is lower than the setting, the Electric heater will automatically turn on to
provide a heating effect. If the room temperature is higher than the setting, the heater will automatically turn off to
stop heating operation. If indoor fan is programed to be turned off with heater signal, it will turn off once heater is
cut off but subject to 30 sec dispersing remaining heat timing.
Dry Mode: The fan speed runs automatically at low speed and compressor stopping and running is controlled by
the difference between room and setting temperatures and by continuous running time. If indoor fan is programed
to be turned off with comp signal, it will turn off once comp is cut off
- In Dry mode, the humidity is reduced in the space to be air-conditioned.
Fan Mode: There will be no cooling or heating effects; only the fans of indoor unit will run for ventilation at the
selected speed (High, Med, and Low).
- In COOL or HEAT mode and if AUTO fan speed is selected; Fan speed is automatically selected by controller
according to the difference between setting temperature and room temperature, fan will be continuously
running at low speed after setting temperature is achieved.
Notes:
a) Temperature setting range is 16C to 30C or 60F to 85F.
b) Hold down at the same time for about 5 seconds, Temp down and fan keys will toggle the temperature
setting from degree C to degree F and vice versa.
c) Press any temperature key will flash the current setting temperature for 4 seconds, Should there be no
further key press, it will revert to room temperature display. Temperature display range is 0 C to 50 C or 32 F
to 99 F.
d) Temp keys are invalid in Fan mode.
6) Sleep Key: Press this key to set the SLEEP timer and then the sleep led will light on, to cancel the sleep timer
press this key again.
- Sleep function for healthy sleep to control automatically the room temperature and stop automatically the
operation of the air conditioner after certain set off time.
- Sleep mode is valid in cool or heat mode and invalid in Fan mode.
7) Timer Key: Upon count down of the set hours, the system will switch from OFF to ON or vice-versa.
- OFF Timer Function to stop automatically, the air conditioner after certain set OFF time.
- ON Timer Function to start automatically, the air conditioner after certain set ON time.
* Timer setting is 1 Hour to 24 Hour. The timer led will light on when operating the Timer Function
First key press will flash the digital display and Timer Led for 3 seconds.
Notes:
a) The digital displays show the number of hours previously set, only the Timer Led flashes.
b) Subsequent 3 seconds will show the number of hours previously set; only the timer led flashes.
c) Should there be no further key press, it will revert to normal mode.
d) Should Timer key is not released timer setting will increase automatically every 0.5-second.
8) Sensor: Receives the remote controllers signal
9) Display Screen: Displays the set temperature and displays also the TIMER settings when adjusting it.
10) Key Lock Mode: To activate key lock mode, hold down for 3 seconds, temp. Down Key (5) and Mode Key (2).
In key lock mode, all keys are not valid except ON/OFF Key (1) to turn ON/OFF the system.
Notes:
a) Hold down Temp Down and Sleep button for one second to enter into coil temperature display mode.
Press Temp Up key to display indoor coil temperature, High Fan LED flashes. With the same sequence to
exit coil temperature display mode. Temperature display range is -9C to 78 C.
FAN
b) Hold down and buttons for only 1 second ( 5 sec to toggle between C and F temperature )
to activate temperature display setting and auto fan LED flashes. Repeat the same sequence to cancel
this function. Press or button to change the setting from 1 to 2. 1 means disable room
temperature display and 2 means enable room temperature display.
Menu Parameter Set Range Default value Remarks
Temperature display, Auto fan 1: Disable room temp display
1 1~2 1
LED flashing 2: Enable room temp display
Cool mode fan control function, 1: Comp OFF, Fan ON
2 1~2 1
Auto & High fan LED flashing 2: Comp OFF, Fan OFF
Heat mode fan control function, 1: Heater OFF, Fan ON
3 1~2 1
Auto & Medium fan LED flashing 2: Heater OFF, Fan OFF

Page 12
Application Data
FIELD SUPPLIED
TYPE L REFRIGERANT
TUBING
FEMALE SWEAT FIELD SUPPLIED
CONNECTIONS 24 V CONTROL
AT SERVICE VALVES WIRING

FIELD SUPPLIED
FIELD SUPPLIED WEATHERPROOF
FILTER DRIER FUSED DISCONNECT
AND WIRING PER NEC

FIELD SUPPLIED
CONDENSATE
DRAIN LINE
TO OPEN DRAIN

FIELD SUPPLIED
42TX /MX

FUSED DISCONNECT
AND WIRING PER NEC

REMOTE CONTROL
CONTROL BOARD

NOTES:
1. All piping must follow standard refrigerant piping techniques.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended for a special installation.
4. Insulate condensate line if run above a conditioned space.

Page 13
Options and Accessories
Electric Heater Option (Factory Supplied - Field Installed Option)

A single heater element having capacity of 2.0 and 2.5 kW or two heater elements with a combined capacity of 4.0
kW can be factory installed (Option); the electric heater is open type with thermal protection and fuse for more
safety. Heater capacities are available as shown in the following table:

Models Heaters No ; Watts/Heaters Total Heating Capacity kW


42TXP018-33 1 ; 2000 2
42TXP024-33 1 ; 2500 2.5
42TXP030-33
42TXP036-33
2 ; 2000 4
42TXP048-33
42TXP060-32

Connection Side Option

Standard coil connection and electric box position is Right Hand facing air flow direction while the optional position
is Left Hand facing the air flow for both coil connection and electric box. Customers can order this option directly
from the factory also units are designed to be field exchangeable if needed in the field.

Control Board Wire Extension

Standard wire length for control board is 15m optional extensions are available to enlarge the wire up to 30 m. if
extension are required, please contact your local Carrier dealer.

UV-C Ready (Factory Supplied - Field Installed Option)

Unit is UV-C Ready for easy installation, UV-C is factory supplied for field installation with field exchangeable
connections available for size 30-60.

Page 14
Guide Specifications
Cooling Only/Electric Heat Fan Coil Unit
HVAC Guide Specifications
Size Range: 1.5 to 5 Nominal Tons
General

System Description
The fan coil unit is designed for under ceiling installation, electrically controlled cooling and heating (option). Unit
shall be horizontal installation. Standard unit shall include washable permanent aluminum filter. Unit shall be
designed for medium external static pressure up to 0.5 inch water.

Quality Assurance
A. Unit shall be rated in accordance with SASO 2681-2682/2007.
B. Unit shall be designed in accordance with ISO 9001:2000, and shall be manufactured in a facility registered
by ISO 9001:2000.

Products
A. The unit shall be factory assembled single piece cooling unit, with optional electric heat.
B. Unit cabinet shall be constructed of galvanized steel. The unit shall be insulated with polyester urethane
insulation that is 1/2 inch thickness & 24 kg/m^3 density, Unit cabinet panels shall be single skin
C. Unit shall have a permanent washable aluminum filter. Filter shall be flame retardant and easy accessible
through an access panel.

D. Units shall have external drain pan with inch insulation, the drain pane shall be galvanized steel coated
with polyester powder for extra protection.

E. The unit fan wheel shall be directly connected to the motor. The fan wheel shall be dynamically balanced
with double inlet forward curved type blower wheel.

F. Unit coil shall have aluminum fins mechanically bonded to seamless smooth copper tubes 3/8 inch with all
joints brazed. Unit coil shall be accessible for cleaning.

G. The coil connection shall be sweat type; it shall be RH/LH exchangeable.

H. The unit fan motor shall have permanently lubricated sleeve bearing and 3 speeds, the motor shall have
internal overload protection and B class insulation.

I. Unit shall have a wired control board with a built-in thermostat to be installed in the air-conditioned area
and it shall have the following Features:
i. Control Modes Cool, Dry, Fan, Heat, Auto Cool-Heat and Sleep mode.
ii. Compressor protections 3 minutes restart protection.
iii. Indoor coil anti-freeze protection.
iv. Failure monitoring for room sensor and indoor coil sensor.
v. Nonvolatile memory keep system settings.
vi. Programmable On/Off timer.
vii. Random Restart Time Delay to minimize voltage dip during compressor first cut in cycle
upon power up for multiple units operation.

J. Unit shall have a wireless remote to control all the functions of the control board at a distance.

K. All electric parts shall be easy accessible for service.

L. Unit control board shall be 230V/1Ph.

Page 15
Manufacturer reserves the rights to discontinue or change at any time, specifications or designs without notice and without incurring any obligations.
Supersedes Version: 42TXP-PDC2 Page 16 Catalog Number: 42TXP-PDC03
Effective Date: 18-01-2015 Phase: 60Hz