Sunteți pe pagina 1din 4

Application Note Why Choosing a Molded

Page 2 Effective: December 2007 Case Circuit Breaker


Makes Sense

System Unbalance and Single Phase Enhanced Safety


Prevention As greater demands are placed on electrical systems, more
power is required to ensure reliable operation. Along with
The majority of faults in an electrical system are phase to
greater power comes an increase in the amount of electrical
ground. Single phasing is caused when only one fuse
energy available at various points in the electrical system.
interrupts in a circuit during a phase to ground fault. The
To ensure the safety of people working around high current
amperage in the other two phases will typically increase by
systems, circuit protection devices need to not only act
173 percent. This is a problem when using fuses.
rapidly to clear faults, but also to reduce the amount of
energy available to a safe level. The current limiting arc
design of circuit breakers reduces arc flash energy, requiring
A 10A x 173% only Category 1 Personal Protective Equipment for
B 0 maintenance personnel.
Motor
C Fault
10A x 173%

Dual Element Fuse

A 0

B 0
Motor
C Fault 0

Motor Circuit Protector (MCP)

Figure 4. Single Phasing Example Circuit

Figure 5. Example of Tool Contacting Live Parts of a Panel


Motors are often oversized and in these cases, the load is
not large enough to blow the other two fuses. Conductors
and motors can eventually burn up due to the heating Although personnel should never work on live equipment,
caused by only two phases turning the motor. faults are often caused by someone contacting a tool with a
live uncovered part, such as a fusible switch, older design
This also creates a dangerous situation since the motor acts starter or bus bar. Circuit breakers are self-contained, dead
like a generator, back feeding the fault to approximately four front units that increase personnel safety by protecting from
times the full load amps of the motor on the phase which the exposure to these live parts.
fuse has blown. Circuit breakers and motor circuit protectors
are designed to open all three phases at once, thus Circuit breakers can also be remotely reset using the handle
preventing the damaging effects of single phasing. mechanism on the enclosure or using a motor operator that
is remotely operated. This is a safety benefit that keeps the
operator out of the panel. Although you can turn a fusible
switch on and off remotely, the operator must still go into
the panel to change or check the fuses.

For more information visit: www.eaton.com AP01200005E


Why Choosing a Molded Application Note
Case Circuit Breaker Effective: December 2007 Page 3
Makes Sense

Ground Faults Accessorization


Another safety concern are low level ground faults. These Circuit breakers offer the widest range of internal and
faults are below the melting point of fuses, yet severe external accessories. The safety benefits of externally
electrical damage can result. Molded case circuit breakers mounted handle mechanisms and motor operators have
are available with internal ground fault and earth leakage already been mentioned. Others include shunt trips, under
protection. With these protective features, the circuit breaker voltage releases, auxiliary switches, alarm switches,
will trip on a ground fault according to user-selectable terminal shields, lock offs, interlocking devices, etc. These
settings, isolating the fault before it propagates throughout accessories provide diagnostic information to the user and
the system. This safety feature protects personnel and consume no additional panel space and are not available in
equipment from low level arcing currents. Fused devices will fuses.
only interrupt a high level ground fault that exceeds the fuse
overload blow point and require external sensors, relays
and remote switching devices to detect and clear ground
faults.

Figure 7. Series G Circuit Breaker with Installed Internal Accessories

Figure 6. Example of Motor Damage Due to Ground Fault

Reliability and Uptime


Every molded case circuit breaker is tested off the
manufacturing line. This assures that all units operate within Figure 8. Series G Breakers and Accessories
the characteristics that are claimed. Fusible switches can
only be tested once. Therefore you must rely on the next
replacement fuse to have the same operating characteristics.
Breakers are also subject to very stringent follow-up testing Effective Use of Capital
witnessed by UL Laboratories. The UL tests consist of up to
10,000 ON/OFF endurance operations, multiple interruption The installed cost of the circuit breaker distribution
tests, calibration tests and dielectric withstand tests, just to equipment is generally less than equivalent fused
name a few. This testing guarantees the circuit breakers equipment plus fuses. An added cost advantage results from
performance. the resettability of circuit breakers reducing downtime in all
installations, and eliminating the need for maintenance fuse
Circuit breakers are reset, not replaced, guaranteeing system inventories in industrial settings. Todays molded case circuit
coordination based on the original system design. breakers are designed in compact frames that consume less
Replacement of fuses of different types or from different panel space, saving real estate over fusible switch offerings.
manufacturers voids coordination and system protection. In
addition, fuses of different ratings can look similar and be Testing without destruction of overcurrent protective
erroneously placed into the same fuse holder. Using circuit devices is an additional way to lower start-up costs.
breakers reduces the possibility for misapplication, which Available breaker options include internal accessories for
can occur when replacing fuses. The resettable nature of remote indication and control, Zone Selective Interlocking to
breakers removes the need to search for replacement fuses reduce potential system arc flash energy, and
during a downtime situation. This allows you to get your communications without adding costs for increased panel
process up and running in the shortest amount of time. space.

AP01200005E For more information visit: www.eaton.com


Application Note Why Choosing a Molded
Page 4 Effective: December 2007 Case Circuit Breaker
Makes Sense

Circuit Breakers Make Sense Additional Information on Selected Topics


Eatons electrical business has been in www.eaton.com/breakervfuse
the circuit protection business for over
100 years. Eaton offers the widest Pub. Number Description
selection of application solutions in TP08324001E: Applying Low-Voltage Circuit Breakers to Limit Arc Flash Energy
the industry from fused switches to the
most sophisticated circuit breakers. CC01200004E: Eaton Molded Case Circuit Breaker Arc Flash Frame Comparison
Using modern circuit breakers for
MZ01220001E: Maximizing the Life of Molded Case Circuit Breakers
motor protection, electrical power
distribution and in control panels AP01211001E: Molded Case Circuit Breakers Motor Circuit Protectors and High
makes sense. Efficiency Motors
AP01200004E: Application of Multi-Wire Terminals for Molded Case Circuit
Conclusion Breakers
The following is a summary of the top SA08300002E: LEED Credits Guide to Eaton Products and Services
10 reasons to use a circuit breaker as
your circuit protection choice: SA05800001E: Understanding UL508A Frequently Asked Questions

1. Resettable IA01200002E: Tested Breaker Combinations for Selective Coordination

2. Dead front, no exposed live parts


3. Prevents single phasing
4. Adjustable motor protection
5. Ability to protect during ground
faults
6. Accessorization
7. Testable
8. Space savings
9. Prevents downtime
10. More cost-effective over the life of
your equipment

Eaton Corporation
Electrical Group
1000 Cherrington Parkway
Moon Township, PA 15108
United States
877-ETN CARE (877-386-2273)
Eaton.com

2007 Eaton Corporation


All Rights Reserved
Printed in USA
Publication No. AP01200005E/CPG
December 2007

S-ar putea să vă placă și