Sunteți pe pagina 1din 50

NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION

127/220 v
RESIDENTIAL CUSTOMERS

Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
25 4 2.5 2 30 11.43 3 x 25 (100)
50 8 5.0 4
74 11 7.4 5.5

75 12 7.5 6 60 22.86 3 x 25 (100)


100 16 10.0 8
125 20 12.5 10
150 24 15.0 12
174 27 17.4 13.5

175 28 17.5 14 100 38.11 3 x 25 (100)


200 32 20.0 16
225 36 22.5 18
250 40 25.0 20
275 43 27.5 21.5
300 46 30.0 23
324 49 32.4 24.5

325 50 32.5 25 150 57.16 3 x 40 (160)


350 53 35.0 26.5
375 56 37.5 28
400 60 40.0 30
425 63 42.5 31.5
450 66 45.0 33
475 70 47.5 35
500 73 50.0 36.5
524 75 52.4 37.5

525 76 52.5 38 200 76.21 C.T.


550 80 55.0 40
575 83 57.5 41.5
600 86 60.0 43
625 90 62.5 45
650 93 65.0 46.5
674 95 67.4 47.5

SAH / MNMG1 (updated 2) / R T-1 1:12 PM , 4/7/2002


NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION

127/220 v
RESIDENTIAL CUSTOMERS

Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
675 96 67.5 48 300 114.32 C.T.
700 100 70.0 50 (See Note 1)
725 103 72.5 51.5
750 106 75.0 53
775 110 77.5 55
800 113 80.0 56.5
825 116 82.5 58
850 120 85.0 60
875 123 87.5 61.5
900 126 90.0 63
925 130 92.5 65
950 133 95.0 66.5

951 134 95.1 67 400 152.42 C.T.


975 136 97.5 68
1000 140 100.0 70
1025 143 102.5 71.5
1050 146 105.0 73
1075 150 107.5 75
1100 152 110.0 76

1101 153 110.1 76.5 500 190.53 C.T.


1125 156 112.5 78
1150 160 115.0 80
1175 163 117.5 81.5
1200 166 120.0 83
1300 180 130.0 90
1382 190 138.2 95

1383 191 138.3 95.5 600 228.63 C.T.


1400 193 140.0 96.5
1500 206 150.0 103
1600 220 160.0 110
1658 228 165.8 114

1659 229 165.9 114.5 700 266.74 C.T.


1700 233 170.0 116.5
1800 246 180.0 123
1900 260 190.0 130
1953 266 195.3 133

1954 267 195.4 133.5 800 304.84 C.T.


2000 273 200.0 136.5
2100 286 210.0 143
2200 300 220.0 150
2236 305 223.6 152.5
Note 1 : Use 400 A fuses in place of 300 A fuses.

SAH / MNMG1 (updated 2) / R T-1 1:12 PM , 4/7/2002


NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION

127/220 v
COMMERCIAL CUSTOMERS

Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
25 6 3.0 3.6 30 11.43 3 x 25 (100)
50 10 6.0 6
55 11 6.6 6.6

56 12 6.7 7.2 60 22.86 3 x 25 (100)


75 16 9.0 9.6
100 22 12.0 13.2
125 27 15.0 16.2

126 28 15.1 16.8 100 38.1 3 x 25 (100)


150 32 18.0 19.2
175 38 21.0 22.8
200 43 24.0 25.8
225 48 27.0 28.8
230 49 27.6 29.4

231 50 27.7 30 150 57.15 3 x 40 (160)


250 54 30.0 32.4
275 59 33.0 35.4
300 64 36.0 38.4
325 70 39.0 42
350 75 42.0 45

351 76 42.1 45.6 200 76.2 C.T.


375 80 45.0 48
400 86 48.0 51.6
425 91 51.0 54.6
449 95 53.9 57

450 96 54.0 57.6 300 114.3 C.T.


475 102 57.0 61.2 (See Note 1)
500 107 60.0 64.2
525 112 63.0 67.2
550 118 66.0 70.8
575 123 69.0 73.8
600 128 72.0 76.8
624 133 74.9 79.8

625 134 75.0 80.4 400 152.4 C.T.


650 139 78.0 83.4
675 144 81.0 86.4
700 150 84.0 90
711 152 85.3 91.2

SAH / MNMG1 (updated 2) / C T-2 11:16 AM , 4/6/2002


NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION

127/220 v
COMMERCIAL CUSTOMERS

Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
Note 1 : Use 400 A fuses in place of 300 A fuses.
712 153 85.4 91.8 500 190.5 C.T.
725 155 87.0 93
750 160 90.0 96
775 166 93.0 99.6
800 171 96.0 102.6
825 176 99.0 105.6
850 182 102.0 109.2
875 187 105.0 112.2
893 190 107.16 114

894 191 107.3 114.6 600 228.6 C.T.


900 192 108.0 115.2
925 198 111.0 118.8
950 203 114.0 121.8
975 208 117.0 124.8
1000 214 120.0 128.4
1025 219 123.0 131.4
1050 224 126.0 134.4
1069 228 128.3 136.8

1070 229 128.4 137.4 700 266.7 C.T.


1075 230 129.0 138
1100 235 132.0 141
1125 240 135.0 144
1150 246 138.0 147.6
1175 250 141.0 150
1200 256 144.0 153.6
1249 266 149.9 159.6

1250 267 150.0 160.2 800 304.8 C.T.


1300 278 156.0 166.8
1400 299 168.0 179.4
1429 305 171.5 183

SAH / MNMG1 (updated 2) / C T-2 11:16 AM , 4/6/2002


NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION

220/380 v
RESIDENTIAL CUSTOMERS

Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
25 4 2.5 2 30 19.74 3 x 25 (100)
50 8 5.0 4
75 12 7.5 6
100 16 10.0 8
124 19 12.4 9.5

125 20 12.5 10 60 39.48 3 x 25 (100)


150 24 15.0 12
175 28 17.5 14
200 32 20.0 16
225 36 22.5 18
250 40 25.0 20
275 43 27.5 21.5
300 46 30.0 23
312 47 31.2 23.5

313 48 31.3 24 100 65.8 3 x 25 (100)


325 50 32.5 25
350 53 35.0 26.5
375 56 37.5 28
400 60 40.0 30
425 63 42.5 31.5
450 66 45.0 33
475 70 47.5 35
500 73 50.0 36.5
525 76 52.5 38
550 80 55.0 40
575 83 57.5 41.5
598 85 59.8 42.7

599 86 59.9 43 150 98.7 3 x 40 (160)


625 90 62.5 45
650 93 65.0 46.5
675 96 67.5 48
700 100 70.0 50
725 103 72.5 51.5
750 106 75.0 53
775 110 77.5 55
800 113 80.0 56.5
825 116 82.5 58
850 120 85.0 60
875 123 87.5 61.5
900 126 90.0 63
930 130 93.0 65.2

SAH / MNMG1 (updated 2) / R380 T-3 11:16 AM , 4/6/2002


NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION

220/380 v
RESIDENTIAL CUSTOMERS

Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
931 131 93.1 65.35 200 131.6 C.T.
950 133 95.0 66.5
975 136 97.5 68
1000 140 100.0 70
1025 143 102.5 71.5
1050 146 105.0 73
1075 150 107.5 75
1100 152 110.0 76
1125 156 112.5 78
1150 160 115.0 80
1175 163 117.5 81.5
1188 164 118.8 82

1189 165 118.9 82.5 300 197.4 C.T.


1200 166 120.0 83 (See Note 1)
1300 180 130.0 90
1400 193 140.0 96.5
1500 206 150.0 103
1600 220 160.0 110
1679 230 167.9 115

1680 231 168 115.5 400 263.2 C.T.


1700 233 170.0 116.5
1800 246 180.0 123
1900 260 190.0 130
1923 263 192.3 131.5

1924 264 192.4 132 500 329.0 C.T.


2000 273 200.0 136.5
2100 286 210.0 143
2200 300 220.0 150
2300 313 230.0 156.5
2400 326 240.0 163
2424 329 242.4 164.5

2425 330 242.5 165 600 394.8 C.T.


2500 340 250.0 170
2600 353 260.0 176.5
2700 366 270.0 183
2800 380 280.0 190
2900 393 290.0 196.5
2916 395 291.6 197.5

2917 396 291.7 198 700 460.6 C.T.


3000 406 300.0 203
3200 433 320.0 216.5
3409 460 340.9 230

3410 461 341.0 230.5 800 526.4 C.T.


3600 487 360.0 243.5
3800 514 380.0 257
3890 526 389.0 263
Note 1 : Use 400 A fuses in place of 300 A fuses.

SAH / MNMG1 (updated 2) / R380 T-3 11:16 AM , 4/6/2002


NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION

220/380 v
COMMERCIAL CUSTOMERS

Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)
25 6 3.0 3.6 30 19.74 3 x 25 (100)
50 10 6.0 6
75 16 9.0 9.6
92 19 11.0 11.4

93 20 11.2 12 60 39.48 3 x 25 (100)


100 22 12.0 13.2
125 27 15.0 16.2
150 32 18.0 19.2
175 38 21.0 22.8
200 43 24.0 25.8
224 47 26.9 28.2

225 48 27.0 28.8 100 65.8 3 x 25 (100)


250 54 30.0 32.4
275 59 33.0 35.4
300 64 36.0 38.4
325 70 39.0 42
350 75 42.0 45
375 80 45.0 48
399 85 47.9 51

400 86 48.0 51.6 150 98.7 3 x 40 (160)


425 91 51.0 54.6
450 96 54.0 57.6
475 102 57.0 61.2
500 107 60.0 64.2
525 112 63.0 67.2
550 118 66.0 70.8
575 123 69.0 73.8
600 128 72.0 76.8
611 130 73.3 78

612 131 73.4 78.6 200 131.6 C.T.


625 134 75.0 80.4
650 139 78.0 83.4
675 144 81.0 86.4
700 150 84.0 90
725 155 87.0 93
750 160 90.0 96
772 164 92.6 98.4

SAH / MNMG1 (updated 2) / C380 T-4 11:16 AM , 4/6/2002


NEW MINISTRY GUIDELINES FOR CUSTOMER LOAD ESTIMATION

220/380 v
COMMERCIAL CUSTOMERS

Covered Area Total Unit A/C Estimated Contracted Load KWH Meter
(Sq. Meter) Connected Connected Demand C.B. Rating Size (Amps)
Load (KVA) Load (KVA) Load (KVA) (Amps) (KVA)

773 165 92.8 99 300 197.4 C.T.


775 166 93.0 99.6 (See Note 1)
800 171 96.0 102.6
825 176 99.0 105.6
850 182 102.0 109.2
875 187 105.0 112.2
900 192 108.0 115.2
925 198 111.0 118.8
950 203 114.0 121.8
975 208 117.0 124.8
1000 214 120.0 128.4
1025 219 123.0 131.4
1050 224 126.0 134.4
1075 230 129.0 138

1076 231 129.1 138.6 400 263.2 C.T.


1100 235 132.0 141
1125 240 135.0 144
1150 246 138.0 147.6
1175 250 141.0 150
1200 256 144.0 153.6
1233 263 148.0 157.8

1234 264 148.1 158.4 500 329 C.T.


1300 278 156.0 166.8
1400 299 168.0 179.4
1300 278 156.0 166.8
1400 299 168.0 179.4
1500 320 180.0 192
1542 329 185.0 197.4

1543 330 185.2 198 600 394.8 C.T.


1600 342 192.0 205.2
1700 363 204.0 217.8
1800 384 216.0 230.4
1852 395 222.2 237

1853 396 222.4 237.6 700 460.6 C.T.


1900 405 228.0 243
2000 427 240.0 256.2
2100 448 252.0 268.8
2162 460 259.4 276

2163 461 259.6 276.6 800 526.4 C.T.


2200 469 264.0 281.4
2300 491 276.0 294.6
2400 512 288.0 307.2
2465 526 295.8 315.6

SAH / MNMG1 (updated 2) / C380 T-4 11:16 AM , 4/6/2002


CIRCUIT BREAKER SIZE AND CUSTOMER LOAD RANGE IN AMPERES

No. Connected Amps. Range C.B. Size Customer Cable Size (Cu) , Sq. mm

Greater than Less or Equal to (Amps.) Minimum Maximum

1 00 29 30 1x(4x25) 1x(4x25)

2 29 72 60 1x(4x35) 1x(4x50)

3 72 130 100 1x(4x50) 1x(4x50)

4 130 198 150 1x(4x50) 1x(4x50)

5 198 250 200 1x(4x95) 1x(4x120)

6 250 350 300 1x(4x150) 1x(4x185)

7 350 400 400 1x(4x240) 1x(4x240)

8 400 500 500 2x(4x185) 2x(4x300)

9 500 600 600 2x(4x185) 2x(4x300)

10 600 700 700 2x(4x240) 2x(4x300)

11 700 800 800 2x(4x300) 2x(4x300)

12 800 1000 1000

13 1000 1250 1250

14 1250 1600 1600

15 1600 2000 2000

16 2000 2500 2500

Note : Customer cable size shall be determined by Engineering Units for loads exceeding 800 Amps.

SAH/ Mnmg1/AmpRange T-9 4/6/2002

S-ar putea să vă placă și