Sunteți pe pagina 1din 2

Smoke control system design

Smoke control systems keep building occupants safe from smoke generated during unwanted fires.
Requirements for smoke control systems are given in Section 909 of the 2007 and 2010 International Fire Modeling
Building Code (IBC), the primary model building code used in the United States. For atrium smoke control,
IBC 909 refers to NFPA 92B, "Standard for Smoke Management Systems in Malls, Atria, and Large Spaces" Design of Smoke Control System
for design of smoke control systems.
Performance based design
Smoke control system design in high-rise buildings is accomplished using the pressurization method (IBC
909.6). Mechanical ventilation systems are used to create small pressure differences (minimum of 0.05
inches of water column) across smoke barriers, a special type of fire-resistant construction defined in IBC 709 Structural Fire Engineering
and IBC 909.5. Maximum pressure differences are limited by door opening forces, which must remain less
than 30 lb. During a fire, small pressure differences created by smoke control systems keep smoke confined ASET/RSET analysis
to one smoke control zone. Smoke control systems based on the pressurization method are designed to
prevent smoke from spreading to adjacent smoke control zones, but they are not intended to maintain a
tenable environment in the smoke control zone where the fire originates. Instead, that is the purpose of
smoke control systems based on the exhaust method -- widely used for atrium smoke control.

Atrium smoke control


Atrium smoke control, and smoke control in similar large volume spaces, is achieved using the exhaust Contacts
method (IBC 909.8). Exhaust inlets located near the ceiling remove smoke at a rate that is greater than or
Reax Engineering Inc.
equal to the rate at which it is generated, or at a rate that maintains a tenable environment during 1921 University Avenue
evacuation. Due to the prescriptive requirements of IBC 909.8.1, smoke control systems in an atrium are Berkeley, CA 94704
often designed to maintain the smoke layer 6 ft above the highest occupiable walking surface by exhausting
smoke at a rate that is greater than or equal to the smoke production rate. For reasons discussed below, this 510-629-4930
can lead to unnecessary overdesign of atrium smoke control systems. info@reaxengineering.com

The smoke production rate (and the required exhaust rate) for a fire in an atrium increases as the heat
Based in the San Francisco
release rate of the design fire increases. Therefore, establishment of the design fire is the most critical step in Bay Area but serving clients
design of atrium smoke control systems. IBC 909.9 requires the design fire to be determined by a "registered across the US and abroad
design professional" (meaning a licensed Professional Engineer) based on a "rational analysis". Once the
design fire has been established by a licensed Fire Protection Engineer, the required exhaust rate (cubic feet
per minute, or cfm) must be calculated.

For smoke control system in "small" or "simple" atriums, the required exhaust rate can be calculated by
applying the algebraic plume entrainment equations presented in NFPA 92B. However, these equations have a
limited range of applicability and there are several common situations where NFPA 92B's algebraic equations
are not appropriate for design of atrium smoke control systems, either because they lead to unnecessarily
high exhaust rates, or their inherent assumptions break down. Examples include:

1. Tall spaces (> 5 stories). The algebraic equations in NFPA 92B assume that all air entrained into a fire
plume instantly becomes smoke, and the total amount of smoke produced increases super-linearly with
height above the fire. Application of NFPA 92B's algebraic equations to determine exhaust rates in tall
atria will lead to unnecessarily large exhaust requirements. This will result in an over-designed atrium
smoke control system, which adds significant construction costs but does not improve occupant safety
over an appropriately-sized system.

2. Very large-volume atriums. The algebraic equations in NFPA 92B do not account for any effect of
smoke dilution, which can be significant in large-volume spaces. The NFPA 92B algebraic equations
would require the same exhaust rate in an indoor sports arena and a a 10 ft by 10 ft building shaped
like a church steeple, provided the design fire and height of the highest occupiable level are the same!
However, it is common sense that the sports arena should require less exhaust because the smoke is
spread out over the large volume of air contained in the arena. However, this is not recognized by the
NFPA 92B algebraic equations, and application of these equations to very large-volume spaces will lead
to unnecessary overdesign of atrium smoke control systems.

3. Atriums and similar large-volume spaces that do not have a single central floor opening with a large
plan area. The algebraic axisymmetric and balcony spill plume equations in NFPA 92B are not
applicable to design of atrium smoke control systems unless the plume is not affected by upper
balconies or walls. Thus, their range of applicability is limited to spaces having a well-defined central

opening, and inappropriate use of these equations can lead to erroneous design.

4. Spaces where the smoke layer depth cannot be maintained at a minimum of 20% of the floor-to-ceiling
height. When designing an atrium smoke control system where the highest occupiable walking surface
is close to the ceiling, it is sometimes not possible to simultaneously meet NFPA 92B requirements for
minimum smoke layer depth (20% of the floor-to-ceiling height) and simultaneously maintain the
smoke layer 6 ft above the highest occupiable walking surface as required by the International Building
Code. Specifically, NFPA 92B requires that the minimum design depth of the smoke layer shall be
twenty percent of the floor to ceiling height or "based on an engineering analysis". When these
prescriptive requirements cannot be met simultaneously, NFPA 92B's algebraic equations cannot be
used to size atrium smoke control systems, and an engineering analysis (often entailing computer fire
modeling) is required.

For cases where the NFPA 92B algebraic equations for smoke exhaust rate do not apply, or would lead to
unnecessarily large exhaust rates, computer fire modeling is usually applied to determine the required
exhaust rate. This is accomplished by performance-based design, or an ASET/REST analysis (Available Safe
Egress Time vs. Required Safe Egress Time) which is usually addressed through IBC 104.11 "Alternative
materials, design and methods of construction and equipment" or California Building Code Section 108.7
"Alternate materials, designs, tests and methods of construction".

Applying techniques such as computer fire modeling, ASET/RSET analyses, and performance-based design to
atrium smoke control systems can often lead to significant construction cost savings and make innovative
designs possible. Since makeup air (or supply air) is usually provided at 85% to 95% of the exhaust rate,
reduction of the exhaust rate can lead to major reductions in makeup air requirements. From an aesthetic
and cost standpoint, this is often more significant than reducing the exhaust rate because exhaust fans and
inlets can usually be incorporated in the ceiling construction, but low-level makeup air inlets are often
problematic in atria.

Reax Engineering, Inc. has considerable expertise in sizing and design of smoke control systems, including
application of NFPA 92B's algebraic equations, computer fire modeling, ASET/RSET analyses, and
performance-based design. For inquiries related to smoke control system design or atrium smoke control,
please contact David Rich.

Back to Reax Fire Protection Engineering services

Copyright 2014 Reax Engineering Inc. All rights reserved Services - People - Media - Contacts - Privacy Policy

S-ar putea să vă placă și