1 (4/97)
Replaces 572.0 (12/93)
JS JH JD RH
1/4 to 5 HP
JS/JD Semi-hermetic Indoor Condensing Units
Features
The Model JS (Reed Valve) and JD (Discus) indoor Features include:
condensing units are designed for use in refrigeration
applications where a compact unit is required. Typical Semi-hermetic Copeland Compressor (JS and JD)
applications include undercounter units, small walk-in High Efficiency Fan Motors
coolers and freezers, and self-contained reach-in Copper-Tube/Aluminum Fin Condenser Coil
freezers and coolers. Semi-hermetic units are Fan Guard
available in 1/2 through 5 horsepower configurations for Electric Wire Protection
high, medium and low temperature applications. The Pressure Limiting Device Where Required
JS/JD are UL listed condensing units.
J S 0050 L7 A
J = UL Listed S = Semi-Hermetic
R = UL Recognized D = Discus ELECTRICAL CHARACTERISTICS
H = Hermetic A - 115/60/1
B - 208-230/60/1
C - 208-230/60/3
G - 230/60/1
NOMINAL HORSEPOWER
0025 - 1/4 HP 0150 - 1-1/2 HP
0033 - 1/3 HP 02XX - 2 HP
0050 - 1/2 HP 03XX - 3 HP
REFRIGERANT
0075 - 3/4 HP 0400 - 4 HP
2 - HCFC-22
0100 - 1 HP 0500 - 5 HP
4 - HFC-134a
5 - CFC-502
6 - HFC-404A/507 or CFC-502
Elec. code" is a part of the model number. 7 - HCFC-22 or CFC-502
2
Performance Data - Indoor Condensing Units - HCFC-22
HCFC-22 LOW TEMPERATURE UNITS - UL LISTED
Capacity BTUH @ 90F. Ambient
Suction temperature F.
MODEL COMPRESSOR 0F. -5F. -10F. -20F. -25F. -30F. -40.F.
JS-0050L7 KAN-0050 3260 2880 2500 1820 1510 1230 780
JS-0051L2 HAT-0051 3800 3400 3010 2320 1950 1670 1220
SEMI- JS-0075L7 KAM-0075 5410 4850 4300 3300 2840 2430 1710
HERMETIC JS-0100L7 KAJ-0100 6820 6120 5430 4130 3610 3100 2210
JS-0152L2 KAK-0200 7880 7060 6250 4810 4180 3600 2600
JS-0200L2 EAD-0200 11690 10410 9130 6870 5830 4890 3200
JS-0201L7 EAV-0210 13750 12250 10750 8110 6970 5800 4300
JS-0299L7 LAH-0310 20800 18550 16310 12190 10310 8440 5670
JS-0300L7 LAH-0310 22390 19870 17340 12820 10800 8910 5980
For remote applications, additional receiver capacity may be necessary to assure adequate pumpdown capacity.
3
Performance Data - Indoor Condensing Units - HFC-404A/507
HFC-404A/507 LOW TEMPERATURE UNITS - UL LISTED
Capacity BTUH @ 90F. Ambient
Suction temperature F.
MODEL COMPRESSOR 0F. -5F. -10F. -20F. -25F. -30F. -40F.
JS-0050L6 KANB-005E 4080 3530 3120 2160 1820 1510 1000
JS-0075L6 KAMB-007E 5840 5260 4680 3480 2820 2410 1720
SEMI- JS-0100L6 KAJB-010E 8090 7010 6250 4880 4000 3460 2560
HERMETIC JS-0150L6 KALB-015E 10570 9550 8610 6860 6070 4930 3660
JS-0200L6 EADB-021E 12570 11310 10080 7790 6760 5830 4330
JS-0210L6 EAVB-021E 13580 12430 11230 8820 7670 6610 4890
JS-0301L6 LAHB-032E 24880 22030 19530 14660 12510 10520 7110
JS-0400L6 NRD1-032E 27120 24660 22200 17430 15170 13030 9150
NRD1-040E
3 phase model- R404A & R507.
1 phase model - R404A only.
For remote applications, additional receiver capacity may be necessary to assure adequate pumpdown capacity.
4
Performance Data - Indoor Condensing Units - CFC-502/HFC-134A
CFC-502 LOW TEMPERATURE UNITS - UL LISTED
Capacity BTUH @ 90F. Ambient
Suction temperature F.
MODEL COMPRESSOR 0F. -5F. -10F. -20F. -25F. -30F. -40F.
JS-0050L5 KAN-0050 3530 3180 2840 2220 1940 1690 1270
JS-0075L7 KAM-0075 5220 4850 4260 3350 2930 2540 1890
SEMI- JS-0100L7 KAJ-0100 6930 6120 5710 4440 3940 3400 2510
HERMETIC JS-0152L5 KAL-0150 9340 8450 7570 5950 5230 4600 3580
JS-0201L7 EAV-0210 13450 12290 11140 8980 7980 7040 5360
JS-0299L7 LAH-0310 21520 19400 17280 13280 11490 9920 7600
JS-0300L7 LAH-0310 23740 21230 18720 14210 12250 10550 8050
For remote applications, additional receiver capacity may be necessary to assure adequate pumpdown capacity.
5
Dimensional Data - Indoor Condensing Units - HCFC-22
HCFC -22 LOW TEMPERATURE UNITS - UL LISTED
CONN. (ID) RECEIVER DIMENSIONS SHIP.
LIQ. SUCT. 90% FULL D W H WT.
MODEL HP COMPRESSOR LBS. FAN(S) IN. IN. IN. LBS.
JS-0050L7 1/2 KAN-0050 1/4 5/8 6 1 20.5 14.5 11.8 124
JS-0051L2 1/2 HAT-0051 1/4 5/8 6 1 20.5 14.5 11.8 113
SEMI- JS-0075L7 3/4 KAM-0075 3/8 5/8 6 1 21.9 18.0 13.8 160
HERMETIC JS-0100L7 1 KAJ-0100 3/8 5/8 6 1 21.9 18.0 13.8 164
JS-0152L2 1-1/2 KAK-0200 3/8 7/8 6 1 21.9 18.0 16.8 172
JS-0200L2 2 EAD-0200 3/8 7/8 11 2 22.9 32.5 19.0 290
JS-0201L7 2 EAV-0210 3/8 7/8 11 2 22.9 32.5 19.0 290
JS-0299L7 3 LAH-0310 3/8 1-1/8 11 2 22.9 32.5 19.0 410
JS-0300L7 3 LAH-0310 1/2 1-1/8 25 1 30.3 36.0 28.5 465
For remote applications, additional receiver capacity may be necessary to assure adequate pumpdown capacity.
6
Dimensional Data - Indoor Condensing Units - HFC-404A/507
HFC-404A/507 LOW TEMPERATURE UNITS - UL LISTED
CONN.(ID) RECEIVER DIMENSIONS SHIP.
LIQ. SUCT. 90% FULL D W H WT.
MODEL HP COMPRESSOR LBS. FAN(S) IN. IN. IN. LBS
JS-0050L6 1/2 KANB-005E 1/4 5/8 6 1 20.5 14.5 11.8 124
JS-0075L6 3/4 KAMB-007E 3/8 5/8 6 1 21.9 18.0 13.8 160
SEMI- JS-0100L6 1 KAJB-010E 3/8 5/8 6 1 21.9 18.0 13.8 164
HERMETIC JS-0150L6 1-1/2 KALB-015E 3/8 7/8 6 1 21.9 18.0 16.8 172
JS-0200L6 2 EADB-021E 3/8 7/8 11 2 22.9 32.5 19.0 290
JS-0210L6 2 EAVB-021E 3/8 7/8 11 2 22.9 32.5 19.0 290
JS-0301L6 3 LACB-032E 1/2 1-1/8 25 1 30.3 36.0 28.5 465
JS-0400L6 4 NRD1-032E* 1/2 1-1/8 25 1 30.3 36.0 28.5 465
NRD1-040E**
* 3 PHASE MODEL- R404A/ R507
** 1 PHASE MODEL - R404A ONLY
MCA is minimum circuit ampacity value developed for U.L. This value has a calculated safety factor and can be used for wire sizing.
All three phase models use single phase fan motors.
Operating voltage rangeplus 10%, minus 10% including 208/230 volt (187 to 253 volt)
For remote applications, additional receiver capacity may be necessary to assure adequate pumpdown capacity.
9
Electrical Data - Indoor Condensing Units
CFC-502 & HCFC-22 & HFC-134A
HCFC-22 & CFC-502 MEDIUM AND HIGH TEMP. UNITS - HERMETIC - UL LISTED
115-60-1 208/230-60-1 208/230-60-3
ELEC. MAX. ELEC. MAX. ELEC. MAX.
MODEL COMPRESSOR CODE MCA FUSE CODE MCA FUSE CODE MCA FUSE
JH-0050H2 JRE1-0050 A 12.5 20 B 7.3 15
JH-0051M2 JRF4-0050 A 18.8 30 B 9.0 15
JH-0075H2 RSE4-0075 A 19.7 30 B 9.9 15
JH-0077M2 RRG4-0100 A 18.3 30 B 8.5 15
JH-0101H2 REK3-0125 B 9.8 15 C 6.9 15
JH-0101M2 REB3-0150 B 11.6 20
JH-0151D7 CRA1-0150 B 14.8 25 C 12.9 20
JH-0201M7 CRD1-0200 B 18.1 30 C 12.2 20
JH-0201D7 CRD1-0200 B 19.4 30 C 13.5 20
JH-0301D7 CRJ3-0300 B 30.7 50 C 20.5 30
JH-0401D7 CRM3-0401 B 41.9 70 C 25.8 40
JH-0501D7 CRN5-0500 B 46.4 80 C 30.3 50
HCFC-22 & CFC-502 MEDIUM AND HIGH TEMP. UNITS - HERMETIC - UL RECOGNIZED
115-60-1 208/230-60-1
ELEC. MAX. ELEC. MAX.
MODEL COMPRESSOR CODE MCA FUSE CODE MCA FUSE
10
Electrical Data - Indoor Condensing Units - HFC404A/507
11
Since product improvement is a continuing effort at Heatcraft, we reserve the right to make changes in specifications without notice.