Type CDG 21/61

IDMT Overcurrent and Earth Fault Relay with Highset


Type CDG 21/61
IDMT Overcurrent and Earthfault Relay with high-set instantaneous unit.

Features ensures good contact pressure base of the graduated time


even at currents near pick-up. multiplier scale. A high-set
Identical time/ current instantaneous overcurrent/
characteristics on all taps. Damping of the disc earth fault unit is fitted in the
Self-powered, no necessity movement is by a removable same case to provide
for separate auxiliary high retentivity permanent instantaneous protection
supply. magnet. The unique method under maximum short circuit
High torque, ensuring of winding the operating coil conditions and to improve
consistent timing even ensures that the time/current discrimination on time graded
under adverse conditions. characteristics are identical on protective systems
Very low overshoot. each of the seven current
Simple construction, easily taps. Selection of the required Technical data
accessible. current setting is by means of
a plug setting bridge, which Current ratings
Comprehensive range of
has a single insulated plug. 1A or 5A.
high-set unit ratings.
Dustproof drawout case The maximum current tap is
IDMT settings
and tropicalised finish. automatically connected when
the plug is withdrawn from 50 - 200% in seven equal
the bridge, allowing the steps of 25%.
Application setting to be changed under 20 - 80% in seven equal
load without risk of open steps of 10%.
Selective phase and earthfault 10 - 40% in seven equal
circuiting the current
protection, in time graded transformers. The IDMT relay steps of 5%.
systems for AC machines, has an auxiliary unit which is Other setting ranges
transformers, feeders etc. powered by a secondary available on request.
winding on the electromagnet
General description through a rectifier and as Starting current
such a separate auxiliary 103 - 105% of current setting.
A non-directional heavily supply is not required. The
damped induction disc relay, Closing current
disc unit operates and closes Not more than 130% of
which has an adjustable its contacts, the auxiliary
inverse time/current current setting.
element connected across the
characteristic with a definite secondary winding on the Instantaneous highset
minimum time. CDG 21and electromagnet operates and settings
CDG 61 are 1 & 3 pole one normally open contact of E/F 100 - 400%,
versions of CDG11 with the auxiliary element O/C 400 - 1600%
highset instantaneous unit reinforces the disc contact.
respectively. The relay has a Other setting ranges
Two other contacts of the available on requests
high torque movement auxiliary element are brought
combined with low burden For special applications
out to the terminals of the
and low overshoot. The relay highest unit with low
relay.
disc is so shaped that as it transient overreach is also
rotates the driving torque available as option.
The relay operating time can
increases and offsets the Please contact our
be adjusted by movement of
changing restraining torque application department
the disc backstop which is
of the control spring. This for details.
controlled by rotating a
feature combined with the knurled moulded disc at the
high torque of the relay
Burden
Time settings Time grading unaffected by
3VA nominal
Operating time such small error, since all
2VA on the lowest tap
0 - 3 seconds or relays are similarly affected.
3.5VA on high-set tap.
0 - 1.3 seconds at 10 times
current setting. Temperature error
For 10 times setting current, Case and finish
Resetting time at ambient temperature 1D vertical or 3D vertical,
4 seconds for 1.3 seconds between horizontal case suitable for
relay and 9 seconds for 3 +45C and 5C, flush or projection mounting
seconds relay with time percentage timing errors are and finished eggshell black
multiplier setting at 1.0 as follows: and tropicalised. Suitable trip
3 seconds relay: 3% isolating switch and CT
Overshoot and +4% shorting switches provided on
Overshoot time on removal of 1.3 seconds relay: 4% the cradle
20 times setting current. and +4%.
Less than 0.065 second
for 1.3 seconds relay Auxiliary units and operation Information required with
Less than 0.04 second for indicators Order
3 seconds relay. Self-powered auxiliary unit
will have following contact 1. Current transformer
Thermal rating combinations: secondary
Maximum continuous rating.
current rating for 60C 1. S/R - 2N/O or 2. Current setting range.
rise in coil temperature . 2. H/R - 2N/O + 2 N/C. 3. Characteristic (0 - 3.0 sec.
Operating
or
Coil tap
1 2 3 4 5 6 7
Contact ratings auxiliary unit 0 - 1.3 sec. at 10 times
Times
current 4.5 3.7 3.2 2.7 2.6 2.4 2.2 contact current
setting
Make and carry for 0.5 setting).
Withstand 20 times second 7500 VA with maxima 4. Operation indicator
maximum setting current of 30 amps/ 660 volts ac/dc. inscription, if
for 3 seconds. required.
Insulation 5. Auxiliary contacts - hand or
Accuracy The relay meets the
Error class index self
requirements of reset.
E7.5 as per BS 142-1966 IS 3231-1965/IEC.265-6
7.5 as per IS 3231-1965 6. Current setting range of
series C-2 kV for 1 minute. high-set
Frequency error unit, if required.
Timing error less than 8% for 7. Case size.
2 Hz frequency variations. 8. Type of mounting - flush or
projection.
Dimensions and weights

Relay Case Maximum overall dimensions Approximate


size Height Width Depth* gross weight
mm mm mm Kg.
CDG 21 1D Vert. 233 170 203 6.0
CDG 61 3D Horz. 233 454 203 15.5
3D Vert. 524 170 203 15.0
* Add 76 mm for maximum length of terminal studs, alternatively, 29 mm for terminal screws.
The approximate gross weights given above are inclusive of cartons, mounting appendages and terminal details.
The relays comply fully with the requirements of IS 3231-1965 and are suitable for use in normal tropical environments.
ALSTOM Limited Pallavaram Works: 19/1, GST Road, Pallavaram, Chennai-600 043. India.
Tel: 91-044-2368621 Fax: 91-044-2367276 Email: plw.applications@alstom.sprintrpg.eml.vsnl.net.in.
1998 ALSTOM Limited