Sunteți pe pagina 1din 15

Energy and Buildings 150 (2017) 224238

Contents lists available at ScienceDirect

Energy and Buildings


journal homepage: www.elsevier.com/locate/enbuild

A comprehensive cost-optimal approach for energy retrot of existing


multi-family buildings: Application to apartment blocks in Turkey
Nese Ganic Saglam a, , A. Zerrin Ylmaz a , Cristina Becchio b , Stefano P. Corgnati b
a
Istanbul Technical University (ITU) Faculty of Architecture, Taskisla Campus, 34437, Istanbul, Turkey
b
DENERG, Politecnico di Torino, Corso Duca degli Abruzzi 24, 10129 Torino, Italy

a r t i c l e i n f o a b s t r a c t

Article history: This research presents a comprehensive cost-optimal approach for existing building retrots. The
Received 21 December 2016 approach incorporates energy efciency measures related to building envelope, building energy systems
Received in revised form 4 April 2017 and renewable energy, all at once. Moreover, the cost-optimal calculation scope is extended through
Accepted 10 June 2017
integration of occupant behaviour.
Available online 13 June 2017
The comprehensive approach is implemented for a reference building which represents high-rise apart-
ment blocks in Turkey; these building types accommodate 4500 families corresponding to 23.1% of
Keywords:
the national households. Three different climatic regions, that show signicant distinction from each
Energy efciency measures
Energy retrot
other, were selected for the sample application of the approach in order to refer different climates. Cost-
Cost-optimal level optimal calculations were performed for more than 1300 scenarios. Integration of occupant behaviour
Cost-effectiveness into this calculation procedure was demonstrated with sensitivity analyses; the present application of
Occupant behaviour the approach was focused on the use of window openings by occupants.
Multi-family buildings Results reveal that cost-effective energy saving potential is higher than 70% in high-rise apartments.
Climatic conditions Moreover, occupant behaviour related to window openings is able to raise this rate above 80%. The
ndings indicate the necessity of comprehensive approach and demonstrate that integration of occupant
behaviour into cost-optimal calculations is fundamental in order to reach signicant and stable results.
2017 Elsevier B.V. All rights reserved.

1. Introduction in force. Subsequently, after 2020, the cost optimal energy perfor-
mance level is expected to meet the NZEB level [6].
Energy efciency in buildings is accepted as one of the key In Europe, approximately 40% of the building stock was con-
strategies to achieve intended energy saving in the world since structed before 1960s [7] and these existing buildings represent the
energy consumed in building sector corresponds to one-third of highest energy saving potential [8]. Therefore, cost-optimality con-
nal energy consumption [1]. Accordingly in European Union (EU), cept of EPBD recast refers not only to new constructions but also
building sector is responsible from the largest share as well and to existing building retrots. Since 75% of the existing buildings
leads to 40% of the nal energy consumption [2]. Therefore, building in Europe are residential [9], considerable number of the studies
energy efciency targets of EU were set through the recast of Energy focused on the cost-optimal retrots of national residential build-
Performance of Buildings Directive 2010/31/EU (EPBD recast) [3]. ing stock as presented below.
Considering that realization of high energy performance in build- In Sweden, Brown et al. investigated residential building stock
ings is not only an energy aspect but also economic practice, EPBD and suggested to consider also national environmental ratings in
recast introduced cost-optimality and nearly-zero energy build- order to integrate indoor environmental quality assessment into
ing (NZEB) concepts for building energy performance assessment. building energy retrot process [10]. Liu et al., on the other hand,
According to EPBD recast, Member States are obliged to calculate considered future targets and indicated that although there are
cost-optimal energy efciency levels for buildings by adapting the challenges, 50% saving potential exists in Swedish multifamily
methodology framework provided in EU Regulation No.244/2012 buildings energy use by 2050 [11]. Bonakdar et al. presented a
[4,5] and to compare the results with the existing requirements method for cost optimal analysis of multifamily building retrots
which includes comparison between different nancial scenarios
and the national building codes of Sweden [12]. In Estonia, as the
Corresponding author.
result of their analyses on wooden apartment buildings, Arumgi
E-mail addresses: neseganic@gmail.com, ganicn@itu.edu.tr (N.G. Saglam).
and Kalamees [13] declared that in order to ensure cost-effective

http://dx.doi.org/10.1016/j.enbuild.2017.06.026
0378-7788/ 2017 Elsevier B.V. All rights reserved.
N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238 225

energy savings, envelope retrots are required to be supported by In line with the aim, this paper demonstrates the proposed com-
building service system retrots. Kuusk et al. [14] investigated the prehensive approach through a sample application for Turkey. This
brick apartments and pointed out the necessity of deep renova- sample application of the approach may refer to the various build-
tion perspective and nancial support. Eventually these research ing refurbishment strategies in Europe as long as Turkey involves
activities supported the Estonian energy roadmap development, as different climatic regions that show signicant distinction from
presented by Kurnitski et al. in [15] and Pikas et al. in [16]. Similar each other. Although the mild climate is observed in the greater
to the procedure followed in Estonia, also in Portugal the research area of Turkey, Turkeys cold climatic region is able to refer North-
activities on residential building refurbishment resulted with a sup- ern Europe since it is characterized by cold, strong and long winter
port to the policy-makers. Brando de Vasconcelos et al. started period where the air temperatures are mostly below zero. On the
from the reference building denition procedure [17] as the rst contrary, hot humid climatic region, which appears in the Mediter-
stage and then focused on the whole cost-optimal approach for Por- ranean coast of Turkey with hot humid summers and warm wet
tuguese residential building stock [18] until the sensitivity analyses winters, is indeed able to refer to other Mediterranean countries.
which were concluded with policy implications [19]. The authors Moreover, in Turkey, similar trends that characterize the Euro-
reported that envelope measures are required to be combined as pean building stock are recognizable since buildings sector is the
packages in order to obtain more benets and discount rates are second biggest energy consumer that is responsible for 30% of
one of the major factors affecting the cost-optimal calculations. In total nal energy consumption [27] and correspondingly ensuring
Italy, Corrado et al. studied a new procedure for the optimization energy efciency in buildings is among the future strategic tar-
of the cost optimal levels of an Italian residential reference build- gets of the country [28]. This strategic target is indeed related to
ing [20]. Fabbri et al. [21] identied strengths and weaknesses of recent EU legislation on building energy performance that Turkey
the cost-optimal approach through its application to the refurbish- follows within the EU harmonization process [29,30]. Since resi-
ment of a residential case study. Desogus et al. [22] investigated dential buildings represent 75% of the national building stock [31],
existing masonry public dwellings in terms of cost-efciency with EPBD recast related research activities in Turkey also focused ini-
different investment evaluation methods. Becchio et al. highlighted tially on the residential buildings [32,33]. Findings of these research
the use of cost-optimal methodology as a decision-making tool for activities are in line with previously mentioned studies as well,
supporting architects in the retrot energy design of a single family as Ashraan et al. indicated that it is necessary to develop stud-
house [23]. ies which combine envelope retrots with mechanical system
The abovementioned studies validate the signicance of cost- improvements in order to achieve lower energy consumption levels
effective retrot of existing residential buildings on achieving the in building retrots [34].
ambitious future energy efciency targets. These recent studies Accordingly in this study, a Turkish residential reference build-
also point out essentiality of examining retrot measure combina- ing (RB) is examined for the sample application of the proposed
tions rather than considering only single measures and moreover approach. The RB is a high-rise apartment building; the choice of
emphasise the importance of covering building service system this building typology is due to the fact that in Turkey 23.1% of
retrots in addition to envelope retrots. Nevertheless, as Pombo households, which correspond to 4500 families, reside in dwellings
et al. demonstrated in their review [24], among the research studies which have 6 or more oors [35].
on cost-effective retrot of existing residential buildings, passive In order to accomplish a complete view, mild, hot-humid and
strategies are the most commonly addressed measures and there cold climatic regions of Turkey were taken into consideration
are only limited number of studies combining retrot measures based on their potentials to refer European climates. These cli-
related to passive strategies, building service systems and renew- matic regions are represented respectively by Istanbul, Antalya and
able energy use all at once. As a consequence of these ndings, Erzurum cities.
it is obvious that a comprehensive approach is required for the In compliance with the cost-optimal methodology framework,
cost-optimal analyses. retrot scenarios, consist of energy efciency measures or packages
On the other hand, while the cost-optimal calculations for exist- of measures, were investigated in terms of both primary energy
ing building retrots have still been progressing, new perspectives consumption and global cost with the aim of deriving cost-optimal
were introduced. The recent studies in literature indicated the levels.
necessity of addressing occupant behaviour within NZEB analyses Energy consumption of the RB is calculated using the detailed
through cost-optimal approach. As Barthelmes et al. revealed in dynamic simulation tool EnergyPlus (version 8.2) [36]. Energy con-
their research [25], occupant behaviour affects the energy perfor- sumption of different retrot scenarios are also evaluated using
mance of NZEBs more than 150% and accordingly it is needed to be this tool and converted in primary energy to make a comparative
addressed in related studies. Moreover, Becchio et al., drew atten- assessment, that considers primary energy consumption for space
tion to the importance of regarding the effect of occupant behaviour heating and cooling, domestic hot water production (DHW) and
in cost-optimal analyses in order to actualize future targets based lighting.
on recently raised concepts such as post-carbon cities as explained Economic calculations of this study are based on the global
in [26]. Therefore, the existing cost-optimal approach is also needed cost concept of EN15459 standard [37]. Global cost calculations
to be extended by regarding effect of occupant behaviour. were performed for each scenario considering 30 years calcula-
Considering the abovementioned gaps and necessities in cost- tion period. These calculations mainly consider investment cost,
optimal calculations, the aim of this study is to introduce a replacement cost, energy cost, maintenance cost and residual value
comprehensive cost-optimal approach for evaluating existing at the end of the calculation period.
building retrots. The approach incorporates three main con- The cost-optimal levels of RB retrots were derived considering
stituents of a whole building retrot: envelope, building energy a reference occupant behaviour at the beginning. Then, sensitivity
systems and renewable energy use. Moreover, it extends the analyses on cost-optimal calculations were performed to analyse
scope of cost-optimal calculations by integrating effect of occupant the effect of occupant behaviour relevant to use of window open-
behaviour into the energy and economic assessment of building ings. This extended cost-optimal approach can be widen to all other
retrots. In this way the approach regards occupant behaviour as aspects of occupant behaviour as well. Finally, some observations
an integral part of cost-effective retrot of existing buildings to are deduced from the results of the analyses in order to give useful
guide actualization of recently introduced future targets.
226 N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238

Fig. 1. Flow chart of the approach.

guidelines to policy-makers of Turkey but also to other countries whole approach is given with Fig. 1. This section presents detailed
with similar features. denition of this approach through a sample application while the
results and sensitivity analyses are presented in the following sec-
tion.
2. Methodology

The comprehensive approach applied in this research is based 2.1. The reference building
on adaptation of the EU cost-optimal methodology framework to
national conditions. Accordingly the approach involves reference The reference building (RB) is a residential building that was
building denition, identication of energy efciency measures, dened in a national research project [32] and represents the high-
constitution of packages of measures, energy performance calcu- rise apartments constructed between 1985 and 1999. It has an
lations and global cost calculations. A owchart representing the unconditioned basement and twelve superior oors with four ats
N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238 227

Fig. 2. The oor plan and geometry of the RB.

Table 1
Thermal properties of the building envelope.

Layers Thickness (m) (W/mK) U-value (W/m2 K)

External Concrete External Plaster 0.005 1.4 1.04


Wall Reinforced Concrete 0.2 2.1
Herapor Thermal Insulation 0.035 0.051
Internal Plaster 0.005 0.7
External Concrete Reinforced Concrete 0.12 2.1 1.09
Panel Wall Herapor Thermal Insulation 0.035 0.051
Internal Plaster 0.005 0.7
Basement Ceiling Oak Parquet 0.016 0.2 1.25
Asphalt 0.005 0.7
Concrete Screed 0.03 1.4
Reinforced Concrete 0.16 2.1
Herapor Thermal Insulation 0.025 0.09
Attic slab Rockwool 0.05 0.045 0.71
Reinforced Concrete 0.16 2.1
Ceiling Plaster 0.01 0.87

in each as shown in Fig. 2. Total net oor area of the RB is 5186 m2 , Since average household size is 3.8 people in Turkey [35] and
total facade area is 3823 m2 with 590 m2 glazing area. 54% of the households consist of a couple with children, it is
The construction type of the RB is reinforced concrete tunnel assumed as in each apartment at, a family consists of parents
form system and the facades were completed using concrete panel and two children [39]. Moreover, the occupancy schedules were
walls. Layers, thermal conductivities () and calculated overall heat dened based on the ofcial surveys on Turkish family structure
transfer coefcients (U-value) of the building envelope compo- [40,41]. Activity level values are gathered from ASHRAE-55 stan-
nents are shown with Table 1. dard according to the related activity [42]. The occupancy and
The windows have double glazing with two layers of 4 mm at activity levels considered for every single at are presented in
glass and 12 mm air gap between them while material of the frame Table 2. In order to take heat gain from home appliances into con-
is polyvinyl chloride (PVC). Overall heat transfer coefcient of the sideration, the power and operating time of these appliances are
window glazing (Uwindow ) is 2.9 W/m2 K, visible transmittance (Tvis ) assumed as in Table 3 [32].
is 0.80 and solar heat gain coefcient (SHGC) is 0.75. Lighting power density (LPD) of spaces were calculated using
User prole and schedules related to occupancy, activities, DIALux evo software [43]. Boundaries for illuminance levels are
equipment use and lighting system are previously dened in 200 lx for kitchen, 300 lx for children bedroom and 100 lx for liv-
the national research project as a part of the reference building ing room, bedroom, corridor and bathroom. The required luminous
denition considering national and international standards and ux is met by compact uorescent lamps and the obtained light-
statistical data gathered from Turkish Statistical Institute (TURK- ing power densities are provided with Table 4 together with the
STAT) database [38]. These are explained below. operating time of the lighting system [44,45]
228 N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238

Table 2
Occupancy and Activity Level Schedules.

Hours Number of Person Activity Activity Level (W/m2 ) Name of the Space

WEEKDAYS 00:00 07:00 4 Sleeping 40 Bedrooms


07:00 07:30 4 Breakfast 60 Kitchen
07:30 12:30 1 Housework 115 All spaces
12:30 15:30 1 Rest 45 Living Room
15:30 16:30 1 Housework 115 All spaces
16:30 19:00 3 1 person: Housework 2 115 All spaces
people: Rest 45
19:00 20:00 4 1 person: Housework 3 115 Kitchen
person: Light work 60 Living Room
20:00 20:30 4 Dinner 60 Kitchen
20:30 23:00 4 Reclining, Light work 60 Living Room, Bedrooms
23:00 24:00 4 Sleeping 40 Bedrooms
WEEKEND 00:00 00:30 4 Reclining, Light work 60 Living Room, Bedrooms
00:30 08:30 4 Sleeping 40 Bedrooms
08:30 12:30 4 Reclining, Light work 60 Living Room, Bedrooms
12:30 15:30 0
15:30 18:30 2 Reclining, Light work 60 Living Room, Bedrooms
18:30 22:30 3 Reclining, Light work 60 Living Room, Bedrooms
22:30 24:00 4 Rest 45 Living Room, Bedrooms

Table 3 The energy efciency measures were applied on the RB individu-


Power and Operating Time of the Electrical Equipment.
ally and also as packages of measures. As displayed in Fig. 1, in order
Home Appliance Power (W) Operating Time to constitute packages, thermal insulation and glazing retrots and
Refrigerator 38 All day (24 h) their combinations were analysed initially. According to the energy
Oven 2600 4 h in a week performance and cost calculation results of this rst set of analy-
Dishwasher 1030 5 h in a week ses, a number of scenarios were selected to be used in following
Washing Machine 851 4 h in a week extensive packages. As an example, decrease in the primary energy
Tea Kettle 1650 Weekdays: 3 h in a day
consumption provided by thermal insulation retrots applied on
Weekend: 2 h in a day
Iron 2300 2 h for 2 days in a week the attic slab (IN-R) and basement ceiling (IN-F) are between 0.52%
Vacuum Cleaner 2000 2 h for 2 days in a week while the change in the global cost is less than 1%. Therefore these
TV 105 Weekdays: 5 h in a day measures were not included in the following packages in all three
Weekends: 4 h in a day
climates. On the other hand, among these building envelope retrot
Notebook 120 3 h in a day
Stove 1800 2.5 h in a day scenarios, glazing retrots (GL) represent the cost-optimal range
Cooker hood 290 1.5 h in a day for Antalya by providing up to 13% primary energy saving and
9% global cost saving; that these are widely addressed in the fol-
lowing packages for Antalya. Besides the cost-optimal results, the
The heating energy demand of the RB is met by a central hot most energy efcient scenarios were also considered in subsequent
water boiler using natural gas. The nominal thermal efciency of packages in order to analyse the possible global cost decreases by
this natural gas boiler is 80%. In each at, there are radiators for combining them with low cost measures. Together with these enve-
emitting the heat generated by the boiler through circulating hot lope scenarios, 500 scenarios for Istanbul, 472 scenarios for Antalya
water. The cooling energy demand is met by individual split air con- and 332 scenarios for Erzurum were analysed in total.
ditioners using electricity. SEER value (seasonal energy efciency
ratio) of the split air conditioners are equal to 5.8 kWh/kWh. DHW
system is also individual and an electric water heater with 80% ther- 2.3. Energy performance calculations
mal efciency that exists in each at in order to provide hot water
for the occupants. The heating and cooling systems were assumed The geometric model for the energy calculations was consti-
as being operated continuously with setpoints 20 C for heating and tuted using Legacy Open Studio Plug-in for SketchUp 8 [48,49]. In
26 C for cooling [32]. The air change rate is assumed as 0.5 h1 in this model, thermal zones were also identied considering each
accordance with National Building Energy Performance Calculation at as a thermal zone and the common circulation areas as different
Methodology of Turkey [46]. thermal zones at each oor. This model was exported to EnergyPlus
(version 8.2) tool [36] to prepare a complete energy model with all
2.2. Energy efciency measures other inputs and to perform energy calculations through conduc-
tion transfer function algorithm. EnergyPlus is a modular building
In order to analyse on the RB, 37 different energy efciency mea- energy analysis and thermal load simulation program, developed
sures, which refer to thermal insulation, glazing, shading devices, by U.S. Department of Energy. It has been chosen for the aim of this
heating, cooling and DHW systems, lamps and renewable energy study for being an open-source free software, well-known, good
use considering solar thermal panels and photovoltaics, were iden- enough in terms of capabilities and widely used all over the world
tied. The energy efciency measures and their abbreviated names for building and HVAC system design and dynamic simulation [50].
are presented in Table 5. For each analysed scenario, a detailed sub-hourly simulation of the
Since the maximum limits of U-values in national heat insula- building was conducted. In the calculations, IWEC (International
tion standard TS 8252013 [47] differ based on climatic regions, the Weather for Energy Calculations) weather le was used for Istan-
analysed thermal insulation levels applied on the building envelope bul while the weather les for Antalya and Erzurum were derived
differ according to the analysed city as well. The maximum allowed by integrating national weather data representing typical mete-
limits in TS 8252013 and the calculated U-values corresponding orological year with meteonorm les since there is no available
to the retrot measures are provided in Table 6. international weather data for these cities [51].
N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238 229

Table 4
Lighting Power Densities.

Room Area (m2 ) LPD (W/m2 ) Operating Time

Bedroom 12.5 9.6 2 h/day


Bedroom 10.0 8.0
Children Bedroom 13.8 17.4 Manually controlled depending on the
Children Bedroom 14.0 20.0 illuminance level in occupied hours
Living Room 28.0 5.7
Kitchen 9.0 10.7 4 h/day
Bathroom 5.4 7.4 2 h/day
Bathroom 4.8 8.3
WC 2.1 10.0
Corridor 4.5 8.9
Entrance 8.0 10.0

Table 5
Energy efciency measures.

Name Denition of the measure

THERMAL INSULATION IN1-W External wall insulation with extruded polystyrene (xps) panels to meet the maximum
allowed U-values in national heat insulation standard (TS825-2013) [47].
IN2-W External wall insulation with xps panels to meet 25% lower U-values than the maximum limits
of TS 8252013.
IN3-W External wall insulation with xps panels to meet 50% lower U-values than the maximum limits
of TS 8252013.
IN4-W External wall insulation with xps panels to meet 75% lower U-values than the maximum limits
of TS 8252013.
IN1-R Attic slab insulation with rock wool panels to meet the maximum allowed U-values in
TS825-2013.
IN2-R Attic slab insulation with rock wool panels to meet 25% lower U-values than the maximum
limits of TS 8252013.
IN3-R Attic slab insulation with rock wool panels to meet 50% lower U-values than the maximum
limits of TS 8252013.
IN4-R Application of rock wool panels on attic slab to meet 75% lower U values than the maximum
limits of TS 8252013.
IN1-F Basement ceiling insulation with xps panels to meet the maximum allowed U-values in TS
8252013.
IN2-F Basement ceiling insulation with xps panels to meet 25% lower U-values than the maximum
limits of TS 8252013.
IN3-F Basement ceiling insulation with xps panels to meet 50% lower U-values than the maximum
limits of TS 8252013.
IN4-F Basement ceiling insulation with xps panels to meet 75% lower U-values than the maximum
limits of TS 8252013.
IN1-E Whole envelope (external walls, attic slab, basement ceiling) insulation to meet maximum
allowed U-values in TS 8252013.
IN2-E Whole envelope insulation to meet 25% lower U values than the maximum limits of
TS 8252013.
IN3-E Whole envelope insulation to meet 50% lower U values than the maximum limits of
TS 8252013.
IN4-E Whole envelope insulation to meet 75% lower U values than the maximum limits of
TS 8252013.
GLAZING GL1 Window glass replacement: U-value = 1.8 W/m2 K, Tvis = 0.79, SHGC = 0.56
GL2 Window glass replacement: U-value = 1.6 W/m2 K, Tvis = 0.79, SHGC = 0.56
GL3 Window glass replacement: U-value = 1.6 W/m2 K, Tvis = 0.71, SHGC = 0.44
GL4 Window glass replacement: U-value = 1.3 W/m2 K, Tvis = 0.71, SHGC = 0.44
GL5 Window glass replacement: U-value = 1.1 W/m2 K, Tvis = 0.71, SHGC = 0.44
GL6 Window glass replacement: U-value = 0.9 W/m2 K, Tvis = 0.69, SHGC = 0.48
GL7 Window glass replacement: U-value = 0.9 W/m2 K, Tvis = 0.63, SHGC = 0.39
SOLAR CONTROL SHD1 Fixed aluminium shading device installation: 60 cm width overhangs on south facade, 60 cm
width overhang and ns on east and west facades.
SHD2 Installation of external semi-transparent textile blinds with manual control:
Solar transmittance: 35%, solar reectance: 60%, visible transmittance: 35%,
visible reectance: 65%
HEATING & COOLING & DHW SYSTEMS BOI Central boiler replacement: new condensing boiler with 95% nominal thermal efciency.
RF Replacement of the existing heating system with radiators to radiant oor system
CHW Change of the individual domestic hot water systems to the central hot water system supplied
by the central boiler.
AC Upgrade SEER value of split type air conditioners to 8.5 kWh/kWh by replacement.
VRV Installation of a central variable refrigerant volume (VRV) system in substitution for split air
conditioners. Gross rated cooling coefcient of performance (COP) is equal to 3.1.
LIGHTING SYSTEM LED Installation of LED lamps to provide same illuminance levels. LPD after retrot are as
following: Bedroom-1: 5.3 W/m2 , Bedroom-2: 4.4 W/m2 , Children bedroom-1: 10.4 W/m2 ,
Children bedroom-2: 11 W/m2 , Living room: 3.1 W/m2 , Kitchen: 6.9 W/m2 , Bathroom-1:
4.1W/m2 , Bathroom-2: 4.6W/m2 , WC: 7.6W/m2 , Corridor: 4.9W/m2 , Entrance: 5.5W/m2 .
RENEWABLE ENERGY SP Installation of 48 solar thermal panel at roof with 120m2 total gross area.
USE PV Installation of photovoltaic system at roof with 11 kW rated power
230 N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238

Calculated energy consumptions for space heating and cooling, The global cost calculation period is 30 years and residual value
lighting and DHW were converted to primary energy using national at the end of the calculation period is also considered.
primary energy conversion factors which are 1 for natural gas and
2.36 for electricity in Turkey.
3. Results
2.4. Global cost calculations
Following the abovementioned method, initially nal use and
Global cost calculation are based on the Net Present Value primary energy consumptions of the RB were calculated. Fig. 3
Method (NPV) in accordance with EN15459 standard [37]. This presents the nal energy uses subdivided by different energy car-
cost estimation method considers time value of the money by riers and primary energy consumption results for the RB.
converting all future incomes and outcomes to a present value Final energy use for space heating is extremely high in Erzu-
using a discount rate. Since 67% of residential units in Turkey are rum while energy use for space cooling is the highest in Antalya.
owner-occupied [39], the calculation method followed in this study Moreover, primary energy consumption of the RB is the highest in
concerns micro-economic (individual end-user) perspective and Erzurum and the lowest in Istanbul.
global cost was calculated based on the following equation: Since it is not feasible and practical to analyse all combination
  possibilities of measures, proper building envelope retrot scenar-
  ios were selected among thermal insulation and glazing retrots. In
Cg () = CI + (Ca,i (j) Rd (i)) Vf, (j) (1) accordance with the results obtained from rst set of calculations,
j i=1 appropriate building envelope retrot scenarios were selected to be
combined with other measures. Primary energy consumption and
where,  is calculation period, Cg () is global cost over the calcula- global cost results for the initially selected scenarios are presented
tion period, CI is initial investment cost for the measure, Ca,i (j) is with Table 8. In the table, RB represents the existing situation of
annual cost during year i for measure j, Vf, (j) is residual value at the reference building and the measures constituting a package are
the end of calculation period and Rd (i) is discount rate. The formula separated by a plus (+) sign.
to calculate discount rate is as below: After the rst set of calculations, the selected building envelope
 1
p measures and packages were combined with other measures refer-
Rd (p) = (2) ring to heating, cooling, DHW and lighting systems, shading devices
1 + RR
and renewable energy systems considering the climatic context.
where, p is number of years and RR is real discount rate. Real dis- The results are displayed in cost-optimal graphs in order to enable
count rate was calculated using Eq. (3). a comparison between different scenarios.
R Ri In the cost-optimal graphs, each point represents a different
RR = (3) scenario. Horizontal axis of the cost-optimal graph expresses the
1 + Ri
primary energy consumption in kWh/m2 y and the vertical axis
In the formula R is the market interest rate and Ri is the ination expresses the global cost in D /m2 considering the total net oor
rate. area of the RB. In case of renewable energy system inclusion in the
The xed expenses and the costs related to the building ele- scenarios, primary energy consumption refers to the net primary
ments that does not affect the energy performance of the building energy consumption left after subtraction of produced primary
were not included in the cost calculations [4]. energy. In order to emphasise signicant scenarios, horizontal and
Investment costs of energy efciency measures are based on vertical dashed lines were used to highlight exact numerical result
market prices and presented with Table 7 both in Euros (D ) and of primary energy consumption and global cost. Fig. 4 presents the
Turkish Liras (TL). Since beginning year of the calculations is 2015, cost-optimal graph for the retrot scenarios analysed for Istanbul.
the exchange rate is assumed as the average of all months in 2015 In Istanbul, the retrot package combining GL7, BOI, CHW, LED
and therefore D /TL is equal to 3.02 [52]. and PV retrots represents the cost-optimal level. This cost-optimal
Annual cost items considered in this research are replacement package achieves 65.5 kWh/m2 y saving that corresponds 45% of
cost, maintenance cost and energy cost. Lifespan of the building RB primary energy consumption and 30.9 D /m2 saving that corre-
components are assumed as 50 years for thermal insulation of sponds 27% of global cost of the RB. The simple payback period of
walls, 40 years for thermal insulation of attic slab and basement this cost-optimal package is 5.1 years.
ceiling, 30 years for windows and shading devices. Lifespan of the As seen from the graph, it is possible to decrease energy con-
energy system components are gathered from Annex A of EN 15459 sumption of the RB until 39.8 kWh/m2 y in a cost-effective way
standard [37]. Annual maintenance and operation costs of these by applying the energy efciency package involving GL, BOI, VRV,
systems are also calculated based on this annex. As an exception CHW, LED, RF, SP and PV retrots. This decrease corresponds to 73%
only for the rst set of calculations, aimed at selection of appropri- primary energy saving in Istanbul while the global cost is almost
ate envelope retrot scenarios, costs related to energy systems are the same with the RB. In comparison to this cost-effective package,
not included since those are the same for all scenarios. affording 19.9 D /m2 higher global cost for applying also thermal
In order to calculate real discount rate, economic indicators were insulation retrot brings 10 kWh/m2 y additional primary energy
investigated using statistics provided by Central Bank of the Repub- saving. Beyond this primary energy consumption level around
lic of Turkey (CBRT) and TURKSTAT [52,38] and average of the last 29.8 kWh/m2 y, primary energy saving amount corresponding to
5 years before 2015 were used in the calculations. In this con- the unit global cost increase is lower. In detail, 21.4 D /m2 increase
text, ination rate is assumed as 8.054% and market interest rate is in the global cost results only with 1.2 kWh/m2 y additional primary
assumed as 14.3%. Using Eq. (3), real discount rate was calculated energy saving since the effect of the additional thermal insulation
as 5.78%. thickness is limited while the investment cost is respectively high.
Energy costs were calculated based on the calculated energy All of the energy efciency packages that involve at least two
consumptions and average energy prices for 2015. Tax included of the highest level of thermal insulation (IN4), shading devices
prices are 0.1213 D /kWh for electricity, 0.0370 D /kWh for natu- (SHD2) or installation of air conditioners (AC) resulted with a global
ral gas in Istanbul, 0.0368 D /kWh for natural gas in Antalya and cost higher than 160 D /m2 since these measures have a very high
0.03457 D /kWh for natural gas in Erzurum [5356]. initial investment cost.
N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238 231

Table 6
U-values of building components corresponding to the retrot measures.

U-values (W/m2 K)

Istanbul Antalya Erzurum

TS 825 Limits Uwall 0.57 0.66 0.36


Uroof 0.38 0.43 0.21
Ufloor 0.57 0.66 0.36
Uwindow 1.80 1.80 1.80
Values corresponding IN1-W (wall) 0.56 0.60 0.34
to the retrots IN1-R (roof) 0.36 0.39 0.21
IN1-F (oor) 0.56 0.66 0.35
IN2-W 0.42 0.48 0.26
IN2-R 0.27 0.32 0.15
IN2-F 0.42 0.48 0.25
IN3-W 0.29 0.31 0.18
IN3-R 0.17 0.18 0.11
IN3-F 0.29 0.29 0.18
IN4-W 0.14 0.16 0.12
IN4-R 0.10 0.11 0.08
IN4-F 0.14 0.17 0.09

Table 7
Investment cost of the energy efciency measures.

Total Investment Cost (TL) Cost per unit oor area Total Investment Cost Cost per unit oor area
2 2
(TL/m ) (D /m ) (TL/m2 ) (D /m2 )

IN1W Istanbul: 281934.9 54.4 18.0 IN1E Istanbul: 312574.1 60.3 20.0
Antalya: 275852.9 53.2 17.6 Antalya: 305621.7 58.9 19.5
Erzurum: 335659.9 64.7 21.4 Erzurum: 368893.5 71.1 23.6
IN2W Istanbul: 306924.3 59.2 19.6 IN2E Istanbul: 339041.5 65.4 21.6
Antalya: 294099.1 56.7 18.8 Antalya: 325229.9 62.7 20.8
Erzurum: 390574.9 75.3 24.9 Erzurum: 431115.0 83.1 27.5
IN3W Istanbul: 371976.1 71.7 23.8 IN3E Istanbul: 406960.7 78.5 26.0
Antalya: 351878.8 67.9 22.5 Antalya: 386264.0 74.5 24.7
Erzurum: 646988.0 124.8 41.3 Erzurum: 691483.5 133.3 44.2
IN4W Istanbul: 729666.9 140.7 46.6 IN4E Istanbul: 778070.5 150.0 49.7
Antalya: 671405.3 129.5 42.9 Antalya: 716500.2 138.2 45.7
Erzurum: 855883.8 165.0 54.6 Erzurum: 908020.9 175.1 58.0
IN1R Istanbul: 7259.4 1.4 0.46 GL1 51985.3 10.0 3.3
Antalya: 6678.8 1.3 0.43 GL2 53377.7 10.3 3.4
Erzurum: 8982.2 1.7 0.57 GL3 59177.0 11.4 3.8
IN2R Istanbul: 7854.1 1.5 0.50 GL4 60569.4 11.7 3.9
Antalya: 7259.4 1.4 0.46 GL5 65213.1 12.6 4.2
Erzurum: 15113.5 2.9 0.96 GL6 69153.5 13.3 4.4
IN3R Istanbul: 10152.7 2.0 0.65 GL7 74723.1 14.4 4.8
Antalya: 9553.3 1.8 0.61 SHD1 114903.7 22.2 7.3
Erzurum: 17364.9 3.3 1.11 SHD2 517108.6 99.7 33.0
IN4R Istanbul: 19134.9 3.7 1.22 BOI Istanbul: 43348.8 8.4 2.8
Antalya: 17364.9 3.3 1.11 Antalya: 43348.8 8.4 2.8
Erzurum: 20305.4 3.9 1.30 Erzurum: 46013.8 8.9 2.9
IN1F Istanbul: 23379.8 4.5 1.49 RF 367067.4 70.8 23.4
Antalya: 23090.0 4.5 1.47 CHW 22157.7 4.3 1.4
Erzurum: 24251.4 4.7 1.55 AC Istanbul: 311788.2 60.1 19.9
IN2F Istanbul: 24263.1 4.7 1.55 Antalya: 323294.3 62.3 20.6
Antalya: 23871.4 4.6 1.52 Erzurum: 302035.2 58.2 19.3
Erzurum: 25426.6 4.9 1.62 VRV Istanbul: 386300.5 74.5 24.7
IN3F Istanbul: 24831.9 4.8 1.59 Antalya: 451824.3 87.1 28.8
Antalya: 24831.9 4.8 1.59 LED 84052.4 16.2 5.4
Erzurum: 27130.6 5.2 1.73 SP 107941.8 20.8 6.9
IN4F Istanbul: 29268.7 5.6 1.87 PV 53744.7 10.4
Antalya: 27730.0 5.3 1.77
Erzurum: 31831.7 6.1 2.03

The package combining IN1-E and GL1 retrots which cor- result is provided by using GL7 retrot within this package and
responds to the U-values stated in the national heat insulation it corresponds to 96.4 kWh/m2 y primary energy consumption
standard is not a cost-effective solution in Istanbul although it pro- and 97.8 D /m2 global cost. The cost-optimal package ensures
vides 27.4 kWh/m2 y decrease in primary energy consumption of 64.5 kWh/m2 y energy saving which is equal to 40% of RB primary
the RB. However, cost-effective results are achievable when the energy consumption and 35 D /m2 cost saving that is 26% of total
packages involving thermal insulation and glazing retrots are global cost of the RB. The payback period of the cost-optimal pack-
combined with other measures. age is 4.3 years in Antalya.
The cost-optimal graph for Antalya is given with Fig. 5. Energy It is possible to provide 43.8 kWh/m2 y further energy saving
efciency packages combining GL, CHW, LED and PV retrots by affording 4.6 D /m2 higher global cost than the cost-optimal
achieve the cost-optimal results for Antalya. The exact optimal package in order to apply also VRV and SP measures in this Mediter-
232 N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238

Fig. 3. Energy consumption of the RB.

Table 8
Primary energy consumption and global cost results for selected envelope retrot scenarios.

ISTANBUL

Scenario Primary Energy Consumption Global Cost Scenario Primary Energy Consumption Global Cost
(kWh/m2 y) (D /m2 ) (kWh/m2 y) (D /m2 )

RB 145.3 97.2 IN4-W + GL5 111.0 115.7


GL5 132.3 92.0 IN4-W + GL7 109.4 115.9
GL6 132.3 93.2 IN2-E + GL7 112.7 103.9
GL7 131.0 92.3 IN3-E + GL4 111.6 106.3
IN2-W + GL7 114.9 100.6 IN3-E + GL5 111.2 106.5
IN3-W + GL4 114.0 101.6 IN3-E + GL7 109.7 106.1
IN3-W + GL5 113.5 101.9 IN4-E + GL4 109.0 126.8
IN3-W + GL7 112.0 101.9 IN4-E + GL5 108.7 115.5
IN4-W + GL4 111.4 115.6 IN4-E + GL7 107.1 127,0

ANTALYA

Scenario Primary Energy Consumption Global Cost Scenario Primary Energy Consumption Global Cost
(kWh/m2 y) (D /m2 ) (kWh/m2 y) (D /m2 )

RB 160.9 114.9 IN3-W + GL5 128.7 118.0


GL3 142.0 104.7 IN3-W + GL7 126.6 117.2
GL4 141.5 104.5 IN4-W + GL7 125.3 135.3
GL5 141.4 104.8 IN2-E + GL7 126.8 116.0
GL6 143.5 106.9 IN3-E + GL3 126.0 117.9
GL7 139.8 104.3 IN3-E + GL4 126.1 118.1
IN2-W + GL7 128.8 115.0 IN3-E + GL5 126.4 118.7
IN3-W + GL3 128.5 117.4 IN3-E + GL7 124.3 118.0
IN3-W + GL4 128.4 117.5 IN4-E + GL7 123.2 136.6

ERZURUM

Scenario Primary Energy Consumption Global Cost Scenario Primary Energy Consumption Global Cost
(kWh/m2 y) (D /m2 ) (kWh/m2 y) (D /m2 )

RB 216.3 127.8 IN4-W + GL7 141.9 146.3


GL6 200.5 123.5 IN1-E + GL6 149.2 121.1
GL7 202.1 124.3 IN2-E + GL6 143.5 122.2
IN1-W + GL6 155.6 122.1 IN2-E + GL7 143.8 122.1
IN2-W + GL6 150.7 123.0 IN3-E + GL5 140.0 135.3
IN2-W + GL7 151.3 123.1 IN3-E + GL6 137.8 135.0
IN3-W + GL6 145.7 135.9 IN3-E + GL7 137.9 134.8
IN3-W + GL7 145.9 135.8 IN4-E + GL5 135.5 146.1
IN4-W + GL5 143.9 146.8 IN4-E + GL6 133.5 146.0
IN4-W + GL6 141.6 146.4 IN4-E + GL7 133.3 145.6

ranean climate. The package, that involves GL7, VRV, CHW, LED, VRV, CHW, LED, SP and PV retrots results with 39.7 kWh/m2 y pri-
SP and PV retrot measures results with 52.6 kWh/m2 y primary mary energy consumption and 118 D /m2 global cost. This result
energy consumption and 102.4 D /m2 global cost. Investing also shows that it is possible to achieve 75% primary energy saving in a
on the thermal insulation together with this package is still cost- cost-effective way in Antalya. After this point, global cost shows a
effective until the third level of insulation (IN3). However, when the rapid increase and only 3.5 kWh/m2 y decrease in energy consump-
heat insulation level applied with this package is increased further, tion is achieved with 50.3 D /m2 increase in global cost (IN4-E, GL7,
the result is not cost-effective. The package that includes IN3-E, GL7, VRV, CHW, LED, SP, PV, SHD2).
N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238 233

Fig. 4. Cost-optimal graph of retrot scenarios analysed for Istanbul.

Similar to Istanbul, energy efciency packages which resulted sures. This level corresponds to 78% primary energy saving with
with a global cost higher than 170 D /m2 in Antalya involve at least 168.6 kWh/m2 y decrease in energy consumption in Erzurum.
two of the IN4, AC and SHD2 measures. Contrary to Istanbul and Antalya, in Erzurum IN1-E+GL1 pack-
IN1-E+GL1 retrot package is not cost-effective in Antalya age which represents the national standard is cost-effective. This
as well. Nevertheless, there are cost-effective building envelope package achieves 58 kWh/m2 y primary energy saving (27%) with
retrot scenarios such as IN2-W+GL7 package even though the ini- 2% decrease in the global cost. Even though, the energy performance
tial investment cost is higher. Moreover, it is possible to decrease level obtained through the national requirements corresponds to
the global cost more by combining the envelope retrot scenarios 158.3 kWh/m2 y primary energy consumption which is not poten-
with other measures for energy systems and renewable energy use. tially reliable for future targets when it is compared with more
The cost-optimal graph for Erzurum is presented with Fig. 6. As effective retrot scenarios.
seen from this graph, the energy efciency package, which consists
of GL6, BOI, CHW, LED and PV retrots, achieves the cost-optimal 3.1. Sensitivity analyses: the effect of occupant behaviour on
result in Erzurum. This package results with 132.1 kWh/m2 y pri- window openings
mary energy consumption that leads to 39% energy saving and
103.8 D /m2 saving which is equal to 28% of RB global cost. Payback After the cost-optimal graphs were obtained, sensitivity anal-
period of this cost-optimal package is 4.2 years in Erzurum. yses were performed in order to examine effect of occupant
In comparison with the cost-optimal package, 43.5 kWh/m2 y behaviour relevant to use of window openings. The scenarios on
further decrease in primary energy consumption is achievable only the boundary of cost-optimal curve were selected for these analy-
with 1 D /m2 increase in the global cost by combining the cost- ses. Besides the existing assumption of the RB description, which
optimal package with the thermal insulation retrot IN1-E. Instead, refers to air change rate of 0.5 h1 , greater use of the window open-
only around 3 D /m2 rise in the global cost value enables to decrease ings in addition to this air change rate were also analysed. In the
the primary energy consumption of a 28%, reaching 71.5 kWh/m2 y analyses, it is considered that RB occupants control up to 3.6 m2
(IN2-E, GL6, BOI, CHW, LED, SP, PV). Despite the global cost point opening area and leave windows open while the outdoor tempera-
of view, when the investment costs are compared, the variation ture is between 21 C and 26 C. This alternate occupant behaviour
between this scenario and the cost optimal scenario is equal to is regarded as a measure and abbreviated as OB.
102.7 D /m2 and consequently the payback period is the double of Results of the sensitivity analyses considering the effect of occu-
the cost optimal solution. A further action shows that application pant behaviour for Istanbul are presented in Fig. 7. As shown in
of RF measure together with this package decreases the primary this gure, proper use of window openings decreases the pri-
energy consumption of the RB until 53.3 kWh/m2 y and increases mary energy consumption of the cost-optimal package around
the global cost up to 119.2 D /m2 . 20.2 kWh/m2 y and decreases the global cost of this package around
The global cost level of the RB is associated with very different 14.7 D /m2 in Istanbul. Accordingly, the cost-optimal package
energy performance levels up to 47.7 kWh/m2 y which is achieved achieves 59.6 kWh/m2 y primary energy consumption level and
by applying IN4-E, GL7, BOI, CHW, LED, RF, SP, and PV retrot mea- 69.1 D /m2 global cost.
234 N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238

Fig. 5. Cost-optimal graph of retrot scenarios analysed for Antalya.

Fig. 6. Cost-optimal graph of retrot scenarios analysed for Erzurum.


N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238 235

Fig. 7. Cost-optimal graph of the sensitivity analyses for RB retrots in Istanbul.

In Istanbul, the occupant behaviour affects results of all other D /m2 global cost and appears as the cost-optimal solution for the
packages in a positive way as well. The package with IN3, GL7, BOI, RB in Erzurum.
CHW, LED, SP and PV retrot measures results with 28.7 kWh/m2 y The package including IN4-E, GL7, BOI, CHW, LED, RF, SP, and PV
primary energy consumption and 84.3 D /m2 global cost when OB is retrots, which was previously resulted with a global cost slightly
applied in Istanbul. In this case, the package achieves 80% primary higher than RB, results in a cost-effective way when OB is con-
energy saving in a cost-effective way. The energy efciency package sidered. This package results with 39.1 kWh/m2 y primary energy
that combines IN4, GL, BOI, VRV, CHW, LED, RF, SP and PV retrots consumption and 138.7 D /m2 global cost; accordingly it achieves
achieves 17.0 kWh/m2 y primary energy consumption level when 82% primary energy saving.
the building occupants operates the windows as considered. This
package is able to achieve primary energy savings up to 88% in Istan- 4. Discussion
bul and to save 128.3 kWh/m2 y primary energy with an appropriate
use of window openings, however it is still not cost-effective. Results of this study reveal that cost-effective energy saving
Results of the sensitivity analyses examining OB in Antalya are potential for the existing high-rise apartment buildings is higher
displayed with Fig. 8. Conscious use of window openings changes than 70% in all analysed climatic regions. Moreover, occupant
the cost-optimal result to 74.3 kWh/m2 y primary energy consump- behaviour related to conscious use of window openings is able to
tion level and 81.8 D /m2 global cost level in Antalya. This scenario raise this rate above 80%.
saves 22.1 kWh/m2 y more primary energy and 16.0 D /m2 more The obtained results verify the dependence of cost-optimal lev-
global cost in comparison to the cost-optimal scenario without els to the climate. For the same RB, the cost-optimal scenarios range
considering OB. Moreover, the primary energy consumption level between 79.8 and 132.1 kWh/m2 y (in terms of primary energy con-
achieved by the package involving IN4-E, GL7, VRV, CHW, LED, SP sumption) depending on the climate while the reference occupant
and PV retrots, is moved from 38.4 kWh/m2 y to 26.9 kWh/m2 y behaviour is considered. This variation of primary energy consump-
while the global cost is also decreased around 8.4 D /m2 . This result tion corresponds to a 20 D /m2 alteration in global cost. On the
corresponds to 83% energy saving with 3% decrease in global cost other hand, these variations refer to similar improvement rates
comparing to the RB without OB. which are between 39% (Erzurum) and 45% (Istanbul) in terms of
Fig. 9 shows results of the sensitivity analyses related to OB for primary energy consumption and between 26% (Antalya) and 28%
Erzurum. In Erzurum, energy savings related to OB is lower in com- (Erzurum) in terms of global cost.
parison to Istanbul and Antalya since this city has a cold climate. Results also display that, for all climatic zones, envelope retrots
However, this occupant behaviour changes the cost-optimal sce- have limited effect on the energy performance of the high-rise
nario in Erzurum since the global cost variation between the most apartment buildings. The highest primary energy saving ratio
cost-effective packages is minor. When OB is considered, the pack- achieved by the envelope retrots is only between 23% (Antalya)
age that combines IN1-E, GL6, BOI, CHW, LED, SP and PV measures and 38% (Erzurum) while cost-effectiveness is not assured in
achieves 68.8 kWh/m2 -a primary energy consumption and 100.0 every case. Moreover, combination of the envelope improvements
and other retrot actions related to building service systems and
236 N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238

Fig. 8. Cost-optimal graph of the sensitivity analyses for RB retrots in Antalya.

Fig. 9. Cost-optimal graph of the sensitivity analyses for RB retrots in Erzurum.


N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238 237

renewable energy use is able to provide global cost decrease. It is mance level for multi-family buildings. The approach incorporates
obvious that the comprehensive approach is not only needed to building envelope improvements, energy system retrots and
achieve higher energy performance but also to ensure global cost renewable energy use all at once. Moreover, this comprehen-
decrease. sive approach was upgraded by integration of occupant behaviour
On the other hand, the comparison between the results of build- effect into the cost-optimal calculations. In particular, the proposed
ing envelope retrot scenarios obtained in this research and the approach was applied to a reference high-rise apartment block con-
previous study in [34] shows that a number of building envelope sidering three different representative climates of Turkey which
retrots which are cost-effective for low-rise residential buildings accommodate a large population.
are not cost-effective for high-rise residential buildings while the Application of the proposed approach demonstrates a signi-
cost-optimal solutions are also different than each other. Therefore, cant cost-effective energy saving potential for the analysed RB. This
it can be clearly stated that besides the different building cate- potential afrms a remarkable energy and cost saving when the
gories, different sub-categories also require particular attention in existing apartment stock is considered. In this respect, obtained
cost-optimal analyses obliged by the EU Directive. results are important for implementing Article 4 of Directive
EPBD recast and related legislation specify that national mini- 2012/27/EU, which obliges to prepare future strategies including
mum energy performance requirements are needed to be revised cost-effective deep retrot approach for existing buildings [8].
if these are less ambitious than the calculated cost-optimal levels In particular, the ndings of the research reveal that national
[3,6]. Calculation results for IN1-E+GL1 package, which represents standard and regulations are required to be assessed in terms of
the thermal insulation level indicated in the national standard cost-optimality since these are not favourable for all cases as in
TS825-2013 [47], show that, although this solution provides energy high-rise apartments in Turkey. The assessment is needed to be
efciency for the high-rise reference apartment building in all cli- done by extending the comprehensive approach presented in this
mates, it is not cost-effective for the RB in mild and hot-humid study to cover all building types. Subsequent to this assessment and
climates. This package is slightly cost-effective in Erzurum which related modications, the further focusing point is to move towards
represents cold climatic region. Nevertheless, the results display NZEB. This study also notify about the path towards NZEB by dis-
that the national standard is less ambitious than the cost-optimal playing the scenarios that are resulted with more ambitious energy
levels in all three climates. In spite of these ndings, the national performance level in comparison to the cost-optimal scenario.
standards are required to be likewise analysed for new construc- The present study refers to the cost-effective retrot solutions
tions since validity of these results is limited to existing building for multi-family buildings considering various climatic regions.
renovations. The sample application for the hot-humid climate (Antalya) rep-
Another important result to consider in energy policy is the resents a comprehensive Mediterranean cost-optimal approach
presence of common measures that are involved in the cost- that requires particular attention to keep cooling energy consump-
optimal packages for all three climates. These measures, which are tion under control. On the contrary, a comprehensive cost-optimal
GL (window glass replacement), LED (installation of LED lamps), approach for the cold climatic region is also displayed through
CHW (centralization of DHW production) and PV (installation of the analyses for Erzurum. Correspondingly, climate-specic retrot
photovoltaic system), are required to be promoted for building strategies are demonstrated such as central cooling systems for
renovation activities. Mediterranean climate and radiant oor heating for the cold cli-
Although some measures may not be applicable for all buildings mate. Findings for these strategies guide also to the following
that are represented by the analysed RB in practice, it is impor- analyses on possible government support for cost-effective reno-
tant to consider them in cost-optimal calculations to consolidate vation in different climates.
cost-effective energy efciency. For instance, even though CHW The research also signies that integration of occupant
(centralization of DHW production) or RF (transition to radiant oor behaviour into cost-optimal calculations is fundamental for further
system) require certain conditions to implement, the results show studies since it is a determinative factor for the cost-optimal level.
that these measures provide higher energy efciency in a cost- In order to demonstrate the integration approach under sensitivity
effective way especially in cold climatic region. These results may analyses, this study addressed the occupant behaviour related to
also refer to the measures to be involved in cost-optimal analyses the use of window openings. In accordance with the results, it can
for new buildings. be stated that the inuence of the occupant behaviour also varies
An important consequence of the results is the effectiveness of based on the climate. For instance, the highest variation for the cost-
conscious occupant behaviour related to use of window openings optimal level is observed in the hot-humid climate when conscious
on the cost-optimal results. This alternate occupant behaviour (OB) occupant behaviour is considered. The further studies following the
is able to slide the cost-optimal levels until the range between presented approach need to include also other occupant behaviour
59.6 kWh/m2 y (Istanbul) and 74.3 kWh/m2 y (Antalya) of primary congurations such as activities, equipment use, heating and cool-
energy consumption. OB provides more than 20 kWh/m2 y addi- ing system operations (temperatures, scheduling, etc.). In order to
tional primary energy saving and more than 14 D /m2 global cost have an absolute perspective, comfort analyses would be required
saving for the cost-optimal scenarios in mild and hot-humid cli- in these further research activities as well.
mates. The effectiveness of OB in the cold climate is not as high as Besides revealing the essentiality of a comprehensive cost-
in the other two climates. However, it is a signicant indicative on optimal approach for the existing building retrots, the study
the cost-optimal scenario in cold climate since the calculated global indicates importance of integrating the occupant behaviour in the
costs of different energy efciency packages are not signicant. approach. Considering the signicant effect of the occupant, build-
This result shows that, OB is not only determinative on the cost- ing users trainings may also be considered as a tool within national
optimal energy performance level but also on the identication of plans towards future targets.
the cost-optimal scenario.

5. Conclusion and future studies Acknowledgement

This research proposes a comprehensive cost-optimal approach This work was supported by The Scientic and Technological
for existing building retrots in order to maximise energy perfor- Research Council of Turkey (TUBITAK) with a PhD researcher grant.
238 N.G. Saglam et al. / Energy and Buildings 150 (2017) 224238

References [25] V.M. Barthelmes, C. Becchio, S.P. Corgnati, Occupant Behavior Lifestyles in a
residential nearly zero energy building: effect on energy use and thermal
[1] Transition to Sustainable Buildings, Strategies and Opportunitiesto 2050, comfort, Sci. Technol. Built Environ. 22 (2016) 960975.
International Energy Agency, 2013 (Cedex). [26] C. Becchio, S.P. Corgnati, C. Delmastro, V. Fabi, P. Lombardi, The role of
[2] Communication From The Commission to the European Parliament, the nearly-zero energy buildings in the transition towards Post-Carbon Cities,
Council, the European Economic and Social Committee and The Committee of Sust. Cities Soc. 27 (2016) 324337.
the Regions, Energy Efciency Plan 2011, COM(2011) 109 nal, Brussels, 2011. [27] Tapping the Potential for Energy Savings in Turkey, Sustainable Development
[3] EPBD recast, Directive 2010/31/EU of the European Parliament and of Council Department (ECSSD) Europe and Central Asia Region (ECA) Document of the
of 19 May 2010 on the energy performance of buildings (recast), J. Eur. Union World Bank, 2010.
L153/13-35 (2010). [28] Energy Efciency Strategy Paper 20122023, Republic of Turkey Ofcial
[4] Commission Delegated Regulation (EU) No 244/2012 of 16 January 2012 Gazette, 28215, Ankara, 2012.
supplementing Directive 2010/31/EU of the European Parliament and of the [29] Binalarda Enerji Performans Ynetmeligi [Energy Performance of Buildings
Council on the energy performance of buildings by establishing a comparative Regulation], Ministry of Public Works and Settlements, Republic of Turkey
methodology framework for calculating cost-optimal levels of minimum Ofcial Gazette, 27075, Ankara, 2008 (in Turkish).
energy performance requirements for buildings and building elements, J. Eur. [30] Enerji Verimliligi Kanunu [Energy Efciency Law], Law Number: 5627,
Union L81/18-36 (2012). 18.04.2007. Republic of Turkey Ofcial Gazette, 26510, Ankara, 2007 [in
[5] Guidelines Accompanying on Supplementing Directive 2010/31/EU, of the Turkish].
European Parliament and of the Council on energy performance of buildings [31] Building Census 2000, State Institute of Statistics Prime Ministry Republic of
(recast) by establishing a comparative methodology framework for Turkey, Ankara, 2001. ISBN 975 19 2819-2.
calculating cost-optimal levels of minimum energy performance [32] A. Z. Yilmaz, N. Ganic Saglam, G., Gali, T., Ashraan, A., Akguc, Determination
requirements for buildings and building element, J. Eur. Union C115/1-28 of Turkish Reference Residential Buildings and National Method for Dening
(2012). Cost Optimum Energy Efciency Level of Buildings, Scientic and
[6] Commission Recommendation (EU) 2016/1318 of 29 July 2016 on guidelines Technological Research Council of Turkey (TUBITAK), 2015, Project
for the promotion of nearly zero-energy buildings and best practices to no:113M596.
ensure that, by 2020, all new buildings are nearly zero-energy buildings, [33] N. Ganic Saglam, A. Z. Ylmaz, G., Gali, T. Ashraan Bonab, A. Akgc, Reference
Brussels, 2016. Building Establishment Procedure for the Residential Buildings in Turkey,
[7] BPIE (Building Performance Institute Europe) (2011). Europes building under Heiselberg, P. K. (Ed.) (2016). CLIMA 2016 proceedings of the 12th REHVA
the microscope. Brussels. World Congress: volume 6. Aalborg: Aalborg University, Department of Civil
[8] Directive 2012/27/EU of The European Parliament and of the Council of 25 Engineering.
October 2012 on energy efciency, amending Directives 2009/125/EC and [34] T. Ashraan, A.Z. Yilmaz, S.P. Corgnati, N. Moazzen, Methodology to dene
2010/30/EU and repealing Directives 2004/8/EC and 2006/32/EC, Ofcial cost-optimal level of architectural measures for energy efcient retrots of
Journal of the European Union, 2012. existing detached residential buildings in Turkey, Energy Build. 120 (2016)
[9] Financing the energy renovation of buildings with Cohesion Policy funding, 5877.
Final Report, European Commission 2014. ISBN:978-92-79-35999-6. [35] Population and Housing Census, 2011, Turkish Statistical Institute, No: 15843,
[10] N.W.O. Brown, T. Malmqvist, W. Bai, M. Molinari, Sustainability assessment of 2013.
renovation packages for increased energy efciency for multi-family [36] EnergyPlus Energy Simulation Software Web Site. Available online:
buildings in Sweden, Build. Environ. 61 (2013) 140148. http://apps1. eere.energy.gov (data retrievedon November 2014).
[11] L. Liu, B. Moshfegh, J. Akander, M. Cehlin, Comprehensive investigation on [37] CEN. [European Committee for Standardization]. Energy performance of
energy retrots in eleven multi-family buildings in Sweden, Energy Build. 84 buildings Economic evaluation procedure for energy systems in buildings.
(2014) 704715. Standard EN 15459:2007, Brussels : CEN; 2007.
[12] F. Bonakdar, A. Dodoo, L. Gustavsson, Cost-optimum analysis of building [38] http://www.turkstat.gov.tr (accessed on November 2015).
fabric renovation in a Swedish multi-story residential building, Energy Build. [39] Income and Living Conditions Survey 2012, Turkish Statistical Institute
84 (2014) 662673. (TURKSTAT), Publication Number 4143, 2014.
[13] E. Arumgi, T. Kalamees, Analysis of energy economic renovation for historic [40] Family Structure Survey 2011, Turkish Republic Ministry of Family and Social
wooden apartment buildings in cold climates, Appl. Energ. 115 (2014) Policies, Ankara, 2011.
540548. [41] Family Structure Survey 2013, Turkish Republic Ministry of Family and Social
[14] K. Kuusk, T. Kalamees, M. Maivel, Cost-effectiveness of energy performance Policies, Ankara, 2013.
improvements in Estonian brick apartment buildings, Energy Build. 77 (2014) [42] ASHRAE STANDARD 552010, Thermal Environmental Conditions for Human
313322. Occupancy, ISSN 10412336, American Society of Heating, Refrigerating and
[15] J. Kurnitski, K. Kuusk, T. Tarka Aivar Uutar, E. Kalamees, Energy and Air-Conditioning Engineers, Inc., 2010.
investment intensity of integrated renovation and 2030 cost-optimal savings, [43] https://www.dial.de (data retrieved on February 2016).
Energy Build. 75 (2014) 5159. [44] . Smengen, A. Kknel Yener, Konutlarda Aydnlatma Enerjisi Performans
[16] E. Pikas, J. Kurnitski, R. Liias, M. Thalfeldt, Quantication of economic benets ve Grsel Konfor Kosullar [Lighting Energy Performance and Visual Comfort
of renovation of apartment buildings as a basis for cost-optimal 2030 energy Conditions in Residential Buildings], 7. Ulusal Aydnlatma Sempozyumu,
efciency strategies, Energy Build. 86 (2015) 151160. 2013, Izmir, [in Turkish].
[17] EPBD cost-optimal methodology: application to the thermal rehabilitation of [45] IESNA/Illuminating Engineering SocietyThe Lighting Handbook Reference
the building envelope of a Portuguese residential reference building. Ana and Application, in: D.L. DiLaura, K.W. Houser, R.G. Mistrick, G.R. Steffy, (Eds.),
Brando de Vasconcelos, Manuel Duarte Pinheiro, Armando Manso, Antnio 10th edition, 2011.
Cabaco, Energy Build. 111 (2016) 1225. [46] Bina Enerji Performans Hesaplama Yntemi, Bina Enerji Performans Istma
[18] A. Brando de Vasconcelos, M.D. Pinheiro, A. Manso, A. Cabaco, Portuguese ve Sogutma icin Net Enerji Ihtiyacnn Hesaplanmas [Building Energy
approach to dene reference buildings for cost-optimal methodologies, Appl. Performance Calculation Method, Building Energy Performance Calculation
Energ. 140 (2015) 316328. of net energy demand for heating and cooling], Republic of Turkey Ofcial
[19] A. Brandode Vasconcelos, A. Cabaco, M.D. Pinheiro, A. Manso, The impact of Gazette, 27778, Ankara, 2010.
building orientation and discount rates on a Portuguese reference building [47] TSE. [Turkish Standards Institution]. Binalarda Is Yaltm Kurallar [Thermal
refurbishment decision, Energy Policy 91 (2016) 329340. Insulation Requirements for Buildings], TS 825, ICS 91.120.10 Ankara, TSE,
[20] V. Corrado, I. Ballarini, S. Paduos, Assessment of cost-optimal energy 2013 [in Turkish].
performance requirements for the Italian residential building stock, Energy [48] www.sketchup.com (data retrieved on November 2014).
Procedia 45 (2014) 443452. [49] www.openstudio.net (data retrieved on Novemner2014).
[21] K. Fabbri, L. Tronchin, V. Tarabusi, Energy retrot and economic evaluation [50] D.B. Crawley, J.W. Hand, M. Kummert, B.T. Grifth, Contrasting the
priorities applied at an Italian case Study, Energy Procedia 45 (2014) 379384. capabilities of building energy performance simulation programs, Build.
[22] G. Desogus, L. Di Pilla, S. Mura, G.L. Pisano, R. Ricciu, Economic efciency of Environ. 43 (2008) 661673.
social housing thermal upgrade in Mediterranean climate, Energy Build. 57 [51] www.meteonorm.com (data retrieved on May 2014).
(2013) 354360. [52] http://www.tcmb.gov.tr (data retrieved on February 2016).
[23] C. Becchio, M.C. Bottero, S.P. Corgnati, C. Ghiglione, nZEB design: challenging [53] http://www.tedas.gov.tr (data retrieved on February 2016).
between energy and economic targets, Energy Procedia 78 (2015) 20702075. [54] http://www.bedas.com.tr (data retrieved on February 2016).
[24] O. Pombo, B. Rivela, J. Neila, The challenge of sustainable building renovation: [55] http://www.palen.com.tr (data retrieved on February 2016).
assessment of current criteria and future outlook, J. Clean. Prod. 123 (2016) [56] http://www.enerya.com.tr (data retrieved on February 2016).
88100.

S-ar putea să vă placă și