_INV080_Reset (1/3)

INV
080 Error Reset: _INV080_Reset
Basic Resets an Inverter error.
function
Symbol Always ON (P_ON)
_INV080_Reset
(BOOL) (BOOL)
EN ENO
Inverter No. (INT) (BOOL) Error reset completed
NodeNo Done
Start (BOOL) (BOOL) Error
Execute Error
I/F Area ID (WORD) (WORD) Error code
AreaID ErrorID
I/F Area No. (INT)
AreaNo

File name Lib\FBL\omronlib\Inverter\INVRT\Serial\_INV080_Reset20.cxf


Applicable Inverters 3G3MV Series, 3G3RV Series
models CIMR-V7AZ, CIMR-F7Z, CIMR-E7Z, CIMR-L7Z, CIMR-G7 (Sold by OYMC)
CPU Unit CS1*-CPU**H Unit version 3.0 or higher
CJ1*-CPU**H Unit version 3.0 or higher
CJ1M-CPU** Unit version 3.0 or higher
CP1H
CP1L (except 10 points CPU)
Serial ports See _INV002_Refresh for detail
Combination FB _INV002_Refresh version 2.0 or higher
CX-Programmer Version 5.0 or higher
Conditions The inverter is to be connected to a Serial port controlled by the Refresh FB Status Refresh
for usage (_INV002_Refresh). (See the reference for the Refresh FB for applicable products and serial port.)
Additionally, Requests for sending commands and reading status are sent to the Refresh FB.
That means this FB only makes reservation for sending messages and does not control the serial port.
II/F Area (Always operating)
Start trigger Operation Area ID Area No
commands Command & Status Communications
Request commands
This FB Status read Refresh FB

Response
Result

MSG Area - Priority setting


MSGAreaID, MSGAreaNo - Sends FINS commands
Parameter setting Refresh settings
Error code read - FINS error processing
Message commands
Monitor item read Message response

Shared Resources
I/F area and MSG area used for the FB _INV002_Refresh
Inverter Settings
The inverter communication parameters and Serial Communication Unit parameter .
The Serial communication unit parameters can be changed by CX-Programmer or using FB library
_INV600_SetComm.
Function Resets errors on the inverter specified with the Area No. (AreaID and AreaNo) and Inverter No. (NodeNo).
description When Start (Execute) is OFF, the Error reset completed (Done) will be turned OFF.
While Start (Execute) is ON, the Error reset command will be turned ON every cycle.
When Start (Execute) is turned ON and Error (Error) is turned OFF, the Error reset completed (Done) will be
turned ON.
FB This FB takes several cycles to finish processing.
precautions Timing Chart
Start (Execute) ON
OFF

Error reset completed ON


(Done) or Error OFF
(Error)
Error reset completed here

EN input Connect the EN input to the Always ON flag (P_ON).


condition
Restrictions Use Always ON (P_ON) input to EN.
Input When any input variable is out of range, ENO will be turned OFF and the FB will not be executed.
variables The Inverter node number is 1 to 31 node 0 and 32 are not available.
_INV080_Reset (2/3)

Application When the Bit A is turned ON, the error on the Inverter 20 will be reset.
example
Unit No.: 10 (SCU)

&10
_INV002_Refresh
CPU SCU I/F Area: EM0_1000 to EM0_1061
MSG Area: EM0_1150 to EM0_1194
Serial port No.: 1

Inverter: 20
Command units (n152) = 0.1Hz

Inverter

Always ON (P_On) _INV080_Reset


(BOOL) (BOOL)
Inverter No. EN ENO Error reset completed
(INT) (BOOL) Bit B
&20
Start NodeNo Done
Bit A (IBOOL) (BOOL) Error
I/F Area ID Execute Error
Same as setting of the P_EM0 (WORD) (WORD) Error code
FB Status Refresh I/F Area No AreaID ErrorID
&1000 (INT)
AreaNo

Always ON (P_On) _INV002_Refresh


(BOOL) (BOOL)
Unit selection EN ENO
&10 (INT) (BOOL) Busy flag
Serial port No. UnitSelect BUSY
&1 (INT) (INT) Current axis No.
Scan List No. PortNo NodeAddr
#00100000 (DWORD) (BOOL) Error
Model Type List Scanlist Error
#00000000 (DWORD) (WORD) Error code
Interval Count ModelTypeMV ErrorID
&10 (UINT)
I/F Area ID IntervalCount
P_EM0 (WORD)
I/F Area No AreaID
&1000 (INT) _INV002_Refresh is required for
Message Area ID AreaNo each MODBUS line.
(WORD) more than one _INV002_Refresh
P_EM0
MSGAreaID cannot be used to control same
Message Area No
(INT) PortNo. It does not work correctly
&1150
MSGAreaNo

Related SYSDRIVE 3G3MV Series Multi-function Compact Inverter Users Manual (I527)
manuals SYSDRIVE 3G3RV Series High-function General-purpose Inverter Users Manual (I532)
CIMR-F7Z Users Manual (YEG-TOE-S616-55.1-OY)
CIMR-E7Z Users Manual (YEG-TOE-S616-56.1-OY)
CIMR-L7Z Users Manual (TOMCC71067600AA-OY)
CIMR-G7 Users Manual (TOE-S616-60.2)
_INV080_Reset (3/3)

Variable Table
Input Variables
Name Variable name Data type Default Range Description
EN EN BOOL 1 (ON): Starts FB
0 (OFF): Does not start FB
Inverter No. NodeNo INT &1 &1 to &31 The axis No. of the inverter used inside the Status
Refresh FB _INV002_Refresh should be specified
here.
Start Execute BOOL 0(OFF) 1 (ON): Resets errors on the inverter.
I/F Area ID AreaID WORD #0082 The Area specified for the Refresh FB
I/F Area No AreaNo INT &0 _INV002_Refresh that controls the concerned
serial port.

Output Variables
Name Variable name Data type Range Description
ENO ENO BOOL 1 (ON): FB operating normally
(May be omitted) 0 (OFF): FB not started or ended with error
Error reset Done BOOL 0 (OFF): Other than the below
completed 1 (ON): Error reset completed
Error Error BOOL 0 (OFF): Other than the below
1 (ON): An error has occurred in the FB
Error code ErrorID WORD #0000: No error, or failed to acquire due to communications
error
#0001 to #FFFF: The error code of the error occurring in
the inverter. For details, refer to the manuals indicated in
the Related manuals.

Revision History
Version Date Contents
1.00 2005.4.22 Original production
1.10 2005.7.22 Suport CJ1M CPU
2.00 2007.6.8 The acquisition bank calculation mistake of EM is corrected.
(Combination with _INV002_Refresh version 2.0 or higher)
Note
This document explains the function of the function block.
It does not provide information of restrictions on the use of Units and Components or combination of them. For actual applications,
make sure to read the operation manuals of the applicable products.

S-ar putea să vă placă și