HIGH STATIC DUCTED DX SPLIT SYSTEM

TECHNICAL MANUAL R22/R407C


(LOCAL/EXPORT)
Table Of Contents

Important Note.... i

General Information... ii

Unit Preview.... iii

Nomenclature..... 1

Features...... 2

General.... 3

Specification Indoor Unit-Local (R22/R407C).... 4

Specification Indoor Unit-Export (R22/R407C).. 12

Specification Outdoor Unit-Local (R22)..... 20

Specification Outdoor Unit-Export (R22)... 24

Specification Outdoor Unit-Local (R407C).... 28

Specification Outdoor Unit-Export (R407C).... 32

Outline & Dimension-Indoor Unit... 36

Outline & Dimension-Outdoor Unit 45

Fan Performance Curve.. 48

Operating Range.. 62

Refrigerant Circuit Diagram.... 63

Wiring Diagram-Local.. 65

Wiring Diagram-Export 72

Installation Guide 81

Service & Maintenance.. 90

Operation. 91

Troubleshooting.. 92

Exploded View & Part List. 96


i
ii
KHD-6009C4~7509C5

KHD-3009C2~5009C4

KHD-1509~2509C2

KHD-1009/1259C-S

KHD-809C

KHD-409/509/609C

KC-401~501 KC-601 KC-1009~1509


KC-809

iii
1
KHD-409C-KHD-7509C5 models comes with standard horizontal air discharge. However, the range from
KHD-3009C2 to KHD-7509C5 are designed to cater for either horizontal or vertical air discharge application
(Optional). This optional is not standard design, need to request before ordering.

KHD-1509C series and above using belt driven fan such that the air volume and static required can be adjusted according to the
requirement. This exibility allows for wider application.

2
Kool. ans Ducted-split units are designed for duct type air-conditioning system in commercial

Koolmans High Static Ducted system easier and exible


structure design air discharge to carter for either horizontal or
vertical air discharge application.
(Optional for model KHD-3009C2 to KHD-7509C5)

from 4 or 6 blades aluminium material and direct driven by weatherproof

Each coil consist of staggered row of seamless copper tubes,

3
4
5
6
7
43mm (1 1/4" BSP)

8
43mm (1 1/4" BSP)

9
43mm (1 1/4" BSP) 48mm (1 1/2" BSP)

10
48mm (1 1/2" BSP)

11
12
13
14
Squirrel Induction/Sequential

15
Squirrel Induction/Sequential

43mm (1 1/4" BSP)

16
Squirrel Induction/Sequential

43mm (1 1/4" BSP)

17
Squirrel Induction/Sequential

43mm (1 1/4" BSP) 48mm (1 1/2" BSP)

18
Squirrel Induction/Sequential

48mm (1 1/2" BSP)

19
8.1
4720

20
21
Condenser Coil Size (H x W)

12.5 15.8
6750 9000

22
Condenser Coil Size (H x W)

17.6 25.6
10100 13600

23
8.1
4720

24
25
Condenser Coil Size (H x W)

12.5 15.8
6750 9000

26
Condenser Coil Size (H x W)

17.6 25.6
10100 13600

27
7.9 8.9
4200 4956

28
10.5
5880

29
Condenser Coil Size (H x W)

12.9 16
6950 8950

30
Condenser Coil Size (H x W)

17.7 26.5
10150 13650

31
7.9 8.9
4200 4956

32
10.5
5880

33
Condenser Coil Size (H x W)

12.9 16
6950 8950

34
Condenser Coil Size (H x W)

17.7 26.5
10150 13650

35
36
37
38
39
KHD-3009C2 (Ver cal Air Discharge)

KHD-3009C2 (Horizontal Air Discharge)

40
41
42
43
44
KC-401AF & KC-501AF

700

350 370

1000

1000

KC-601AF

45
46
47
48
KHD-409C

49
KHD-509C & KHD-609C & KHD-1009C-S

50
KHD-809C

51
KHD-1259C-S

52
FAN CURVE : KHD-1509C

SPZ190(1610-25)

SPZ100(1210-24)

SPZ

875 MM

53
FAN CURVE : KHD-2009C2

2SPZ170(2012-30)

2SPZ100(1610-28)

SPZ

772 MM

54
FAN CURVE : KHD-2509C2

2SPZ170(2012-30)

2SPZ100(1610-28)

SPZ

825 MM

55
FAN CURVE : KHD-3009C2

2SPZ236(2012-35)

SPZ118(1610-28)

SPZ

1150 MM

56
FAN CURVE : KHD-3509C3

2SPA280(2517-35)

2SPA132(2012-38)

SPZ

1350 MM

57
FAN CURVE : KHD-4009C4

2SPA280(2517-35)

2SPA132(2012-38)

SPZ

1350 MM

58
FAN CURVE : KHD-5009C4

2SPA355(2517-40)

2SPA150(2012-38)

SPZ

1582 MM

59
FAN CURVE : KHD-6009C4

2SPB355M/3020
-45 MM
2SPB140MM/2012
-22 MM

SPZ

1500 MM

60
FAN CURVE : KHD-7509C5

3SPB355MM/3020-
45 MM
3SPB150MM/2517-
42 MM
SPZ

1700 MM

61
46

19

15

62
Local Model Cooling Mode Operation

63
Export Model Cooling Mode Operation

Filter Drier

Vacuum
Indoor
Side

64
8. WIRING DIAGRAM (LOCAL)
KHD-409C/KC-401AF
KHD-509C/KC-501AF

*FIELD SUPPLY THERMOSTAT WITH


3 MIN DELAY FOR COMPRESSOR

THERMOSTAT
(MODEL : AC811 A2 L D3)

N Hi Me Lo V L
1 2 3 4 5 6 7

INDOOR UNIT KHD-409/509C

DOL
STARTER
51 COMP
TB 1
TB 2
RD
BK
WH

WH
RD
BL

BL

Y/GN Y/GN
R
T
S

T1

N
BL

WFK

LED 1

J3
J1
N

LED 2

JC : CONTACTOR WH : WHITE OR : ORANGE


WH

CM : COMPRESSOR BL : BLUE Y/GN : YELLOW/GREEN


JC COIL
MF : FAN MOTOR RD : RED COMP/1L : COMPRESSOR SIGNAL
PRESSURE
C : FAN CAPACITOR BL : BLACK
SWITCH

TB1,2 : TERMINAL BLOCK


J1,3 : RELAY
BL C
JC LED : WORKING CIRCUMSTANCES
RD
OR
CONNECTOR LED 1(RED): WORKING POWER INDICATOR
WH BK RD

W
V U OR
LED 2(GREEN): WHEN THE LAMP IS ON, PHASE IS CORRECT
WHEN THE LAMP IS OFF, PHASE IS REVERSE OR SCARCE.
CM
MF

Y/GN
Y/GN
OUTDOOR UNIT KC-401 & 501AF

65
KHD-609C / KC-601AF

*FIELD SUPPLY THERMOSTAT WITH


3 MIN DELAY FOR COMPRESSOR

THERMOSTAT
(MODEL : AC811 A2 L D3)

N Hi Me Lo V L
1 2 3 4 5 6 7

INDOOR UNIT KHD-609

D.O.L
STARTER
51 COMP

OUTDOOR UNIT KC-601AF

66
KHD-809C / KC-809

INDOOR UNIT KHD-809C OUTDOOR UNIT KC-809

67
KHD-1009C-S / 1259C-S

INDOOR UNIT KHD-1009C-S / 1259C-S OUTDOOR UNIT KC-1009 / 1259

68
KHD-1509C / KC-1509

INDOOR UNIT KHD-1509C OUTDOOR UNIT KC-1509

69
KHD-2009C2 / KC-1009 X 2, KHD-2509C2 / KC-1259 X 2
KHD-4009C4 / KC-1009 X 4, KHD-5009C4 / KC-1259 X 4

CIRCUIT MULTIPLY
ACCORDING TO THE
NUMBER
CIRCUIT MULTIPLY
OF OUTDOOR UNIT
ACCORDING TO THE
NUMBER
OF OUTDOOR UNIT

STAR DELTA
STARTER
BM
51 BM

70
KHD-3009C2 / KC-1509 X 2, KHD-6009C4 / KC-1509 X 4
KHD-7509C5 / KC-1509 X 5

CIRCUIT MULTIPLY
ACCORDING TO THE
NUMBER
CIRCUIT MULTIPLY
OF OUTDOOR UNIT
ACCORDING TO THE
NUMBER
OF OUTDOOR UNIT

STAR DELTA
STARTER
BM
51 BM

STAR DELTA
STARTER
BM
51 BM

71
8. WIRING DIAGRAM (EXPORT)
KHD-409C-E/KC-401AF
KHD-509C-E/KC-501AF

HF 1 MF 1 LF 1 N HF 2 MF 2 LF 2 N

3 SPEED RELAY
THERMOSTAT
(MODEL : AC811 A2 L D3)

L N Hi Me Lo N Hi Me Lo V L
1 2 3 4 5 6 7

INDOOR UNIT KHD-409/509C-E


TB 1
TB 2
RD
BK
WH

WH
RD
BL

BL

Y/GN Y/GN
R
T
S

T1

N
BL

WFK

LED 1

J3
J1
N

LED 2
WH

JC COIL JC : CONTACTOR WH : WHITE OR : ORANGE


CM : COMPRESSOR BL : BLUE Y/GN : YELLOW/GREEN
PRESSURE
SWITCH
MF : FAN MOTOR RD : RED COMP/1L : COMPRESSOR SIGNAL
C : FAN CAPACITOR BL : BLACK
BL C
TB1,2 : TERMINAL BLOCK
JC
RD
J1,3 : RELAY
WH BK RD
OR
CONNECTOR LED : WORKING CIRCUMSTANCES
LED 1(RED): WORKING POWER INDICATOR
V U OR
W

CM LED 2(GREEN): WHEN THE LAMP IS ON, PHASE IS CORRECT


MF
WHEN THE LAMP IS OFF, PHASE IS REVERSE OR SCARCE.
Y/GN
Y/GN

OUTDOOR UNIT KC-401 & 501AF

72
KHD-609C-E / KC-601AF

HF 1 MF 1 LF 1 N HF 2 MF 2 LF 2 N

3 SPEED RELAY
THERMOSTAT
(MODEL : AC811 A2 L D3)

L N Hi Me Lo N Hi Me Lo V L
1 2 3 4 5 6 7

INDOOR UNIT KHD-609-E

OUTDOOR UNIT KC-601AF

73
KHD-809C-E / KC-809-E

HF 1 MF 1 LF 1 N HF 2 MF 2 LF 2 N

3 SPEED RELAY
THERMOSTAT
(MODEL : AC811 A2 L D3)

L N Hi Me Lo N Hi Me Lo V L
1 2 3 4 5 6 7

220-240/1Ph/50Hz
(FIELD SUPPLY)
INDOOR UNIT KHD-809-E

HP - HIGH PRESSURE SWITCH


LP - LOW PRESSURE SWITCH
OL - OVER LOAD
MC - MAGNETIC CONTACTOR
C1 - COMPRESSOR 1
PP - PHASE PROTECTOR

OUTDOOR UNIT KC-809-E

74
KHD-1009C/1259-E & KC-1009/KC-1259-E

HF 1 MF 1 LF 1 N HF 2 MF 2 LF 2 N

3 SPEED RELAY
THERMOSTAT
(MODEL : AC811 A2 L D3)

L N Hi Me Lo N Hi Me Lo V L
1 2 3 4 5 6 7

220-240/1Ph/50Hz
(FIELD SUPPLY)
INDOOR UNIT KHD-1009C/1259C-E

HP - HIGH PRESSURE SWITCH


LP - LOW PRESSURE SWITCH
OL - OVER LOAD
MC - MAGNETIC CONTACTOR
C1 - COMPRESSOR 1
PP - PHASE PROTECTOR

OUTDOOR UNIT KC-1009/1259-E

75
KHD-1509C/1509-E

THERMOSTAT
(MODEL : AC811 A2 L D3)

N Hi Me Lo V L
1 2 3 4 5 6 7

220-240/1Ph/50Hz
(FIELD SUPPLY)

380-415/3Ph/50Hz
(FIELD SUPPLY)
INDOOR UNIT KHD-1509C

380-415/3Ph/50Hz
(FIELD SUPPLY)

HP - HIGH PRESSURE SWITCH


LP - LOW PRESSURE SWITCH
OL - OVER LOAD
MC - MAGNETIC CONTACTOR
C1 - COMPRESSOR 1
PP - PHASE PROTECTOR

OUTDOOR UNIT KC-1509-E

76
KHD-2009C2-E / KC-1009-E X 2
KHD-2509C2-E / KC-1259-E X 2
KHD-3009C2-E / KC-1509-E X 2
INDOOR UNIT KHD-2009C2-E
INDOOR UNIT KHD-2509C2-E
INDOOR UNIT KHD-3009C2-E

380-415/3Ph/50Hz 220-240/1Ph/50Hz
(FIELD SUPPLY)
(FIELD SUPPLY)

N C1 N C2

PHASE PROTECTOR &


VOLTAGE PROTECTION
DO 1 DO 2
R S T
RETURN AIR SENSOR AI 1
15 16 SUPPLY AIR TEMP SENSOR AI 3
INDOOR COIL TEMP SENSOR 1 AI 4
INDOOR COIL TEMP SENSOR 2 AI 5 DI 2 DO11A
Common
SWITCHING POWER
SUPPLY BOARD

BLUE/BLACK

DIP SWITCH

MC : MAGNETIC CONTACTOR
L : LIVE
N : NEUTRAL

1 2 3 4 5 6 7 8

C2

OUTDOOR UNIT KC-1009-E X 2


OUTDOOR UNIT KC-1259-E X 2
OUTDOOR UNIT KC-1509-E X 2

77
KHD-3509C3-E / KC-1009-E & KC-1259-E

INDOOR UNIT KHD-3509C3-E

380-415/3Ph/50Hz 220-240/1Ph/50Hz
(FIELD SUPPLY)
(FIELD SUPPLY)

N C1 N C2 N C3

PHASE PROTECTOR &


VOLTAGE PROTECTION

R S T DO 1 DO 2 DO 3
RETURN AIR SENSOR AI 1
15 16 SUPPLY AIR TEMP SENSOR AI 3
INDOOR COIL TEMP SENSOR 1 AI 4
INDOOR COIL TEMP SENSOR 2 AI 5
INDOOR COIL TEMP SENSOR 3 AI 6
DI 2 DO11A
Common
SWITCHING POWER
SUPPLY BOARD

BLUE/BLACK

DIP SWITCH

MC : MAGNETIC CONTACTOR
L : LIVE
N : NEUTRAL

1 2 3 4 5 6 7 8

C2 C3

OUTDOOR UNIT KC-1009-E X 1


OUTDOOR UNIT KC-1259-E X 2

78
KHD-4009C4-E / KC-1009-E X 4
KHD-5009C4-E / KC-1259-E X 4
KHD-6009C4-E / KC-1509-E X 4
INDOOR UNIT KHD-4009C4-E
INDOOR UNIT KHD-5009C4-E
INDOOR UNIT KHD-6009C4-E

380-415/3Ph/50Hz 220-240/1Ph/50Hz
(FIELD SUPPLY)
(FIELD SUPPLY)

N C1 N C2 N C3 N C4

PHASE PROTECTOR &


VOLTAGE PROTECTION

R S T DO 1 DO 2 DO 3 DO 4
RETURN AIR SENSOR AI 1
15 16 SUPPLY AIR TEMP SENSOR AI 3
INDOOR COIL TEMP SENSOR 1 AI 4
INDOOR COIL TEMP SENSOR 2 AI 5
INDOOR COIL TEMP SENSOR 3 AI 6
INDOOR COIL TEMP SENSOR 4 AI 7 DI 2 DO11A
Common
SWITCHING POWER
SUPPLY BOARD

BLUE/BLACK

DIP SWITCH

MC : MAGNETIC CONTACTOR
L : LIVE
N : NEUTRAL

1 2 3 4 5 6 7 8

C2

C4 C3

OUTDOOR UNIT KC-1009-E X 4


OUTDOOR UNIT KC-1259-E X 4
OUTDOOR UNIT KC-1509-E X 4

79
KHD-7509C5-E / KC-1509-E
220-240/1Ph/50Hz
(FIELD SUPPLY) INDOOR UNIT KHD-7509C5-E

380-415/3Ph/50Hz
(FIELD SUPPLY)

TO OUTDOOR BOARD
(A1,B1)

RETURN AIR SENSOR AI 1


INDOOR COIL 1 AI 2
INDOOR COIL 2 AI 3
INDOOR COIL 3 AI 4
INDOOR COIL 4 AI 5
INDOOR COIL 5 AI 6

BLUE/BLACK

DIP SWITCH

MC : MAGNETIC CONTACTOR
L : LIVE
N : NEUTRAL

1 2 3 4 5 6 7 8

* INDOOR UNIT KHD-7509C5-E WITH PCB BOARD

220-240/1Ph/50Hz
(FIELD SUPPLY)

380-415/3Ph/50Hz 380-415/3Ph/50Hz
(FIELD SUPPLY) (A1,B1) (FIELD SUPPLY)
DIP SWITCH
COMP HP A1

PHASE ERROR/ COMP OVERLOAD


COMP LP A2

COMP HP A2

COMP LP A1

FROM INDOOR BOARD


(A1,B1)

TO OUTDOOR
(A1 @ B1 @ B2)
DI 4

DI 2
DI 5

DI 3

DI 1

AMBIENT SENSOR
OUTDOOR COIL
SENSOR A1
OUTDOOR COIL
DO 1

DO 3
DO 2

DO 6
DO 5
DO 4

SENSOR A2
COMP A1

FAN A1

FAN A2
COMP A2

FAN
COMP A
MOTOR A1

MC - MAGNETIC CONTACTOR HPA2 - HIGH PRESSURE A2 MC - MAGNETIC CONTACTOR HPA2 - HIGH PRESSURE A2
L - LIVE CA 2 - COMPRESSOR A2 L - LIVE CA 2 - COMPRESSOR A2
N - NEUTRAL FA 2 - FAN MOTOR A2 N - NEUTRAL FA 2 - FAN MOTOR A2
COMP - COMPRESSOR LP - LOW PRESSURE SWITCH COMP - COMPRESSOR LP - LOW PRESSURE SWITCH
COM - COMMON HP - HIGH PRESSURE SWITCH COM - COMMON HP - HIGH PRESSURE SWITCH
LPA2 - LOW PRESSURE A2 LPA2 - LOW PRESSURE A2

* OUTDOOR UNIT KC-1509-E-(A1) WITH PCB BOARD * OUTDOOR UNIT KC-1509-E-(A2) WITHOUT PCB BOARD

220-240/1Ph/50Hz
(FIELD SUPPLY)

220-240/1Ph/50Hz
(FIELD SUPPLY)
380-415/3Ph/50Hz 380-415/3Ph/50Hz 380-415/3Ph/50Hz
(FIELD SUPPLY) (FIELD SUPPLY) (FIELD SUPPLY) (A1,B1)
(A1,B1)
DIP SWITCH DIP SWITCH
COMP HP A1

PHASE ERROR/ COMP OVERLOAD


COMP LP A2

COMP HP A2

COMP LP A1
COMP HP A1

PHASE ERROR/ COMP OVERLOAD


COMP LP A2

COMP HP A2

COMP LP A1

FROM INDOOR BOARD FROM INDOOR BOARD


(A1,B1) (A1,B1)

TO OUTDOOR TO OUTDOOR
(A1 @ B1 @ B2) (A1 @ B1 @ B2)
DI 4

DI 2
DI 5

DI 3

DI 1
DI 4

DI 2
DI 5

DI 3

DI 1

AMBIENT SENSOR AMBIENT SENSOR


OUTDOOR COIL OUTDOOR COIL
SENSOR A1 SENSOR A1
OUTDOOR COIL OUTDOOR COIL
DO 1

DO 3
DO 2

DO 6
DO 5
DO 4
DO 1

DO 3
DO 2

DO 6
DO 5
DO 4

SENSOR A2 SENSOR A2
COMP A1

FAN A1

FAN A2
COMP A2
COMP A1

FAN A1

FAN A2
COMP A2

FAN FAN
COMP A COMP A
MOTOR A1 MOTOR A1

MC - MAGNETIC CONTACTOR HPA2 - HIGH PRESSURE A2 MC - MAGNETIC CONTACTOR HPA2 - HIGH PRESSURE A2 MC - MAGNETIC CONTACTOR HPA2 - HIGH PRESSURE A2
L - LIVE CA 2 - COMPRESSOR A2 L - LIVE CA 2 - COMPRESSOR A2 L - LIVE CA 2 - COMPRESSOR A2
N - NEUTRAL FA 2 - FAN MOTOR A2 N - NEUTRAL FA 2 - FAN MOTOR A2 N - NEUTRAL FA 2 - FAN MOTOR A2
COMP - COMPRESSOR LP - LOW PRESSURE SWITCH COMP - COMPRESSOR LP - LOW PRESSURE SWITCH COMP - COMPRESSOR LP - LOW PRESSURE SWITCH
COM - COMMON HP - HIGH PRESSURE SWITCH COM - COMMON HP - HIGH PRESSURE SWITCH COM - COMMON HP - HIGH PRESSURE SWITCH
LPA2 - LOW PRESSURE A2 LPA2 - LOW PRESSURE A2 LPA2 - LOW PRESSURE A2

* OUTDOOR UNIT KC-1509-E-(B1) WITH PCB BOARD * OUTDOOR UNIT KC-1509-E-(B2) WITHOUT PCB BOARD * OUTDOOR UNIT KC-1509-E-(C1) WITH PCB BOARD
OUTDOOR UNIT KC-1509-E X 5

80
81
82
83
84
85
86
KHD-409C KC-401AF 3/8" 3/4" 2.45
KHD-509C KC-501AF 3/8" 3/4" 3.20
KHD-609C KC-601AF 3/8" 3/4" 5.05
KHD-809C KC-809 1/2" 7/8" 6.40
KHD-1009C KC-1009 5/8" 1-1/8" 7.40
KHD-1259C KC-1259 5/8" 1-3/8" 8.0
KHD-1509C KC-1509 5/8" 1-3/8" 10.1
KHD-2009C2 KC-1009 x 2 5/8" 1-1/8" 7.6 x 2
KHD-2509C2 KC-1259 x 2 5/8" 1-3/8" 8.0 x 2
KHD-3009C2 KC-1509 x 2 5/8" 1-3/8" 10.1 x 2
KHD-3509C3 KC-1009 + KC-1259 x 2 5/8" 1-1/8" & 1-3/8" 7.6 + 8.0 x 2
KHD-4009C4 KC-1009 x 4 5/8" 1-1/8" 7.6 x 4
KHD-5009C4 KC-1259 x 4 5/8" 1-3/8" 8.0 x 4
KHD-6009C4 KC-1509 x 4 5/8" 1-3/8" 10.1 x 4
KHD-7509C5 KC-1509 x 5 5/8" 1-3/8" 10.1 x 5

87
88
89
90
91
92
93
94
95
Indoor Accurator

96
MODEL : KHD-509C/E

97
MODEL : KHD-609C/E

98
99
MODEL : KHD-1009C-S/E

100
MODEL : KHD-1259C-S/E

101
102
103
MODEL : KHD-2509C2/E

104
105
106
107
108
109
110
111
112
113
114
115
116
117
118
119
120
121
MODEL : KC-1509

122
123
KHD-409C-E~KHD1509C-E (EXPORT)
KHD-2009C2-E~KHD6009C4-E (EXPORT)

1. Interface

1.1. Mode of operation : Heating, Cooling, Dehumidify, Fan only

1.2. Indoor blower speed : Low, Medium, High, Auto

1.3. Error code : Show error code (if any) ; Symbol No shows unit number

1.4. Clock and timer : Days, Am/Pm, Timer on/off status

1.5. Temperature display : Ambient temperature/Domestic water temperature

1.6. System status : Electric heater, defrost, compressor 1#/2#/3#/4#, water pump, key lock
2. On/Off

2.1. Press to On/Off the unit

3. Mode of operation

3.1. Press to select mode of operation: Heating, Cooling, Fan only, Dehumidify

4. Indoor blower speed

4.1. Press to select speed: Low, Medium, High, Auto

5. Key lock

5.1. Press and hold and for 1s to activate keylock (Only button is effective during keylock)

5.2. To deactivate key lock, repeat 5.1

6. Temperature setting

6.1. Press or to select desire temperature

6.2. Ambient temperature will be shown when there is no input for 6s

6.3. Not applicable in fan only mode

7. Clock setting

7.1. To set day

7.1.1. Press to select day (Day symbol blinks) SUN-MON-TUE-WED-THU-FRI-SAT

7.1.2. Press to save (Auto save when there is no input for 6s)

7.2. To set time

7.2.1. Press and then or to select time 00:0000:0111:58-- 11:59--AMPM

7.2.2. Press to exit without save

7.2.3. Press to save and exit


8. Timer On/Off setting

8.1. Timer default OFF

8.2. Timer symbol light up when timer set to ON

8.3. To set timer, press once, temperature display area shows 1 and timer symbol blinks

8.3.1. Within 3s, press to enter timer setting interface

8.3.2. Timer symbol blinks, temperature display area shows Px x = 1 ~ 4 which represent timer set

number, maximum 4 set in a day

8.3.3. Press to select timer set number (maximum 4 set in a day), temperature display area shows P1 ~

P4

8.3.4. Interface automatically return to default page if there is no input within 3s

8.3.5. Press to select timer day

SUN-MON-TUE-WED-THU-FRI-SAT

8.3.6. Press or to select timer time

00:0000:0111:58-- 11:59-- AMPM

8.3.7. Press to select timer On/Off status

8.3.8. Press to exit without save

8.3.9. Press to save and exist

8.3.10. Press and hold for 1s to cancel current timer setting, clock area displays -:--

8.3.11. Press and hold for 3s to cancel all timer setting, day display area all lights up, clock display area

displays -:--

8.3.12. Timer setting will be saved and exit automatically if there is no input for 30s
9. Check various temperature readings

9.1. Press and hold and for 3s to enter various temperature readings page

9.2. Error code display area shows unit number; Temperature display area shows category; Clock display area

shows readings; No displays on all other area

9.3. Press or to select unit

9.4. Press or to select category

9.5. Press to exit (Auto exit when there is no input for 60s)

9.6. Temperature category

Model Category Temperature display


1 Return air temperature
2 Outdoor air temperature
3 Supply air temperature
4 1# indoor coil temperature
5 2# indoor coil temperature
Air-cooled
6 3# indoor coil temperature
package
7 4# indoor coil temperature
8 1# outdoor coil temperature
9 2# outdoor coil temperature
10 3# outdoor coil temperature
11 4# outdoor coil temperature
10. Error codes display

10.1. Error code display area symbol lights up and error code shows during system error

10.2. All error codes (if more than 1) will be showed one after another

10.3. Press to clear error (for those with error rectified only)

10.4. Error codes table reference

10.5. Error codes table reference

Model Error code Descriptions


(E) 01 Phase/Power failure error
(E) 02 Indoor blower error
(E) 03 1# outdoor fan error
(E) 04 2# outdoor fan error
(E) 05 3# outdoor fan error
(E) 06 4# outdoor fan error
(E) 07 1# compressor high pressure error
(E) 08 1# compressor low pressure error
(E) 09 2# compressor high pressure error
(E) 10 2# compressor low pressure error
(E) 11 3# compressor high pressure error
(E) 12 3# compressor low pressure error
(E) 13 4# compressor high pressure error
(E) 14 4# compressor low pressure error
(E) 15 Electric heater error
Air-cooled
(E) 16 Return air temperature sensor error
package
(E) 17 Outdoor air temperature sensor error
(E) 18 Supply air temperature sensor error
(E) 19 1# indoor coil temperature sensor error
(E) 20 2# indoor coil temperature sensor error
(E) 21 3# indoor coil temperature sensor error
(E) 22 4# indoor coil temperature sensor error
(E) 25 1# indoor coil anti-freeze protection
(E) 26 2# indoor coil anti freeze protection
(E) 27 3# indoor coil anti freeze protection
(E) 28 4# indoor coil anti freeze protection
(E) 33 1# outdoor coil temperature sensor error
(E) 34 2# outdoor coil temperature sensor error
(E) 35 3# outdoor coil temperature sensor error
(E) 36 4# outdoor coil temperature sensor error
99 Main board and wallpad communication error
11. Parameters setting

11.1. Press twice (Temperature display area shows 2, key lock symbol blinks), and press within

3s to enter parameters setting interface

11.2. Clock display area shows --- pending password entry

11.3. Interface automatically exit if no input within 3s

11.4. Press or to select password for first digit and press to confirm and proceed to second digit

password entry

11.5. Repeat step 11.4 for complete password entry 8699 to enter parameters setting interface

11.6. Temperature display area shows parameter category and correspondence category value will be shown at

clock display area

11.7. Press or to select different parameter category

11.8. Press or to change and select parameter value

11.9. Press and hold for 1s to save and exit

11.10.Press and hold for 1s to exit without save

11.11.To reset all parameters to default value

11.11.1. Press and , follow steps 11.2 to 11.4 for complete password entry 1919
11.12.Parameters setting reference table

Minimum Default Maximum


Model Category Descriptions
value value value
1 Tcpoff 0C 5C 10C
2 Tdif 3C 5C 15C
3 ODoff 10C 15C 30C
4 ODdif 1C 3C 10C
5 Compressor anti-short cycle 3min 5min 8min
Compressor loading/unloading
6 3s 300s 600s
control cycle
7 Minimum set temperature 5C 16C 20C
8 Maximum set temperature 25C 30C 45C
9 Return air temperature correction -5C 0C 5C
10 Outdoor air temperature correction -5C 0C 5C
11 Supply air temperature correction -5C 0C 5C
1# Indoor coil temperature
12 -5C 0C 5C
correction
2# Indoor coil temperature
13 -5C 0C 5C
correction
3# Indoor coil temperature
14 -5C 0C 5C
correction
Air-cooled 4# Indoor coil temperature
15 -5C 0C 5C
package correction
16 Automatically/manual restart 0 0 1
17 Unit number 0 0 199
Outdoor ambient air and outdoor
18 4C 8C 20C
coil temperature difference
19 Defrost cycle interval, TM1 20min 45min 150min
20 Defrost cycle interval, TM2 15min 30min 150min
21 Defrost stop temperature 6C 15C 30C
22 Defrost duration, N 3min 5min 10min
23 Defrost maximum waiting time 5min 10min 20min
Outdoor ambient temperature
24 0 1 1
sensor IN USED/NOT IN USED ?
Supply air temperature sensor IN
25 0 1 1
USED/NOT IN USED ?
26 1# Outdoor coil temp correction -5C 0C 5C
27 2# Outdoor coil temp correction -5C 0C 5C
28 3# Outdoor coil temp correction -5C 0C 5C
29 4# Outdoor coil temp correction -5C 0C 5C
12. Limited operation time setting

12.1. Press twice (Temperature display area shows 2, key lock symbol blinks), and press within

3s to enter limited operation time setting

12.2. Clock display area shows --- pending password entry

12.3. Interface automatically exit if no input within 3s

12.4. Press or to select password for first digit and press to confirm and proceed to second digit

password entry

12.5. Repeat step 11.4 for complete password entry 2828 to enter limited operation time setting

12.6. Temperature display area shows parameter category and correspondence category value will be shown at

clock display area

12.7. H High limited run time ; L Low limited run time

12.8. Set range 0 99 hours

12.9. Press or to select different parameter category

12.10.Press or to change and select parameter value

12.11.Press and hold for 1s to save and exit

12.12.Press and hold for 1s to exit without save

13. Manual defrost

13.1. Press and hold and for 3s to enter manual defrost mode

13.2. Temperature display area shows ON/OFF to determine manual defrost status

13.3. Clock display area shows PX where X = compressor number (1 to 4)

13.4. Press or to select manual defrost ON/OFF

13.5. Press or to select compressor number

13.6. Press to save and exit

13.7. Press and hold to exit without save


14. Reset to default value

14.1. Press and hold and for 3s then enter password 1919

15. Error reset

15.1. Press and hold and for 3s

16. Functional test

16.1. Press and hold and for 3s within 1 minute upon power on to test function on mainboard

16.2. Use for PCB testing only


KHD-7509C5-E (EXPORT)
OPERATION INSTRUCTIONS

1. On/Off

 Press to start or stop the air conditioner.

2. Temperature setting

 Press <<Menu>> once to enter setting


 Press or to decrease or increase the set temperature
 Press <<Confirm>> to exit

3. Mode setting
 Press <<Menu>> twice to enter

 Press or to change mode: Coolfandehumidifyheatautocool

 Press <<Confirm>> to exit

4. Fan speed setting


 Press <<Menu>> 3 times to enter

 Press or to change fan speed

 Press <<Confirm>> to exit

5. Real time clock setting


 Press <<Menu>> 4 times to enter (3 times in single fan speed mode)

 Press or to change time

 Press and hold or to change time in hour

 Press On/Off to change week

 Press <<Confirm>> to exit


6. On and off timer setting
 Press <<Menu>> 5 times to enter (4 times in single fan speed mode) (for On timer)

 Press <<Menu>> 6 times to enter (5 times in single fan speed mode) (for Off timer)

 If on timer for this day is empty, timer display area shows , otherwise the on
or off timer setting will be shown.
 Press or button to change the on or off timer setting. Holding down the
button will change the setting in a faster speed (toggle in hour)
 Press On/Off to toggle between week (On timer)

 lights up indicating if there is timer being programmed and the corresponding

ON or OFF will also lights up.

 Press <<Confirm>> to exit

7. Manual defrost

Press and for 3 seconds under heat mode to enter manual defrost. Clock area display
dEF1, press or to choose system to be defrost, press Enter to exit. Press Info to
cancel and exit.

8. Key lock
Press MENU and ENTER keys on the main menu for 3 sec to activate this function. Follow the
same sequence to exit key lock. In key lock mode, user is allowed to access to On/Off key only.
9. Information

Press INFO key on the main menu to enter. Press or key to select the required information
as follow:

Temp display section Timer display section Remarks


0 Main board DIP switch setting
1 Indoor coil 1 temperature Display range -40 ~ 87
2 Indoor coil 2 temperature Display range -40 ~ 87
3 Indoor coil 3 temperature Display range -40 ~ 87
4 Indoor coil 4 temperature Display range -40 ~ 87
5 Indoor coil 5 temperature Display range -40 ~ 87
6 Indoor coil 6 temperature Display range -40 ~ 87
7 Indoor coil 7 temperature Display range -40 ~ 87
8 Indoor coil 8 temperature Display range -40 ~ 87
9 Return air temperature Display range -40 ~ 87
10 Supply air temperature Display range -40 ~ 87
11 Outdoor coil 1 temperature Display range -40 ~ 87
12 Outdoor coil 2 temperature Display range -40 ~ 87
13 Outdoor coil 3 temperature Display range -40 ~ 87
14 Outdoor coil 4 temperature Display range -40 ~ 87
15 Outdoor coil 5 temperature Display range -40 ~ 87
16 Outdoor coil 6 temperature Display range -40 ~ 87
17 Outdoor coil 7 temperature Display range -40 ~ 87
18 Outdoor coil 8 temperature Display range -40 ~ 87
19 Ambient temperature Display range -40 ~ 87

Press Confirm to exit.


10. System control parameter

Press MENU and keys on the main menu for 3 sec to activate this function. Timer display
section shows 0--- asking for password entry. Press or key to change the value of the
current digit being edit. Press On/Off key to change the digit to be edited. Upon key in the correct
password of 8699, press ENTER key to enter into the following menu:

Temp display section Timer display section Remarks


In : Return air control
0 Return/Supply air control
Out : Supply air control
1 ~ 3C
1 Temperature control resolution
Default 1C
Compressor (Heater) start 1 ~ 5C
2
temperature difference Default 1.5C
Compressor (Heater) stop 1 ~ 5C
3
temperature difference Default 1.5C
1 ~ 10min
4 Compressor anti-short cycle
Default 5min
1 ~ 10min
5 Compressor minimum stop time
Default 3min
1 ~ 10min
6 Compressor (Heater) loading delay
Default 5min
Compressor (Heater) unloading 1 ~ 10min
7
delay Default 5min
10 ~ 15C
8 Defrost stop temperature
Default 10C
5 ~ 20s
9 Indoor blower pre-start run time
Default 15s
30 ~ 90s
10 Indoor blower stop delay time
Default 60s
0 ~ 99min
11 Unit number
Default 0
5 ~ 10min
12 Defrost stop time
Default 5min

Press On/Off key to select the item to be changed. Press or key to change the value of
the item selected.
Press INFO key to exit without save
Press CONFIRM key to exit and save the settings
11. Error code display
Backlight will turned to red when there is any system failure. ERR light will turn on and error
display section will show the relevant error code as follow:

Error code Remarks


1 Blower error (Manual reset)
2 Electric heater protection (Manual reset)
3 Pressure switch (Manual reset)
4
5
6 Ambient temperature sensor (Auto reset)
7 Supply air temperature sensor (Auto reset)
8 Return air temperature sensor (Auto reset)
9
10 Outdoor coil temperature sensor 1 (Auto reset)

11 High pressure protection 1 (Manual reset)

12 Low pressure protection 1 (Locked: Manual reset ; Others: Auto reset)

13 Phase protection 1 (Manual reset)

14 Indoor coil temperature sensor 1 (Auto reset)

15 Low temperature protection 1 (Auto reset)

16 High temperature protection 1 (Auto reset)

17 Insufficient refrigerant 1 (Manual reset)

18 System 1 communication error (Auto reset)

19
20 Outdoor coil temperature sensor 2 (Auto reset)

21 High pressure protection 2 (Manual reset)

22 Low pressure protection 2 (Locked: Manual reset ; Others: Auto reset)

23 Phase protection 2 (Manual reset)

24 Indoor coil temperature sensor 2 (Auto reset)

25 Low temperature protection 2 (Auto reset)

26 High temperature protection 2 (Auto reset)

27 Insufficient refrigerant 2 (Manual reset)

28 System 2 communication error (Auto reset)

29
30 Outdoor coil temperature sensor 3 (Auto reset)

31 High pressure protection 3 (Manual reset)

32 Low pressure protection 3 (Locked: Manual reset ; Others: Auto reset)

33 Phase protection 3 (Manual reset)

34 Indoor coil temperature sensor 3 (Auto reset)

35 Low temperature protection 3 (Auto reset)

36 High temperature protection 3 (Auto reset)

37 Insufficient refrigerant 3 (Manual reset)


38 System 3 communication error (Auto reset)

39
40 Outdoor coil temperature sensor 4 (Auto reset)

41 High pressure protection 4 (Manual reset)

42 Low pressure protection 4 (Locked: Manual reset ; Others: Auto reset)

43 Phase protection 4 (Manual reset)

44 Indoor coil temperature sensor 4 (Auto reset)

45 Low temperature protection 4 (Auto reset)

46 High temperature protection 4 (Auto reset)

47 Insufficient refrigerant 4 (Manual reset)

48 System 4 communication error (Auto reset)

49
50 Outdoor coil temperature sensor 5 (Auto reset)

51 High pressure protection 5 (Manual reset)

52 Low pressure protection 5 (Locked: Manual reset ; Others: Auto reset)

53 Phase protection 5 (Manual reset)

54 Indoor coil temperature sensor 5 (Auto reset)

55 Low temperature protection 5 (Auto reset)

56 High temperature protection 5 (Auto reset)

67 Insufficient refrigerant 5 (Manual reset)

58 System 5 communication error (Auto reset)

59
60 Outdoor coil temperature sensor 6 (Auto reset)

61 High pressure protection 6 (Manual reset)

62 Low pressure protection 6 (Locked: Manual reset ; Others: Auto reset)

63 Phase protection 6 (Manual reset)

64 Indoor coil temperature sensor 6 (Auto reset)

65 Low temperature protection 6 (Auto reset)

66 High temperature protection 6 (Auto reset)

67 Insufficient refrigerant 6 (Manual reset)

68 System 6 communication error (Auto reset)

69
70 Outdoor coil temperature sensor 7 (Auto reset)

71 High pressure protection 7 (Manual reset)

72 Low pressure protection 7 (Locked: Manual reset ; Others: Auto reset)

73 Phase protection 7 (Manual reset)

74 Indoor coil temperature sensor 7 (Auto reset)

75 Low temperature protection 7 (Auto reset)

76 High temperature protection 7 (Auto reset)

77 Insufficient refrigerant 7 (Manual reset)

78 System 7 communication error (Auto reset)

79
80 Outdoor coil temperature sensor 8 (Auto reset)

81 High pressure protection 8 (Manual reset)

82 Low pressure protection 8 (Locked: Manual reset ; Others: Auto reset)

83 Phase protection 8 (Manual reset)

84 Indoor coil temperature sensor 8 (Auto reset)

85 Low temperature protection 8 (Auto reset)

86 High temperature protection 8 (Auto reset)

87 Insufficient refrigerant 8 (Manual reset)

88 System 8communication error (Auto reset)

Power off to clear error

12. Communication indication


Communication LED will flash at regular speed if the communication between wallpad and main
board is normal

13. Hardware test

Press Menu and Confirm for 3 seconds after system booted for 90s to enter hardware
check mode. Auto exit after 1 minute
DOCUMENT REVISION

TITLE: HIGH STATIC DUCTED TECHNICAL MANUAL


No. Date Revision Descriptions Person in charge
1 1/1/2016 0 Original first copy Firdaus Chamari
Add phase protection & voltage protection for
2 6/1/2016 1 Firdaus Chamari
export indoor wiring diagram (Pg:77,78,79)

3 4/3/2016 2 Amended wiring symbol DI 12 TO DI 2 (Pg:77,78,79) Firdaus Chamari


4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30