I/O DETAILS

Integration With BMS


No of Data points for
Sl.No. Description Qty AI AO DI DO

A ACMV Automation system

ACMV PLANT ROOM AT SECOND BASEMENT


Water Cooled Chillers- Qty 2
1 Chiller Enable command 2
2 Chiller ON/OFF status 2
3 Chiller Auto / Manual status 2
4 Chiller trip status 2
5 Set charge / Operating temperature 3
6 Outlet and inlet temperature of Individual chillers 4
Common supply & return header temperature
7 6
/each circuit
Butterfly ON/OFF Chiller isolation valves
8 2 2
command & status

Primary chilled Water Pumps Qty 3


1 Pumps ON / OFF command 3
2 Pumps ON / OFF Status 3
3 Pumps Auto / Manual status 3
4 Pumps trip status 3
Secondary Chilled Water Circulation Pumpsets 3
Integration of Pumpsets for retrieving internal
1 15
data for monitoring & control
2 Pumps VFD run Status 3
3 Pumps VFD trip status 3
Pumps ON / OFF command - Command to Logic
4 3
Control Panel
5 Pumps speed control through VFD 3
6 Pump ON/OFF Status 3
7 VFD Panel on Auto/manual Status 3
Chilled Water DP Sensor across common
8 3
Supply & return header circuits
Integration of Chillers to BAS System

Integration of Chillers for retrieving internal data


1 2 40
for monitoring & control

Condensor Water Pumps Qty 3


9 Pumps ON / OFF command 3
10 Pumps ON / OFF Status 3
11 Pumps Auto / Manual status 3
12 Pumps trip status 3
DDC for Chillers , Primary Pumps, Secondary
13 3 38 13 58
Pumps & Condenser Pumps

OVERHEAD TANK 1
1 Level Switch - High
2 Level Switch - Low 1
3 Level Switch - Medium

Cooling towers 2

1 Cooling tower fan ON / OFF command 2


2 Cooling tower fan ON / OFF Status 2
3 Cooling tower fan Auto / Manual status 2
4 Cooling tower fan trip status 2
5 Cooling tower basin level low 2
6 Cooling tower basin level high 2
7 Outlet & Inlet condensor water temperature 4

DDC for Cooling Towers & Overhead Tanks 5 0 10 2 0

TOTAL I/O FOR CHILLER PLANT 18 3 48 15 58

B AIR HANDLING UNITS


Typ Office Floor AHU

Air Handling Units - Qty in each of AHU Room 1


1 AHU ON/OFF Command (VFD enable) 1
2 AHU ON/OFF status 1
3 AHU Auto/Manual Status 2
4 Return air Temperature and Rh 2
5 Filter status EU -7 & EU-4 Filters 2
6 CHW 2-Way Valve Control 1
Immersion type temperature sensors to measure
7 2
CHW in/outlet temperature
8 Fire Damper Status - SA, RA, reset command 2
9 Return air Co2 level 2
VFD Speed control, Duct static pressure reading
11 2 2 2 20
& monitoring. Integration of VFDS
12 AHU trip status 1
15 Supply air Canvas Temperature in AHU's 2
16 Outside fresh air velocity sensor. 1
2 11 3 8 1 20
OFFICE AREA - AIR HANDLING UNIT ROOMS
I/O List for Air Handling Units
Total no of AHUS 17
Total I/O for AHU 17 187 51 136 17 340

C HRW UNITS 2
17 HRW SUPPLY AIR FAN ON/OFF Command 2
18 HRW SUPPLY AIR FAN ON/OFF Status 2
19 HRW SUPPLY AIR FAN Auto/Manual status 2
20 HRW RETURN AIR FAN ON/OFF Command 2
21 HRW RETURN AIR FAN ON/OFF Status 2
22 HRW RETURN Auto/Manual STATUS 2
23 HRW Wheel ON/OFF Command 2
24 HRW Wheel ON/OFF Status 2
25 HRW wheel Auto/Manual status 2
26 Outdoor Air Temperature Entering 2
27 Supply Air Temperature and Rh leaving Wheel 2
28 Return Air Temperature & RH Entering Wheel 2
29 Air Temperature and Rh Leaving Wheel 2
Filter status on air entering wheel & air entering
30 2
conditioned space
31 HRW supply, exhaust and wheel trip status 3

Total I/O for HRW 8 0 17 6 0

D CEILING SUSPENDED UNITS

CSU Qty 1
1 CSU ON/OFF Command 1
2 CSU FAN ON/OFF status 1
3 CSU Auto/Manual Status 1
4 Return air Temperature and Rh 2
5 Filter status 1
6 Return air Co2 level 1
7 CHW 2-Way Valve Control 1
8 AHU trip status 1
9 Supply air Canvas Temperature in AHU's 1
Total I/O for CSU Typical 4 1 4 1 0

Total no of CSU's 5
Total I/O for CSU 5 20 5 20 5 0

E CASSETE UNITS

CASSETE Qty 27
1 Cassete ON/OFF Command 27
2 FCU FAN ON/OFF status 27
3 Return air Temperature + RH Sensor 54
4 Cassete trip status 27
Total I/O for cassete 54 0 54 27 0

F FAN COIL UNITS

FCU Qty 1
1 FCUON/OFF Command 1
2 FCU FAN ON/OFF status 1
3 FCU Auto/Manual Status 1
4 Return air Temperature and Rh 2
5 Filter status 1
6 Return air Co2 level 1
7 CHW 2-Way Valve Control 1
8 FCU trip status 1
Total I/O for FCU Typical 3 1 4 1 0

Total no of FCU's 1
Total I/O for FCU 1 3 1 4 1 0

G STP & PUMP ROOM FRESH AIR FANS

FRESH AIR FAN - Qty 2


1 Fresh Air Fan ON/OFF Command 2
2 Fresh Air Fan ON/OFF status 2
3 Fresh Air Fan Auto/Manual status 2
5 Fresh Air fan trip status 2
Total I/O for FCU 0 0 6 2 0

H KITCHEN EXHAUST FAN -CAFETERIA

KITCHEN EXHAUST FAN - Qty 1


1 Exh Fan ON/OFF Command 1
2 EX. Fan ON/OFF status 1
3 Exh Fan Auto/Manual status 1
4 exh. fan trip status 1

Total I/O for FCU 0 0 3 1 0

STP EXHAUST, PANTRY EXHAUST, COPIER


EXHAUST, MAIN ELECTRICAL ROOM,
I
ELECTRICAL ROOM EXHAUST, PUMP ROOM
EXHAUST FAN

FRESH AIR/AIR WASHER FAN - Qty 6


1 Fresh Air Fan ON/OFF Command 6
2 Fresh Air Fan ON/OFF status 6
3 Fresh Air Fan Auto/Manual status 6
5 Fresh Air fan trip status 6

Total I/O for FCU 0 0 18 6 0

TOILET EXH FANS LOCATED AT TERRACE


J
FLOOR

TOILET EXHAUST FAN - Qty 2


1 Toilet Exh Fan ON/OFF Command 2
2 Toilet Fan ON/OFF status 2
3 Toilet Exh Fan Auto/Manual status 2
4 Toilet exh. fan trip status 2

Total I/O for FCU 0 0 6 2 0

K BASEMENT EXHAUST/ FRESH AIR FANS - TYP

EXHAUST FANS 10
1 Exhaust air Ventilation Fan ON / OFF Command. 10

2 Exhaust air Ventilation Fan ON / OFF Status. 10


3 Exhaust air Ventilation Fan trip Status. 10
4 Exhaust air Ventilation Fan A/M Status. 10

Total I/O for Exhaust Fans 0 0 30 10 0

L OVERHEAD TANKS - Qty 1

Level Switch - High - Fire, flush water and potable


5 1
water tanks
Level Switch - Low - Fire, flush water and potable
6 1
water tanks
Level Switch - Medium - Fire, flush water and
7 1
potable water tanks

Total I/O for Exhaust Fans 0 0 3 0 0

M STP - I/O LIST


LOCATION IN STP ROOM 1

STP EQUIPMENTS - STP ROOM


1 Raw Effluent PumpON/OFF status 1
2 Treated Effluent PumpON/OFF status 1
3 Air Blower ON/OFF status 1
4 Filter Feed Pumpsets ON/OFF status 1
5 Return Sludge Pumpsets ON/OFF status 1
6 UV Sterilizer ON/OFF status 1
7 Waste Water Sump Pump ON/OFF status 1
Waster Water Sump Level Switch - High, Low &
8 1
Medium
9 Final Sump Pump ON/OFF status 1
10 Final Sump Level Switch - High, Low & Medium 1
Treated Effluent Sump Level Switch - High, Low
11 1
& Medium
HVAC Makeup Water Tank Level Switch - High,
12 1
Low & Medium
13 PH Meter 1
14 Dissolved Oxygen Probe 1
15 Flow Meter 1
Final Sump to HVAC Makeup Pump ON/OFF
18 2
status
Total I/O for STP Plant 7 0 10 0 0

N DAY OIL TANKS


LOCATION IN DG ROOM

TANKS 0
HSD Day Oil TankLevel Switch - High, Low &
1 0
Medium

Total I/O for STP Plant 0 0 0 0 0

O PHE PUMPS
LOCATION IN PUMP HOUSE BASEMENT

Storm Water Pumps 2


1 Storm Water Pumps ON/OFF Command 2 2
2 Storm water PumpON/OFF status 2
3 Pumps Auto / Manual status 2
4 Pumps trip status 2

Total I/O for storm water pumps 0 0 6 2 0

PHE PUMPS-water supply pumps-domestic 2


1 Pump ON/OFF Command 2 2
2 Pump ON/OFF status 2
3 Pumps Auto / Manual status 2
4 Pumps trip status 2
5 Water Meter in supply line 1 1
Total I/O for water supply pumps-domestic 0 0 7 2 0

PHE PUMPS-flushing water supply pumps 2


1 Pumps ON/OFF Command 2 2
2 PumpON/OFF status 2
3 Pumps Auto / Manual status 2
4 Pumps trip status 2
5 Water Meter in supply line 1 1

Total I/O for flushing water supply pumps 0 0 7 2 0

BASEMENT DRAINAGE PUMPS


De watering Submersible pumps 2
1 Pumps ON/OFF Command 2 2
2 PumpON/OFF status 2
3 Pumps Auto / Manual status 2
4 Pumps trip status 2

Total I/O for PHE PUMPS 0 0 6 2 0

SEWAGE PUMP 2
1 Pumps ON/OFF Command 2 2
2 PumpON/OFF status 2
3 Pumps Auto / Manual status 2
4 Pumps trip status 2

Total I/O for PHE PUMPS 0 0 6 2 0

WTP PUMP(Filter Feed Pump) 2


1 Pumps ON/OFF Command 2 2
2 PumpON/OFF status 2
3 Pumps Auto / Manual status 2
4 Pumps trip status 2

Total I/O for PHE PUMPS 0 0 6 2 0


Rain water Harvesting pump 2
1 Pumps ON/OFF Command 2 2
2 PumpON/OFF status 2
3 Pumps Auto / Manual status 2
4 Pumps trip status 2
Total I/O for PHE PUMPS 0 0 6 2 0

Total I/O for WTP PUMPS,SEWAGE PUMP &


Rain water harvesting pumps,Storm water
0 0 44 14 0
pumps,water supply pumps,flushing water
supply pumps,de-water subermisible pumps,

p OTHER EQUIPMENTS- MONITORING



Pump sets- STATUS
1 Landscape Irrigation Pump set 2 2
2 Raw Water Lift Pump to Water Treatment Plant 2
Domestic Treated Water Lift Pump to Overhead
3 2
Tank
4 Borewell Pump sets 4
5 Softwater Pump sets 2

Tanks
Raw Water Tank 1
7 High Level
8 Low Level 1
9 Over Flow
Treated Water Tank 1
10 High Level
11 Low Level 1
12 Over Flow
Fire Tank 1
13 High Level
14 Low Level 1
15 Over Flow

Total I/O for other equipment s 3 0 12 0 0

Q FIRE PROTECTION SYSTEM- MONITORING

Fire Pumps Main Pump 2


1 Fire pump ON/OFF status. 2
2 Fire pump trip status. 2
3 Fire pump Auto / Manual status. 2
Jocky Pump 1
1 Jocky pump ON/OFF status. 1
2 Jocky pump trip status. 1
3 Jocky pump Auto / Manual status. 1
Diesel Engine Driven Pump 1
1 Diesel engine driven pump ON/OFF status. 1
2 Diesel engine driven pump trip status. 1
3 Diesel engine driven pump Auto / Manual status. 1
Terrace Booster Pumps 1
1 Pump ON/OFF status. 1
2 Pump trip status. 1
3 Pump Auto / Manual status. 1
Total I/O for Fire Protection System 0 0 15 0 0

R ELECTRICAL SYSTEMS- ONLY MONITORING


1 11kV SWITCHGEAR 2
2 Breaker ON/OFF status 2
3 Breaker trip status 2
4 Breaker service status 2
5 Breaker test status 2
6 Breaker Remote status 2
7 Breaker spring charged/discharged status 1
Monitoring of electrical parameters V, I, Hz, pf,
8 2
KW, KWH
9 D.C.Supply Failure 1
LV SWITCHGEAR PCC1 (Power Control
Centre ) 1 Incomer & 2 Outgoing
10 Breaker ON/OFF status 16
11 Breaker trip status 16
Monitoring of electrical parameters V, I, Hz, pf,
12 16
KW, KWH
LV SWITCHGEAR PCC2 (Power Control
Centre ) 3 Incomer & 20 Outgoing [4 Future]

13 Breaker ON/OFF status 20


14 Breaker trip status 20
Monitoring of electrical parameters V, I, Hz, pf,
15 20
KW, KWH
Synchronising Panel (1)
16 Breaker ON/OFF status 1
17 Breaker trip status 1
Monitoring of electrical parameters V, I, Hz, pf,
18 1
KW, KWH
Transformer 2
19 Buchholz Alarm 2
20 Buchholz Trip 2
21 Oil temperature High / Low 2
22 Winding temperature High / Low 2
23 Magnetic oil level gauge 2
24 Oil surge relay 2
Lighting DB's
25 Lighting DB ON/OFF command. 15
26 Lighting DB ON/OFF status 15
DG Set [Through integration] 5 100
Total I/O for Electrical System 0 0 94 15 158

S ELEVATOR MONITORING 5
Elevator in normal mode, maintenance mode, fire
1 20
mode, alarm bell status

Total I/O for ELEVATOR MONITORING 0 0 0 0 20


Total IO POINTS 300 60 520 121 576
SPARE @ 10% 30 6 52 12 58

GRAND TOTAL IO POINTS 330 66 572 133 634