PROGRAMMING GUIDE
Sales Offices : +
BENGALURU CHENNAI COIMBATORE MUMBAI DELHI HYDERABAD USA UAE ALPHA - A / 3A / V / 3V / VAF / 3VAF
PG/APO/V5/0217 www.elmeasure.com

1. FEATURES 5. LED INDICATION


STAR (Wye)/ DELTA/1 phase programmable (3V, 3A,3VAF) LED Status Alpha+ 3A - Meaning LED Status Alpha+ VAF - Meaning
PT ratio programmable (V, 3V, VAF & 3VAF) R - ON R Phase Amps K - ON Kilo
CT ratio programmable including CT secondary (A , 3A, VAF & 3VAF) Y - ON Y Phase Amps VLN - ON Voltage Line to Neutral
Universal Voltage Input (80 - 550 VAC) and Current Secondary (0.05 to 6A) B - ON B Phase Amps A - ON Amps
Universal Auxiliary (80 - 300 VAC / DC ) supply K - ON Kilo Hz Frequency
RYB - ON Amps Average Value Communication ON
Simultaneous sampling of Volts & Amps
Communication ON LED Status Alpha+ 3VAF - Meaning
True RMS measurement Alpha+ 3V - Meaning R Phase Amps
LED Status R & A - ON
R - ON R Phase Voltage(VLN) Y &A - ON Y Phase Amps
2. UNIQUE FEATURES
Y - ON Y Phase Voltage (VLN) B &A - ON B Phase Amps
Optional Programmable relay output maximum 2 and tripping time up to B - ON B Phase Voltage (VLN) Hz Frequency
180 seconds. Hz Frequency RY & VLL - ON R-Y Voltage (VLL)
1 channel Analog output (0 to Full Scale/ 4 to 20mA) RY- ON R-Y Voltage (VLL) YB & VLL - ON Y-B Voltage (VLL)
Clearance & creepage distance meets UL 61010 standard YB - ON Y-B Voltage (VLL) BR & VLL- ON B-R Voltage (VLL)
1Row, 4digit display BR- ON B-R Voltage (VLL) R & VLN- ON R Phase Voltage (VLN)
Auto-scaling of kilo decimal point. K - ON Kilo Y & VLN - ON Y Phase Voltage (VLN)
RYB- ON VLL Average Value B & VLN - ON B Phase Voltage (VLN)
Compact size and light weight
RYB- OFF VLN Average Value VLL Voltage Line to Line
Optional RS485 VLN
Communication ON Voltage Line to Neutral
3. KEY FUNCTIONS LED Status Alpha+ A/V - Meaning A Amps
K - ON Kilo Communication ON
Key In SET (Programming) mode In RUN (Measurement) mode
Communication ON K - ON Kilo
Right/UP To select the value and accept the value To scroll pages in UPWARD direction
(it act as a Right key in programming and view different parameters
mode) 6. ENTERING CONFIGURATION (SETUP) MODE
DOWN To edit the value/system types To scroll pages in DOWNWARD
To configure the setup parameters through front panel, the following steps can be
downward in edit mode and scroll direction and view different
through the parameters. parameters followed.

4. WIRING DIAGRAM - Alpha Plus Series Step Actions Display Reads Range/Options/Comments
RS 485 1 Press RIGHT & first digit
DOWN keys together to 0 blinking
U
X

enter SETUP
_________
80-300VDC
80-300VAC

Single phase connection 2 Press DOWN key to If any other password is


AR

VR
AY

VY
AB

VB
S2

S2

S2
S1

S1

S1

decrement the first digit already set press RIGHT and


R
to 9 sequentially come first digit 1 blinking. DOWN key to reach the
S1 S2

LINE DELIVERED RECEIVED LOAD


N to digit 1. right password
3 Press RIGHT key Press RIGHT key
RS 485 four times to accept the ELEMENT to view options.
password. Defines the power system Options: STAR /DELTA/
U
X

configuration SINGLE PHASE


_________
80-300VDC
80-300VAC

(Applicable only for 3V, 3A


AR

VR
AY

VY
AB

VB
S2

S2

S2
S1

S1

S1

Delta connection (2E) & 3VAF models)


3Phase 3 wire system 4 Press RIGHT key Options can be
or
to select changed by pressing
S1 S2
R
Y
STAR/DELTA/1. PHASE or DOWN key.
B
S1 S2
N
LINE DELIVERED RECEIVED LOAD

selected system blinks


RS 485 5 Press RIGHT key
or
to accept the edited mode
U
X

or
_________
80-300VDC
80-300VAC

Star connection (3E) S1 AR S2 S1 AY S2 S1 AB S2 VR VY VB N

3Phase 4wire system Selected system stabilizes


S1 S2
R 6 Press DOWN key PT Primary Applicable only for
Y
S1 S2
S1 S2
B V, 3V, VAF & 3VAF models
N
LINE DELIVERED RECEIVED LOAD
7 Press RIGHT key 28 Press RIGHT Key to Options: 600,1200,
to view PT primary value view the value 2400,4800,9600, 19.20k.
415.0 : Default /factory set
The required value can be
8 Press RIGHT key First digit blinks Edit the digit using selected using DOWN key.
to edit the value DOWN key.
Press RIGHT key to accept
9 Press RIGHT key Program Range for the selected value.
to accept the edited value PT Primary : 100V to 999kV 29 Press DOWN key Internal communication
Second digit blinking, can
for first digit. error check
be edited using DOWN key.
Press RIGHT key to accept the 30 Press RIGHT Key to EUEn (even)/odd
edited value. Continue the view the option (odd)/no(no parity)
same method till fourth digit The required value can be
10 Press RIGHT key Ex: To set 11.00kV selected using DOWN key.
Set first four digits (1100) Press RIGHT key to accept
Decimal point blinking.
as explained above keep the selected option.
Can be set at appropriate
pressing DOWN key to 31 Press DOWN key Defines the (ID)
location using DOWN key. device ID
place decimal point at communications
Ascertain the correct scale
appropriate location. identification number.
(Kilo) is selected by Letter K.
K LED indicate Kilo.
Press RIGHT key to accept the 32 Press RIGHT Key to Repeat steps 8 Option:1 to 247
edited value. view the value to 10 to change
11 Press DOWN key PT Secondary Range: 50V to 550V the settings.
33 Press DOWN key Press RIGHT Key to
12 Press RIGHT key Repeat steps 8 to 10 to view the options
Analog output Options: 1. A & 3A A, dSbL
to view PT Secondary value change the settings.
415.0 : default/factory set. 2. V- VLL, dSbL
13 Press DOWN key CT Primary Range:0.5A to 99kA 3. 3V- VLL/VLn,F,dSbL
Applicable only for 4. VAF - VLn, A, F, dSbL
A , 3A, VAF & 3VAF models 5. 3VAF - VLL/VLn, A, F, dSbL
6. F & RPM F, dSbL

14 Press RIGHT key 34 Press RIGHT Key to Blinks the option which Press RIGHT key to
to view CT Primary value select the option was set previously. Press accept the selected option
5.000 : default/factory set. DOWN key to change the
Repeat steps 8 to 10 to options.
change the settings. 35 Press DOWN key Offset value
15 Press DOWN key CT Secondary Range: 0.5A to 6A

16 Press RIGHT key 36 Press RIGHT Key to Options- 0.t.FS/4.t.20


to view CT Secondary value view the option Press RIGHT key to
5.000 : default/factory set. Press DOWN key
Repeat steps 8 to 10 to
accept the selected
to change the options.
change the settings. option
17 Press DOWN key Press RIGHT Key
37 Press DOWN key If n(no) is selected
to view options then Meter enters into
1st digital output parameter 1. A & 3A - Under /Over A,dSbL Save YES RUN mode without
2. V- Under /Over V,dSbL Y blinking affecting any edited
3. 3V- Under/Over V,F ,dSbL Values in the setup
4. VAF,3VAF Under/Over V,A,F, dSbL
5. F & RPM - Under /Over F,dSbL Once the required parameter is programmed press the DOWN key continuously till it
18 Press RIGHT key Disable The required reaches SAVE page.
to select the required parameter can be selected Comment: If value set is above the maximum programmable range, display returns
parameter using DOWN key. Press to maximum Programmable value.
RIGHT key to accept the
selected option. 7. The List of parameters can be configured and the range is given
19 Press DOWN key Digital output below
1 threshold value Default
Sl.No. Parameter setup Range / Options
20 Press RIGHT key Range : 0.001 to 999.9K
1 Connection mode(ELEM) STAR STAR/ DELTA/ 1.Phase
1000 : Default/Factory set
2 PT Primary (PT.Pr) 415.0 100V- 999kV
Repeat steps 8 to 10 to
change the settings. 3 PT Secondary (PT SEC) 415.0 50V - 550V
4 CT Primary (CT.Pr) 5.000 0.5A - 99kA

5 CT Secondary (CT SEC) 5.000 0.5A - 6A


21 Press DOWN key Press RIGHT Key 6 1st Digital Output parameter (dO1.P) Options mentioned in 19
dSbL
to view options
2nd digital output parameter 1. A & 3A - Under /Over A,dSbL 7 1st Digital Output threshold Value (d.1.th) 1000. 0.001 t0 999.9K
2. V- Under /Over V,dSbL 8 2nd Digital Output parameter (dO.2.P) dSbL Options mentioned in 23
3. 3V- Under/Over V,F ,dSbL
4. VAF,3VAF Under/Over V,A,F, dSbL
9 2nd Digital Output threshold Value (d.2.th) 1000. 0.001 t0 999.9K
5. F & RPM - Under /Over F,dSbL 10 Digital output trip delay (d.dEL) 3.000 1.000 to 180.0 Sec
22 Press RIGHT key Disable The required 11 Baud rate (bAUd) 9600 600 to 19.2K
to select the required parameter can be selected 12 Parity (Prty) Even Even/ Odd/ no
parameter using DOWN key. Press 13 Device Id (dU.Id) 1.000 1.000 to 247.0
RIGHT key to accept the Options mentioned in 33
14 Analog output (An.OP) dSbL
selected option.
15 Offset (OFF.S) 0.t.FS 0.t.FS/4.t.20mA
23 Press DOWN key Digital output
2 threshold value
8. Enabling and Disabling of Auto scrolling: (Applicable only for
24 Press RIGHT key Range : 0.001 to 999.9K
3A, 3V, 3VAF & VAF models)
1000 : Default/Factory set Enabling auto scrolling: Press UP key continuously for 5 seconds or until display
Repeat steps 8 to 10 to shows EnbL for upward scrolling. Press Down key continuously for 5 seconds or until
change the settings. display shows EnbL for downward scrolling.
25 Press DOWN key Digital Output trip delay Disabling auto scrolling: Press any key (UP/DOWN), display show dSbL and returns to
time normal mode.
26 Press RIGHT Key to Range: 1 to 180 seconds
view the value 9. Mechanical Specification:
3.000 : Default/Factory set
Repeat steps 8 to 10 to Dimension Bezel:
change the settings. 96 x 96 mm (Depth 50mm behind Bezel)
27 Press DOWN key Defines the baud rate.
Panel Cutout: 90+2 +2
-0 x 90 -0 mm
baud rate communication