Lecture 04

Design Criteria

RHU-CIVE519
Dr. Zaher Abou Saleh
Outline of the Design Criteria
The Basic Design Criteria
Limit States Design Philosophy
The Speed of Erection
Loading
Sequential Loading
Strength and Stability
Drift Limitations
Stiffness
Human Comfort
Fire
Creep, Shrinkage, and Temperature
Foundation Settlement and
Soil-Structure Interaction
1. The Basic Design Criteria for Tall Buildings.
The pressure p = f(H2); in other words, the pressure on a 100-story building is 16x the
pressure on a 25-story building.

(a) The building must not break in shear and (b) must not deflect excessively in shear.
The bending resistance of a building must provide, (a) that the building must not
overturn, (b) the columns must not fail in tension or compression, and (c) the deflection
due to bending (drift index) must not be excessive.
2. Limit States Design Philosophy.

The aim of this approach is to ensure that all structures and their constituent
components are designed to resist with reasonable safety the worst loads and
deformations that are liable to occur during construction and service, and to have
adequate durability during their lifetime.

The entire structure, or any part of it, is considered as having failed when it reaches
any one of various limit states. Two types of limit states must be considered:

The ultimate limit states, corresponding to the loads to cause failure, endangering
lives and causing serious financial losses, the probability of failure must be low.

The serviceability limit states, which involve the criteria governing the service life
of the building. Since the consequences are not catastrophic, a much higher
probability of occurrence is permitted.

A particular limit state may be reached as a result of an adverse combination of


random conditions. Partial safety factors are employed for different conditions that
reflect the probability of certain occurrences or circumstances of the structure and
loading existing. The implicit objective of the design calculations is then to ensure that
the probability of any particular limit state being reached is maintained below an
acceptable value for the type of structure concerned.
3. The Speed of Erection Process.

The speed of erection is a vital factor in obtaining a return on the investment by


minimizing the cost of interest payments on the large capital costs involved in such
large-scale projects.

Most tall buildings are constructed in congested city sites with difficult access, and
with no storage areas.

Careful planning and organization of the construction sequence become essential.

The story-to-story uniformity of most multi-story buildings encourages construction


through repetitive operations and prefabrication techniques.

The progress in the ability to build tall buildings has gone hand in hand with the
development of more efficient equipment and improved methods of construction,
such as:

- Slip- and flying-formwork


- Concrete pumping
- The use of climbing tower cranes and large mobile cranes.
4. Loading.

The structure must be designed to resist the gravitational and lateral forces, both
permanent and transient that will be sustained during construction and during the
expected useful life of the structure (from 60 to 100 years). These forces will depend
on the size and shape of the building, and its location. Load combinations depend on
the probable accuracy of estimating the dead and live loads, and the probability of the
simultaneous occurrence of different combinations of gravity loading, both dead and
live, with either wind or earthquake forces. The accuracy of these loads is included in
limit states design through the use of prescribed factors.

5. Sequential Loading.

For dead loads, the construction sequence should be considered to be the worst case. It
is usual to shore the freshly placed floor upon several previously cast floors. The
construction loads on the supporting floors due to the weight of wet concrete and its
formwork will greatly exceed the loads of normal service conditions. These loads must
be calculated considering the sequence of construction and the rate of erection.
However, the designer rarely knows who the contractor will be, nor his method of
construction.
If column axial deformations are calculated as though the dead loads are applied to
the completed structure, bending moments in the horizontal components (for
example, beams) will result from any differential column shortening.

Because of the cumulative effects of column axial deformations over the height of the
building, the effects are greater in the highest levels of the building. However, the
effects of such differential movements could be greatly overestimated because in
reality, during the construction sequence, a particular horizontal member is
constructed on columns in which the initial axial deformations due to the dead weight
of the structure up to that particular level have already taken place.

The deformations of that particular floor will then be caused by the loads that are
applied subsequent to its construction.

Such sequential effects must be considered if an accurate assessment of the structural


actions due to dead loads is to be achieved.
6. Strength and Stability.

The primary requirement of the ultimate limit state design procedure is that the
structure have adequate strength to resist and remain stable under the worst
probable loads during its lifetime. This includes all critical load combinations,
augmented moments from second-order deflections (P- ) plus an adequate reserve,
study all critical members whose failure may lead to a progressive collapse of part or
the whole structure. Finally, the whole building must be checked against toppling as a
rigid body about one edge of the base. Moments are taken about that edge with the
resisting moment of the dead weight of the structure to be greater than the
overturning moment by an acceptable factor of safety (FS > 3).
A simple model of a tall
building is to represent it
as a cantilevered beam
fixed to its foundations.

The lateral deflection of


the cantilever due to the
wind force shown at left is
the drift at the top floor.
7. Drift Limitations.

The parameter that measures the lateral stiffness is the sway index. It is defined as
the ratio of the maximum deflection at the top of the building to the total height of
the building. In addition, each floor has an index called the story drift index which
checks for localized excessive deformation.

There is no national code requirement for the sway index, but 1/500 is a traditionally
accepted limit.

Different countries use from 0.001 to 0.005 (1/1,000 to as low as 1/200).

Lower values are used for hotels and condominiums because the noise and discomfort
at those levels are unacceptable.

For conventional structures, the preferred range is 0.0015 to 0.0030 (in other words,
from 1/700 to 1/350).
Deflections must be limited, in order to:

1)Prevent second-order P- effects due to gravity loading, precipitating collapse;

2) Allow the functioning of non-structural components, such as elevators and


doors;

3) Avoid distress in the structure;

4) Prevent excessive cracking and consequent loss of stiffness;

5) Avoid any redistribution of load to non-load-bearing partitions, in-fills,


cladding, or glazing;

6) Prevent dynamic motions from causing discomfort to occupants, or affecting


sensitive equipment.
In the design process, the stiffness of joints, particularly in precast or prefabricated
structures, must be given attention to develop lateral stiffness of the structure and
present progressive failure.

Torsional deformations must not be overlooked, especially due to diurnal thermal


drift in steel frames.

As building height increases, the drift index should become lower to keep the top
story deflection to a suitably low level.

If excessive, the drift of a structure can be reduced by:

1) Changing the geometric configuration to alter the mode of lateral load


resistance;
2) Increasing the bending stiffness of the horizontal members;
3) Adding additional stiffness by the inclusion of stiffer wall or core members;
4) Achieving stiffer connections, by sloping the exterior columns;
5) In extreme circumstances, it may be necessary to add dampers, which may
be of the passive or active type.
8. Stiffness.
The lateral stiffness is a major consideration in the design of a tall building. Under the
ultimate limit state, the lateral deflections must be limited to prevent 2nd-order P-
effects from gravity loading to be large enough to precipitate a collapse. In addition,
serviceability requires these deflections not to affect elevator rails, doors, glass
partitions, and prevent dynamic motions to cause discomfort to the occupants and
sensitive equipment. This is one of the major differences of tall buildings with respect
to low-rise buildings.

9. Human Comfort.
Buildings subjected to both lateral and torsional deflections (plus vortex shedding and
other usual effects) may induce in their human occupants from discomfort to acute
nausea. These are major factors in the final design of the building.

When a tall structure is subjected to lateral loads, the resulting oscillatory movements
can induce a wide range of responses in the buildings occupants, ranging from mild
discomfort to acute nausea. This may prove the structure undesirable or un-rentable.

There are no codified standards for comfort criteria. A dynamic analysis is required
to determine the response of the structure in order to determine its adequacy to the
comfort criteria.
10. Fire.

One of the most extreme conditions placed upon a building is fire.

Fire is a primary concern during design. The temperature range and its duration
must be estimated from its probable cause and the materials present in the
building that could provide fuel for its continuation. Also of interest are possible
sources of ventilation, and egress from alterative paths must be considered. The
behavior of the different structural components must be known. For example,
mild steel at 700C is only 15% of the yield strength at 20C, and its elastic
modulus drops to only 45% of its original value.
11. Creep, Shrinkage, and Temperature.

In very tall buildings, the cumulative vertical movements due to creep and shrinkage
may cause distress in the structure and induce forces into horizontal elements
especially in the upper regions of the building. During the construction phase, elastic
shortening will occur in the vertical elements of the lower levels due to the additional
loads imposed by the upper floors as they are completed. Cumulative differential
movements will affect the stresses in the subsequent structure, especially in the
building that includes both in-situ and pre-cast components. Buildings subjected to
large temperature variations between their external faces and the internal core, and
that are restrained, will experience induced stresses in the members connecting both.

Important factors in determining long-term deformations include:

1) Concrete properties;
2) Loading history;
3) The age of the concrete at the time of load application;
4) Volume-surface ratio and amount of reinforcement in the members
concerned;
5) Achieving a uniformity of stress in the vertical components will reduce any
relative vertical movement due to creep and elastic shortening.
12. The Effect of Foundation Settlement upon the Tall Building.

The gravity and lateral forces on the structure will be transmitted to the earth
through the foundation system. Because of its height, a tall buildings columns may
be very heavy. In areas with bedrock, appropriate foundations can be shallow
foundations, drilled shafts, or deep basements.

In areas with poor soil conditions, differential settlements must be avoided. A typical
solution is the use of mat (or raft) foundation, where the weight of soil equals to a
significant portion of the gross building weight. This method is called partially
compensated foundation.

Overturning moments and resisting moments and shears must be checked. Minor
movements of the foundations are greatly exaggerated by a tall building, leading to
very large inclinations of the tower. If an overall rotational settlement of the entire
foundation occurs, the ensuing lateral deflections will be magnified by the height,
increasing maximum drift and incurring P- effects.
13. Soil-Structure Interaction.

Soil-structure interaction involves both static and dynamic behaviour. The former is
generally treated by simplified models of subgrade behaviour, and finite element
methods of analysis are customary.

When considering dynamic effects, both interactions between soil and structure, and
any amplification caused by a coincidence of the natural frequencies of building and
foundation must be included.

Seismic forces may develop excessive hydrostatic pressures, causing liquefaction of


the soil. These types of conditions must be considered and avoided.