Important Note.... i
General Information... ii
Nomenclature..... 1
Features...... 2
General.... 3
Operating Range.. 62
Wiring Diagram-Local.. 65
Wiring Diagram-Export 72
Installation Guide 81
Operation. 91
Troubleshooting.. 92
KHD-3009C2~5009C4
KHD-1509~2509C2
KHD-1009/1259C-S
KHD-809C
KHD-409/509/609C
iii
1
KHD-409C-KHD-7509C5 models comes with standard horizontal air discharge. However, the range from
KHD-3009C2 to KHD-7509C5 are designed to cater for either horizontal or vertical air discharge application
(Optional). This optional is not standard design, need to request before ordering.
KHD-1509C series and above using belt driven fan such that the air volume and static required can be adjusted according to the
requirement. This exibility allows for wider application.
2
Kool. ans Ducted-split units are designed for duct type air-conditioning system in commercial
3
4
5
6
7
43mm (1 1/4" BSP)
8
43mm (1 1/4" BSP)
9
43mm (1 1/4" BSP) 48mm (1 1/2" BSP)
10
48mm (1 1/2" BSP)
11
12
13
14
Squirrel Induction/Sequential
15
Squirrel Induction/Sequential
16
Squirrel Induction/Sequential
17
Squirrel Induction/Sequential
18
Squirrel Induction/Sequential
19
8.1
4720
20
21
Condenser Coil Size (H x W)
12.5 15.8
6750 9000
22
Condenser Coil Size (H x W)
17.6 25.6
10100 13600
23
8.1
4720
24
25
Condenser Coil Size (H x W)
12.5 15.8
6750 9000
26
Condenser Coil Size (H x W)
17.6 25.6
10100 13600
27
7.9 8.9
4200 4956
28
10.5
5880
29
Condenser Coil Size (H x W)
12.9 16
6950 8950
30
Condenser Coil Size (H x W)
17.7 26.5
10150 13650
31
7.9 8.9
4200 4956
32
10.5
5880
33
Condenser Coil Size (H x W)
12.9 16
6950 8950
34
Condenser Coil Size (H x W)
17.7 26.5
10150 13650
35
36
37
38
39
KHD-3009C2 (Ver cal Air Discharge)
40
41
42
43
44
KC-401AF & KC-501AF
700
350 370
1000
1000
KC-601AF
45
46
47
48
KHD-409C
49
KHD-509C & KHD-609C & KHD-1009C-S
50
KHD-809C
51
KHD-1259C-S
52
FAN CURVE : KHD-1509C
SPZ190(1610-25)
SPZ100(1210-24)
SPZ
875 MM
53
FAN CURVE : KHD-2009C2
2SPZ170(2012-30)
2SPZ100(1610-28)
SPZ
772 MM
54
FAN CURVE : KHD-2509C2
2SPZ170(2012-30)
2SPZ100(1610-28)
SPZ
825 MM
55
FAN CURVE : KHD-3009C2
2SPZ236(2012-35)
SPZ118(1610-28)
SPZ
1150 MM
56
FAN CURVE : KHD-3509C3
2SPA280(2517-35)
2SPA132(2012-38)
SPZ
1350 MM
57
FAN CURVE : KHD-4009C4
2SPA280(2517-35)
2SPA132(2012-38)
SPZ
1350 MM
58
FAN CURVE : KHD-5009C4
2SPA355(2517-40)
2SPA150(2012-38)
SPZ
1582 MM
59
FAN CURVE : KHD-6009C4
2SPB355M/3020
-45 MM
2SPB140MM/2012
-22 MM
SPZ
1500 MM
60
FAN CURVE : KHD-7509C5
3SPB355MM/3020-
45 MM
3SPB150MM/2517-
42 MM
SPZ
1700 MM
61
46
19
15
62
Local Model Cooling Mode Operation
63
Export Model Cooling Mode Operation
Filter Drier
Vacuum
Indoor
Side
64
8. WIRING DIAGRAM (LOCAL)
KHD-409C/KC-401AF
KHD-509C/KC-501AF
THERMOSTAT
(MODEL : AC811 A2 L D3)
N Hi Me Lo V L
1 2 3 4 5 6 7
DOL
STARTER
51 COMP
TB 1
TB 2
RD
BK
WH
WH
RD
BL
BL
Y/GN Y/GN
R
T
S
T1
N
BL
WFK
LED 1
J3
J1
N
LED 2
W
V U OR
LED 2(GREEN): WHEN THE LAMP IS ON, PHASE IS CORRECT
WHEN THE LAMP IS OFF, PHASE IS REVERSE OR SCARCE.
CM
MF
Y/GN
Y/GN
OUTDOOR UNIT KC-401 & 501AF
65
KHD-609C / KC-601AF
THERMOSTAT
(MODEL : AC811 A2 L D3)
N Hi Me Lo V L
1 2 3 4 5 6 7
D.O.L
STARTER
51 COMP
66
KHD-809C / KC-809
67
KHD-1009C-S / 1259C-S
68
KHD-1509C / KC-1509
69
KHD-2009C2 / KC-1009 X 2, KHD-2509C2 / KC-1259 X 2
KHD-4009C4 / KC-1009 X 4, KHD-5009C4 / KC-1259 X 4
CIRCUIT MULTIPLY
ACCORDING TO THE
NUMBER
CIRCUIT MULTIPLY
OF OUTDOOR UNIT
ACCORDING TO THE
NUMBER
OF OUTDOOR UNIT
STAR DELTA
STARTER
BM
51 BM
70
KHD-3009C2 / KC-1509 X 2, KHD-6009C4 / KC-1509 X 4
KHD-7509C5 / KC-1509 X 5
CIRCUIT MULTIPLY
ACCORDING TO THE
NUMBER
CIRCUIT MULTIPLY
OF OUTDOOR UNIT
ACCORDING TO THE
NUMBER
OF OUTDOOR UNIT
STAR DELTA
STARTER
BM
51 BM
STAR DELTA
STARTER
BM
51 BM
71
8. WIRING DIAGRAM (EXPORT)
KHD-409C-E/KC-401AF
KHD-509C-E/KC-501AF
HF 1 MF 1 LF 1 N HF 2 MF 2 LF 2 N
3 SPEED RELAY
THERMOSTAT
(MODEL : AC811 A2 L D3)
L N Hi Me Lo N Hi Me Lo V L
1 2 3 4 5 6 7
WH
RD
BL
BL
Y/GN Y/GN
R
T
S
T1
N
BL
WFK
LED 1
J3
J1
N
LED 2
WH
72
KHD-609C-E / KC-601AF
HF 1 MF 1 LF 1 N HF 2 MF 2 LF 2 N
3 SPEED RELAY
THERMOSTAT
(MODEL : AC811 A2 L D3)
L N Hi Me Lo N Hi Me Lo V L
1 2 3 4 5 6 7
73
KHD-809C-E / KC-809-E
HF 1 MF 1 LF 1 N HF 2 MF 2 LF 2 N
3 SPEED RELAY
THERMOSTAT
(MODEL : AC811 A2 L D3)
L N Hi Me Lo N Hi Me Lo V L
1 2 3 4 5 6 7
220-240/1Ph/50Hz
(FIELD SUPPLY)
INDOOR UNIT KHD-809-E
74
KHD-1009C/1259-E & KC-1009/KC-1259-E
HF 1 MF 1 LF 1 N HF 2 MF 2 LF 2 N
3 SPEED RELAY
THERMOSTAT
(MODEL : AC811 A2 L D3)
L N Hi Me Lo N Hi Me Lo V L
1 2 3 4 5 6 7
220-240/1Ph/50Hz
(FIELD SUPPLY)
INDOOR UNIT KHD-1009C/1259C-E
75
KHD-1509C/1509-E
THERMOSTAT
(MODEL : AC811 A2 L D3)
N Hi Me Lo V L
1 2 3 4 5 6 7
220-240/1Ph/50Hz
(FIELD SUPPLY)
380-415/3Ph/50Hz
(FIELD SUPPLY)
INDOOR UNIT KHD-1509C
380-415/3Ph/50Hz
(FIELD SUPPLY)
76
KHD-2009C2-E / KC-1009-E X 2
KHD-2509C2-E / KC-1259-E X 2
KHD-3009C2-E / KC-1509-E X 2
INDOOR UNIT KHD-2009C2-E
INDOOR UNIT KHD-2509C2-E
INDOOR UNIT KHD-3009C2-E
380-415/3Ph/50Hz 220-240/1Ph/50Hz
(FIELD SUPPLY)
(FIELD SUPPLY)
N C1 N C2
BLUE/BLACK
DIP SWITCH
MC : MAGNETIC CONTACTOR
L : LIVE
N : NEUTRAL
1 2 3 4 5 6 7 8
C2
77
KHD-3509C3-E / KC-1009-E & KC-1259-E
380-415/3Ph/50Hz 220-240/1Ph/50Hz
(FIELD SUPPLY)
(FIELD SUPPLY)
N C1 N C2 N C3
R S T DO 1 DO 2 DO 3
RETURN AIR SENSOR AI 1
15 16 SUPPLY AIR TEMP SENSOR AI 3
INDOOR COIL TEMP SENSOR 1 AI 4
INDOOR COIL TEMP SENSOR 2 AI 5
INDOOR COIL TEMP SENSOR 3 AI 6
DI 2 DO11A
Common
SWITCHING POWER
SUPPLY BOARD
BLUE/BLACK
DIP SWITCH
MC : MAGNETIC CONTACTOR
L : LIVE
N : NEUTRAL
1 2 3 4 5 6 7 8
C2 C3
78
KHD-4009C4-E / KC-1009-E X 4
KHD-5009C4-E / KC-1259-E X 4
KHD-6009C4-E / KC-1509-E X 4
INDOOR UNIT KHD-4009C4-E
INDOOR UNIT KHD-5009C4-E
INDOOR UNIT KHD-6009C4-E
380-415/3Ph/50Hz 220-240/1Ph/50Hz
(FIELD SUPPLY)
(FIELD SUPPLY)
N C1 N C2 N C3 N C4
R S T DO 1 DO 2 DO 3 DO 4
RETURN AIR SENSOR AI 1
15 16 SUPPLY AIR TEMP SENSOR AI 3
INDOOR COIL TEMP SENSOR 1 AI 4
INDOOR COIL TEMP SENSOR 2 AI 5
INDOOR COIL TEMP SENSOR 3 AI 6
INDOOR COIL TEMP SENSOR 4 AI 7 DI 2 DO11A
Common
SWITCHING POWER
SUPPLY BOARD
BLUE/BLACK
DIP SWITCH
MC : MAGNETIC CONTACTOR
L : LIVE
N : NEUTRAL
1 2 3 4 5 6 7 8
C2
C4 C3
79
KHD-7509C5-E / KC-1509-E
220-240/1Ph/50Hz
(FIELD SUPPLY) INDOOR UNIT KHD-7509C5-E
380-415/3Ph/50Hz
(FIELD SUPPLY)
TO OUTDOOR BOARD
(A1,B1)
BLUE/BLACK
DIP SWITCH
MC : MAGNETIC CONTACTOR
L : LIVE
N : NEUTRAL
1 2 3 4 5 6 7 8
220-240/1Ph/50Hz
(FIELD SUPPLY)
380-415/3Ph/50Hz 380-415/3Ph/50Hz
(FIELD SUPPLY) (A1,B1) (FIELD SUPPLY)
DIP SWITCH
COMP HP A1
COMP HP A2
COMP LP A1
TO OUTDOOR
(A1 @ B1 @ B2)
DI 4
DI 2
DI 5
DI 3
DI 1
AMBIENT SENSOR
OUTDOOR COIL
SENSOR A1
OUTDOOR COIL
DO 1
DO 3
DO 2
DO 6
DO 5
DO 4
SENSOR A2
COMP A1
FAN A1
FAN A2
COMP A2
FAN
COMP A
MOTOR A1
MC - MAGNETIC CONTACTOR HPA2 - HIGH PRESSURE A2 MC - MAGNETIC CONTACTOR HPA2 - HIGH PRESSURE A2
L - LIVE CA 2 - COMPRESSOR A2 L - LIVE CA 2 - COMPRESSOR A2
N - NEUTRAL FA 2 - FAN MOTOR A2 N - NEUTRAL FA 2 - FAN MOTOR A2
COMP - COMPRESSOR LP - LOW PRESSURE SWITCH COMP - COMPRESSOR LP - LOW PRESSURE SWITCH
COM - COMMON HP - HIGH PRESSURE SWITCH COM - COMMON HP - HIGH PRESSURE SWITCH
LPA2 - LOW PRESSURE A2 LPA2 - LOW PRESSURE A2
* OUTDOOR UNIT KC-1509-E-(A1) WITH PCB BOARD * OUTDOOR UNIT KC-1509-E-(A2) WITHOUT PCB BOARD
220-240/1Ph/50Hz
(FIELD SUPPLY)
220-240/1Ph/50Hz
(FIELD SUPPLY)
380-415/3Ph/50Hz 380-415/3Ph/50Hz 380-415/3Ph/50Hz
(FIELD SUPPLY) (FIELD SUPPLY) (FIELD SUPPLY) (A1,B1)
(A1,B1)
DIP SWITCH DIP SWITCH
COMP HP A1
COMP HP A2
COMP LP A1
COMP HP A1
COMP HP A2
COMP LP A1
TO OUTDOOR TO OUTDOOR
(A1 @ B1 @ B2) (A1 @ B1 @ B2)
DI 4
DI 2
DI 5
DI 3
DI 1
DI 4
DI 2
DI 5
DI 3
DI 1
DO 3
DO 2
DO 6
DO 5
DO 4
DO 1
DO 3
DO 2
DO 6
DO 5
DO 4
SENSOR A2 SENSOR A2
COMP A1
FAN A1
FAN A2
COMP A2
COMP A1
FAN A1
FAN A2
COMP A2
FAN FAN
COMP A COMP A
MOTOR A1 MOTOR A1
MC - MAGNETIC CONTACTOR HPA2 - HIGH PRESSURE A2 MC - MAGNETIC CONTACTOR HPA2 - HIGH PRESSURE A2 MC - MAGNETIC CONTACTOR HPA2 - HIGH PRESSURE A2
L - LIVE CA 2 - COMPRESSOR A2 L - LIVE CA 2 - COMPRESSOR A2 L - LIVE CA 2 - COMPRESSOR A2
N - NEUTRAL FA 2 - FAN MOTOR A2 N - NEUTRAL FA 2 - FAN MOTOR A2 N - NEUTRAL FA 2 - FAN MOTOR A2
COMP - COMPRESSOR LP - LOW PRESSURE SWITCH COMP - COMPRESSOR LP - LOW PRESSURE SWITCH COMP - COMPRESSOR LP - LOW PRESSURE SWITCH
COM - COMMON HP - HIGH PRESSURE SWITCH COM - COMMON HP - HIGH PRESSURE SWITCH COM - COMMON HP - HIGH PRESSURE SWITCH
LPA2 - LOW PRESSURE A2 LPA2 - LOW PRESSURE A2 LPA2 - LOW PRESSURE A2
* OUTDOOR UNIT KC-1509-E-(B1) WITH PCB BOARD * OUTDOOR UNIT KC-1509-E-(B2) WITHOUT PCB BOARD * OUTDOOR UNIT KC-1509-E-(C1) WITH PCB BOARD
OUTDOOR UNIT KC-1509-E X 5
80
81
82
83
84
85
86
KHD-409C KC-401AF 3/8" 3/4" 2.45
KHD-509C KC-501AF 3/8" 3/4" 3.20
KHD-609C KC-601AF 3/8" 3/4" 5.05
KHD-809C KC-809 1/2" 7/8" 6.40
KHD-1009C KC-1009 5/8" 1-1/8" 7.40
KHD-1259C KC-1259 5/8" 1-3/8" 8.0
KHD-1509C KC-1509 5/8" 1-3/8" 10.1
KHD-2009C2 KC-1009 x 2 5/8" 1-1/8" 7.6 x 2
KHD-2509C2 KC-1259 x 2 5/8" 1-3/8" 8.0 x 2
KHD-3009C2 KC-1509 x 2 5/8" 1-3/8" 10.1 x 2
KHD-3509C3 KC-1009 + KC-1259 x 2 5/8" 1-1/8" & 1-3/8" 7.6 + 8.0 x 2
KHD-4009C4 KC-1009 x 4 5/8" 1-1/8" 7.6 x 4
KHD-5009C4 KC-1259 x 4 5/8" 1-3/8" 8.0 x 4
KHD-6009C4 KC-1509 x 4 5/8" 1-3/8" 10.1 x 4
KHD-7509C5 KC-1509 x 5 5/8" 1-3/8" 10.1 x 5
87
88
89
90
91
92
93
94
95
Indoor Accurator
96
MODEL : KHD-509C/E
97
MODEL : KHD-609C/E
98
99
MODEL : KHD-1009C-S/E
100
MODEL : KHD-1259C-S/E
101
102
103
MODEL : KHD-2509C2/E
104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
MODEL : KC-1509
122
123
KHD-409C-E~KHD1509C-E (EXPORT)
KHD-2009C2-E~KHD6009C4-E (EXPORT)
1. Interface
1.3. Error code : Show error code (if any) ; Symbol No shows unit number
1.6. System status : Electric heater, defrost, compressor 1#/2#/3#/4#, water pump, key lock
2. On/Off
3. Mode of operation
3.1. Press to select mode of operation: Heating, Cooling, Fan only, Dehumidify
5. Key lock
5.1. Press and hold and for 1s to activate keylock (Only button is effective during keylock)
6. Temperature setting
7. Clock setting
7.1.2. Press to save (Auto save when there is no input for 6s)
8.3. To set timer, press once, temperature display area shows 1 and timer symbol blinks
8.3.2. Timer symbol blinks, temperature display area shows Px x = 1 ~ 4 which represent timer set
8.3.3. Press to select timer set number (maximum 4 set in a day), temperature display area shows P1 ~
P4
SUN-MON-TUE-WED-THU-FRI-SAT
8.3.10. Press and hold for 1s to cancel current timer setting, clock area displays -:--
8.3.11. Press and hold for 3s to cancel all timer setting, day display area all lights up, clock display area
displays -:--
8.3.12. Timer setting will be saved and exit automatically if there is no input for 30s
9. Check various temperature readings
9.1. Press and hold and for 3s to enter various temperature readings page
9.2. Error code display area shows unit number; Temperature display area shows category; Clock display area
9.5. Press to exit (Auto exit when there is no input for 60s)
10.1. Error code display area symbol lights up and error code shows during system error
10.2. All error codes (if more than 1) will be showed one after another
10.3. Press to clear error (for those with error rectified only)
11.1. Press twice (Temperature display area shows 2, key lock symbol blinks), and press within
11.4. Press or to select password for first digit and press to confirm and proceed to second digit
password entry
11.5. Repeat step 11.4 for complete password entry 8699 to enter parameters setting interface
11.6. Temperature display area shows parameter category and correspondence category value will be shown at
11.11.1. Press and , follow steps 11.2 to 11.4 for complete password entry 1919
11.12.Parameters setting reference table
12.1. Press twice (Temperature display area shows 2, key lock symbol blinks), and press within
12.4. Press or to select password for first digit and press to confirm and proceed to second digit
password entry
12.5. Repeat step 11.4 for complete password entry 2828 to enter limited operation time setting
12.6. Temperature display area shows parameter category and correspondence category value will be shown at
13.1. Press and hold and for 3s to enter manual defrost mode
13.2. Temperature display area shows ON/OFF to determine manual defrost status
14.1. Press and hold and for 3s then enter password 1919
16.1. Press and hold and for 3s within 1 minute upon power on to test function on mainboard
1. On/Off
2. Temperature setting
3. Mode setting
Press <<Menu>> twice to enter
Press <<Menu>> 6 times to enter (5 times in single fan speed mode) (for Off timer)
If on timer for this day is empty, timer display area shows , otherwise the on
or off timer setting will be shown.
Press or button to change the on or off timer setting. Holding down the
button will change the setting in a faster speed (toggle in hour)
Press On/Off to toggle between week (On timer)
7. Manual defrost
Press and for 3 seconds under heat mode to enter manual defrost. Clock area display
dEF1, press or to choose system to be defrost, press Enter to exit. Press Info to
cancel and exit.
8. Key lock
Press MENU and ENTER keys on the main menu for 3 sec to activate this function. Follow the
same sequence to exit key lock. In key lock mode, user is allowed to access to On/Off key only.
9. Information
Press INFO key on the main menu to enter. Press or key to select the required information
as follow:
Press MENU and keys on the main menu for 3 sec to activate this function. Timer display
section shows 0--- asking for password entry. Press or key to change the value of the
current digit being edit. Press On/Off key to change the digit to be edited. Upon key in the correct
password of 8699, press ENTER key to enter into the following menu:
Press On/Off key to select the item to be changed. Press or key to change the value of
the item selected.
Press INFO key to exit without save
Press CONFIRM key to exit and save the settings
11. Error code display
Backlight will turned to red when there is any system failure. ERR light will turn on and error
display section will show the relevant error code as follow:
19
20 Outdoor coil temperature sensor 2 (Auto reset)
29
30 Outdoor coil temperature sensor 3 (Auto reset)
39
40 Outdoor coil temperature sensor 4 (Auto reset)
49
50 Outdoor coil temperature sensor 5 (Auto reset)
59
60 Outdoor coil temperature sensor 6 (Auto reset)
69
70 Outdoor coil temperature sensor 7 (Auto reset)
79
80 Outdoor coil temperature sensor 8 (Auto reset)
Press Menu and Confirm for 3 seconds after system booted for 90s to enter hardware
check mode. Auto exit after 1 minute