Documente Academic
Documente Profesional
Documente Cultură
February 2000
4.1. Summary..................................................................................4-3
4-1
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4-2
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
4.1. Summary
Both analogue and binary I/P signals pass through a signal con-
ditioning stage before being processed by the main processor:
Analogue signals go through the chain comprising the input
transformer, shunt, low-pass filter (anti-alias filter), amplifier,
sampling (sample and hold), multiplexer and A/D converter. As
digital signals they are then separated by digital filters into real
and apparent components before entering the main processor.
The binary signals are isolated by opto-couplers in the input cir-
cuits and are evaluated by the main processor.
Only now are the protection algorithms and the logic functions
processed in the main processor.
A delay function and a logic function are also included. The de-
lay function enables a time to be defined between pick-up (I/P of
the function) and its operation. A setting is also provided for the
reset time. The logic function provides an AND, OR or RS gate
for combining different O/P signals (of functions and binary
I/Ps).
The distance protection function is equipped with overcurrent or
underimpedance starters. In ungrounded systems, all the usual
cyclic and acyclic phase preference schemes are available.
The residual (neutral) current and/or residual (zero-sequence)
voltage are monitored to detect earth faults.
The first distance zone, the overreaching zone and the reverse
zone measure simultaneously. All of the distance zones have
wide setting ranges and can be set completely independently of
each other, also with respect to whether they measure in the
forwards or reverse direction. There are three directional dis-
tance zones and a fourth, which can be either directional or non-
directional as demanded by the application. The overreaching
and reverse zones are for use in transfer tripping schemes with
signal transmission between the units at the two ends of a line.
The operating characteristics are polygons with the reactance
borders slightly inclined to give an ideal tripping area. For close
three-phase faults with very low voltages, the use of a reference
voltage comprising a healthy voltage and the voltage of a mem-
ory feature ensures a reliable directional decision.
Compensation of the mutual zero-sequence impedance of paral-
lel circuits can be achieved by appropriate selection of the zero-
sequence impedance factor (k0) or the residual current of the
parallel circuit using k0m.
4-3
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4-4
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
4-5
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4.2.1. High-impedance
4.2.1.1. General
In a high-impedance scheme, the measuring circuit represents a
high-impedance across a circulating current circuit. High-imped-
ance protection is used for
phase and possibly earth fault protection for generators,
motors and compensator reactors
restricted E/F protection for transformers
The main advantage of a high-impedance scheme compared
with a normal differential scheme is its better stability for rela-
tively low through-fault currents (between IN and 5 IN).
The disadvantages are
the high voltage across the circulating current circuit during
internal faults
the special requirements to be fulfilled by the c.ts.
A high-impedance scheme is used to advantage where
fault currents are relatively low
discrimination is absolutely essential.
This is the case for phase faults on air-cored compensator reac-
tors and earth faults on power transformers, which are grounded
via an impedance. In some instances solidly grounded trans-
former can also be protected.
Either an overcurrent function with a series resistor or an over-
voltage function can be used in a high-impedance scheme. The
application of an overcurrent function in a high-impedance
scheme is illustrated by a restricted earth fault protection (R.E.F)
in the following Section.
The required level of through-fault stability is determined by the
value of the high impedance presented by the protection meas-
uring circuit.
4-6
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
4.2.1.2.2. Design
The E/F current is determined by
a) the generator and step-up transformer reactances when the
HV circuit-breaker is open (see Fig. 4.1)
b) in addition to a) by the HV power system when the HV cir-
cuit-breaker is closed (see Fig. 4.2).
As a result of the current distribution for a through-fault, the star-
point c.t. conducts the highest current in the case of a solidly
grounded transformer as shown in Fig. 4.2. Apart from the
burden, the high fault level results in a high c.t. flux and the
probability of it saturating is then also high.
The influence of through faults on the circulating current circuit is
limited, especially if the connections between the c.t. cores can
be kept short. It is for this reason, that phase faults are ne-
glected when designing a scheme for a solidly grounded system.
Phase faults have to be taken into consideration, however,
where a system is impedance grounded.
The value of the stabilising resistor is chosen such that the volt-
age drop caused by the highest external E/F and possibly phase
fault current across the secondary winding and leads of the
saturated c.t. cannot reach the pick-up setting of the protection
(see Fig. 4.3).
4-7
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
The knee-point voltage of the c.ts is specified such that the c.ts
can supply sufficient current during an internal fault to enable the
protection to trip. The knee-point voltage Uk of the c.ts must
therefore be appreciably higher than the voltage drop Ua.
Symbols used:
IE primary star-point current (AC component) for a
through-fault
I2 secondary current of the non-saturated c.ts
I2N c.t. secondary rated current
IN protection rated current
R2 secondary resistance of the saturated c.t. at 75C
RL lead resistance according to Fig. 4.3
Ua , Ui voltage drop across the circulating current circuit
for external, respectively internal faults.
Uk knee-point voltages of the c.ts
peak value of voltage
I current setting
RS stabilising resistor
IF highest primary fault current (AC component) for an
internal E/F.
Equations:
Ua = (R2 + 2 RL) I2
Uk 2 Ua
I = 0.25 I2N (solidly grounded star-point)
I = 0.10 I2N (impedance grounded star-point)
Ua
RS
I
Ui = RS I2 (I2 is given by IF)
Umax = 2 2 Uk (Ui Uk )
4-8
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
4.2.1.2.3. Example
Determination of the stabilising resistor:
C.ts 1000/1 A
R2 = 5
100 m
RL = = 0.5
50 4 mm2
(c.t. leads 100 m long with a specific conductance of
50 -1 m/mm2 and a gauge of 4 mm2)
This would be the current for an E/F on the HV system for the
following data:
xd" = x2 = 0.2 ; xT = xT0 = 0.1 ; xsys = xsys 0 = 0.01
1
I2 = 10 000 = 10A (r.m.s)
1000
Ua = (5 + 2 x 0.5) x 10 = 60 V (r.m.s)
Uk 2 Ua = 120 V (r.m.s)
Chosen
Uk = 200 V (r.m.s)
4-9
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
1
I2 = 100 000 = 100 A
1000
Ui = RS I2 = 300 x 100 = 30,000 V
=2 2 Uk ( Ui Uk )
4-10
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
G T
4.286
HV system
4.286
4-11
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
95.8793
95.8793
4.1238
105.4672
2.0619
2.0619
5.4641
9.5879
T
G
4-12
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
IE
IE External E/F
R2
RS
Ui
I>
I2 I2
RS
VDR Shorting contact
I>
4-13
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
u
2
Ui =
2 . 30 kV
=
u2 6905 V u2
i2
2 . 100 A
=
i2 23 A i2
4-14
1
9
8
7
6 METROSIL NON-LINEAR RESISTORS
5
Fig. 4.5
4 Typical Voltage - Current Characteristics (D.C.)
3 Type 600 A/S1/256 C = 900
Type 600 A/S1/793 C = 650 1088
2
Type 600 A/S1/1088 C = 450
1000 793
1
6
8
7 256
9
5
4
3
RE. 216 1MDU02005-EN / 4 / Rev. D
Voltage (volts)
1
100 9
8
7
6
5
10 1
1 2 3 4 5 6 7 8 91 2 3 4 5 6 7 8 91 2 3 4 5 6 7 8 91 2 3 4 5 6 7 8 91 2 3 4 5 6 7 8 9 1
4-15
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4.2.2.1. General
The purpose of the standstill protection is to isolate the genera-
tor from the system as quickly as possible, if it is connected to
the system by mistake, e.g. when at standstill, during start-up or
when running without voltage.
The protection must have a short operating time to minimise the
mechanical stress on the rotors and bearings of generator and
turbine, if the unit is suddenly connected to the system in these
circumstances. Nevertheless, it must remain stable during ex-
ternal faults and transients.
Standstill protection can be provided by a fast overcurrent or
power function. Function modules for both alternatives are in-
cluded in the function library. The following example shows the
overcurrent alternative.
4-16
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
Trip Trip
U U set = 0.85 UN TRIP time = 0.0 s
Delay = 1.00 s Reset time = 20.0 s
Block
4.2.3.1. Application
The use of a Voltage protection function in combination with an
ancillary unit Type YWX111-11 or YWX111-21 enables earth
faults on the rotor windings of synchronous alternators and mo-
tors to be detected.
The protection scheme is coupled via capacitors (d.c. isolation)
to the positive and negative poles of the excitation circuit and to
the shaft ground. The YWX111-11/-21 ancillary unit, the cou-
pling capacitors and the normal ground (shaft) capacitance of
the rotor winding form a balanced bridge in normal operation. An
earth fault represents a leakage resistance across the capaci-
tance of the rotor winding to ground (shaft) and disturbs the bal-
ance of the bridge. The voltage difference occurring across the
bridge is applied to an I/P v.t. of the RE. 216 and causes the
corresponding voltage function to trip.
Design
The ancillary unit Type YWX111-11/-21 is in a casing for surface
mounting having dimensions of 183 x 113 x 81 mm.
4-17
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
In principle any value can be set within the setting ranges for the
pick-up value Rf and the time delay t.
The setting of the voltage function should no be too sensitive to
avoid mal-operation of RE. 216 during fast regulation of load
changes. This is especially important where the protection trips
the field switch and shuts the unit down.
Recommended settings:
Stage 2: "Trip"
R < 2000
t > 1.5 s
Stage 1: "Alarm"
R < 5000
t > 1.5 s
Note that the voltage across the bridge is low for a high leakage
resistance and high for a low leakage resistance.
4-18
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
YWX111-11/-21 connections
The auxiliary supply of 100 V AC or 220 V AC can be obtained
from a voltage divider within the plant of from one of the genera-
tor v.ts. In the case of the compact version of the RE. 216, the
auxiliary a.c. supply can be taken from the input terminals of the
input transformer unit used for measuring the generator voltage.
Since double ground connections can cause problems, it may be
necessary to disconnect the YWX111-11/-21 ground connection
at terminal 3 within the cubicle (shaft ground).
4-19
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
YWX 111-11/-21
Standard: R 9 = 120
(normal sensitivity)
Units with a shaft filter: R 9 = 1 k
(increased sensitivity)
Refer to Fig. 4.14 for the location of the resistor R9.
4.2.3.5. Commissioning
The commissioning procedure is given in Sections 4.2.3.5.1 to
4.2.3.5.4. The tripping circuits of the RE. 216 must be inter-
rupted while carrying out commissioning.
4-20
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
4-21
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
Procedure:
Interrupt the tripping circuits from the RE. 216.
Connect and AC voltmeter to terminals 1 and 2 of
YWX111-11/-21.
Connect a capacitor decade in place of CX.
Close the field switch.
Switch on the auxiliary supply USH.
Vary the capacitor decade in place of CX until the output
voltage at terminals 1 and 2 of YWX111-11/-21 becomes a
minimum; normally < 50 mVr.m.s..
Theoretical value of CX
4-22
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
Procedure:
Interrupt the tripping circuits from the RE. 216.
Connect resistors for RP = 5000 , 2000 and RP = 0 to
the positive pole of the excitation circuit.
Close the field switch.
Switch on the auxiliary supply USH.
Measure the voltage across the bridge corresponding to the
different values of resistance.
Set the voltages measured at the two resistances of 2000
and 5000 on the RE. 216. They should lie between 0.5 and
3 V.
Repeat the procedure with the resistors RP = 5000 ,
2000 and RP = 0 connected to the negative pole of the
excitation circuit.
4-23
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
Procedure:
Test conditions: Machine running at rated speed, on load and
excited. Test switch open.
Interrupt the tripping circuits.
Set the RE. 216 to the voltage measured in Section 4.2.3.5.3.
Close the test switch ES.
Reduce the value set for U set in steps until the protection
trips.
Caution: The tripping signal has a time delay.
Repeat the above procedure with the test resistor RP con-
nected to the negative pole of the excitation circuit.
4-24
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
4-25
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4.2.3.6.2. Maintenance
The ancillary unit requires no special maintenance. It should,
however, be checked regularly as is the case with all safety de-
vices. This can take place according to the procedure given in
Section 4.2.3.5.
The shaft grounding brush must be checked frequently and,
where necessary, cleaned and the spring pressure adjusted.
The contact resistance of the brush must be as low as possible
and above all constant.
4.2.3.7. Fault-finding
Fault-finding is limited to using the test procedures described in
Section 4.2.3.5. to determine whether the protection is function-
ing correctly. Faulty devices must be returned to the nearest
ABB office or agent or to ABB, Baden, Switzerland.
4.2.3.9. Appendices
Fig. 4.10 Wiring diagram of the relay RE. 216 and ancillary
unit Type YWX111-11/-21 - Connection to the d.c.
part of the excitation circuit
Fig. 4.11 Wiring diagram of the relay RE. 216 and ancillary
unit Type YWX111-11/-21 - Connection to the a.c.
part of the excitation circuit
Fig. 4.12 Wiring diagram of a two-stage scheme
Fig. 4.13 Block diagram and terminals of the ancillary unit
Type YWX111-11/-21
Fig. 4.14 Component side of the PCB in the ancillary unit
Type YWX111-11/-21
4-26
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
Fig. 4.10 Wiring diagram of the relay RE. 216 and ancillary
unit Type YWX111-11/-21
Connection to the d.c. part of the excitation circuit
Fig. 4.11 Wiring diagram of the relay RE. 216 and ancillary
unit Type YWX111-11/-21
Connection to the a.c. part of the excitation circuit
4-27
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4-28
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
4-29
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
Ext. trip/
CHI Blocking Signal CH Trip CH Signal CH Signal
No system System
01 01 01 failure 02 ready
02 02 03 04
03 03 05 06
04 04 07 08
05 05 09 10
06 06 11 12
07 07 13 14
08 08 15 16
09 216NG6. 17 18
10 Division 1 19 20
11 Signal 21 22
K 24 V
12 100 failure 23 24
13 216NG6. 25 26
14 Division 19 *) 27 28
15 Signal 29 30
K 24 V
16 100 failure 31 32
4-30
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
Inputs Outputs
216GE61 216GA62
01
02
03
04
05
06
07
08
09
10
Tripping
channels
4-31
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4-32
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
4-33
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
Allocation of phases:
Current: phase A
Voltage: phases A, B
4-34
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
4.5.1. Introduction
The underreactance protection function can be used for a num-
ber of purposes. It is normally used, however, to detect out-of-
step conditions for load angles 90. It is similarly applicable
to monitoring a maximum load angle, e.g. = 70.
4-35
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4-36
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
instable
stable
instable
stable
instable
generator/transformer set
generator connected to busbar
Tripping
area
Tripping
area
4-37
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4-38
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
4-39
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4-40
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
4-41
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
Short-time
Voltage transformer
sec. rating
U1N [V] U2N [V] S [kVA] [A] for 10 s
4-42
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
Should the ground fault detector pick up for a ground fault on the
busbar, it gives alarm but the fault is not tripped. The resistor Rp
must therefore be rated for continuous operation. A resistor
rated for 1 or 2 A is frequently used, which while being satisfac-
tory for most v.ts, only has a limited damping effect on transient
voltages. In the case of the v.t. in the example, the v.t. output
power varies for a constant current of 2 A between 577 and
831 VA.
Should it be considered necessary to limit the risk of mal-opera-
tion still further, the resistor Rp can be designed for the maxi-
mum permissible continuous rating of the v.t. This is usually in
the range 5 to 10 % of the permissible 10 s rating. If the v.t. is
also used for metering purposes, it must be borne in mind that
both voltage and phase errors are higher at the maximum con-
tinuous rating.
UN Ubroken Rp Re I2
4.6.7. Contactor
The contactor switches both ends of the grounding resistor Re.
4-43
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4-44
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
Block
Generator ground fault signal
4-45
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4-46
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
1
3
U> 2
5
P> 6 7 8
U> 9
UR
UTR USR U TR
U
UT US
HEST 965039 FL
U SR
where:
4-47
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4-48
RE. 216 1MDU02005-EN / 4 / Rev. D ABB Power Automation Ltd
Injection
transformer
unit REX 011
Injection
unit
REX 010 RE. 216
4-49
ABB Power Automation Ltd RE. 216 1MDU02005-EN / 4 / Rev. D
4-50