6:00am March1,2007
9420
DCStepVoltageAndSurgeTestingOfMotors
Forgetthecontroversy.Thesetestsclearlyarenondestructiveinnature.Understandingthe
advantagesthesemethodshaveoverotherscanmakethemmightypowerfultoolsinyour
PdMprogram.
Beforeanycompanyinvestigateselectricalpredictivemaintenance(PdM)instrumentation,itshould
knowthestrengthsofitsequipmentsinsulation,thevoltagesitsmotorsareexposedtodaily,howa
motortypicallyfailsandwherethesefaultstypicallyexist.Onlythencanyoureallymakeadecision
astowhichelectricalPdMequipmentisthemostappropriateforyouroperations.
Howamotortypicallyfails
Themotorstatorhastwomaininsulatingsystemsthatincludethegroundwallandturntoturn
insulation.Whenthisinsulationisinagoodconditionitcanwithstandthenormaldaytodayvoltage
spikesthatexistduringstartingandstopping.Overtime,thisinsulationwilldeteriorateasaresultof
mechanicalmovementofthewindings,torquetransients,heat,contamination,andother
environmentalcontaminates.Oncethedielectricstrengthofthisinsulationfallsbelowtheincoming
voltagespikes,anotherfailuremechanismisintroduced:ozone.
Ozoneisaverycorrosivegasthatwillquicklydeteriorateinsulation.Althoughthemotorwillcontinue
torunwhenthisfailuremechanismisintroduced,asitseescontinualvoltagespikes,the
deteriorationratewillaccelerate.Eventually,thedielectricstrengthoftheinsulationwillfallbelow
operatingvoltageordeterioratetothepointthatcopperwirewilltouchturntoturn.Atthispointa
turntoturnorhardweldedshorthasdeveloped.
AccordingtoTransientModelforInductionMachineswithStatorWindingTurnFaultswrittenfor
IEEEbyRangarajanM.Tallam,TomG.HabetlerandRonaldG.Harley,whenahardweldedturnto
turnshortdevelops,theshortedwindingswilldevelophighcirculatingcurrents.Thesecurrents,
whichcanbeintheorderof1620timesfullloadamps,createexcessiveheatthattheinsulation
cannotwithstand.Thisintenseamountofheatwillburnquicklythroughtheinsulationcausingmotor
failurewithinminutes.
AstudyperformedatOregonStateUniversity,byDr.ErnestoWiedenbrug,lookedatamotor
speciallydesignedwithaturntoturnfaultbyinstallingtwowiresconnectedtoturnoneandturntwo
ofthesamephase.Thesewireswerethenbroughtouttoaswitch.Themotorwasplacedona
dynamometerandrunatabout80%load.Whentheturntoturnshortwasengagedthroughthe
switch,themotorbeganvisiblysmokingwithin45seconds.Whilemostmotorswillnotrunforlong
withaturntoturnshort,someexceptionsdoexist.Amotorwithahighresistanceorfloatingground
willrunwithashortedphase,butonceasecondphaseshorts,themotorwillfailcatastrophically.
RecommendedtestsThetestslistedonthenextpagearerecommendedinofflinefieldtesting:
KelvinMethodWinding
MegOhm
PolarizationIndex(PI)
StepVoltage
Surge
Eachofthesetestmethodsevaluatesadifferentsectionofthemotor.Briefdescriptionsofthefirst
threetestsaregiveninordertoofferacompletearrayoftestinginformation.Thenatureofhigh
voltagetestingandthenecessityoftheStepVoltageandSurgemethods,however,remainthemain
focusofthisarticle.
KelvinMethodWinding
TheKelvinMethodWindingtestmeasurestheresistanceofthecopperwireofthemotorcircuit.If
testedinaPdMapplication,thetestistypicallyperformedfromtheMotorControlCenter(MCC).This
testfindsissueswithmissconnections,shorts,opens,unbalancedturncountinonephaseto
anotheranddifferentsizediametercopperinonephasetoanother.Thistestisveryvaluableand
shouldbeperformedforpredictivemaintenance,troubleshootingandqualityassurance.
MegOhmTest
TheMegOhmTestappliesaDCpotential(typicallyoperatingvoltage)tothewindingswhileholding
thecasetoground.TableIshowstherecommendedtestvoltagesfordifferentvoltageclassmotors.
MegOhmtestingistypicallyutilizedtofindgroundedmotors.ItalsoisaveryvaluablePdMtoolfor
findingwetanddirtymotors.Itsnottypicallyusedforqualityassurancebecauseofthelowvoltage
levelatwhichthetestisperformed.
PolarizationIndex(PI)Test
ThistestismuchliketheMegOhmTest,butitisperformedfor10minutes.Overthistimeperiod,the
moleculesintheslotlinerpaperpolarize.Whenthemoleculespolarize,theinsulationresistance
valuesshouldincreaseoverthe10minuteperiod.Iftheresistanceincreasesduringthistime,itsan
indicationofgoodgroundwallinsulationwithnomoistureorcontamination.
Insulationtesting
Untilnowwehaveonlydiscussedthelowvoltagetests.Uponsuccessfullycompletingthesetests
thefollowingisknown:thewindingresistanceisbalanced.Thatmeansthemotorhasnoshorts,
opensormissconnectionsandtheMegOhmandPIindicatethatthemotorisbothcleananddry.
Thesetests,however,stillhavenotconfirmedthatthemotoriscapableofstartingorrunningforany
lengthoftime.Themainreasonforperformingpredictivemaintenanceonamotoristolearnifitwill
continuetoprovideuninterruptedservice.Becauselowvoltagetestingisnotperformedatthe
voltageamotortypicallysees,itcantprovidethisinformation.
Manyarticleshavediscussedthevoltagespikesmotorsseeduringstartingandstopping.Asstated
inTurnInsulationCapabilityofLargeACMotors,PartISurgeMonitoring,byB.K.Gupta,B.A.
Lloyd,G.C.Stone,andS.RCampbell(IEEETransactionsonEnergyConversion,Vol.EC2,No.4,
December1987),thesevoltagespikescanbeintheorderof5PU(PerUnit):
Calculatingthisformulafora480Vthreephasemotor,thePUwouldbe391.9volts,orapproximately
1960voltsonstartup.Logically,ifthemotoristestedtoonlyoperatingvoltageorbelowtheoperating
voltage,theusercannotbesureifthespikeshavecauseddamagetothemotorsinsulationthatwill
interruptservice.Theotherissueisthattheturntoturninsulationhasnotbeenevaluated.In
addition,theMegOhmandPIdonotevaluatethegroundwallinsulationforstrengthortheabilityto
withstandthehighvoltagesitseesduringdailyoperation.Thewindingresistancetestisonly
evaluatingthemotorcircuitandnottheinsulation.
Themosteffectivewaytoensurethemotorwillstartandcontinuetoprovidereliableserviceistotest
itatthevoltagesthemotorseesduringnormaloperationwhichincludesstartingandstopping.This
isaccomplishedwithtwotests:StepVoltageandSurge.Thesemethodsevaluatethegroundwall
andturntoturninsulationrespectively.
StepVoltageTest
ThisDCTestisperformedtoavoltagethatamotortypicallyseesduringstartingandstopping.The
testvoltages,governedbyIEEE,arereflectedinTableII.
TheDCvoltageisappliedtoallthreephasesofthewinding
andraisedslowlytoapreprogrammedvoltagestepleveland
heldforapredeterminedtimeperiod.Itisthenraisedtothe
nextvoltagestepandheldfortheappropriatetimeperiod.
Thisprocesscontinuesuntilthetargettestvoltageis
reached.Typicalstepsfora4160Vmotorare1000volt
increments,holdingatminuteintervals.Formotorslessthan4160V,thestepvoltagesshouldbe500
volts(seeFig.1).
Dataisloggedattheendofeachstep.Thisistoensurethecapacitivechargeandpolarization
currentisremovedandthatonlyrealleakagecurrentremains,thusprovidingatrueindicationofthe
groundwallinsulationcondition.If,atthispoint,theleakagecurrent(IA)doubles,insulation
weaknessesareindicatedandthetestshouldbestopped.Iftheleakagecurrent(IA)rises
consistentlylessthandouble,themotorinsulationisingoodstanding.
TheStepVoltageTestisnecessarytoensurethatthegroundwallinsulationandcablecan
withstandthenormaldaytodayvoltagespikesthemotortypicallyseesduringoperation.IfaDC
StepVoltageTestisnotperformed,theoperatorcannotbeassuredthatthemotorwillstartand
operatewithoutfailinginservice.
SurgeTest
TheSurgeTestishighlyimportant.Thatsbecause
80%ofallelectricalfailuresinthestatorbeginat
weakinsulationturntoturn.Thesetypesof
catastrophicfailuresarewhyNFPA70B
recommendsthatSurgeandHiPottestingbe
performed.Regardlessofanindividualspersonal
viewofSurgetesting,knowingthatamotorsturnto
turninsulationissoundiscrucialforsafetyandmotor
reliability.
DuringaSurgeTest,theequipmentwillchargeupacapacitorinsidetheunitanddissipateitinto
onephasewhileholdingtheothertwophasestoground.Then,automatically,thetestunitwillslowly
increasethevoltagefrom0voltstothetargettestvoltage.Thisgeneratesawaveform,inashape
basedupontheinductanceofthecoilthatisdisplayedonthetestequipmentscreen.Ifthetargettest
voltageisattainedwithoutanyfrequencychangeinthewaveform,theturntoturninsulationintegrity
hasbeenrealized.Fig.2isagraphicalrepresentationofthewaveformatonethird,twothirdsand
fullvoltageofonephase.Thisiswhatawaveformwilllooklikewhentheinsulationisinagood
condition.
If,atanytime,thetestequipmentseesweakinsulationbetweentheturns,thewaveformwillshiftto
theleftasshowninFig.3.Thewhitelineonthegraphshowsthefailedwaveformatabout1000
volts.
Surgetestingtheory
Whenthecapacitorisdischargedintothewinding,itisperformedataveryfastrisetime(.1micro
second).Thisproducesanonlinearvoltagedropacrosstheturns,producingapotentialdifference
betweentheturnsinsuccession.Astherisetimeslows,theoperatorwillnoticethatthevoltage
potentialdifferencebetweentheturnsisdramaticallyreduced.Thisisincontrasttoanyothersignal
utilizedtodiagnosemotorissues.NoDCtest(orACtestssuchasaninductance,capacitance,
impedance,phaseangleorHiPot)willproducethispotentialdifferencebetweentheturns.
PhysicsprovidesuswithPaschensLaw,whichstatesthattwobarewiresplacednexttooneanother
justathicknessofahairawayneedaminimumof325voltstojumptheairgapbetweenthetwo
conductors.ThesetwoconceptsarethecorereasonwhySurgetestingisthenaturalchoicefor
testingturntoturninsulation.Themainreasonisthatifthetestequipmentdoesntproducea
potentialdifferencebetweentheturnsabovePaschensLaw,thecurrentcannotflowthroughthe
fault.Ifcurrentcantflowthroughthefault,itwillcontinuethroughallthecoilsandnotshowa
difference.
WhenSurgeTestingacoilwithweakinsulationturntoturn,thevoltageappliedcanjumpacrossthe
weakinsulation.Removingthesebypassedturnsfromthecircuitreducestheinductanceofthe
circuitandcausesthewaveformfrequencytoringfaster.Thiswillproducethefrequencyshifttothe
leftinthewaveform.Fortunately,advancementsintechnologyhaveledtorefinementsinthe
analysisofwaveforms,tothepointthatsometestunitsautomaticallyrecognizefailures(see
sidebar).
SurgecomparisonInthepasttheSurgeTesthasbeencalledaSurgeComparisonTest.Although
someindividualsbelievetheSurgeTeststillneedstobeperformedinthismanner,itreallydepends
onwhatisbeinganalyzed.
Forfindingweakinsulation,surgecomparisonisnotnecessary.Aspreviouslynoted,weak
insulationisdiagnosedbyafrequencyshifttotheleftandiscomparedtosuccessivewaveforms
withinonephase.If,however,thefollowinglistreflectsproblemsyoureseekingtouncoverand
eliminate,acomparisonofeachphaseisrecommended.
Shorts
Opens
Differentsizediametercopperbetweenphases
Unbalancedturncountbetweenphases
Reversedcoils
Shortedlaminations
Hereagain,asreferencedintheaccompanyingsidebar,instrumentationthatautomaticallydetects
theseproblemsisnowavailable.
Oldervs.newerequipment
Justlikecomputers,highvoltagetestequipmenthaschangedvastlyoverthepast20years.
Todaysequipmentincorporatesmodern,highspeedelectronicevaluationofchangestoresistance,
leakagecurrent,leakagecurrentversustime,voltage,stepvoltage,dielectricabsorption,frequency
response,waveshape,coronainceptionvoltage(C.I.V.)andmoretodetectfaultsatorunderthe
levelsofenergyexposedtothemotorduringoperation.Microprocessorcontrolledinstantaneous
tripsallowwindingconditionstobeevaluatedwithoutcompromisingdielectricintegrity.Moreover,
theadditionoffielddevelopedPASS/FAILtestcriterianowmakesthistestingextremelyrepeatable.
Oneofthegreatestadvancesinhighvoltagetestinghascomefromviasolidstate,highvoltage
powersuppliesreplacingtheheavystepuptransformer.Thishasresultedinbigimprovementsto
equipmentportability.Everytestisnowdigitizedandcomparedtothepreviouslyappliedpulse.If
anyweaknessisdetected,thetestisinstantaneouslystopped,preservingdielectric.Thelevelof
weaknessisstoredforfuturereference,inthememorybank.
Whattolookfor
WhenevaluatingelectricalPdMequipment,keepinmindthateverymanufacturerisslightly
different.Testunits,though,shouldbeabletoperformthefollowingsafetycheckstoensurethatyour
motorsarentdamagedduringtesting:
1.AcceptableMegOhmreadingsshouldbeobtained.
2.AcceptablePITestshouldbeperformed.
3.ThetestunitshouldevaluatetheMegOhmreadingsattheendofeachstep.Ifthemotordoesnotmeetthecriteriathe
testsetshouldautomaticallystopthetest.
4.Currentleakageshouldbemonitoredcontinuouslyandtheunitshouldautomaticallystopthetestifanovercurrent
leakageconditionexists.Typicalovercurrenttripsettingsare1,10,100and1000microampsofcurrentleakage.
5.Microarcdetectioniscrucialifthetestseesatinyarctheunitshouldautomaticallystopthetest.
6.Realtimedisplayonthescreenisamustthisallowstheoperatortoseethevoltageandcurrentwhilethetestisin
operation.Iftheoperatorseesanyabnormalcondition,he/shecanstopthetest.
Casestudy:StepVoltagetesting
ExelonNuclear,LimerickStation
TheStationPredictiveMaintenanceprogramatLimerickroutinelyperformselectricaltestingoflarge
motorsatatwoyearfrequency.Thistestingconsistsofwindingresistance,insulationresistance,PI
Capacitance/dissipationfactorandDCstepvoltagetestingto20kV.Theresultingdatahasbeen
trackedandtrendedforalmost20years.
Onafewoccasionsduring2002,Operationspersonnelreportedthatanacridodorwaspresentat
the1CCirculatingWaterPumpMotor.ThePdMgrouphadbeentrackingthismotoronawatchlist
thatcameaboutasaresultofanincreasingtrendinleakagecurrentdetectedbyDCstepvoltage
testingfrom1997to2002(seeFig.4).
Aspartofitsincreasedtroubleshootingactivities,theLimerickStationPdMteammonitoredthe
motorthroughthesummerof2002,utilizingacousticmonitoringandvibrationandwinding
temperature/RTDmonitoringonamonthlybasis.InSeptember2002,anactionrequestwasmadeto
replacethemotorinthewinter,basedupontheelectricaltestingresults,increasingvibrationatstator
slotfrequenciesandhigheracoustic/ultrasonicnoise.
Oncethemotorwasremoved,itshowedhighleakagecurrentontheAphasemotorwinding
comparedtotheothertwowindings.Aftercleaning,avisualinspectionofthewindingidentified
partialdischargeatthejunctionwherethecoreslotwindingtaptransitionstotheend
winding/knuckletape.Investigationrevealedalackofpropercoronasuppressiontapeatthis
criticaljunctionpointinthewinding.
Amongthelessonslearnedfromthiseventwasthefactthattrackingandtrendingleakagecurrent
versusappliedvoltageonaDCStepVoltageTest,aspresentedbytheBakerAWAofflinetester,
cananddoesindicatepotentialproblemsinthewinding.Furthermore,whenthisdataiscombined
withotherpredictivetechnologies,itwillallowforproactivereplacementofamotorpriortoanin
servicefailure.
Casestudy:Surgetesting
Pulp&PaperOperation
A2300Vformwoundmotoratapulpandpaperplantwasfoundtohaveweakturntoturninsulation.
Ofallthetestsperformedonthismotor,theonlyonethatfoundtheturntoturnweaknesswasthe
SurgeTest.Thecontroversyaroundsurgetesting,though,isthatafterfindingaproblemwith
insulation,couldthetesterhavesodegradedthemotorthatitwouldnotrun?
ThisPulp&Paperindustrycasestudyeasilyputs
thismythtorest.Themotorinquestionwas
immediatelyputbackinserviceaftertesting.It
wasstartedupandranforthefourmonths
requireduntilitcouldbeshutdownandremoved
forrepair.Again,asnotedinFig.5,theSurgeTest
wastheonlymethodtoidentifytheinsulation
weakness.Theproblemwaswellaboveline
voltage,sootherlowvoltagetestswouldnothave
approachedthisthreshold.(Thesurgesummary
inFig.5highlightsthefaultweaknessesfound
withthetester.)
ThisparticularPulp&Papersitemotortakesabout67hourstochange.Thus,itcouldhavecost
about$42,000indowntimehadtheSurgeTestnotfoundtheproblem.Interestingly,80%ofall
electricalmotorfailuresbeginwithweakinsulationturntoturn.TheSurgeTestisclearlythebest
methodavailabletofindthisproblem.Thatswhyitissoimportanttoperformthistypeofnon
destructivetestingonallmotors.
Summary
TheStepVoltageandSurgeTestsarenecessaryforaneffectivePdMprogram.Theyidentify
problemsthatlowvoltagetestscantfind.
Asthecasestudiesinthisarticlehaveshown,bothofthesetestsarenondestructiveinthatthe
testedunitswerereturnedtoserviceuntilthenextavailabletimecouldbescheduledtoreplace
them.
Finally,thesetestsareperformedatvoltagelevelsamotorisexposedtoduringnormaloperation.If
amotorcannotpasstheStepVoltageandSurgeTests,youcanbankonthefactthatitis
approachingtheendofitsservicelife.Consequently,provisionsshouldbemadeassoonasfeasibly
possibletohavethatmotorremovedbeforeunscheduleddowntimeoccurs.
JoeGeimanholdsaB.S.fromColoradoStateUniversityinIndustrialTechnologyManagement.He
travelsextensivelywithintheWesternandSoutheasternregionsoftheUnitedStatesandhastested
andanalyzedhundredsofmotorsforavarietyofindustries.Telephone:(800)7528272or(970)
2821200email:jgeiman@bakerinst.com
Youmayalsolike:
Video|RemoteConditionMonitoringforLowVoltageMotors
Video|RemoteConditionMonitoringforLowVoltageMotors
AGeneralToolforAcceptanceTesting
Video|RemoteConditionMonitoringforLowVoltageMotors
PushofaButtonPanduitVeriSafeAbsenceofVoltageTesterBoostsSafety,Productivity
WhatsThreeMinutesofMotorTestingWorth?
[ what's this ]
AboutKathy FollowUs
ViewallpostsbyKathy
Uptime:WeCanDoIt! Viewpoint:CommitmentToEthicalConductAndCulture
0Comments MaintenanceTechnology
1 Login
Startthediscussion
Bethefirsttocomment.
ALSOONMAINTENANCETECHNOLOGY
BuildingAndUsingEffectiveVisual ListeningToIBMsBuildingWhisperer
ManagementBoards 1comment3yearsago
1comment2yearsago Harman7111ZitoTelecomprovidesbusinesses
ProjectCanvasThankyouRickforthe ofallsizeswithastable,reliable,enterprisegrade
comprehensivearticle.ProjectCanvas hostedPBX
(www.projectcanvas.dk)mightbeof
MonitoringSlowSpeedBearingsWith InfraredInspectionsOfInstalledMotors
Ultrasound 1commentamonthago
1commentayearago ThomasKremserhttps://uploads.disquscdn.c...
JohnMcRaeRon,congratulationson Wellsaid.I'vebeenperformingIRsurveysof
successfullyimplementingaclassicaltargeted
conditionmonitoringprogram.
Search...
Backtotop
QuickLinks
Advertise
ContactUs
Events
Products
Subscribe
Videos
Webinars
WhitePapers
RecentPosts
SmartWaterInfrastructureContinuestoGrow,butRealChallengesPersist
ProcessOperatorsandToolsMayBridgetheGaptoPredictiveMaintenance
MTOnlinePodcast:CloudComputingwithSaadiKermani
MindShareDesignAcquiresCMMSProviderWorkStraight
DoesYourLubeProgramMeasureUp?
LatestIssue
Broughttoyouby:
Tweets
TVA'sMission:Energy,Environment,andEconomicDevelopment.Managinganintegratedriversystem&howwateris
usediskey.#MARCON20175daysago
PerJacindaWoodward,manyTVApowergensitesstillhavesignagestatingtheywere"BuiltforthePeopleofthe
UnitedStates."#MARCON2017:5daysago
FollowmtmagazineonTwitter
2017MaintenanceTechnology.AllRightsReserved.