Documente Academic
Documente Profesional
Documente Cultură
for
Pt.Bekaert Indonesia
Prepared By:
SAN/ANP
MSI
9/21/2017
Fire - Fire Sprinkler Hydraulics Calculation Program Elite Software Development, Inc.
pReJkEr ISC Building Sprinkler System
Hell Page 2
General Data
Project Title: ISC Building Sprinkler System Project File Name: ISC building_A..fiw
Designed By: SAN/ANP Date: 9/21/2017
Code Reference: NFPA 13 Approving Agency:
Client Name: Pt.Bekaert Indonesia Phone:
Address: City, State Zip Code:
Company Name: MSI Representative:
Company Address: City And State:
Phone:
Building Name: ISC Building Building Owner:
Contact at Building: Phone at Building:
Address Of Building: City, State Zip Code:
Project Data
Description Of Hazard: Ex. Haz. Gp. 1 Sprinkler System Type: Wet
Design Area Of Water Application: 232 m Maximum Area Per Sprinkler: 9 m
Default Sprinkler K-Factor: 165.86 Km Default Pipe Material: SCHED 40 WET STEEL
Inside Hose Stream Allowance: 0.00 Lpm Outside Hose Stream Allowance: 0.00 Lpm
In Rack Sprinkler Allowance: 0.00 Lpm
Sprinkler Specifications
Make: Model:
Size: Temperature Rating: -17.77 C
-
1 2 0 4922.14 0.00 0.00 4922.143 511.21
16736609
Sprinkler Summary
Sprinkler System Type: Wet
Specified Area Of Application: 232.00 m
Minimum Desired Density: 12.224 Lpm/m
Application Average Density: 21.218 Lpm/m
Application Average Area Per Sprinkler: 9.28 m
Sprinkler Flow: 4922.51 Lpm
Average Sprinkler Flow: 196.90 Lpm
600
540
511
480
420
Pressure kPa
360
300
240
180
120
60
0
5 10 15 20 25 30 35 40 45 50
Flowrate(x100) Lpm