Sunteți pe pagina 1din 2

ONCOLOGY WARDS & DAY CARE CENTRE AT THE ROYAL HOSPITAL

SCHEDULE OF AIR COOLED CHILLERS


SL NO. DESCRIPTION
1 UNIT LOCATION SERVICE BUILDING
2 MAKE CARRIER (FRANCE)

3 MODEL 30XA1002
4 REFERENCE NO. CHILLER 18. 19 & 20.

5 TYPE AIRCOOLED SCREW

6 REFRIGERANT R134a

7 QUANTITY 3 NOS

8 COOLING CAPACITY 888.8 KW EACH

9 CHW FLOW 37.17 L/s EACH


10 CHWS TEMPERATURE 6.7 C

11 CHWR TEMPERATURE 12.2 C

12 ENTERING AIR TEMPERATURE 48 C

13 POWER REQUIREMENT 375 KW

14 OPERATING WEIGHT 8226 KG


ONCOLOGY WARDS & DAY CARE CENTRE AT THE ROYAL HOSPITAL
HVAC EQUIPMENT SCHEDULE

SHCEDULE OF CHILLED WATER PUMP SET

Area Served Model/Make Duty Power Quantity/Tag No.

2 Duty & 1 Standby


Oncology Wards & Day 36.02 LPS @ 35
NK 80-315 / Grundfos 22KW CHW pump - 23,24 &
care Centre Mtrs. 25

S-ar putea să vă placă și