GAPS Guidelines GAP.14.2.2.

A Publication of Global Asset Protection Services LLC

WAFER CHECK VALVES

INTRODUCTION
Wafer check valves include balanced-clapper and butterfly check valves and come in several
designs. The valve body of these check valves may be fabricated from either bronze or iron
(malleable, cast or ductile). The balanced-clapper check valves, designed with an off-center post and
single clapper, and butterfly check valves, designed with a center post and a bi-parting clapper, are
listed by Underwriters Laboratories (UL) under the check valve category. They are also approved by
FM Global (FM) as antiwater-hammer check valves specifically for fire pump discharge use. FM also
approves single disk check valves.
Wafer check valves have no end connections and are installed between two flanges. Since these
check valves take up less space in the pipe line and are somewhat more economical to install than a
conventional swing check valve, some sprinkler contractors advocate their use. Because of their
smaller streamline design, valve clearance may present corrosion issues and obstructions if used in a
non-potable water supply.
The non-slamming characteristic operation of these check valves is obtained by having the single
off-center pivoted clapper (see Figure 1), by having spring-loaded bi-parting clappers (see Figure 2)
that close slightly before reversal of the water flow, or by cushioning the movement of the disk with a
specially designed spring which controls the valve closure. (See Figure 3).

POSITION
Balanced-clapper check valves, butterfly check valves and disk check valves are acceptable if they
are:
Listed by a recognized testing laboratory for fire protection service;
Used in fire pump discharge piping installations in which the non-slamming feature is necessary
(do not install in pump suction piping);
Used with potable water supplies and pumper connections;
Accessible;
Easily removed for inspection and servicing.

100 Constitution Plaza, Hartford, Connecticut 06103 Copyright 2015, Global Asset Protection Services LLC

Global Asset Protection Services LLC and its affiliated organizations provide loss prevention surveys and other risk management, business continuity and facility asset
management services. Unless otherwise stated in writing, our personnel, publications, services, and surveys do not address life safety or third party liability issues. The
provision of any service is not meant to imply that every possible hazard has been identified at a facility or that no other hazards exist. Global Asset Protection Services LLC
and its affiliated organizations do not assume, and shall have no liability for the control, correction, continuation or modification of any existing conditions or operations. We
specifically disclaim any warranty or representation that compliance with any advice or recommendation in any document or other communication will make a facility or
operation safe or healthful, or put it in compliance with any law, rule or regulation. If there are any questions concerning any recommendations, or if you have alternative
solutions, please contact us.
GAP.14.2.2.4

FLOW FLOW

Spring

Clapper
(Open)
Clapper

Clapper
(Closed)

Figure 1. Balanced Clapper Valve Figure 2. Butterfly Check Valve


(side view) (top view)

Figure 3. Spring-Loaded Disk Check Valve


(side view)

DISCUSSION
UL lists valves of this type in UL 312. Some of the highlights of the standard include:
The valves require a minimum clearance of !/2 in. (12.7 mm) between the clapper and the body of
iron-bodied valves, or !/4 in. (6.4 mm) for bronze-bodied valves. These clearances anticipate their
use with potable or clean water supplies. The center post might become a point of obstruction by
water-borne debris.
Check valves weighing more than 60 lbs (27 kg) require an access cover, lifting lug or an eyebolt
to facilitate servicing.
Do not install in pump suction piping.
The in-stream design of the clapper results in a higher friction loss than the swing check valve more
conventionally used in fire service.
Cast-iron bodies tend to tuberculate, particularly when there is frequent water turnover such as in a
city water connection. Any design with minimal clearance between clappers and body could lead to
early failure of a cast-iron bodied valve under such action.
Wafer type valves can be inspected or serviced only by removing the entire valve body from the pipe
line. The use of swing check valves with an access cover is recommended in below-grade pits
because of the potential difficulty of removal and reinstallation when inspection and cleaning are

GAPS Guidelines
2 A Publication of Global Asset Protection Services LLC
GAP.14.2.2.4

performed. The rigidity of the pipe system and close quarters in pits make flange spreading and
gasket insertion more difficult. This could result in prolonged impairments unless there is flexibility in
the attached pipe lines.
Balanced-clapper check valves and butterfly check valves equipped with grooved couplings permit
easier removal. Otherwise, a flanged elbow located near the check valve can be instrumental in
removal.
Where check valves of this type are designed for removal from the pipe for inspection and
maintenance, pre-fabricate a properly sized spool piece and store it in an accessible location for use
during the procedure.

GAPS Guidelines
3 A Publication of Global Asset Protection Services LLC